HomeMy WebLinkAboutFMC 2024Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10132177 04/16/2024 Jaco #9933 Fastrip 4800 Fairfax Road Bakersfield 93306 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fisher 1073967 10278702 03/10/25 Veeder Root - C33847 07/24/25 Vaporless Manufacturing LLC #5346 03/14/25 04/16/2024 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder Root TLS350 336.02 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 409 Reg 87 Annular L2 208 Reg 87 STP Sump L3 208 Reg 87 Fill L4 208 Super 91 STP L5 409 Super 91 Annular L6 208 Super 91 Fill L7 409 Diesel Annular L8 208 Diesel STP Sump L9 208 Diesel Fill L10 208 1/2 UDC L11 208 3/4 UDC L12 208 6/6 UDC L13 208 7/8 UDC L14 208 9/10 UDC L15 208 11/12 UDC L16 208 Vent Box UDC Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V 87 Unleaded T2 FX1V 91 Premium T3 FX1DV Diesel Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. 04/16/24 LEGEND L1 87 ANNULAR L2 87 STP L3 87 FILL L4 91 STP L5 97 ANNULAR L6 97 FILL L7 DSL ANNULAR L8 DSL STP L9 DSL FILL L10 UDC 1 - 2 L11 UDC 3 - 4 L12 UDC 5 - 6 L13 UDC 7 - 8 L14 UDC 9 - 10 L15 UDC 11 - 12 L16 VENT BOX 87 GAS 3/2 INCH DBL WALLED PIPE 91 GAS 3/2 INCH DBL WALLED PIPE DIESEL 3/2 INCH DBL WALLED PIPE VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE VAPOR VENT 3/2 INCH DOUBLE WALLED PIPE PRODUCT SPILL CONTAINER VAPOR SPILL CONTAINER ANNULAR EMERGENCY SHUT-OFF OVERFILL ALARM FIRE EXTINGUISHER HEALY CAS EVACUATION MEETING POINT UST ELECTRICAL PANEL AUTOMATIC TANK GAUGE AIR AND WATER DISPENSER HAZWASTE DRUM A H P V EXISTING BUILDING FSTPL8AL712,000 GALLONDIESELFVSTPL412,000 GALLONPREMIUMFV STPL212,000 GALLON87 UNLEADEDAL5AL1L9L6L321L10CATCHBASIN NO PARKING NO PARKINGNO PARKING43L11 6 5 L12 87 L13109L141211 L1 5 L16HDUMPSTER PRICE SIGN CATCHBASIN N FAIRFAX RD. PROPERTY LINE AUBURN ST.PROPERTY LINE SCALE: SITE MAP C1 VICINITY MAP PROJECT DATA 3/32"=1'-0" INCHES012 SHEET SIZE 22 X 34 4800 FAIRFAX RD. BAKERSFIELD, CA 93306 PROJECT OWNER: FASTRIP OIL COMPANY PO. BOX 82515 BAKERSFIELD, CA 93380 CONTACT: SITE PLOT PLAN FOR: CERS ID 10132177 FACILITY ID 15-021-103469 FASTRIP #9933 4800 FAIRFAX RD. BAKERSFIELD, CA 93306 04/24/17 REV.FAIRFAX RD.AUBURN ST. APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Jaco #9933 Fastrip4800 Fairfax RoadBakersfield101321773/47/8 11/12MPDMPDMPDMPDMPDMPD1/25/69/10ProductProductProductProductProductProductMark Fisher Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10132177 04/16/2024 Jaco #9933 Fastrip 4800 Fairfax Road Bakersfield 93306 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fisher 1073967 10278702 03/10/25 OPW - 1193587 08/04/25 PEI1200, 1 hour hydrostatic test All Spill Buckets 04/16/2024 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. 87 OPW 91 OPW Diesel OPW FASTRIP #9933 SYSTEM SETUP Responses Received: 200 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 APR 16, 2024 8:58 TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 REGULAR 87 5021 38.61 0.0 61.0 6606 2 SUPER 91 8804 60.20 0.0 64.2 2823 3 DIESEL 7373 51.61 0.0 71.3 4254 I90500 APR 16, 2024 8:58 SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 APR 16, 2024 8:58 SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS I50201 APR 16, 2024 8:58 SHIFT TIME 1 : DISABLED I50202 APR 16, 2024 8:58 SHIFT TIME 2 : DISABLED I50203 APR 16, 2024 8:58 SHIFT TIME 3 : DISABLED I50204 APR 16, 2024 8:58 SHIFT TIME 4 : DISABLED I54600 APR 16, 2024 8:58 TANK PER TST NEEDED WRN: DISABLED I54900 APR 16, 2024 8:58 TANK ANN TST NEEDED WRN: DISABLED I55300 APR 16, 2024 8:58 LINE RE-ENABLE METHOD PASS LINE TEST I55600 APR 16, 2024 8:58 LINE PER TST NEEDED WRN: DISABLED I55900 APR 16, 2024 8:58 LINE ANN TST NEEDED WRN: DISABLED I50D00 APR 16, 2024 8:58 PRINT TC VOLUMES ENABLED I50E00 APR 16, 2024 8:58 TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 APR 16, 2024 8:58 STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 APR 16, 2024 8:58 H-PROTOCOL DATA FORMAT HEIGHT I51A01 APR 16, 2024 8:58 DAYLIGHT SAVING TIME DISABLED I51B00 APR 16, 2024 8:58 I51600 APR 16, 2024 8:58 RE-DIRECT LOCAL PRINTOUT DISABLED I50400 APR 16, 2024 8:58 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 APR 16, 2024 8:58 TANK CHART SECURITY DISABLED I5BD00 APR 16, 2024 8:58 CUSTOM ALARM LABELS DISABLED I56000 APR 16, 2024 8:58 MASS/DENSITY DISABLED I88101 APR 16, 2024 8:58 PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 APR 16, 2024 8:58 PORT SETTINGS: COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88103 APR 16, 2024 8:58 PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 APR 16, 2024 8:58 I88105 APR 16, 2024 8:58 PORT SETTINGS: COMM BOARD : 5 (RS-485) BAUD RATE : 2400 PARITY : EVEN STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88106 APR 16, 2024 8:58 PORT SETTINGS: COMM BOARD : 6 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I52000 APR 16, 2024 8:58 RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE FEB 6, 2020 DISABLED 2 ON DATE FEB 6, 2020 DISABLED 3 ON DATE FEB 6, 2020 DISABLED 4 ON DATE FEB 6, 2020 DISABLED 5 ON DATE FEB 6, 2020 DISABLED 6 ON DATE FEB 6, 2020 DISABLED 7 ON DATE FEB 6, 2020 DISABLED 8 ON DATE FEB 6, 2020 DISABLED I60100 APR 16, 2024 8:58 TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 REGULAR 87 ON 2 SUPER 91 ON 3 DIESEL ON 4 OFF I60200 APR 16, 2024 8:58 TANK PRODUCT LABEL TANK PRODUCT LABEL 1 REGULAR 87 2 SUPER 91 3 DIESEL 4 I60300 APR 16, 2024 8:58 TANK PRODUCT CODE TANK PRODUCT LABEL 1 REGULAR 87 1 2 SUPER 91 2 3 DIESEL 3 4 4 I60900 APR 16, 2024 8:58 TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 REGULAR 87 0.000700 2 SUPER 91 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 APR 16, 2024 8:58 TANK DIAMETER TANK PRODUCT LABEL INCHES 1 REGULAR 87 92.00 2 SUPER 91 92.00 3 DIESEL 92.00 4 0.00 I60A00 APR 16, 2024 8:58 TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 REGULAR 87 4 PTS 11627 2 SUPER 91 4 PTS 11627 3 DIESEL 4 PTS 11627 4 1 PT 0 I60400 APR 16, 2024 8:58 TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 REGULAR 87 11627 2 SUPER 91 11627 3 DIESEL 11627 4 0 I60500 APR 16, 2024 8:58 TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 REGULAR 87 11627 10128 6403 2453 2 SUPER 91 11627 10128 6403 2453 3 DIESEL 11627 10128 6403 2453 4 0 0 0 0 I60600 APR 16, 2024 8:58 TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 REGULAR 87 11627 0 0 0 0 10128 0 0 0 0 6403 0 0 0 0 2453 0 0 0 0 2 SUPER 91 11627 0 0 0 0 10128 0 0 0 0 6403 0 0 0 0 2453 0 0 0 0 3 DIESEL 11627 0 0 0 0 10128 0 0 0 0 6403 0 0 0 0 2453 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 APR 16, 2024 8:58 TANK PRODUCT LABEL METER DATA 1 REGULAR 87 NO 2 SUPER 91 NO 3 DIESEL NO 4 NO I62F00 APR 16, 2024 8:58 MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 REGULAR 87 4.0 IN. 2 SUPER 91 4.0 IN. 3 DIESEL 4.0 IN. I62700 APR 16, 2024 8:58 TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 REGULAR 87 2.0 2 SUPER 91 2.0 3 DIESEL 2.0 I64200 APR 16, 2024 8:58 WATER ALARM FILTER TANK PRODUCT LABEL 1 REGULAR 87 LOW 2 SUPER 91 LOW 3 DIESEL LOW I62400 APR 16, 2024 8:58 TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 REGULAR 87 3.0 2 SUPER 91 3.0 3 DIESEL 3.0 I62800 APR 16, 2024 8:58 TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR 87 11627 2 SUPER 91 11627 3 DIESEL 11627 4 0 I62300 APR 16, 2024 8:58 TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR 87 10464 2 SUPER 91 10464 3 DIESEL 10464 4 0 I62200 APR 16, 2024 8:58 TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR 87 11046 2 SUPER 91 11046 3 DIESEL 11046 4 0 I62900 APR 16, 2024 8:58 TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR 87 1163 2 SUPER 91 1163 3 DIESEL 1163 4 0 I62100 APR 16, 2024 8:58 TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR 87 800 2 SUPER 91 800 3 DIESEL 800 4 0 I62600 APR 16, 2024 8:58 TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR 87 99 2 SUPER 91 99 3 DIESEL 99 4 99 I62500 APR 16, 2024 8:59 TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR 87 99 2 SUPER 91 99 3 DIESEL 99 4 99 I60800 APR 16, 2024 8:59 TANK TILT TANK PRODUCT LABEL INCHES 1 REGULAR 87 1.00 2 SUPER 91 1.50 3 DIESEL 1.75 4 0.00 I60B00 APR 16, 2024 8:59 STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 APR 16, 2024 8:59 TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 REGULAR 87 0.00 2 SUPER 91 0.00 3 DIESEL 0.00 4 0.00 I61200 APR 16, 2024 8:59 TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 REGULAR 87 NONE NONE 2 SUPER 91 NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 APR 16, 2024 8:59 PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 REGULAR 87 5813 2 SUPER 91 5813 3 DIESEL 5813 4 0 I62A00 APR 16, 2024 8:59 ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 REGULAR 87 5813 2 SUPER 91 5813 3 DIESEL 5813 4 0 I62C00 APR 16, 2024 8:59 TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 REGULAR 87 STANDARD 2 SUPER 91 STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 APR 16, 2024 8:59 TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 REGULAR 87 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 SUPER 91 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 APR 16, 2024 8:59 TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 REGULAR 87 OFF OFF 2 SUPER 91 OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 APR 16, 2024 8:59 IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 REGULAR 87 OFF 2 SUPER 91 OFF 3 DIESEL OFF 4 OFF I63200 APR 16, 2024 8:59 TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 REGULAR 87 OFF 2 SUPER 91 OFF 3 DIESEL OFF 4 OFF I61000 APR 16, 2024 8:59 TANK DELIVERY DELAY TANK PRODUCT LABEL 1 REGULAR 87 1 2 SUPER 91 1 3 DIESEL 1 4 1 I63A00 APR 16, 2024 8:59 LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 REGULAR 87 10.00% 2 SUPER 91 10.00% 3 DIESEL 10.00% 4 10.00% I61100 APR 16, 2024 8:59 LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK MAY 29, 2015 START TIME : 7:55 PM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 APR 16, 2024 8:59 CSLD PROBABLITY OF DETECTION I61400 APR 16, 2024 8:59 CSLD CLIMATE FACTOR I61600 APR 16, 2024 8:59 TANK PRODUCT LABEL CAL UPDATE 1 REGULAR 87 IMMEDIATE 2 SUPER 91 IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 APR 16, 2024 8:59 IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 REGULAR 87 DISABLED 2 SUPER 91 DISABLED 3 DIESEL DISABLED 4 DISABLED I61B00 APR 16, 2024 8:59 IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 APR 16, 2024 8:59 CSLD REPORT ONLY I62B00 APR 16, 2024 8:59 TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 REGULAR 87 ??? 0, 0 2 SUPER 91 ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 APR 16, 2024 8:59 LEAK TEST REPORT FORMAT: NORMAL I63400 APR 16, 2024 8:59 RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR 87 0 2 SUPER 91 0 3 DIESEL 0 4 0 I63500 APR 16, 2024 8:59 RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR 87 1 2 SUPER 91 1 3 DIESEL 1 4 1 I63900 APR 16, 2024 8:59 ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 REGULAR 87 END FACTOR: NONE 2 SUPER 91 END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 APR 16, 2024 8:59 I77700 APR 16, 2024 8:59 I77800 APR 16, 2024 8:59 I78C00 APR 16, 2024 8:59 I78300 APR 16, 2024 8:59 I78F00 APR 16, 2024 8:59 I78700 APR 16, 2024 8:59 I70200 APR 16, 2024 8:59 LIQUID LABEL DEVICE LABEL 1 REG 87 ANN 2 REG 87 STP SUMP 3 REG 87 FILL 4 SUPER 91 STP 5 SUPER 91 ANN 6 SUPER 91 FILL 7 DIESEL ANN 8 DIESEL STP SUMP 9 DIESEL FILL 10 1-2 UDC 11 3-4 UDC 12 5-6 UDC 13 7-8 UDC 14 9-10 UDC 15 11-12 UDC 16 VENT BOX UDC I70300 APR 16, 2024 8:59 LIQUID TYPE SENSOR LOCATION TYPE 1 REG 87 ANN TRI-STATE (SINGLE FLOAT) 2 REG 87 STP SUMP TRI-STATE (SINGLE FLOAT) 3 REG 87 FILL TRI-STATE (SINGLE FLOAT) 4 SUPER 91 STP TRI-STATE (SINGLE FLOAT) 5 SUPER 91 ANN TRI-STATE (SINGLE FLOAT) 6 SUPER 91 FILL TRI-STATE (SINGLE FLOAT) 7 DIESEL ANN TRI-STATE (SINGLE FLOAT) 8 DIESEL STP SUMP TRI-STATE (SINGLE FLOAT) 9 DIESEL FILL TRI-STATE (SINGLE FLOAT) 10 1-2 UDC TRI-STATE (SINGLE FLOAT) 11 3-4 UDC TRI-STATE (SINGLE FLOAT) 12 5-6 UDC TRI-STATE (SINGLE FLOAT) 13 7-8 UDC TRI-STATE (SINGLE FLOAT) 14 9-10 UDC TRI-STATE (SINGLE FLOAT) 15 11-12 UDC TRI-STATE (SINGLE FLOAT) 16 VENT BOX UDC TRI-STATE (SINGLE FLOAT) I70400 APR 16, 2024 8:59 LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 REG 87 ANN ANNULAR SPACE 2 REG 87 STP SUMP STP SUMP 3 REG 87 FILL PIPING SUMP 4 SUPER 91 STP STP SUMP 5 SUPER 91 ANN ANNULAR SPACE 6 SUPER 91 FILL PIPING SUMP 7 DIESEL ANN ANNULAR SPACE 8 DIESEL STP SUMP STP SUMP 9 DIESEL FILL PIPING SUMP 10 1-2 UDC DISPENSER PAN 11 3-4 UDC DISPENSER PAN 12 5-6 UDC DISPENSER PAN 13 7-8 UDC DISPENSER PAN 14 9-10 UDC DISPENSER PAN 15 11-12 UDC DISPENSER PAN 16 VENT BOX UDC OTHER SENSORS I74200 APR 16, 2024 8:59 I74300 APR 16, 2024 8:59 I74400 APR 16, 2024 8:59 I74700 APR 16, 2024 8:59 I74800 APR 16, 2024 8:59 I74900 APR 16, 2024 8:59 I7BC00 APR 16, 2024 8:59 I80200 APR 16, 2024 8:59 I80300 APR 16, 2024 8:59 I80400 APR 16, 2024 8:59 I80700 APR 16, 2024 8:59 RELAY LABEL DEVICE LABEL 1 REG 87 2 SUPER 91 3 DIESEL 4 OVERFILL I80900 APR 16, 2024 8:59 RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 REG 87 NORMALLY CLOSED 2 SUPER 91 NORMALLY CLOSED 3 DIESEL NORMALLY CLOSED 4 OVERFILL NORMALLY OPEN I80B00 APR 16, 2024 8:59 RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 REG 87 1 2 SUPER 91 2 3 DIESEL 3 4 OVERFILL NONE I80A00 APR 16, 2024 8:59 RELAY TYPE RELAY DESIGNATION TYPE 1 REG 87 STANDARD 2 SUPER 91 STANDARD 3 DIESEL STANDARD 4 OVERFILL STANDARD I80C00 APR 16, 2024 8:59 I80800 APR 16, 2024 8:59 RELAY SETUP REPORT R 1:REG 87 TYPE: STANDARD NORMALLY CLOSED TANK #: 1 IN-TANK ALARMS T 1:HIGH WATER ALARM LIQUID SENSOR ALMS L 2:FUEL ALARM L 3:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L 2:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L15:SENSOR OUT ALARM L 2:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM L15:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD SENSOR OUT FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL R 2:SUPER 91 TYPE: STANDARD NORMALLY CLOSED TANK #: 2 IN-TANK ALARMS T 2:HIGH WATER ALARM LIQUID SENSOR ALMS L 4:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L 4:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L15:SENSOR OUT ALARM L 4:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM L15:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD SENSOR OUT FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL R 3:DIESEL TYPE: STANDARD NORMALLY CLOSED TANK #: 3 IN-TANK ALARMS T 3:HIGH WATER ALARM LIQUID SENSOR ALMS L 8:FUEL ALARM L11:FUEL ALARM L13:FUEL ALARM L15:FUEL ALARM L 8:SENSOR OUT ALARM L11:SENSOR OUT ALARM L13:SENSOR OUT ALARM L15:SENSOR OUT ALARM L 8:SHORT ALARM L11:SHORT ALARM L13:SHORT ALARM L15:SHORT ALARM R 4:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:HIGH WATER ALARM ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 APR 16, 2024 9:00 EDIM:1 VR:349867-001-A TD:15.10.21.11.32 I79100 APR 16, 2024 9:00 I72300 APR 16, 2024 9:00 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 1-2 FM AIR FLOW METER 02 3-4 FM AIR FLOW METER 03 5-6 FM AIR FLOW METER 04 7-8 FM AIR FLOW METER 05 9-10 FM AIR FLOW METER 06 11-12 FM AIR FLOW METER 07 VAPOR PRESS SENSOR VAPOR PRESSURE 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 APR 16, 2024 9:00 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 APR 16, 2024 9:00 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 APR 16, 2024 9:00 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 VAPOR PROCESSOR TYPE NONE IV4700 APR 16, 2024 9:00 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 ASSESSMENT TIME START TIME: 10:00 TIME DELAY MINUTES: 1 IV5200 APR 16, 2024 9:00 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 ACCEPT HIGH ORVR: NO IV4A00 APR 16, 2024 9:00 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 02 BLEND3 02 02 02 01 02 BLEND3 03 03 03 02 02 BLEND3 04 04 04 02 02 BLEND3 05 05 05 03 02 BLEND3 06 06 06 03 02 BLEND3 07 07 07 04 02 BLEND3 08 08 08 04 02 BLEND3 09 09 09 05 02 BLEND3 10 16 10 05 02 BLEND3 11 17 11 06 02 BLEND3 12 18 12 06 02 BLEND3 IV4B00 APR 16, 2024 9:00 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 01/01 09/01 xx/xx 02 01 02/02 01/02 09/02 xx/xx 03 02 02/03 01/03 09/03 xx/xx 04 02 02/04 01/04 09/04 xx/xx 05 03 02/05 01/05 09/05 xx/xx 06 03 02/06 01/06 09/06 xx/xx 07 04 02/07 01/07 09/07 xx/xx 08 04 02/08 01/08 09/08 xx/xx 09 05 02/09 01/09 09/09 xx/xx 16 05 02/10 01/10 09/10 xx/xx 17 06 02/11 01/11 09/11 xx/xx 18 06 02/12 01/12 09/12 xx/xx IV4900 APR 16, 2024 9:00 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 APR 16, 2024 9:00 ISD VERSION: 01.07 FASTRIP #9933 ALARM HISTORY BEFORE: Responses Received: I10200 APR 16, 2024 9:01 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9451440 9466118 2 4 PROBE / G.T. 162519 163018 3 INTERSTITIAL BD 199924 200533 4 INTERSTITIAL BD 200717 201245 5 UNUSED 9402984 9447020 6 8SMARTSENSOR BD 39229 39377 7 UNUSED 9394908 9458065 8 UNUSED 9398533 9443698 9 RELAY BOARD 14941 14992 10 UNUSED 9391675 9450286 11 UNUSED 9387767 9447954 12 UNUSED 9395192 9449406 13 UNUSED 9384706 9441837 14 UNUSED 9379821 9442167 15 UNUSED 9377064 9445270 16 UNUSED 9387072 9455611 COMM 1 ELEC DISP INT. 100453 100741 COMM 2 SERIAL SAT BD 483966 485847 COMM 3 RS232 SERIAL BD 14963 15036 COMM 4 UNUSED 9392152 9448086 COMM 5 RS485 SERIAL BD 68538 68755 COMM 6 RS232 SERIAL BD 15007 15080 I90200 APR 16, 2024 9:01 SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 APR 16, 2024 9:01 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 8 STP SUMP DIESEL STP SUMP FUEL ALARM CLEAR APR 14 2024 18:54 L 8 STP SUMP DIESEL STP SUMP FUEL ALARM ALARM APR 14 2024 15:28 L 9 PIPE DIESEL FILL FUEL ALARM CLEAR APR 14 2024 13:15 L 9 PIPE DIESEL FILL FUEL ALARM ALARM APR 14 2024 11:57 L 8 STP SUMP DIESEL STP SUMP FUEL ALARM CLEAR APR 13 2024 20:11 L 9 PIPE DIESEL FILL FUEL ALARM CLEAR APR 13 2024 19:57 L 8 STP SUMP DIESEL STP SUMP FUEL ALARM ALARM APR 13 2024 17:08 L 9 PIPE DIESEL FILL FUEL ALARM ALARM APR 13 2024 16:32 T 3 TANK DIESEL PROBE OUT CLEAR APR 11 2024 8:44 T 3 TANK DIESEL PROBE OUT ALARM APR 11 2024 8:44 T 3 TANK DIESEL PROBE OUT CLEAR APR 11 2024 8:32 T 3 TANK DIESEL PROBE OUT ALARM APR 11 2024 8:32 T 1 TANK REGULAR 87 OVERFILL ALARM CLEAR APR 6 2024 22:37 T 1 TANK REGULAR 87 OVERFILL ALARM ALARM APR 6 2024 22:34 T 1 TANK REGULAR 87 OVERFILL ALARM CLEAR APR 6 2024 1:40 T 1 TANK REGULAR 87 OVERFILL ALARM ALARM APR 6 2024 1:36 L 4 STP SUMP SUPER 91 STP SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L 3 PIPE REG 87 FILL SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L 7 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L 1 ANNULAR REG 87 ANN SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L 2 STP SUMP REG 87 STP SUMP SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L 5 ANNULAR SUPER 91 ANN SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L 8 STP SUMP DIESEL STP SUMP SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L 6 PIPE SUPER 91 FILL SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L13 DISP PAN 7-8 UDC SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L12 DISP PAN 5-6 UDC SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L11 DISP PAN 3-4 UDC SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L10 DISP PAN 1-2 UDC SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L16 OTHER VENT BOX UDC SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L15 DISP PAN 11-12 UDC SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L 9 PIPE DIESEL FILL SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L14 DISP PAN 9-10 UDC SENSOR OUT ALARM CLEAR APR 3 2024 11:19 L 7 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM APR 3 2024 11:16 L 1 ANNULAR REG 87 ANN SENSOR OUT ALARM ALARM APR 3 2024 11:16 L 2 STP SUMP REG 87 STP SUMP SENSOR OUT ALARM ALARM APR 3 2024 11:16 L16 OTHER VENT BOX UDC SENSOR OUT ALARM ALARM APR 3 2024 11:16 L15 DISP PAN 11-12 UDC SENSOR OUT ALARM ALARM APR 3 2024 11:16 L 5 ANNULAR SUPER 91 ANN SENSOR OUT ALARM ALARM APR 3 2024 11:16 L 8 STP SUMP DIESEL STP SUMP SENSOR OUT ALARM ALARM APR 3 2024 11:16 L14 DISP PAN 9-10 UDC SENSOR OUT ALARM ALARM APR 3 2024 11:16 L 6 PIPE SUPER 91 FILL SENSOR OUT ALARM ALARM APR 3 2024 11:16 L 4 STP SUMP SUPER 91 STP SENSOR OUT ALARM ALARM APR 3 2024 11:16 L12 DISP PAN 5-6 UDC SENSOR OUT ALARM ALARM APR 3 2024 11:16 L11 DISP PAN 3-4 UDC SENSOR OUT ALARM ALARM APR 3 2024 11:16 L 3 PIPE REG 87 FILL SENSOR OUT ALARM ALARM APR 3 2024 11:16 L10 DISP PAN 1-2 UDC SENSOR OUT ALARM ALARM APR 3 2024 11:16 L 9 PIPE DIESEL FILL SENSOR OUT ALARM ALARM APR 3 2024 11:16 L13 DISP PAN 7-8 UDC SENSOR OUT ALARM ALARM APR 3 2024 11:16 L 1 ANNULAR REG 87 ANN FUEL ALARM CLEAR APR 3 2024 11:08 L 1 ANNULAR REG 87 ANN FUEL ALARM ALARM APR 3 2024 11:07 I11200 APR 16, 2024 9:01 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK REGULAR 87 INVALID FUEL LEVEL CLEAR APR 16 2024 0:55 T 1 TANK REGULAR 87 INVALID FUEL LEVEL ALARM APR 16 2024 0:54 T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR APR 11 2024 8:33 T 3 TANK DIESEL INVALID FUEL LEVEL ALARM APR 11 2024 8:32 T 1 TANK REGULAR 87 INVALID FUEL LEVEL CLEAR APR 3 2024 23:32 T 1 TANK REGULAR 87 INVALID FUEL LEVEL ALARM APR 3 2024 23:32 T 1 TANK REGULAR 87 INVALID FUEL LEVEL CLEAR APR 1 2024 6:11 T 1 TANK REGULAR 87 INVALID FUEL LEVEL ALARM APR 1 2024 6:11 T 1 TANK REGULAR 87 HIGH PRODUCT ALARM CLEAR MAR 30 2024 11:23 T 1 TANK REGULAR 87 HIGH PRODUCT ALARM ALARM MAR 30 2024 10:01 h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR MAR 11 2024 15:56 h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM MAR 10 2024 10:01 h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN CLEAR FEB 26 2024 17:06 h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN ALARM FEB 23 2024 10:01 T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR FEB 19 2024 22:30 T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM FEB 19 2024 21:44 OTHER ISD GROSS PRES WARN CLEAR FEB 19 2024 10:02 OTHER ISD GROSS PRES WARN ALARM FEB 19 2024 10:01 SYSTEM PRINTER ERROR CLEAR FEB 17 2024 21:42 SYSTEM PAPER OUT CLEAR FEB 17 2024 21:42 SYSTEM PAPER OUT ALARM FEB 17 2024 21:41 SYSTEM PRINTER ERROR ALARM FEB 17 2024 21:41 SYSTEM PRINTER ERROR CLEAR FEB 17 2024 21:41 SYSTEM PRINTER ERROR ALARM FEB 17 2024 21:41 SYSTEM PRINTER ERROR CLEAR FEB 17 2024 21:41 SYSTEM PAPER OUT CLEAR FEB 17 2024 21:41 SYSTEM PRINTER ERROR ALARM FEB 17 2024 21:39 SYSTEM PAPER OUT ALARM FEB 17 2024 21:39 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR FEB 17 2024 10:00 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM FEB 16 2024 10:01 h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR FEB 15 2024 10:00 h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM FEB 14 2024 10:01 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR FEB 12 2024 10:46 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM FEB 11 2024 10:01 OTHER ISD GROSS PRES WARN CLEAR FEB 10 2024 10:03 OTHER ISD GROSS PRES WARN ALARM FEB 10 2024 10:01 T 2 TANK SUPER 91 DELIVERY NEEDED CLEAR FEB 4 2024 14:00 T 2 TANK SUPER 91 DELIVERY NEEDED ALARM FEB 4 2024 14:00 OTHER ISD GROSS PRES WARN CLEAR FEB 1 2024 7:31 OTHER ISD GROSS PRES WARN ALARM JAN 31 2024 10:01 OTHER ISD SENSOR OUT WARN CLEAR JAN 26 2024 12:07 OTHER ISD SENSOR OUT WARN ALARM JAN 26 2024 10:02 T 1 TANK REGULAR 87 INVALID FUEL LEVEL CLEAR JAN 7 2024 17:41 T 1 TANK REGULAR 87 INVALID FUEL LEVEL ALARM JAN 7 2024 17:41 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR JAN 5 2024 10:14 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM JAN 4 2024 10:03 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR DEC 27 2023 10:00 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM DEC 25 2023 10:02 SYSTEM PRINTER ERROR CLEAR DEC 19 2023 8:36 SYSTEM PAPER OUT CLEAR DEC 19 2023 8:36 I20600 APR 16, 2024 9:01 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 TANK ALARM HISTORY TANK 1 REGULAR 87 OVERFILL ALARM APR 6, 2024 22:34 APR 6, 2024 1:36 MAR 30, 2024 9:58 LOW PRODUCT ALARM SEP 1, 2023 18:52 AUG 25, 2023 18:13 HIGH PRODUCT ALARM MAR 30, 2024 10:01 OCT 27, 2023 9:19 INVALID FUEL LEVEL APR 16, 2024 0:54 APR 3, 2024 23:32 APR 1, 2024 6:11 DELIVERY NEEDED FEB 19, 2024 21:44 NOV 16, 2023 18:32 OCT 16, 2023 18:37 TANK 2 SUPER 91 OVERFILL ALARM JUL 25, 2023 6:59 JUL 25, 2023 6:55 JUL 15, 2023 17:16 DELIVERY NEEDED FEB 4, 2024 14:00 TANK 3 DIESEL OVERFILL ALARM MAR 29, 2024 13:22 OCT 18, 2023 22:48 INVALID FUEL LEVEL APR 11, 2024 8:32 PROBE OUT APR 11, 2024 8:44 APR 11, 2024 8:32 TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 APR 16, 2024 9:01 I30200 APR 16, 2024 9:01 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 REG 87 ANN APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 11:07 FUEL ALARM APR 3, 2024 11:05 FUEL ALARM 2 REG 87 STP SUMP APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:22 FUEL ALARM APR 3, 2024 10:07 FUEL ALARM 3 REG 87 FILL APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:21 FUEL ALARM JAN 21, 2024 6:24 FUEL ALARM 4 SUPER 91 STP APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:22 FUEL ALARM FEB 1, 2024 7:28 FUEL ALARM 5 SUPER 91 ANN APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:59 FUEL ALARM APR 3, 2024 10:58 FUEL ALARM 6 SUPER 91 FILL APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:20 FUEL ALARM JUL 31, 2023 13:55 FUEL ALARM 7 DIESEL ANN APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:51 FUEL ALARM APR 3, 2024 10:49 FUEL ALARM 8 DIESEL STP SUMP APR 14, 2024 15:28 FUEL ALARM APR 13, 2024 17:08 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 9 DIESEL FILL APR 14, 2024 11:57 FUEL ALARM APR 13, 2024 16:32 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 10 1-2 UDC APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:24 FUEL ALARM JUL 31, 2023 13:26 FUEL ALARM 11 3-4 UDC APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:25 FUEL ALARM JUL 31, 2023 13:26 FUEL ALARM 12 5-6 UDC APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:26 FUEL ALARM JUL 31, 2023 13:27 FUEL ALARM 13 7-8 UDC APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:25 FUEL ALARM JUL 31, 2023 13:28 FUEL ALARM 14 9-10 UDC APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:27 FUEL ALARM JUL 31, 2023 13:28 FUEL ALARM 15 11-12 UDC APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:28 FUEL ALARM JUL 31, 2023 13:29 FUEL ALARM 16 VENT BOX UDC APR 3, 2024 11:16 SENSOR OUT ALARM APR 3, 2024 10:39 FUEL ALARM JUN 14, 2023 11:04 FUEL ALARM I31600 APR 16, 2024 9:01 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 1-2 FM 2 3-4 FM 3 5-6 FM 4 7-8 FM 5 9-10 FM 6 11-12 FM 7 VAPOR PRESS SENSOR I40200 APR 16, 2024 9:01 I40300 APR 16, 2024 9:01 I34200 APR 16, 2024 9:01 I34700 APR 16, 2024 9:01 IV0100 APR 16, 2024 9:01 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-03-11 10:01:40 A/L RATIO DEGRADATION FP12 BLEND3 0.81 24-03-10 10:01:43 A/L RATIO DEGRADATION FP12 BLEND3 0.79 24-02-26 10:01:17 A/L RATIO DEGRADATION FP11 BLEND3 0.79 24-02-25 10:01:17 A/L RATIO DEGRADATION FP11 BLEND3 0.80 24-02-24 10:01:09 A/L RATIO DEGRADATION FP11 BLEND3 0.79 24-02-23 10:01:09 A/L RATIO DEGRADATION FP11 BLEND3 0.79 24-02-19 10:01:32 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.59 24-02-16 10:01:22 A/L RATIO DEGRADATION FP 6 BLEND3 1.35 24-02-14 10:01:09 A/L RATIO DEGRADATION FP 1 BLEND3 0.81 24-02-12 10:01:10 A/L RATIO DEGRADATION FP 6 BLEND3 1.38 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-10-04 10:03:34 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 23-06-19 10:03:00 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 23-06-11 10:01:33 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 23-05-02 10:01:17 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-05-02 10:01:17 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 23-05-01 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-04-30 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-03-26 10:01:09 A/L RATIO DEGRADATION FP 9 BLEND3 0.73 22-09-06 10:03:02 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 22-09-06 10:03:01 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-04-04 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 24-04-03 11:20:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-04-03 11:20:30 ISD STARTUP 24-04-03 11:20:26 ISD SHUTDOWN 24-04-01 06:31:12 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-03-11 15:56:09 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 24-03-10 03:15:00 TIME CHANGE DETECTED AT: 24-03-10 02:14:17 24-02-26 17:06:08 COLLECTION TEST HH11 GRADE TEST MANUALLY CLEARED 24-02-19 10:02:49 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-02-12 10:46:36 COLLECTION TEST HH06 GRADE TEST MANUALLY CLEARED AFTER: Responses Received: I10200 APR 16, 2024 11:53 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9451440 9402168 2 4 PROBE / G.T. 162519 162386 3 INTERSTITIAL BD 199924 199746 4 INTERSTITIAL BD 200717 200731 5 UNUSED 9402984 9379495 6 8SMARTSENSOR BD 39229 39242 7 UNUSED 9394908 9401883 8 UNUSED 9398533 9386190 9 RELAY BOARD 14941 14940 10 UNUSED 9391675 9394872 11 UNUSED 9387767 9391031 12 UNUSED 9395192 9386707 13 UNUSED 9384706 9380451 14 UNUSED 9379821 9384929 15 UNUSED 9377064 9393664 16 UNUSED 9387072 9388967 COMM 1 ELEC DISP INT. 100453 100394 COMM 2 SERIAL SAT BD 483966 484035 COMM 3 RS232 SERIAL BD 14963 14984 COMM 4 UNUSED 9392152 9377664 COMM 5 RS485 SERIAL BD 68538 68485 COMM 6 RS232 SERIAL BD 15007 15029 I90200 APR 16, 2024 11:53 SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 APR 16, 2024 11:53 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L16 OTHER VENT BOX UDC FUEL ALARM CLEAR APR 16 2024 11:27 L16 OTHER VENT BOX UDC FUEL ALARM ALARM APR 16 2024 11:27 L 8 STP SUMP DIESEL STP SUMP SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L 7 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L 5 ANNULAR SUPER 91 ANN SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L 4 STP SUMP SUPER 91 STP SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L 6 PIPE SUPER 91 FILL SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L 3 PIPE REG 87 FILL SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L 1 ANNULAR REG 87 ANN SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L16 OTHER VENT BOX UDC SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L15 DISP PAN 11-12 UDC SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L14 DISP PAN 9-10 UDC SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L 2 STP SUMP REG 87 STP SUMP SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L13 DISP PAN 7-8 UDC SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L12 DISP PAN 5-6 UDC SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L11 DISP PAN 3-4 UDC SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L10 DISP PAN 1-2 UDC SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L 9 PIPE DIESEL FILL SENSOR OUT ALARM CLEAR APR 16 2024 10:39 L 1 ANNULAR REG 87 ANN SENSOR OUT ALARM ALARM APR 16 2024 10:38 L16 OTHER VENT BOX UDC SENSOR OUT ALARM ALARM APR 16 2024 10:38 L 2 STP SUMP REG 87 STP SUMP SENSOR OUT ALARM ALARM APR 16 2024 10:38 L 8 STP SUMP DIESEL STP SUMP SENSOR OUT ALARM ALARM APR 16 2024 10:38 L15 DISP PAN 11-12 UDC SENSOR OUT ALARM ALARM APR 16 2024 10:38 L 7 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM APR 16 2024 10:38 L14 DISP PAN 9-10 UDC SENSOR OUT ALARM ALARM APR 16 2024 10:38 L12 DISP PAN 5-6 UDC SENSOR OUT ALARM ALARM APR 16 2024 10:38 L 6 PIPE SUPER 91 FILL SENSOR OUT ALARM ALARM APR 16 2024 10:38 L13 DISP PAN 7-8 UDC SENSOR OUT ALARM ALARM APR 16 2024 10:38 L11 DISP PAN 3-4 UDC SENSOR OUT ALARM ALARM APR 16 2024 10:38 L 5 ANNULAR SUPER 91 ANN SENSOR OUT ALARM ALARM APR 16 2024 10:38 L 4 STP SUMP SUPER 91 STP SENSOR OUT ALARM ALARM APR 16 2024 10:38 L10 DISP PAN 1-2 UDC SENSOR OUT ALARM ALARM APR 16 2024 10:38 L 3 PIPE REG 87 FILL SENSOR OUT ALARM ALARM APR 16 2024 10:38 L 9 PIPE DIESEL FILL SENSOR OUT ALARM ALARM APR 16 2024 10:38 L 3 PIPE REG 87 FILL FUEL ALARM CLEAR APR 16 2024 10:18 L 3 PIPE REG 87 FILL FUEL ALARM ALARM APR 16 2024 10:17 L 3 PIPE REG 87 FILL FUEL ALARM CLEAR APR 16 2024 10:17 L 3 PIPE REG 87 FILL FUEL ALARM ALARM APR 16 2024 10:17 L 6 PIPE SUPER 91 FILL FUEL ALARM CLEAR APR 16 2024 10:16 L 6 PIPE SUPER 91 FILL FUEL ALARM ALARM APR 16 2024 10:16 L 9 PIPE DIESEL FILL FUEL ALARM CLEAR APR 16 2024 10:14 L 9 PIPE DIESEL FILL FUEL ALARM ALARM APR 16 2024 10:14 L 7 ANNULAR DIESEL ANN FUEL ALARM CLEAR APR 16 2024 10:09 L 7 ANNULAR DIESEL ANN FUEL ALARM ALARM APR 16 2024 10:03 L 5 ANNULAR SUPER 91 ANN FUEL ALARM CLEAR APR 16 2024 9:54 L 5 ANNULAR SUPER 91 ANN FUEL ALARM ALARM APR 16 2024 9:53 L 5 ANNULAR SUPER 91 ANN FUEL ALARM CLEAR APR 16 2024 9:53 L 5 ANNULAR SUPER 91 ANN FUEL ALARM ALARM APR 16 2024 9:53 L 5 ANNULAR SUPER 91 ANN FUEL ALARM CLEAR APR 16 2024 9:53 L 5 ANNULAR SUPER 91 ANN FUEL ALARM ALARM APR 16 2024 9:51 I11200 APR 16, 2024 11:53 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR APR 16 2024 9:17 SYSTEM PRINTER ERROR ALARM APR 16 2024 9:16 SYSTEM PRINTER ERROR CLEAR APR 16 2024 9:16 SYSTEM PAPER OUT CLEAR APR 16 2024 9:16 SYSTEM PAPER OUT ALARM APR 16 2024 9:15 SYSTEM PRINTER ERROR ALARM APR 16 2024 9:15 T 1 TANK REGULAR 87 INVALID FUEL LEVEL CLEAR APR 16 2024 0:55 T 1 TANK REGULAR 87 INVALID FUEL LEVEL ALARM APR 16 2024 0:54 T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR APR 11 2024 8:33 T 3 TANK DIESEL INVALID FUEL LEVEL ALARM APR 11 2024 8:32 T 1 TANK REGULAR 87 INVALID FUEL LEVEL CLEAR APR 3 2024 23:32 T 1 TANK REGULAR 87 INVALID FUEL LEVEL ALARM APR 3 2024 23:32 T 1 TANK REGULAR 87 INVALID FUEL LEVEL CLEAR APR 1 2024 6:11 T 1 TANK REGULAR 87 INVALID FUEL LEVEL ALARM APR 1 2024 6:11 T 1 TANK REGULAR 87 HIGH PRODUCT ALARM CLEAR MAR 30 2024 11:23 T 1 TANK REGULAR 87 HIGH PRODUCT ALARM ALARM MAR 30 2024 10:01 h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR MAR 11 2024 15:56 h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM MAR 10 2024 10:01 h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN CLEAR FEB 26 2024 17:06 h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN ALARM FEB 23 2024 10:01 T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR FEB 19 2024 22:30 T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM FEB 19 2024 21:44 OTHER ISD GROSS PRES WARN CLEAR FEB 19 2024 10:02 OTHER ISD GROSS PRES WARN ALARM FEB 19 2024 10:01 SYSTEM PRINTER ERROR CLEAR FEB 17 2024 21:42 SYSTEM PAPER OUT CLEAR FEB 17 2024 21:42 SYSTEM PAPER OUT ALARM FEB 17 2024 21:41 SYSTEM PRINTER ERROR ALARM FEB 17 2024 21:41 SYSTEM PRINTER ERROR CLEAR FEB 17 2024 21:41 SYSTEM PRINTER ERROR ALARM FEB 17 2024 21:41 SYSTEM PRINTER ERROR CLEAR FEB 17 2024 21:41 SYSTEM PAPER OUT CLEAR FEB 17 2024 21:41 SYSTEM PRINTER ERROR ALARM FEB 17 2024 21:39 SYSTEM PAPER OUT ALARM FEB 17 2024 21:39 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR FEB 17 2024 10:00 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM FEB 16 2024 10:01 h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR FEB 15 2024 10:00 h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM FEB 14 2024 10:01 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR FEB 12 2024 10:46 h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM FEB 11 2024 10:01 OTHER ISD GROSS PRES WARN CLEAR FEB 10 2024 10:03 OTHER ISD GROSS PRES WARN ALARM FEB 10 2024 10:01 T 2 TANK SUPER 91 DELIVERY NEEDED CLEAR FEB 4 2024 14:00 T 2 TANK SUPER 91 DELIVERY NEEDED ALARM FEB 4 2024 14:00 OTHER ISD GROSS PRES WARN CLEAR FEB 1 2024 7:31 OTHER ISD GROSS PRES WARN ALARM JAN 31 2024 10:01 OTHER ISD SENSOR OUT WARN CLEAR JAN 26 2024 12:07 OTHER ISD SENSOR OUT WARN ALARM JAN 26 2024 10:02 T 1 TANK REGULAR 87 INVALID FUEL LEVEL CLEAR JAN 7 2024 17:41 T 1 TANK REGULAR 87 INVALID FUEL LEVEL ALARM JAN 7 2024 17:41 I20600 APR 16, 2024 11:53 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 TANK ALARM HISTORY TANK 1 REGULAR 87 OVERFILL ALARM APR 6, 2024 22:34 APR 6, 2024 1:36 MAR 30, 2024 9:58 LOW PRODUCT ALARM SEP 1, 2023 18:52 AUG 25, 2023 18:13 HIGH PRODUCT ALARM MAR 30, 2024 10:01 OCT 27, 2023 9:19 INVALID FUEL LEVEL APR 16, 2024 0:54 APR 3, 2024 23:32 APR 1, 2024 6:11 DELIVERY NEEDED FEB 19, 2024 21:44 NOV 16, 2023 18:32 OCT 16, 2023 18:37 TANK 2 SUPER 91 OVERFILL ALARM JUL 25, 2023 6:59 JUL 25, 2023 6:55 JUL 15, 2023 17:16 DELIVERY NEEDED FEB 4, 2024 14:00 TANK 3 DIESEL OVERFILL ALARM MAR 29, 2024 13:22 OCT 18, 2023 22:48 INVALID FUEL LEVEL APR 11, 2024 8:32 PROBE OUT APR 11, 2024 8:44 APR 11, 2024 8:32 TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 APR 16, 2024 11:53 I30200 APR 16, 2024 11:53 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 REG 87 ANN APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:48 FUEL ALARM APR 16, 2024 9:47 FUEL ALARM 2 REG 87 STP SUMP APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:40 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 3 REG 87 FILL APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 10:17 FUEL ALARM APR 16, 2024 10:17 FUEL ALARM 4 SUPER 91 STP APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:39 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 5 SUPER 91 ANN APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:53 FUEL ALARM APR 16, 2024 9:53 FUEL ALARM 6 SUPER 91 FILL APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 10:16 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 7 DIESEL ANN APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 10:03 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 8 DIESEL STP SUMP APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:39 FUEL ALARM APR 14, 2024 15:28 FUEL ALARM 9 DIESEL FILL APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 10:14 FUEL ALARM APR 14, 2024 11:57 FUEL ALARM 10 1-2 UDC APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:33 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 11 3-4 UDC APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:34 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 12 5-6 UDC APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:36 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 13 7-8 UDC APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:35 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 14 9-10 UDC APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:37 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 15 11-12 UDC APR 16, 2024 10:38 SENSOR OUT ALARM APR 16, 2024 9:38 FUEL ALARM APR 3, 2024 11:16 SENSOR OUT ALARM 16 VENT BOX UDC APR 16, 2024 11:27 FUEL ALARM APR 16, 2024 10:38 SENSOR OUT ALARM APR 3, 2024 11:16 SENSOR OUT ALARM I31600 APR 16, 2024 11:54 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 1-2 FM 2 3-4 FM 3 5-6 FM 4 7-8 FM 5 9-10 FM 6 11-12 FM 7 VAPOR PRESS SENSOR I40200 APR 16, 2024 11:54 I40300 APR 16, 2024 11:54 I34200 APR 16, 2024 11:54 I34700 APR 16, 2024 11:54 IV0100 APR 16, 2024 11:54 9933 FASTRIP 4800 FAIRFAX RD BAKERSFIELD CA 93306 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-03-11 10:01:40 A/L RATIO DEGRADATION FP12 BLEND3 0.81 24-03-10 10:01:43 A/L RATIO DEGRADATION FP12 BLEND3 0.79 24-02-26 10:01:17 A/L RATIO DEGRADATION FP11 BLEND3 0.79 24-02-25 10:01:17 A/L RATIO DEGRADATION FP11 BLEND3 0.80 24-02-24 10:01:09 A/L RATIO DEGRADATION FP11 BLEND3 0.79 24-02-23 10:01:09 A/L RATIO DEGRADATION FP11 BLEND3 0.79 24-02-19 10:01:32 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.59 24-02-16 10:01:22 A/L RATIO DEGRADATION FP 6 BLEND3 1.35 24-02-14 10:01:09 A/L RATIO DEGRADATION FP 1 BLEND3 0.81 24-02-12 10:01:10 A/L RATIO DEGRADATION FP 6 BLEND3 1.38 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-10-04 10:03:34 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 23-06-19 10:03:00 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 23-06-11 10:01:33 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 23-05-02 10:01:17 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-05-02 10:01:17 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 23-05-01 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-04-30 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-03-26 10:01:09 A/L RATIO DEGRADATION FP 9 BLEND3 0.73 22-09-06 10:03:02 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 22-09-06 10:03:01 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-04-16 10:40:01 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-04-16 10:40:01 ISD STARTUP 24-04-16 10:39:45 ISD SHUTDOWN 24-04-04 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 24-04-03 11:20:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-04-03 11:20:30 ISD STARTUP 24-04-03 11:20:26 ISD SHUTDOWN 24-04-01 06:31:12 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-03-11 15:56:09 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 24-03-10 03:15:00 TIME CHANGE DETECTED AT: 24-03-10 02:14:17