Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10137943 03/19/2024
Jaco #3367 Fastrip #640 (East)
8001 White Lane Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Billy Lane
1073967
10281488 03/15/2025
Veeder-Root C33867 8/4/2024
03/19/2024 5Billy Lane
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VEEDER ROOT T TLS 350
CURRENT
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L5 208 87 SIPHON FILL
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Replacement in 87 siphon tank on west side. Tested, passed.
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted. NO PARKINGNO PAR
KING
EXISTING BUILDING
L13
L14
L15L16
L17
L18
L12STP
L9STP
L6STP
L3STP
L10
L7
L4
L1
L11
L8
L5
L2
87-2 UNLEADED
12,000 GALLON87-1 UNLEADED
12,000 GALLON DIESEL12,000 GALLON
1/2
43
65
910
78
12/11
#3-366
#3-367
N
91 PREMIUM12,000 GALLON
V F
87-1 UNLEADED12,000 GALLON
87-2 UNLEADED12,000 GALLON91 PREMIUM12,000 GALLON
DIESEL12,000 GALLON
L5STP
L2STP
L11STP
L14STP
AL6
L1
L10
L13
L7/L8
L3
L12
L15
L9
L18
L17
L16L19
L20
L21
18/17
1516
1314
2122
1920
25/24
L22
PROPERTY LINE
PROPERTY LINEH
W
W
H
PRICE SIGN
PRICE SIGNDIESEL PRICE SIGN
#367
#366
NO PARKINGACCESS RAMPS ACCESSRAMPDUMPSTER
G
A
A
A
V F
V F
F
A A
A
A
A
F
F
F
F
V
V
V
366 LEGEND
L1 87-1 ANNULAR
L2 87-1 FILL
L3 87-1 STP
L4 87-2 ANNULAR
L5 87-2 FILL
L6 87-2 STP
L7 91 ANNULAR
L8 91 FILL
L9 91 STP
L10 DSL ANNULAR
L11 DSL FILL
L12 DSL STP
L13 UDC 1 - 2
L14 UDC 3 - 4
L15 UDC 5 - 6
L16 UDC 7 - 8
L17 UDC 9 - 10
L18 UDC 11 -12
367 LEGEND
L1 87-1 ANNULAR
L2 87-1 STP ANNULAR AND SUMP SENSOR 2-TO-1
L3 87-1 FILL
L5 87-2 STP
L6 87- 2 STP ANNULAR
L7 87-2 FILL
L8 87-2 ANNULAR FILL
L9 87-2 ANNULAR
L10 91 ANNULAR
L11 91 STP
L12 91 FILL
L13 DSL ANNULAR
L14 DSL STP
L15 DSL FILL
L16 UDC 13 - 14
L17 UDC 15 - 16
L18 UDC 17 - 18
L19 UDC 19 -20
L20 UDC 21 -22
L21 UDC 23 - 24
L22 VENT BOX ANNULAR AND SUMP SENSOR 2-TO-1
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3/2 INCH DOUBLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
S1: 87-2 UNLEADED VENT LINE
S2: PRODUCT SIPHON LINE AND VACUUM CHASE
S3: VAPOR RETURN LINE
EMERGENCY SHUT-OFF
OVERFILL ALARM
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
FIRE EXTINGUISHER
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
WH
A
F
V
SITE MAP
DATE REVISIONS
DATE:
DRAWN BY:
CHECKED:
APPROVED:
RAC CADFILE:
SHEET NO.
A.P.N.:385-013-21-4
SCALE:
CONVENIENCE MARKET FOR:
3101 STATE RDBAKERSFIELD, CA 93308
PROJECT OWNER:
DRAWING:
CD
FASTRIPS - 3-366-3-367 3366-MSP
FASTRIP FOOD STORE
BAKERSFIELD, CALIFORNIA 933098001 WHITE LN.
JACO HILL
SITE PLAN
C1
TAB:CERS
1"=15'-0"
INCHES012
SHEET SIZE 22 X 34
01/07/2022
8001 WHITE LN.
BAKERSFIELD, CA 93309
GOSFORD RD.
WHITE LN.
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-097250
CERS ID 10137946
FASTRIPS 3-366 / 3-367
8001 WHITE LN.
BAKERSFIELD, CA 93309
02/12/2021 REV.
VICINITY MAP
PROJECT DATA