HomeMy WebLinkAbout2001 oak st_jim burke ust 12.8.23Underground Storage Tank Program
DW-Inspection Report
Bakersfield Fire Department
Prevention Services Division
2101 H Street
Bakersfield, CA 93301
Phone: 661-326-3979 / Fax: 661-852-2171
Inspector: Mark Rodriquez
Date: 12/08/23
Business Jim Burke Ford
2001 Oak St.
Bakersfield, CA. 93301
Owner, Haberfelde Ford Inc
2001 OAK ST
BAKERSFIELD, CA93301
Facility ID#: 15-021-003107
EPA ID#:CAD981441728
Bo #44052439
CERS ID# 10023232
Inspection Type: Routine
Report: Final
DW -Tank- 1 - 11430 Regular
-
DW-Tank-2Premium
DW- ank-3- Diesel J:DW-Tank-4-
Diesel
2030021
Facility has a valid permit to
operate from the CUPA- 23 CCR
16.2711 (d)
HSC 6.7 25284
2010010
UST Operating Permit application
for Facility and Tank Information
Submitted / Maintained 23 CCR
16 2711; HSC 6.7 25284,25286
2030046
A complete and accurate
response plan has been
submitted, approved and
maintained 23 CCR 16 2632 (d)l
2634 (e) 2641 (h) 2712 (i)
2030041
A complete and accurate plot
plan has been submitted,
approved and maintained
23CCR 16 2632 (d) (1) (C) 2641 (h)
2010006
Owner/Operator has not made
false statements or
representation of any required
document. HSC 6.7 2599 (a) (8)
FDDW - 0.0
M.
2030002
Failure to have a properly
qualified service technician test
leak detection equipment as
required every 12 months
(vacuum, pressure, hydrostatic
(VPH) system, sensors, line -leak
detectors (LLD), automatic tank
gauge (ATG), etc.). 23.CCR 16
2638(a) 2638(b) 2641(j) 2715(f)
2030048
Failure to conduct secondary
containment testing or meet one
or more of the following
requirements.
1) Within six months of installation
and every 36 months thereafter.
installation.
2) Using applicable
manufacturer guidelines, industry
codes, engineering standards, or
professional engineer approval.
3) Performed by a certified
service technician.
23 CCR 16 2637(a)-(d) 2712
b 1 F
2010009
Failure to submit:a copy of the
secondary containment test
results on the "Secondary
Containment Testing Report
Form" to the UPA within 30 days
after the test. 23 CCR 16
2637 (e) (f)
2030064
Failure to notify the UPA 48 hours
prior to testing 23 CCR 2637(g)
2637.1(f) 2637.2(f) 2638(e)
2643 2644.1 a) (4
L
2030003
Failure of the leak detection
equipment to have an audible
and visual alarm as required 23
CCR 16 2632(c) (2) (B)
26,34 d 1 A 2636 f l
2030016
Failure to continuously monitor
the interstitial space of a double -
walled tank with an audible and
visual alarm system. 23 CCR
162631 2632 c 2 A & B
2030017
1) The system shuts down the
pump or stops flow when a leak
is detected in the UDC
UDC .23CCR 16 2636 f 4
f
FDDW -- 0.0
2030018
Failure of the double -walled
pressurized piping to be
continuously monitored with a
system that activates. an audible
and visual alarm or stops flow fat
the dispenser when a leak is
detected. 23 CCR 16 2636 (f) (1)
2666(b) (2)
2030043
Failure of the leak detection
equipment to be installed,
calibrated, operated, and/or
maintained in accordance with
manufacturer's instructions. 23
CCR 1.6 2638 a -2641 .
2060005
Failure of the UST system to be
designed and constructed with a
monitoring system capable of
detecting the entry of the
hazardous substance into the
secondary containment. 23 CCR
16.25291 b 2636 a 1
2060015
Failure of leak detection
equipment to be installed,
maintained.. and located such
that the equipment is capable of
detec ing a leak at the earliest
possible opportunity. 23 CCR 16
2630 d 2641 a
2030062
Leak detection equipment
disabled or Pampered with in a
manner thatwould. prevent the
monitoring system from
detecting and/or alerting the
owner/operator of a leak. HSC
6.7 2599 a 9
2060022
Failure of a UST system installed
on or after July 1, 2003, and
before July 11 2004,` to be
designed and constructed with a
monitoring system capable of
detecting the entry of the
hazardous substance stored in
the primary containmentinto the
secondary containment and
capable of detecting wafer
intrusion into the secondary
containment. HSC 6.7 25290.2 d
2030034
Failure to properly affix
tag/sticker on each monitoring
equipment being certified,
repaired, or replaced. 23' CCR 16
2638 f 2641 '
FDDW-0.0
2030065
Failure to maintain the interstitial
space such that a breach in the
primary or secondary
containment is detected before
the liquid or vapor phase of the
hazardous substance stored in
the UST tank is released into the
environment, i.e., vacuum,
pressure, hydrostatic HSC
Chapter 6.7, Section25290.1 e
2060023
Failure of a UST system installed
on or after July 1, 2004, to be
designed and constructed with a
monitoring system capable of
detecting the entry of the liquid
or vapor: -phase of the hazardous
Substance stored in the primary
containment into the secondary
containment and capable of
detecting water intrusion into the
secondary containment. HSC
Chapter 6.7, Section 25290.1 d
v
2060012
Failure to install a line leak
detector (LLD). CCR Title 23,
Chapter 16, Section 2636 (f) (2)
2636(f)(5) (B) .2643(c)(1) 2666(f)
HSC Chapter 6.7, Section
25290.1(h) 25294.2(g). 25291(f)
25292 e
2030027
Failure of the line leak detector
(LLD) monitoring single.walled
pressurized piping to meet the
following requirements:l)
Monitored at least hourly with
the capability of detecting a
release of 30 gallons per hour
leak at 10 pounds per square
inch.2) Shut down the pump
when a leak is detected or when
the LLD fails or is disconnected.
CCR Title 23, Chapter 16, Section
2666 c 2643 c l
2030025
Failure of the functional line leak
detector (LLD) 1) to have the
capability of detecting a release
of 3.0 gallons per hour2) Restrict
or shut off the flow of product
through the piping when a leak is
detected. CCR Title 23, Chapter
16, Section 2636 f 2
FDDW-v3.0
2030008
Failure to keep water & debris
out of the secondary
containment, HSC Chapter
6.7, Section
25290.1 c) 3),25290.2 c (3)
2030040
Failure to maintain
secondarily contained piping
to allow liquid to flow into the
sump in the event of -a leak
CCR Title 23, Chapter 16,
Section 2630 d 2641 a
2030047
Failure to maintain secondary
containment HSC Chapter
6.7, Section 25290.1(e)
25290.1(c) 25290.2(c) CCR
Title 19, Chapter 6.7, Section
25291 a 2
2060020
Spill bucket is installed and
has a functional drain valve.
23 CCR 16 2635 b , 2665
,
2030035
Failure to operate the UST
system to prevent
unauthorized releases
including leaks, spills, and/or
overfills. HSC Chapter 6.7,
Section 25292.1 a
2030036
Overfill prevention system has
not been overridden and
meets the overfill
requirements. 23 CCR 16 2635,
2637.2, 2665, 2712
t
2010007
Failure to submit and maintain
complete and current
Certification of Financial
Responsibility or other
mechanism of financial
assurance. 23 CCR Chapter
16, Section 271 1(a) (11),
Chapter 18, Section 2809-
2809.2, 2808.1 HSC Chapter
6.7, Section 25292.2(a),
Chapter 675, Section
25299.30-25299.34
FDDW-0.0
2010004 Failure to maintain on -site, or
off -site at a readily available
location if approved by the
U PA", copies of f he
"Designated Underground
Storage Tank Operator Visual
Inspection Report" and all
attachments for 36 months.
California Code of
Regulations, Title 23, Chapter
16, Section 271 6(f)
2030013 Failure to comply with one or
more of the following
Designated Operator (DO)
inspection requirements
California Code of
Regulations, Title 23, Chapter
16, Section
2716 (a) (b) (c) (d) (e)
2030012 Do employee training is
current for at least one
employee on site and a
training logbook is kept
California Code of
Regulations, Title 23, Chapter
16, Section 2715 (c) (c) (1)
(c) (2)
2030001 Failure to maintain monitoring
records for 36 months and/or
failure to maintain
maintenance
records (including written
performance claims and
calibration records) for the
release defecfion,system for
60 months. California Code of
Regulations, Title 23, Chapter
16, Section 2712(b)(I)/ (b)(2)
FDDW - 0.0
,. ,.. .1{•. i,. r..-; hl W i'a. .�. � � --, r.., x. :�' i' �.., x, ..;.}.:..
cn.. ._H. F, S, ++:':R•- 2 .,F F l.
L' .. .�. .. xr� - `xr ,., �•.. 'xr ., :: v. .. "L. :.'L�
... .3_ ?J .. _ v..,. 3 J ..3 ti ..3 '.. J .." f
.'}'.. a.
c at �.
.1
.� .-`xr.�,
'Jl .. ,...:.
} .i .. . ,.. .,f. � �
I 1.
.,E� t r E E
L 4'
2 F-....;F..,.. ,i`R• ".-- F.,,.Y F -'.r Y �.Y ; .Y
-. - J. J`. .4 ..% 4 .
-'L �.., .. `F ,.-`>r� r 9`L �.., 'L ... '-'L'. `-. -. :2� 1`>r.�.., ..`F , ..
.!. 3., .!9 ..} .... 3 -.3 3.•...... ......... 3. } �J -.3 .... ...".
2010008
Failure to maintain records of
repairs. linings, and upgrades
on site, or off site if approved
by the U PA, for the life of the
UST California Code of
Regulations, Title 23, Chapter
16, Section 2712(b) (6)
I.. i .r f.. ,. ..r. ., ,. .r ,,
J. .
r ...�. .r... .<.. n.. ,. .c. .[. .,..o�..,,«..tir
. T ... ��
..:.r. ,,
f f f
c?. .- .<...�r... .:,.... r, cr. .- .-<.. �. [r. .- .<.,�r.... ? -, .<.,.,.F„�,,....tir, cr: �. �.{,o
;1 ;1 '.s
2030033
Failure to submit and have
current UST Monitoring Plan
readily accessible at the
facility. California Code of
Regulations, Title 23, Chapter
16, Section 2712(i)
2030037
Failure. to implement or
maintain a written agreement
between the UST owner and
operator. California Code of
Regulations, Title 23, Chapter
16, Section 2620 (b) California
Health and Safety Code,
Chapter 6.7, Section
25284(a) (3) (A) &(B)
2030061
Failure to record any
unauthorized release from the
primary containment.
California Code of
Regulations, Title 23, Chapter
16, Section 2651
California Health and Safety
Code, Chapter 6.7, Section
25294
a
[/�j .■{Y�
f.
r.
Art .::J 1
r
1 1
2030039
Failure to comply with any of
the applicable requirements
of the permit issued for the
operationofi the UST system.
California Code of
Regulations, Title 23, Chapter
16, Section 2712
FD DW 0.0
/
1111
. . .. ... ... .. .._ -... .-. .n..... ... - y.- ..... .,.. .. -. ..... - ....... o,•.. .. ... ..:.. ..... .. .:... ....•, ..., . r,,..... ..i ..n r.._ � ,...._. ,n-,_...,.. 1,,,.. ....a. .. ,, a�. ._),,., ...._.. _,,.- _)w. ,. . -,,. -.._ � ... .._ .SIN ....,-.. .. ..,:_i,.r ...._- -,n ./w ,_ , �, :.
2030015 Failure to demonstrate to the
UPA that the equipment and
methods Used to monitor the
UST system are certified by an
independent third -party as
complying with the standards
set forth in 23 CCR 2643(f).
California Code of
Regulations, Title 23, Chapter
16, Section 2630(d),
2632(c) (2) (A), 2643(f),
2644.1(a) (2)
r..
5 5
.t t :cep :� .... $. `...i .. ,. „ Ykm"r). .. :,•.,..j:,-., Y (� -. S Y Y� S ) � } ,.� -. S , -. S S �. .. ,\. } Y,. -. S
2030045 Red Tag has been removed,
defaced, altered, or
otherwise tampered with so
that the information on the
tag is not legible. California
Code of Regulations, Title 23,
Chapter 16, Section 2717.1(g)
2030044 Owner/operator deposited or
allowed deposit of petroleum
or a hazardous substance into
a UST that has a red tag
affixed to the fill pipe.
California Code of
Regulations, Title 23, Chapter
16, Section 2717.1(f) California
Health and Safety Code,
Chapter 6.7, Section
25292.3(c)
�� cr` � cr:-`. .z-•� ? rz c?s^. ,� cr: ^ <r: ` �� c?: ^ crs^. cr: ^ <r. r .: c?� ^. �� cr>^. .z-o<r>^.-,-+• " <r r r . < r' ..:. .:`.-,..�.<:• 1-.r.... ..,..,.�-,r:.,�,N....,•-,..�1-�-0�, ,,c..,,.. .., .-,..�[.<:� 1x,orr..,�,Nc....,.. 1 1 ,..�[ ..1K
v
A 5- 5- -t -t
m c
r r., r r r ,r r. r r r r •r .� r _. ,. -.-..' I .-,. ,..: :i a, I, .,�.,-s ,. s .--......:z .. a, ,.. -..x .. a, /, � .i � ,. -., . I .': _, I _. ,•-.:. .. I :,-� J I '-. I r I I �.� .,• a,.i, r
THERE WERE NO VIOLATIONS NOTED DURING THIS INSPECTION.
THIS REPORT SHALL SERVE AS A "NOTICE TO COMPLY" FOR VIOLATIONS FOUND
DURING INSPECTION. VIOLATIONS ARE TO BE CORRECTED WITHIN 30 DAYS OF RECEIVING
THIS NOTICE. FAILURE TO COMPLY WILL RESULT IN VIOLATIONS BEING ELEVATED AS WELL
AS FORMAL EN FORCEM ENTS BEING IN N ITIATED.
INSPECTORS SIGNATURE: A0;9!5" " �'' DATE: 12/8/23
Site Representative: �yj�� DATE: 12/8/23