Know what's below.Call before you dig.NOTES:12-01-21
14. APPLICANT TO PROVIDE ADEQUATE P.U.E'S AND/OR ROW'S FOR PG&E FACILITIES. ANY ADDITIONAL REQUIRED
RIGHTS OF WAY ARE TO BE SURVEYED AND DOCUMENTED BY PG&E AT THE APPLICANT'S EXPENSE.
CONDUIT, TRENCHING, AND BACKFILL:
1. ALL DIMENSIONS AND LOCATIONS ARE ESTIMATED, APPROXIMATE AND MAY BE SUPERSEDED BY A JOINT
TRENCH DRAWING. REFER TO THE JOINT TRENCH COMPOSITE DRAWING FOR EXACT TRENCH LOCATION
2. MAINTAIN MAXIMUM PRACTICABLE HORIZONTAL CLEARANCE BETWEEN PG&E FACILITIES AND "WET" UTILITIES
(WATER, SEWER, STORM DRAIN, ETC.). THE MIN. ALLOWABLE SEPARATION BETWEEN PG&E FACILITIES AND
ANY PARALLEL "WET" UTILITY IS 3/FT. WITH A PRESENCE OF 1/FT. OF UNDISTURBED EARTH OR THE
INSTALLATION OF A SUITABLE BARRIER. THIS MEASUREMENT IS BETWEEN THE OUTER EDGE OF THE PG&E
FACILITY AND THE OUTER EDGE OF THE PARALLEL "WET" FACILITY. IF 3/FT. CANNOT BE MAINTAINED, A
FORMAL VARIANCE MUST BE OBTAINED FROM PG&E WORK WITH THE PG&E INSPECTOR (REFERENCE PG&E
UO STANDARD S5453).
3. BOX, PAD, AND CONDUIT SIZES AND LOCATIONS SHALL CONFORM TO THE PG&E ELECTRIC CONSTRUCTION
DRAWING.
4. PROVIDE LONG CONDUIT SWEEPS WHERE INDICATED. RECOMMENDED SWEEP RADIUS (10' OF RADIUS PER
INCH OF CONDUIT DIAMETER) EXAMPLE: 4" CONDUIT = 40' RADIUS
5. DO NOT EXCEED 300 DEGREES OF BENDS IN ANY CONDUIT RUN (INCLUDING FEED LOCATION). NOTE:
SECONDARY AND SERVICE RUNS OF 200 FEET OR LESS MAY HAVE UP TO 315 DEGREES OF BENDS (REFERENCE
PG&E DOCUMENT 038193, REV. 7, DATED 6-28-13).
6. MANUFACTURED BENDS OR APPLICATION OF HEAT SHALL NOT BE USED TO OBTAIN LONG CONDUIT SWEEPS.
7. ALL CONDUITS SHALL BE PROVEN AND A POLYESTER PULLING TAPE INSTALLED.
8. MANUFACTURED BENDS ARE NOT TO BE CUT, SHORTENED, OR ALTERED IN ANY WAY.
9. IDENTIFY ENDS OF BURIED CONDUIT WITH AN ELECTRONIC MARKER AND A VERTICAL CONDUIT SCRAP
INSTALLED FROM RIGID CAP TO GROUND LEVEL.
10. CONDUITS ENTERING PRIMARY BOXES SHALL BE AT A RIGHT ANGLE TO THE WINDOW OR WALL.
11. STUB CONDUITS AT RISER POLES IN QUADRANTS AS SHOWN. AT IDENTIFIED POLE LOCATIONS, THE TRENCHING
AGENT IS TO EXCAVATE TO TRENCH DEPTH AND INSTALL A 30" DIAMETER CARDBOARD TUBE. THE RISER
CONDUIT BEND IS TO BE PLACED OUTSIDE AND ADJACENT TO THE TUBE AT THE POLE QUADRANT INDICATED.
BACKFILL AROUND AND INSIDE TUBE WITH CLEAN NATIVE FILL.
12. LS2 STREET LIGHT CONDUIT GOING TO PG&E BOXES OR PEDESTALS NOT DESIGNATED AS P.O.S. (INCLUDING
TRANSFORMERS) WILL NOT BE ACCEPTED OR CONNECTED.
13. ONLY ONE LS2 STREET LIGHT (P.O.S.) CONNECTION PER BOX OR PEDESTAL.
15. CALL 811 (UNDERGROUND SERVICE ALERT) 48 HOURS PRIOR TO EXCAVATION FOR UNDERGROUND UTILITY
LOCATION
MARKING.
16. 48 HOUR NOTICE REQUIRED FOR UNDERGROUND INSPECTION.
17. MATERIALS AND WORKMANSHIP SHALL BE FIRST QUALITY IN EVERY RESPECT, PLUMB AND TRUE, AND
ACCORDING TO THE SPECIFIC REQUIREMENTS OF THE DRAWINGS AND THE ABOVE APPLICABLE NOTES AND
SPECIFICATIONS.
18. THE APPLICANT IS TO VERIFY ALL PROPOSED INSTALLATIONS, CONDITIONS & SPECIFICATIONS PRIOR TO
COMMENCING WITH ANY PORTION OF WORK. ANY DISCREPANCIES, DELETIONS OR INCONSISTENCIES ARE TO
BE REPORTED TO THE PG&E REPRESENTATIVE IMMEDIATELY. THE APPLICANT SHALL COMPLY WITH ALL
APPLICABLE SPECIFICATIONS. ANY VARIATIONS FROM PLANS OR SPECIFICATIONS RELIEVES PG&E OF ALL
RESPONSIBILITY FOR THE SUBSTRUCTURE OR DESIGN.
REFER TO ELECTRIC & GAS SERVICE REQUIREMENTS (GREEN BOOK) OR SEPARATE PG&E STANDARD DRAWINGS.
CONTACT YOUR PG&E REPRESENTATIVE FOR COPIES, OR ACCESS. WWW.PGE.COM/GREENBOOK
LAND RIGHTS AND EASEMENTS:
SAFETY AND WORKMANSHIP:
VACANT CONDUIT: 1-4"
VACANT CONDUIT: 1-6"
LS2 | CUSTOMER OWNED STREETLIGHT
4'6" x 8'6" x 6' PRIMARY ENCLOSURE
PM TRANSFORMER, DF-LB, W/BOX PAD
LEGEND
EXISTING DESCRIPTIONINSTALLLOC
PMI-9TT
3' x 5' x 3'6" PRIMARY ENCLOSURE
WORK AGENT RESPONSIBILITIES
TO INSTALL ELECTRIC DISTRIBUTION FACILITIES
TO INSTALL DISTRIBUTION CONDUIT & SUBSTRUCTURES
TO INSTALL ELECTRIC SERVICE FACILITIES
TO INSTALL SERVICE CONDUITS & SUBSTRUCTURES
TO PERFORM ALL TRENCHING AND EXCAVATION
TO PERFORM JOINT TRENCH COMPOSITE
TO PERFORM ALL TIE-IN WORK
AVERAGE SQUARE FEET:
MAIN SIZE:
MAX AC TONNAGE:
JOB DETAILS
200A
5 TON
1600 FT²
ELECTRIC VEHICLE LOAD:N/A
SOLAR GENERATION:4kW
WET AND DRY UTILITY CLEARANCES
·THE MINIMUM ALLOWABLE SEPARATION BETWEEN THE EDGE OF THE JOINT
TRENCH AND THE EDGE OF ANY "WET" FACILITY TRENCH IS 3' WITH THE PRESENCE
OF A MINIMUM OF 1' OF UNDISTURBED EARTH OR THE INSTALLATION OF A
SUITABLE BARRIER.
·THE MINIMUM ALLOWABLE SEPARATION BETWEEN THE EDGE OF THE JOINT
TRENCH AND THE EDGE OF ANY "DRY" NON-UTILITY FACILITY TRENCH IS 2' WITH
NO LESS THAN 1' OF UNDISTURBED EARTH OR THE INSTALLATION OF A SUITABLE
BARRIER.
WORK REQUIREMENTS
N/A
N/A
N/AREQUIRED
TRAFFIC CONTROL PLAN / FLAGGING
ENCROACHMENT PERMIT
VEGETATION REMOVAL
REQUIRED
REQUIRED
STREET LIGHT RATE:LS2 (POS)
PRIMARY CABLE: 3-1/0AL EPR 25kV IN NEW 1-4" CONDUIT
SECONDARY ENCLOSURE: 17" x 30" x 18" | MCODE: 040936
SECONDARY CABLE: 1-4/0AL TPX 600V IN 1-3" NEW CONDUIT
RESIDENTIAL
SERVICE CABLE: 1-4/0AL TPX 600V IN 1-3" (N) CONDUIT
TYPICAL SHORT SIDE SERVICE:25'/39'
PRIMARY CABLE: 3-1100AL EPR 25kV IN NEW 1-6" CONDUIT
VACANT CONDUIT: 1-3"
SECONDARY ENCLOSURE: 17" x 30" x 26" | MCODE: 040937
PG&E
APPLICANT
PG&E
APPLICANT
APPLICANT
APPLICANT
APPLICANT
SECONDARY CABLE: 1-350AL TPX 600V IN 1-4" NEW CONDUIT
SECONDARY ENCLOSURE: 24" x 36" x 18" | MCODE: 040940
900A OVERHEAD SWITCH
SOLELY OWNED POLE - SIZE AS SHOWN
LOCATION 23 DETAIL: #5 SPLICE BOX SCALE 1" = 5'
LOCATION 13 & 14 DETAIL: #7 & #5 SPLICE BOX SCALE 1" = 5'
INTERIOR STREET PATTERN
EXTERIOR STREET PATTERN
NON-RESIDENTIAL
SERVICE CABLE: 1-1/0AL TPX 600V IN 1-3" (N) CONDUIT
SECONDARY ENCLOSURE: 24" x 36" x 18" | MCODE: 040942
1.8-6859 PH 1
104
87
8685
84
156 155 154 153 152 151 150 149 148 147
107
106
105
103
104
105
106
107
108 109
110
111
112
113
114
115
116
117
171
172
173
174
175
176
177
178179
180
100
101
102
167
168
169
170
118
119
120
121
122 123
124
125
127 128 129 130 131 132 133 134 135
136
137138139140141142143144145146
147 148 149 150 151 152 153 154 155 156
157158
126
159160161162163164165166
INT-936950SW-442468
SW-878396INT-567898
T147821
T515586
T137994
T475770 T404893
T703791 T829642
T995453
324953TO SSDSWITCH 2855Know what's below.Call before you dig.SEE PAGE 31.8-6859 PH 1
8685
84
83
82
4
5
9 8 7 6
2
3
101112131415161819202122232425
55
103
104
105
106
107
108
111
112
115
116
177
179
180
181
182
91
92
93
94
95
96
97
98
99
100
101
102
21
35
36
22 23 24 25 26
282930313233
38
39
40
41
42
43 44
45
47 48
49
50
51
52
53
54
56
57
58
59 60
61
62
63 64
65
66
67
68
69
707273
7475
767778
79 80 81 82 83 84 85 86 87 88 89 90
1234567
71
37
34
89101112131415161718
19
20
27
46
INT-552368SW-478646
SW-879614INT-681368 INT-936950SW-442468
SW-878396INT-567898
17
T140928T105687
T933316
T211999 T87819T70231
T892288
T620860
T622045
T915143
T386258
T374612 Know what's below.Call before you dig.SEE PAGE 21.8-6859 PH 1
7
7
7
7 Know what's below.Call before you dig.LOCATION 7 DETAIL: PMI-9TT SCALE 1" = 5' LOCATION 9 DETAIL: PMI-9TT SCALE 1" = 5'
LOCATION 5 DETAIL: #7 SPLICE BOX SCALE 1" = 5'LOCATION 3 DETAIL: #7 SPLICE BOX SCALE 1" = 5'1.8-6859 PH 1