HomeMy WebLinkAbout2024 FMCAppendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10134208 04/18/2024
Jaco #3351 Howard's #4
3200 Panama Lane Bakersfield 93313
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
VeederRoot TLS-3XX Technician - C32655 10/11/2024
Vaporless Manufacturing Inc. #5265 10/21/2024
EMCO Wheaton 3-5 03/17/2025
04/18/2024 7
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS-350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208/304 87-1 Unleaded STP
L2 208/304 87-1 Unleaded Fill
L3 208/304 87-2 Unleaded STP
L4 208/304 87-2 Unleaded Fill
L5 208/304 91 Premium STP
L6 208/304 91 Premium Fill
L7 208/304 Diesel STP
L8 208/304 Diesel Fill
L9 208/304 Dispenser 1-2 UDC
L10 208/304 Dispenser 3-4 UDC
L11 208/304 Dispenser 5-6 UDC
L12 208/304 Dispenser 7-8 UDC
L13 208/304 Vent Box
S1 463/464 87-1 Product
S2 463/464 87-1 Vent
S3 436/420 87-1 Tank ANN
S4 463/464 87-2 Product
S5 464/464 87-2 Vent
S6 463/420 87-2 Tank ANN
S7 463/464 87-2 Vapor
S9 463/464 91 Product
S10 463/464 91 Vent
S11 463/420 91 Tank ANN
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
S12 463/464 Diesel Product
S13 463/464 Diesel Vent
S14 463/420 Diesel Tank ANN
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Q1 848480-001 87-1 & 87-2 Unleaded
Q2 848480-001 91 Premium
Q3 848480-001 Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
04/18/2024
STP
PROPERTY LINE
NO PARKING
4 3
8 7
65 21
STP
STP
STP
F
F
F
FV
V
V
12,000 GALLON87-1 UNLEADED
12,000 GALLON87-2 UNLEADED
12,000 GALLONPREMIUM
12,000 GALLONDIESEL
H
PANAMA LN.WIBLE RD.EXISTING BUILDING
W
CATCHBASINPRICE SIGNDUMPSTER
GATED ENCLOSURE WITHA STAND ALONE ROOF
PROPERTY LINE
N
V-GUTTER
SWITCHGEAR
87 GAS 1.5" OMEGAFLEX PIPE
91 GAS 1.5" OMEGAFLEX PIPE
DIESEL 1.5" OMEGAFLEX PIPE
VAPOR RETURN 3/2 INCH DBL WALL PIPE
VAPOR RETURN 3/2 INCH MANIFOLDS
VAPOR RETURN 4/3 INCH DBL WALL PIPE
VAPOR VENT 3/2 INCH DBL WALL PIPE
VACUUM CROSSOVER 3/2 DBL WALL PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
WATER SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
AUTOMATIC TANK GAUGE
UST ELECTRICAL PANEL
CIRCUIT BREAKER
AIR AND WATER DISPENSER
HAZWASTE DRUM
H
F
V
W
S1 87-1 PRODUCT LINE SMART SENSOR
S2 87-1 VENT LINE SMART SENSOR
S3 87-1 TANK ANNULAR SMART SENSOR
S4 87-2 PRODUCT LINE SMART SENSOR
S5 87-2 VENT LINE SMART SENSOR
S6 87-2 TANK ANNULAR SMART SENSOR
S7 87-2 VAPOR LINE SMART SENSOR
S8 TEMPERATURE SENSOR METER
S9 PREMIUM PRODUCT SMART SENSOR
S10 PREMIUM VENT LINE SMART SENSOR
S11 PREMIUM TANK ANNULAR SMART SENSOR
S12 DIESEL PRODUCT SMART SENSOR
S13 DIESEL VENT LINE SMART SENSOR
S14 DIESEL TANK ANNULAR SMART SENSOR
LEGEND
L1 87-1 STP SUMP
L2 87-1 FILL SUMP
L3 87-2 STP SUMP
L4 87-2 FILL SUMP
L5 PREMIUM STP SUMP
L6 PREMIUM FILL SUMP
L7 DIESEL STP SUMP
L8 DIESEL FILL SUMP
L9 UDC 1-2
L10 UDC 3-4
L11 UDC 5-6
L12 UDC 7-8
L13 VENT BOX
DATE:
DRAWN BY:
CHECKED:
APPROVED:
RAC FASTRIP - 3351 CADFILE:
SHEET NO.3351-MSP
HOWARD'S MINI MARKETCONVENIENCE MARKET FOR:
BAKERSFIELD, CALIFORNIA 933133200 PANAMA LN.
DRAWING:
DATE REVISIONS
A.P.N.: 372-021-33
SCALE:
JACO HILL3101 STATE RDBAKERSFIELD, CA 93308
PROJECT OWNER:
CD
SITE MAP SITE PLAN
C1
VICINITY MAP
TAB:CERS
1/8"=1'-0"
0
SHEET SIZE 22 X 34
3200 PANAMA LN.BAKERSFIELD, CA 93313
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-46941
CERS ID 10134208
FASTRIP #3351
3200 PANAMA LN.
BAKERSFIELD, CA 93313
03/01/2021 REV.WIBLE RD.
PANAMA LN.
03/01/2021
PROJECT DATA
5'10'15' 20'
L1,S1,S2,S3 L2
L3,S4,S5,S6,S7 L4
L5,S9,S10,S11 L6
L7,S12,S13,S14 L8
L11 L9
L10
L12
VAPOR MANIFOLDCAPPED
L13
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #3351 Howard's #43200 Panama LaneBakersfield101342083-47-8MPDMPDMPDMPD1-25-6ProductProductProductProductBrandon Nunez
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10134208 04/18/2024
Jaco #3351 Howard's #4
3200 Panama Lane Bakersfield 93313
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
EMCO Wheaton 03/17/2025
PEI 1200 1 Hour Hydrostatic All Spill Containers
04/18/2024 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1: 87-1 UNL
EMCO
T2: 87-2 UNL
EMCO
T3: 91 PNL
EMCO
T4: DSL
EMCO
Jaco 3351 Howard’s System Setup & Alarm History
System Setup
Responses Received:
200
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
APR 18, 2024 8:58 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 87-1 UNLEADED 7258 55.58 0.0 66.7 4742
2 87-2 UNLEADED 7258 55.58 0.0 67.3 4742
3 91 PREMIUM 4259 36.66 0.0 71.0 7741
4 DIESEL 3856 34.04 0.0 76.3 8144
I90500
APR 18, 2024 8:58 AM
SOFTWARE REVISION LEVEL
VERSION 335.00
SOFTWARE# 346335-100-A
CREATED - 18.08.27.10.22
S-MODULE# 330160-066-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
ISD/APM
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I50500
APR 18, 2024 8:58 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
APR 18, 2024 8:58 AM
SHIFT TIME 1 : DISABLED
I50202
APR 18, 2024 8:58 AM
SHIFT TIME 2 : DISABLED
I50203
APR 18, 2024 8:58 AM
SHIFT TIME 3 : DISABLED
I50204
APR 18, 2024 8:58 AM
SHIFT TIME 4 : DISABLED
I54600
APR 18, 2024 8:58 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
APR 18, 2024 8:58 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
APR 18, 2024 8:58 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
APR 18, 2024 8:58 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
APR 18, 2024 8:58 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
APR 18, 2024 8:58 AM
PRINT TC VOLUMES
ENABLED
I50E00
APR 18, 2024 8:58 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
APR 18, 2024 8:58 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
APR 18, 2024 8:58 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
APR 18, 2024 8:58 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
APR 18, 2024 8:58 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
APR 18, 2024 8:58 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
APR 18, 2024 8:58 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
APR 18, 2024 8:58 AM
TANK CHART SECURITY
DISABLED
I5BD00
APR 18, 2024 8:58 AM
CUSTOM ALARM LABELS
DISABLED
I56000
APR 18, 2024 8:58 AM
MASS/DENSITY
DISABLED
I88101
APR 18, 2024 8:58 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
APR 18, 2024 8:58 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
APR 18, 2024 8:58 AM
I88104
APR 18, 2024 8:58 AM
I88105
APR 18, 2024 8:58 AM
PORT SETTINGS:
COMM BOARD : 5 (RS-485)
BAUD RATE : 2400
PARITY : EVEN
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88106
APR 18, 2024 8:58 AM
PORT SETTINGS:
COMM BOARD : 6 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I52000
APR 18, 2024 8:58 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE ??? 18, 2024 DISABLED
2 ON DATE ??? 18, 2024 DISABLED
3 ON DATE ??? 18, 2024 DISABLED
4 ON DATE ??? 18, 2024 DISABLED
5 ON DATE ??? 18, 2024 DISABLED
6 ON DATE ??? 18, 2024 DISABLED
7 ON DATE ??? 18, 2024 DISABLED
8 ON DATE ??? 18, 2024 DISABLED
I60100
APR 18, 2024 8:58 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 87-1 UNLEADED ON
2 87-2 UNLEADED ON
3 91 PREMIUM ON
4 DIESEL ON
I60200
APR 18, 2024 8:58 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 87-1 UNLEADED
2 87-2 UNLEADED
3 91 PREMIUM
4 DIESEL
I60300
APR 18, 2024 8:58 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 87-1 UNLEADED 1
2 87-2 UNLEADED 1
3 91 PREMIUM 2
4 DIESEL 3
I60900
APR 18, 2024 8:58 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 87-1 UNLEADED 0.000700
2 87-2 UNLEADED 0.000700
3 91 PREMIUM 0.000700
4 DIESEL 0.000450
I60700
APR 18, 2024 8:58 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 87-1 UNLEADED 96.00
2 87-2 UNLEADED 96.00
3 91 PREMIUM 96.00
4 DIESEL 96.00
I60A00
APR 18, 2024 8:58 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 87-1 UNLEADED
4 PTS 12032 2 87-2 UNLEADED 4 PTS 12032 3 91
PREMIUM 4 PTS 12032 4 DIESEL 4 PTS
12032
I60400
APR 18, 2024 8:58 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 12032
2 87-2 UNLEADED 12032
3 91 PREMIUM 12032
4 DIESEL 12032
I60500
APR 18, 2024 8:58 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 12032 9715 6056 2387
2 87-2 UNLEADED 12032 9715 6056 2387
3 91 PREMIUM 12032 9715 6056 2387
4 DIESEL 12032 9715 6056 2387
I60600
APR 18, 2024 8:58 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 12032 0 0 0
0 9715 0 0
0 0 6056 0
0 0 0 2387
0 0 0 0
2 87-2 UNLEADED 12032 0 0 0
0 9715 0 0
0 0 6056 0
0 0 0 2387
0 0 0 0
3 91 PREMIUM 12032 0 0 0
0 9715 0 0
0 0 6056 0
0 0 0 2387
0 0 0 0
4 DIESEL 12032 0 0 0
0 9715 0 0
0 0 6056 0
0 0 0 2387
0 0 0 0
I61500
APR 18, 2024 8:58 AM
TANK PRODUCT LABEL METER DATA
1 87-1 UNLEADED NO
2 87-2 UNLEADED NO
3 91 PREMIUM NO
4 DIESEL NO
I62F00
APR 18, 2024 8:58 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 87-1 UNLEADED 4.0 IN.
2 87-2 UNLEADED 4.0 IN.
3 91 PREMIUM 3.0 IN.
4 DIESEL 4.0 IN.
I62700
APR 18, 2024 8:58 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 87-1 UNLEADED 2.0
2 87-2 UNLEADED 2.0
3 91 PREMIUM 2.0
4 DIESEL 2.0
I64200
APR 18, 2024 8:58 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 87-1 UNLEADED LOW
2 87-2 UNLEADED LOW
3 91 PREMIUM LOW
4 DIESEL LOW
I62400
APR 18, 2024 8:58 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 87-1 UNLEADED 3.0
2 87-2 UNLEADED 3.0
3 91 PREMIUM 3.0
4 DIESEL 3.0
I62800
APR 18, 2024 8:58 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 12000
2 87-2 UNLEADED 12000
3 91 PREMIUM 12000
4 DIESEL 12000
I62300
APR 18, 2024 8:58 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 10800
2 87-2 UNLEADED 10800
3 91 PREMIUM 10800
4 DIESEL 10800
I62200
APR 18, 2024 8:58 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 11400
2 87-2 UNLEADED 11400
3 91 PREMIUM 11400
4 DIESEL 11400
I62900
APR 18, 2024 8:58 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 1200
2 87-2 UNLEADED 1200
3 91 PREMIUM 1200
4 DIESEL 1200
I62100
APR 18, 2024 8:58 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 500
2 87-2 UNLEADED 500
3 91 PREMIUM 500
4 DIESEL 500
I62600
APR 18, 2024 8:58 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 99
2 87-2 UNLEADED 99
3 91 PREMIUM 99
4 DIESEL 99
I62500
APR 18, 2024 8:58 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 99
2 87-2 UNLEADED 99
3 91 PREMIUM 99
4 DIESEL 99
I60800
APR 18, 2024 8:58 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 87-1 UNLEADED 0.00
2 87-2 UNLEADED 0.00
3 91 PREMIUM 0.00
4 DIESEL 0.00
I60B00
APR 18, 2024 8:58 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
APR 18, 2024 8:58 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 87-1 UNLEADED 0.00
2 87-2 UNLEADED 0.00
3 91 PREMIUM 0.00
4 DIESEL 0.00
I61200
APR 18, 2024 8:58 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 87-1 UNLEADED NONE 2
2 87-2 UNLEADED NONE 1
3 91 PREMIUM NONE NONE
4 DIESEL NONE NONE
I63600
APR 18, 2024 8:58 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 0
2 87-2 UNLEADED 0
3 91 PREMIUM 0
4 DIESEL 0
I62A00
APR 18, 2024 8:58 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 0
2 87-2 UNLEADED 0
3 91 PREMIUM 0
4 DIESEL 0
I62C00
APR 18, 2024 8:58 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 87-1 UNLEADED STANDARD
2 87-2 UNLEADED STANDARD
3 91 PREMIUM STANDARD
4 DIESEL STANDARD
I62D00
APR 18, 2024 8:58 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 87-1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 87-2 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 91 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
APR 18, 2024 8:58 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 87-1 UNLEADED OFF OFF
2 87-2 UNLEADED OFF OFF
3 91 PREMIUM OFF OFF
4 DIESEL OFF OFF
I63000
APR 18, 2024 8:58 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 87-1 UNLEADED OFF
2 87-2 UNLEADED OFF
3 91 PREMIUM OFF
4 DIESEL OFF
I63200
APR 18, 2024 8:58 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 87-1 UNLEADED OFF
2 87-2 UNLEADED OFF
3 91 PREMIUM OFF
4 DIESEL OFF
I61000
APR 18, 2024 8:58 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 87-1 UNLEADED 1
2 87-2 UNLEADED 1
3 91 PREMIUM 1
4 DIESEL 1
I63A00
APR 18, 2024 8:58 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 87-1 UNLEADED 10.00%
2 87-2 UNLEADED 10.00%
3 91 PREMIUM 10.00%
4 DIESEL 10.00%
I61100
APR 18, 2024 8:59 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
AUG 27, 2018
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
APR 18, 2024 8:59 AM
CSLD PROBABLITY OF DETECTION
I61400
APR 18, 2024 8:59 AM
CSLD CLIMATE FACTOR
I61600
APR 18, 2024 8:59 AM
TANK PRODUCT LABEL CAL UPDATE
1 87-1 UNLEADED IMMEDIATE
2 87-2 UNLEADED IMMEDIATE
3 91 PREMIUM IMMEDIATE
4 DIESEL IMMEDIATE
I61A00
APR 18, 2024 8:59 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 87-1 UNLEADED DISABLED
2 87-2 UNLEADED DISABLED
3 91 PREMIUM DISABLED
4 DIESEL DISABLED
I61B00
APR 18, 2024 8:59 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
APR 18, 2024 8:59 AM
CSLD REPORT ONLY
I62B00
APR 18, 2024 8:59 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 87-1 UNLEADED ??? 0, 0
2 87-2 UNLEADED ??? 0, 0
3 91 PREMIUM ??? 0, 0
4 DIESEL ??? 0, 0
I63300
APR 18, 2024 8:59 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
APR 18, 2024 8:59 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 0
2 87-2 UNLEADED 0
3 91 PREMIUM 0
4 DIESEL 0
I63500
APR 18, 2024 8:59 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 87-1 UNLEADED 1
2 87-2 UNLEADED 1
3 91 PREMIUM 1
4 DIESEL 1
I63900
APR 18, 2024 8:59 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 87-1 UNLEADED
END FACTOR: NONE
2 87-2 UNLEADED
END FACTOR: NONE
3 91 PREMIUM
END FACTOR: NONE
4 DIESEL
END FACTOR: NONE
I78000
APR 18, 2024 8:59 AM
PRESSURE LINE LEAK SETUP
Q 1:87 UNLEADED
TYP:USER DEFINED
1ST LINE LEN: 170 FEET
2ND LINE LEN: 170 FEET
1ST LINE DIAM: 1.50 IN.
2ND LINE DIAM: 1.50 IN.
1ST BULK MOD: 31000 PSI
2ND BULK MOD: 31000 PSI
THERMAL COEFF :0.000700
0.20 GPH TEST: DISABLED
0.10 GPH TEST: DISABLED
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE : 0 PSI
T 2:87-2 UNLEADED
DISPENSE MODE:
MANIFOLDED: ALTERNATE
ACTIVE SWITCHOVER:
ENABLED: NO
SENSOR: NON-VENTED
PRESSURE OFFSET: 0.0PSI
MECHANICAL BLENDER: NO
Q 2:91 PREMIUM
TYP:USER DEFINED
1ST LINE LEN: 160 FEET
2ND LINE LEN: 0 FEET
1ST LINE DIAM: 1.50 IN.
1ST BULK MOD: 31000 PSI
THERMAL COEFF :0.000700
0.20 GPH TEST: DISABLED
0.10 GPH TEST: DISABLED
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE : 0 PSI
T 3:91 PREMIUM
DISPENSE MODE:
STANDARD
SENSOR: NON-VENTED
PRESSURE OFFSET: 0.0PSI
MECHANICAL BLENDER: NO
Q 3:DIESEL
TYP:USER DEFINED
1ST LINE LEN: 150 FEET
2ND LINE LEN: 0 FEET
1ST LINE DIAM: 1.50 IN.
1ST BULK MOD: 31000 PSI
THERMAL COEFF :0.000700
0.20 GPH TEST: DISABLED
0.10 GPH TEST: DISABLED
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE : 0 PSI
T 4:DIESEL
DISPENSE MODE:
STANDARD
SENSOR: NON-VENTED
PRESSURE OFFSET: 0.0PSI
MECHANICAL BLENDER: NO
I77700
APR 18, 2024 8:59 AM
PRESSURE LINE LEAK PRIMARY PIPE DIAMETER
LINE 1ST LINE DIAMETER
Q 1:87 UNLEADED 1.50 INCHES
Q 2:91 PREMIUM 1.50 INCHES
Q 3:DIESEL 1.50 INCHES
I77800
APR 18, 2024 8:59 AM
PRESSURE LINE LEAK SECONDARY PIPE DIAMETER
LINE 2ND LINE DIAMETER
Q 1:87 UNLEADED 1.50 INCHES
I78C00
APR 18, 2024 8:59 AM
PRESSURE LINE LEAK 0.20 TEST SCHEDULE
LINE 0.20 GPH TEST
Q 1:87 UNLEADED DISABLED
Q 2:91 PREMIUM DISABLED
Q 3:DIESEL DISABLED
I78300
APR 18, 2024 8:59 AM
PRESSURE LINE LEAK 0.10 TEST SCHEDULE
LINE 0.10 GPH TEST
Q 1:87 UNLEADED DISABLED
Q 2:91 PREMIUM DISABLED
Q 3:DIESEL DISABLED
I78F00
APR 18, 2024 8:59 AM
PRESSURE LINE LEAK DISPENSE THRESHOLD
LINE LOW PRESSURE
Q 1:87 UNLEADED 0 PSI
Q 2:91 PREMIUM 0 PSI
Q 3:DIESEL 0 PSI
I78700
APR 18, 2024 8:59 AM
PRESSURE LLD SETUP REPORT
Q 1:87 UNLEADED
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
Q 2:91 PREMIUM
LIQUID SENSOR ALMS
L 5:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 5:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 5:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
Q 3:DIESEL
LIQUID SENSOR ALMS
L 7:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
I70200
APR 18, 2024 8:59 AM
LIQUID LABEL
DEVICE LABEL
1 87-1 STP
2 87-1 FILL
3 87-2 STP
4 87-2 FILL
5 91 STP
6 91 FILL
7 DIESEL STP
8 DIESEL FILL
9 DISP 1-2
10 DISP 3-4
11 DISP 5-6
12 DISP 7-8
13 VENT BOX
14 L
15
16
I70300
APR 18, 2024 8:59 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87-1 STP DW SUMP 2-1
2 87-1 FILL DW SUMP 2-1
3 87-2 STP DW SUMP 2-1
4 87-2 FILL DW SUMP 2-1
5 91 STP DW SUMP 2-1
6 91 FILL DW SUMP 2-1
7 DIESEL STP DW SUMP 2-1
8 DIESEL FILL DW SUMP 2-1
9 DISP 1-2 DW SUMP 2-1
10 DISP 3-4 DW SUMP 2-1
11 DISP 5-6 DW SUMP 2-1
12 DISP 7-8 DW SUMP 2-1
13 VENT BOX DW SUMP 2-1
14 L DW SUMP 2-1
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
APR 18, 2024 9:00 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 87-1 STP STP SUMP
2 87-1 FILL PIPING SUMP
3 87-2 STP STP SUMP
4 87-2 FILL PIPING SUMP
5 91 STP STP SUMP
6 91 FILL PIPING SUMP
7 DIESEL STP STP SUMP
8 DIESEL FILL PIPING SUMP
9 DISP 1-2 DISPENSER PAN
10 DISP 3-4 DISPENSER PAN
11 DISP 5-6 DISPENSER PAN
12 DISP 7-8 DISPENSER PAN
13 VENT BOX PIPING SUMP
14 L PIPING SUMP
15 OTHER SENSORS
16 OTHER SENSORS
I74200
APR 18, 2024 9:00 AM
I74300
APR 18, 2024 9:00 AM
I74400
APR 18, 2024 9:00 AM
I74700
APR 18, 2024 9:00 AM
I74800
APR 18, 2024 9:00 AM
I74900
APR 18, 2024 9:00 AM
I7BC00
APR 18, 2024 9:00 AM
I80200
APR 18, 2024 9:00 AM
I80300
APR 18, 2024 9:00 AM
I80400
APR 18, 2024 9:00 AM
I80700
APR 18, 2024 9:00 AM
RELAY LABEL
DEVICE LABEL
1 87-1 TURBINE
2 87-1 UNLEADED
3 91 PREMIUM
4 DIESEL
5 87-2 UNLEADED
6
7
8
I80900
APR 18, 2024 9:00 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 87-1 TURBINE NORMALLY OPEN
2 87-1 UNLEADED NORMALLY OPEN
3 91 PREMIUM NORMALLY OPEN
4 DIESEL NORMALLY OPEN
5 87-2 UNLEADED NORMALLY OPEN
6 NORMALLY OPEN
7 NORMALLY OPEN
8 NORMALLY OPEN
I80B00
APR 18, 2024 9:00 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 87-1 TURBINE 1
2 87-1 UNLEADED NONE
3 91 PREMIUM NONE
4 DIESEL NONE
5 87-2 UNLEADED NONE
6 1
7 1
8 1
I80A00
APR 18, 2024 9:00 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 87-1 TURBINE PUMP CONTROL OUTPUT
2 87-1 UNLEADED STANDARD
3 91 PREMIUM STANDARD
4 DIESEL STANDARD
5 87-2 UNLEADED STANDARD
6 STANDARD
7 STANDARD
8 STANDARD
I80C00
APR 18, 2024 9:00 AM
I80800
APR 18, 2024 9:00 AM
RELAY SETUP REPORT
R 1:87-1 TURBINE
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
PRESSURE LINE LEAK
Q 1:GROSS LINE FAIL
Q 1:PLLD SHUTDOWN ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 2:87-1 UNLEADED
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
T 1:OVERFILL ALARM
T 1:HIGH PRODUCT ALARM
R 3:91 PREMIUM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
T 3:OVERFILL ALARM
T 3:HIGH PRODUCT ALARM
R 4:DIESEL
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
T 4:OVERFILL ALARM
T 4:HIGH PRODUCT ALARM
R 5:87-2 UNLEADED
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
T 2:OVERFILL ALARM
T 2:HIGH PRODUCT ALARM
R 6:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: 1
- NO ALARM ASSIGNMENTS -
R 7:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: 1
- NO ALARM ASSIGNMENTS -
R 8:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: 1
- NO ALARM ASSIGNMENTS -
I79000
APR 18, 2024 9:01 AM
EDIM:1 VR:349867-001-D TD:17.02.14.08.38
I79100
APR 18, 2024 9:01 AM
I72300
APR 18, 2024 9:01 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 87-1 PRODUCT VAC SENSOR
02 87-1 VENT VAC SENSOR
03 87-1 TANK VAC SENSOR
04 87-2 PRODUCT VAC SENSOR
05 87-2 VENT VAC SENSOR
06 87-2 TANK VAC SENSOR
07 87-2 VAPOR VAC SENSOR
08 ATM ATM P SENSOR
09 91 PRODUCT VAC SENSOR
10 91 VENT VAC SENSOR
11 91 TANK VAC SENSOR
12 DIESEL PRODUCT VAC SENSOR
13 DIESEL VENT VAC SENSOR
14 DIESEL TANK VAC SENSOR
15 UNKNOWN
16 UNKNOWN
17 DISP 1-2 FM AIR FLOW METER
18 DISP 3-4 FM AIR FLOW METER
19 DISP 5-6 FM AIR FLOW METER
20 DISP 7-8 FM AIR FLOW METER
21 DISP 1-2 PRES SENSR VAPOR PRESSURE
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
APR 18, 2024 9:01 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
APR 18, 2024 9:01 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
APR 18, 2024 9:01 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
VAPOR PROCESSOR TYPE
NONE
IV4700
APR 18, 2024 9:01 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
ASSESSMENT TIME
START TIME: 10:05 AM
TIME DELAY MINUTES: 1
IV5200
APR 18, 2024 9:01 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
ACCEPT HIGH ORVR: NO
IV4A00
APR 18, 2024 9:01 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 01 BLEND3
02 02 02 01 01 BLEND3
03 03 03 02 01 BLEND3
04 04 04 02 01 BLEND3
05 05 05 03 01 BLEND3
06 06 06 03 01 BLEND3
07 07 07 04 01 BLEND3
08 08 08 04 01 BLEND3
IV4B00
APR 18, 2024 9:01 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 01/01 09/01 xx/xx
02 01 02/02 01/02 09/02 xx/xx
03 02 02/03 01/03 09/03 xx/xx
04 02 02/04 01/04 09/04 xx/xx
05 03 02/05 01/05 09/05 xx/xx
06 03 02/06 01/06 09/06 xx/xx
07 04 02/07 01/07 09/07 xx/xx
08 04 02/08 01/08 09/08 xx/xx
IV4900
APR 18, 2024 9:01 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
APR 18, 2024 9:01 AM
ISD VERSION: 01.05
Pre Alarm History
Jaco 3351 Howard’s Pre Alarm History
Responses Received:
I10200
APR 18, 2024 9:02 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 162966 162990
2 PLLD SENSOR BD 3849 3872
3 7SMARTSENSOR BD 504314 503608
4 8SMARTSENSOR BD 39214 39152
5 8SMARTSENSOR BD 39193 39152
6 INTERSTITIAL BD 200899 200759
7 INTERSTITIAL BD 200433 200337
8 UNUSED 4979078 4988760
9 RELAY BOARD 14966 14980
10 PLLD POWER BD 100334 100336
11 RELAY BOARD 4983978 14959
12 UNUSED 4978294 4995534
13 UNUSED 4981105 4993315
14 UNUSED 4979608 4990296
15 UNUSED 4976878 4990932
16 UNUSED 4979936 4988734
COMM 1 ELEC DISP INT. 100505 100593
COMM 2 RS232 SERIAL BD 14821 14835
COMM 3 UNUSED 4983096 4995575
COMM 4 UNUSED 4971195 4990439
COMM 5 RS485 SERIAL BD 68187 68303
COMM 6 RS232 SERIAL BD 14842 14856
I90200
APR 18, 2024 9:02 AM
SOFTWARE REVISION LEVEL
VERSION 335.00
SOFTWARE# 346335-100-A
CREATED - 18.08.27.10.22
S-MODULE# 330160-066-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
ISD/APM
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I11100
APR 18, 2024 9:02 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 8 PIPE DIESEL FILL FUEL ALARM CLEAR 4-18-24 8:59AM
L 8 PIPE DIESEL FILL FUEL ALARM ALARM 4-13-24 5:17PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM CLEAR 4-10-24 7:09PM
Q 1 OTHER 87 UNLEADED GROSS LINE FAIL CLEAR 4-10-24 7:09PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM ALARM 4-10-24 6:55PM
Q 1 OTHER 87 UNLEADED GROSS LINE FAIL ALARM 4-10-24 6:55PM
L 6 PIPE 91 FILL FUEL ALARM CLEAR 4-05-24 3:34PM
L 8 PIPE DIESEL FILL FUEL ALARM CLEAR 4-05-24 3:28PM
L 8 PIPE DIESEL FILL FUEL ALARM ALARM 4-05-24 10:31AM
L 6 PIPE 91 FILL FUEL ALARM ALARM 4-05-24 10:28AM
s 6 OTHER 87-2 TANK NO VACUUM ALARM CLEAR 4-04-24 2:51PM
s 6 OTHER 87-2 TANK NO VACUUM ALARM ALARM 4-04-24 2:41PM
Q 3 OTHER DIESEL PLLD SHUTDOWN ALARM CLEAR 4-04-24 12:59PM
Q 3 OTHER DIESEL GROSS LINE FAIL CLEAR 4-04-24 12:59PM
Q 2 OTHER 91 PREMIUM PLLD SHUTDOWN ALARM CLEAR 4-04-24 12:58PM
Q 2 OTHER 91 PREMIUM GROSS LINE FAIL CLEAR 4-04-24 12:58PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM CLEAR 4-04-24 12:55PM
L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 4-04-24 12:55PM
L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 4-04-24 12:52PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM ALARM 4-04-24 12:52PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM CLEAR 4-04-24 12:42PM
L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 4-04-24 12:42PM
L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 4-04-24 12:40PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM ALARM 4-04-24 12:40PM
Q 2 OTHER 91 PREMIUM PLLD SHUTDOWN ALARM ALARM 4-04-24 12:36PM
Q 2 OTHER 91 PREMIUM GROSS LINE FAIL ALARM 4-04-24 12:36PM
Q 2 OTHER 91 PREMIUM PLLD SHUTDOWN ALARM CLEAR 4-04-24 12:32PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM CLEAR 4-04-24 12:32PM
L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 4-04-24 12:32PM
L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 4-04-24 12:30PM
Q 2 OTHER 91 PREMIUM PLLD SHUTDOWN ALARM ALARM 4-04-24 12:30PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM ALARM 4-04-24 12:30PM
Q 3 OTHER DIESEL PLLD SHUTDOWN ALARM ALARM 4-04-24 12:27PM
Q 3 OTHER DIESEL GROSS LINE FAIL ALARM 4-04-24 12:27PM
Q 3 OTHER DIESEL PLLD SHUTDOWN ALARM CLEAR 4-04-24 12:15PM
Q 2 OTHER 91 PREMIUM PLLD SHUTDOWN ALARM CLEAR 4-04-24 12:15PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM CLEAR 4-04-24 12:15PM
L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 4-04-24 12:15PM
L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 4-04-24 12:13PM
Q 3 OTHER DIESEL PLLD SHUTDOWN ALARM ALARM 4-04-24 12:13PM
Q 2 OTHER 91 PREMIUM PLLD SHUTDOWN ALARM ALARM 4-04-24 12:13PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM ALARM 4-04-24 12:13PM
L 1 STP SUMP 87-1 STP LOW LIQUID ALARM CLEAR 4-04-24 12:01PM
L 1 STP SUMP 87-1 STP LOW LIQUID ALARM ALARM 4-04-24 12:00PM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM CLEAR 4-04-24 11:51AM
L 1 STP SUMP 87-1 STP SENSOR OUT ALARM CLEAR 4-04-24 11:51AM
L 1 STP SUMP 87-1 STP SENSOR OUT ALARM ALARM 4-04-24 11:43AM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM ALARM 4-04-24 11:43AM
L13 PIPE VENT BOX LOW LIQUID ALARM CLEAR 4-04-24 11:28AM
L13 PIPE VENT BOX LOW LIQUID ALARM ALARM 4-04-24 11:28AM
I11200
APR 18, 2024 9:02 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 4-14-24 5:09PM
SYSTEM PAPER OUT CLEAR 4-14-24 5:09PM
SYSTEM PAPER OUT ALARM 4-14-24 5:08PM
SYSTEM PRINTER ERROR ALARM 4-14-24 5:08PM
OTHER ISD SENSOR OUT WARN CLEAR 3-29-24 9:21AM
OTHER ISD SENSOR OUT WARN ALARM 3-28-24 10:08AM
OTHER ISD SENSOR OUT WARN CLEAR 3-26-24 3:05PM
OTHER ISD SENSOR OUT WARN ALARM 3-26-24 10:07AM
OTHER ISD SENSOR OUT WARN CLEAR 3-25-24 10:11AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 3-25-24 10:10AM
OTHER ISD SENSOR OUT WARN ALARM 3-25-24 10:07AM
h 7 OTHER FP7: BLEND3 GROSS COLLECT WARN CLEAR 3-25-24 10:05AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 3-24-24 10:07AM
h 7 OTHER FP7: BLEND3 GROSS COLLECT WARN ALARM 3-24-24 10:07AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 3-18-24 11:03AM
T 1 TANK 87-1 UNLEADED INVALID FUEL LEVEL CLEAR 3-18-24 11:02AM
T 1 TANK 87-1 UNLEADED INVALID FUEL LEVEL ALARM 3-18-24 7:33AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 3-17-24 7:54PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 3-15-24 6:06PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 3-15-24 7:53AM
SYSTEM PRINTER ERROR CLEAR 3-12-24 6:37PM
SYSTEM PAPER OUT CLEAR 3-12-24 6:37PM
SYSTEM PAPER OUT ALARM 3-12-24 6:34PM
SYSTEM PRINTER ERROR ALARM 3-12-24 6:33PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 3-09-24 10:42PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 3-09-24 10:08PM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 3-07-24 8:43PM
T 4 TANK DIESEL DELIVERY NEEDED ALARM 3-07-24 3:32PM
OTHER ISD GROSS PRES WARN CLEAR 3-04-24 2:11PM
OTHER ISD GROSS PRES WARN ALARM 3-02-24 10:11AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 2-27-24 12:19AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 2-26-24 6:34PM
OTHER ISD VAPOR LEAK WARN CLEAR 2-26-24 12:30PM
T 3 TANK 91 PREMIUM DELIVERY NEEDED CLEAR 2-26-24 12:04PM
T 3 TANK 91 PREMIUM INVALID FUEL LEVEL CLEAR 2-26-24 12:04PM
T 3 TANK 91 PREMIUM INVALID FUEL LEVEL ALARM 2-26-24 11:40AM
T 3 TANK 91 PREMIUM DELIVERY NEEDED ALARM 2-26-24 11:39AM
OTHER ISD VAPOR LEAK WARN ALARM 2-22-24 10:08AM
OTHER ISD VAPOR LEAK WARN CLEAR 2-16-24 1:05PM
OTHER ISD VAPOR LEAK WARN ALARM 2-15-24 10:08AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 2-11-24 12:16AM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 2-10-24 11:50PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 2-10-24 5:53PM
T 4 TANK DIESEL DELIVERY NEEDED ALARM 2-10-24 9:37AM
OTHER ISD GROSS PRES WARN CLEAR 2-05-24 9:07AM
OTHER ISD GROSS PRES WARN ALARM 2-01-24 10:09AM
OTHER ISD GROSS PRES WARN CLEAR 1-25-24 1:53PM
OTHER ISD GROSS PRES WARN ALARM 1-24-24 10:08AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 1-18-24 10:12PM
T 1 TANK 87-1 UNLEADED INVALID FUEL LEVEL CLEAR 1-18-24 10:11PM
I20600
APR 18, 2024 9:02 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
TANK ALARM HISTORY
TANK 1 87-1 UNLEADED
OVERFILL ALARM JAN 10, 2024 9:10 AM
DEC 3, 2023 1:01 AM
DEC 29, 2022 12:20 PM
LOW PRODUCT ALARM MAR 18, 2024 7:54 AM
JAN 18, 2024 5:52 PM
HIGH PRODUCT ALARM JAN 10, 2024 9:10 AM
AUG 15, 2022 2:05 PM
INVALID FUEL LEVEL MAR 18, 2024 7:33 AM
JAN 18, 2024 4:33 PM
PROBE OUT JAN 10, 2024 9:57 AM
JAN 10, 2024 8:48 AM
AUG 15, 2022 2:06 PM
DELIVERY NEEDED MAR 17, 2024 7:54 PM
MAR 15, 2024 7:53 AM
MAR 9, 2024 10:08 PM
TANK 2 87-2 UNLEADED
OVERFILL ALARM JAN 10, 2024 9:44 AM
JAN 10, 2024 9:11 AM
JAN 5, 2024 12:34 AM
HIGH PRODUCT ALARM JAN 10, 2024 9:12 AM
AUG 15, 2022 2:03 PM
JUN 10, 2022 9:12 AM
PROBE OUT JAN 10, 2024 9:55 AM
JAN 10, 2024 9:04 AM
JAN 10, 2024 8:52 AM
HIGH WATER WARNING JAN 10, 2024 8:56 AM
MAX PRODUCT ALARM JUN 10, 2022 9:12 AM
APR 9, 2022 5:56 AM
LOW TEMP WARNING JAN 10, 2024 9:57 AM
AUG 15, 2022 2:04 PM
TANK 3 91 PREMIUM
HIGH WATER ALARM JAN 10, 2024 9:17 AM
OVERFILL ALARM JAN 10, 2024 9:45 AM
JAN 10, 2024 9:13 AM
AUG 15, 2022 2:02 PM
LOW PRODUCT ALARM FEB 26, 2024 11:39 AM
JAN 10, 2024 8:54 AM
DEC 18, 2022 9:40 PM
SUDDEN LOSS ALARM FEB 26, 2024 11:40 AM
HIGH PRODUCT ALARM JAN 10, 2024 9:45 AM
JAN 10, 2024 9:13 AM
JUN 10, 2022 9:13 AM
INVALID FUEL LEVEL FEB 26, 2024 11:40 AM
DEC 18, 2022 7:44 PM
PROBE OUT FEB 28, 2024 2:15 PM
FEB 28, 2024 2:02 PM
FEB 26, 2024 11:41 AM
HIGH WATER WARNING JAN 10, 2024 9:17 AM
DELIVERY NEEDED FEB 26, 2024 11:39 AM
JAN 10, 2024 8:54 AM
NOV 13, 2023 9:07 AM
MAX PRODUCT ALARM JAN 10, 2024 9:13 AM
JUN 10, 2022 9:13 AM
JUN 10, 2022 8:05 AM
LOW TEMP WARNING JAN 10, 2024 9:52 AM
TANK 4 DIESEL
HIGH WATER ALARM FEB 23, 2023 12:19 PM
FEB 23, 2023 11:57 AM
FEB 22, 2023 6:00 PM
OVERFILL ALARM JAN 10, 2024 9:46 AM
JAN 10, 2024 9:15 AM
FEB 23, 2023 12:13 PM
LOW PRODUCT ALARM JAN 10, 2024 8:56 AM
SUDDEN LOSS ALARM DEC 25, 2023 5:43 PM
HIGH PRODUCT ALARM JAN 10, 2024 9:46 AM
JAN 10, 2024 9:15 AM
FEB 23, 2023 12:13 PM
INVALID FUEL LEVEL JAN 10, 2024 8:57 AM
FEB 23, 2023 12:30 PM
FEB 23, 2023 12:28 PM
PROBE OUT JAN 10, 2024 9:48 AM
JAN 10, 2024 8:57 AM
FEB 23, 2023 1:44 PM
HIGH WATER WARNING FEB 23, 2023 12:19 PM
FEB 23, 2023 11:57 AM
FEB 22, 2023 6:00 PM
DELIVERY NEEDED MAR 7, 2024 3:32 PM
FEB 10, 2024 9:37 AM
JAN 10, 2024 8:56 AM
MAX PRODUCT ALARM JAN 10, 2024 9:15 AM
FEB 23, 2023 12:13 PM
JUN 10, 2022 9:14 AM
LOW TEMP WARNING FEB 23, 2023 1:47 PM
FEB 23, 2023 12:44 PM
FEB 23, 2023 11:53 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
APR 18, 2024 9:03 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1:87 UNLEADED
APR 10, 2024 6:55 PM PLLD SHUTDOWN ALARM
APR 10, 2024 6:55 PM GROSS LINE FAIL
APR 4, 2024 12:52 PM PLLD SHUTDOWN ALARM
APR 4, 2024 12:40 PM PLLD SHUTDOWN ALARM
APR 4, 2024 12:30 PM PLLD SHUTDOWN ALARM
APR 4, 2024 12:13 PM PLLD SHUTDOWN ALARM
APR 4, 2024 11:43 AM PLLD SHUTDOWN ALARM
APR 4, 2024 11:24 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:32 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:30 AM PLLD SHUTDOWN ALARM
Q 2:91 PREMIUM
APR 4, 2024 12:36 PM PLLD SHUTDOWN ALARM
APR 4, 2024 12:36 PM GROSS LINE FAIL
APR 4, 2024 12:30 PM PLLD SHUTDOWN ALARM
APR 4, 2024 12:13 PM PLLD SHUTDOWN ALARM
APR 4, 2024 11:24 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:28 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:20 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:18 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:17 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:12 AM PLLD SHUTDOWN ALARM
Q 3:DIESEL
APR 4, 2024 12:27 PM PLLD SHUTDOWN ALARM
APR 4, 2024 12:27 PM GROSS LINE FAIL
APR 4, 2024 12:13 PM PLLD SHUTDOWN ALARM
APR 4, 2024 11:24 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:25 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:20 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:18 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:17 AM PLLD SHUTDOWN ALARM
APR 4, 2024 10:12 AM PLLD SHUTDOWN ALARM
SEP 13, 2023 10:10 AM PLLD SHUTDOWN ALARM
I30200
APR 18, 2024 9:03 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87-1 STP
APR 4, 2024 12:00 PM LOW LIQUID ALARM
APR 4, 2024 11:43 AM SENSOR OUT ALARM
APR 4, 2024 11:24 AM SENSOR OUT ALARM
2 87-1 FILL
APR 4, 2024 11:25 AM SENSOR OUT ALARM
APR 4, 2024 10:00 AM LOW LIQUID ALARM
APR 4, 2024 9:59 AM FUEL ALARM
3 87-2 STP
APR 4, 2024 11:25 AM SENSOR OUT ALARM
APR 4, 2024 10:30 AM LOW LIQUID ALARM
APR 4, 2024 10:30 AM FUEL ALARM
4 87-2 FILL
APR 4, 2024 11:25 AM SENSOR OUT ALARM
APR 4, 2024 10:03 AM LOW LIQUID ALARM
APR 4, 2024 10:02 AM FUEL ALARM
5 91 STP
APR 4, 2024 11:24 AM SENSOR OUT ALARM
APR 4, 2024 10:29 AM LOW LIQUID ALARM
APR 4, 2024 10:28 AM FUEL ALARM
6 91 FILL
APR 5, 2024 10:28 AM FUEL ALARM
APR 4, 2024 11:24 AM SENSOR OUT ALARM
APR 4, 2024 10:16 AM LOW LIQUID ALARM
7 DIESEL STP
APR 4, 2024 11:24 AM SENSOR OUT ALARM
APR 4, 2024 10:26 AM LOW LIQUID ALARM
APR 4, 2024 10:25 AM FUEL ALARM
8 DIESEL FILL
APR 13, 2024 5:17 PM FUEL ALARM
APR 5, 2024 10:31 AM FUEL ALARM
APR 4, 2024 11:25 AM SENSOR OUT ALARM
9 DISP 1-2
APR 4, 2024 11:24 AM SENSOR OUT ALARM
APR 4, 2024 10:17 AM LOW LIQUID ALARM
APR 4, 2024 10:17 AM FUEL ALARM
10 DISP 3-4
APR 4, 2024 12:52 PM FUEL ALARM
APR 4, 2024 12:40 PM FUEL ALARM
APR 4, 2024 12:30 PM FUEL ALARM
11 DISP 5-6
APR 4, 2024 11:24 AM SENSOR OUT ALARM
APR 4, 2024 10:13 AM LOW LIQUID ALARM
APR 4, 2024 10:12 AM FUEL ALARM
12 DISP 7-8
APR 4, 2024 11:24 AM SENSOR OUT ALARM
APR 4, 2024 10:19 AM LOW LIQUID ALARM
APR 4, 2024 10:18 AM FUEL ALARM
13 VENT BOX
APR 4, 2024 11:28 AM LOW LIQUID ALARM
APR 4, 2024 11:27 AM FUEL ALARM
APR 4, 2024 11:24 AM SENSOR OUT ALARM
I31600
APR 18, 2024 9:03 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 87-1 PRODUCT
APR 4, 2024 10:43 AM HIGH LIQUID ALARM
APR 4, 2024 10:42 AM NO VACUUM ALARM
APR 26, 2023 10:37 AM NO VACUUM ALARM
2 87-1 VENT
APR 4, 2024 10:43 AM HIGH LIQUID ALARM
APR 4, 2024 10:42 AM NO VACUUM ALARM
APR 26, 2023 10:37 AM NO VACUUM ALARM
3 87-1 TANK
APR 4, 2024 10:44 AM HIGH LIQUID ALARM
APR 4, 2024 10:44 AM NO VACUUM ALARM
APR 26, 2023 10:48 AM HIGH LIQUID ALARM
4 87-2 PRODUCT
APR 4, 2024 10:48 AM HIGH LIQUID ALARM
APR 4, 2024 10:46 AM NO VACUUM ALARM
APR 26, 2023 10:39 AM NO VACUUM ALARM
5 87-2 VENT
APR 4, 2024 10:48 AM HIGH LIQUID ALARM
APR 4, 2024 10:46 AM NO VACUUM ALARM
APR 26, 2023 10:39 AM NO VACUUM ALARM
6 87-2 TANK
APR 4, 2024 2:41 PM NO VACUUM ALARM
APR 4, 2024 10:54 AM HIGH LIQUID ALARM
APR 4, 2024 10:49 AM NO VACUUM ALARM
7 87-2 VAPOR
APR 4, 2024 10:48 AM HIGH LIQUID ALARM
APR 4, 2024 10:46 AM NO VACUUM ALARM
APR 26, 2023 10:39 AM NO VACUUM ALARM
8 ATM
9 91 PRODUCT
APR 4, 2024 10:59 AM HIGH LIQUID ALARM
APR 4, 2024 10:58 AM NO VACUUM ALARM
APR 26, 2023 10:40 AM NO VACUUM ALARM
10 91 VENT
APR 4, 2024 10:59 AM HIGH LIQUID ALARM
APR 4, 2024 10:58 AM NO VACUUM ALARM
APR 26, 2023 10:40 AM NO VACUUM ALARM
11 91 TANK
APR 4, 2024 11:00 AM HIGH LIQUID ALARM
APR 4, 2024 10:59 AM NO VACUUM ALARM
APR 26, 2023 10:45 AM HIGH LIQUID ALARM
12 DIESEL PRODUCT
APR 4, 2024 11:06 AM HIGH LIQUID ALARM
APR 4, 2024 11:04 AM NO VACUUM ALARM
APR 26, 2023 10:42 AM NO VACUUM ALARM
13 DIESEL VENT
APR 4, 2024 11:06 AM HIGH LIQUID ALARM
APR 4, 2024 11:05 AM NO VACUUM ALARM
APR 4, 2024 11:04 AM NO VACUUM ALARM
14 DIESEL TANK
APR 4, 2024 11:07 AM HIGH LIQUID ALARM
APR 4, 2024 11:07 AM NO VACUUM ALARM
APR 26, 2023 10:43 AM HIGH LIQUID ALARM
17 DISP 1-2 FM
18 DISP 3-4 FM
19 DISP 5-6 FM
20 DISP 7-8 FM
21 DISP 1-2 PRES SENSR
JUN 1, 2023 2:23 PM COMMUNICATION ALARM
I40200
APR 18, 2024 9:03 AM
I40300
APR 18, 2024 9:03 AM
I34200
APR 18, 2024 9:03 AM
I34700
APR 18, 2024 9:03 AM
IV0100
APR 18, 2024 9:03 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-03-28 10:08:38 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 3:DISP 5-6 FM
24-03-26 10:07:18 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:DISP 7-8 FM
24-03-25 10:07:54 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:DISP 7-8 FM
24-03-25 10:07:54 A/L RATIO DEGRADATION FP 7 BLEND3 BLKD
24-03-24 10:07:11 A/L RATIO DEGRADATION FP 7 BLEND3 BLKD
24-03-24 10:07:11 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
24-03-04 10:09:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07
24-03-03 10:09:22 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07
24-03-02 10:11:44 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07
24-02-26 10:08:12 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 186.73
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
24-03-25 10:07:54 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
23-09-12 10:10:10 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-11 10:09:46 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-10 10:09:47 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-04 10:09:14 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-03 10:09:07 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-02 10:09:23 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-10-18 10:10:20 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.02
19-12-18 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
19-11-25 10:02:24 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-04-10 19:08:58 VAPOR PROCESSOR TEST MANUALLY CLEARED
24-04-10 19:08:50 ISD SELFTEST TEST MANUALLY CLEARED
24-04-10 19:08:26 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
24-04-10 19:08:02 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-04-05 10:07:42 READINESS ISD:PP EVR:PP ISD & EVR READY
24-04-04 11:33:38 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-04-04 11:33:38 ISD STARTUP
24-04-04 11:33:32 ISD SHUTDOWN
24-03-29 09:21:54 SENSOR OUT TEST MANUALLY CLEARED
24-03-26 15:05:23 SENSOR OUT TEST MANUALLY CLEARED
Post Alarm History
Responses Received:
I10200
APR 18, 2024 11:21 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 162966 162990
2 PLLD SENSOR BD 3849 3872
3 7SMARTSENSOR BD 504314 503608
4 8SMARTSENSOR BD 39214 39152
5 8SMARTSENSOR BD 39193 39152
6 INTERSTITIAL BD 200899 200759
7 INTERSTITIAL BD 200433 200337
8 UNUSED 4979078 4988760
9 RELAY BOARD 14966 14980
10 PLLD POWER BD 100334 100336
11 RELAY BOARD 4983978 14959
12 UNUSED 4978294 4995534
13 UNUSED 4981105 4993315
14 UNUSED 4979608 4990296
15 UNUSED 4976878 4990932
16 UNUSED 4979936 4988734
COMM 1 ELEC DISP INT. 100505 100593
COMM 2 RS232 SERIAL BD 14821 14835
COMM 3 UNUSED 4983096 4995575
COMM 4 UNUSED 4971195 4990439
COMM 5 RS485 SERIAL BD 68187 68303
COMM 6 RS232 SERIAL BD 14842 14856
I90200
APR 18, 2024 11:21 AM
SOFTWARE REVISION LEVEL
VERSION 335.00
SOFTWARE# 346335-100-A
CREATED - 18.08.27.10.22
S-MODULE# 330160-066-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
ISD/APM
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I11100
APR 18, 2024 11:21 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
s14 OTHER DIESEL TANK NO VACUUM ALARM CLEAR 4-18-24 11:15AM
s14 OTHER DIESEL TANK HIGH LIQUID ALARM CLEAR 4-18-24 11:12AM
s14 OTHER DIESEL TANK HIGH LIQUID ALARM ALARM 4-18-24 11:11AM
s14 OTHER DIESEL TANK HIGH LIQUID ALARM CLEAR 4-18-24 11:07AM
s14 OTHER DIESEL TANK NO VACUUM ALARM ALARM 4-18-24 11:04AM
s 3 OTHER 87-1 TANK NO VACUUM ALARM CLEAR 4-18-24 11:00AM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM CLEAR 4-18-24 10:52AM
Q 1 OTHER 87 UNLEADED GROSS LINE FAIL CLEAR 4-18-24 10:52AM
s 6 OTHER 87-2 TANK NO VACUUM ALARM CLEAR 4-18-24 10:51AM
s 5 OTHER 87-2 VENT HIGH LIQUID ALARM CLEAR 4-18-24 10:50AM
s 7 OTHER 87-2 VAPOR HIGH LIQUID ALARM CLEAR 4-18-24 10:50AM
s 4 OTHER 87-2 PRODUCT HIGH LIQUID ALARM CLEAR 4-18-24 10:50AM
s 5 OTHER 87-2 VENT HIGH LIQUID ALARM ALARM 4-18-24 10:48AM
s 7 OTHER 87-2 VAPOR HIGH LIQUID ALARM ALARM 4-18-24 10:48AM
s 4 OTHER 87-2 PRODUCT HIGH LIQUID ALARM ALARM 4-18-24 10:48AM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM ALARM 4-18-24 10:47AM
Q 1 OTHER 87 UNLEADED GROSS LINE FAIL ALARM 4-18-24 10:47AM
s11 OTHER 91 TANK NO VACUUM ALARM CLEAR 4-18-24 10:46AM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM CLEAR 4-18-24 10:38AM
Q 1 OTHER 87 UNLEADED GROSS LINE FAIL CLEAR 4-18-24 10:38AM
s14 OTHER DIESEL TANK NO VACUUM ALARM CLEAR 4-18-24 10:36AM
Q 1 OTHER 87 UNLEADED PLLD SHUTDOWN ALARM ALARM 4-18-24 10:36AM
Q 1 OTHER 87 UNLEADED GROSS LINE FAIL ALARM 4-18-24 10:36AM
Q 2 OTHER 91 PREMIUM PLLD SHUTDOWN ALARM CLEAR 4-18-24 10:29AM
Q 2 OTHER 91 PREMIUM GROSS LINE FAIL CLEAR 4-18-24 10:29AM
s14 OTHER DIESEL TANK HIGH LIQUID ALARM ALARM 4-18-24 10:28AM
Q 2 OTHER 91 PREMIUM PLLD SHUTDOWN ALARM ALARM 4-18-24 10:28AM
Q 2 OTHER 91 PREMIUM GROSS LINE FAIL ALARM 4-18-24 10:28AM
s10 OTHER 91 VENT HIGH LIQUID ALARM CLEAR 4-18-24 10:18AM
s 9 OTHER 91 PRODUCT HIGH LIQUID ALARM CLEAR 4-18-24 10:18AM
s 9 OTHER 91 PRODUCT NO VACUUM ALARM CLEAR 4-18-24 10:18AM
s10 OTHER 91 VENT NO VACUUM ALARM CLEAR 4-18-24 10:18AM
s10 OTHER 91 VENT NO VACUUM ALARM ALARM 4-18-24 10:18AM
Q 3 OTHER DIESEL PLLD SHUTDOWN ALARM CLEAR 4-18-24 10:16AM
Q 3 OTHER DIESEL GROSS LINE FAIL CLEAR 4-18-24 10:16AM
Q 3 OTHER DIESEL PLLD SHUTDOWN ALARM ALARM 4-18-24 10:14AM
Q 3 OTHER DIESEL GROSS LINE FAIL ALARM 4-18-24 10:14AM
s 9 OTHER 91 PRODUCT NO VACUUM ALARM ALARM 4-18-24 10:08AM
s 9 OTHER 91 PRODUCT HIGH LIQUID ALARM ALARM 4-18-24 10:07AM
s10 OTHER 91 VENT HIGH LIQUID ALARM ALARM 4-18-24 10:07AM
s12 OTHER DIESEL PRODUCT HIGH LIQUID ALARM CLEAR 4-18-24 10:06AM
s13 OTHER DIESEL VENT HIGH LIQUID ALARM CLEAR 4-18-24 10:06AM
s13 OTHER DIESEL VENT NO VACUUM ALARM CLEAR 4-18-24 10:06AM
s12 OTHER DIESEL PRODUCT NO VACUUM ALARM CLEAR 4-18-24 10:06AM
s13 OTHER DIESEL VENT NO VACUUM ALARM ALARM 4-18-24 10:03AM
s12 OTHER DIESEL PRODUCT NO VACUUM ALARM ALARM 4-18-24 10:02AM
s13 OTHER DIESEL VENT HIGH LIQUID ALARM ALARM 4-18-24 10:02AM
s12 OTHER DIESEL PRODUCT HIGH LIQUID ALARM ALARM 4-18-24 10:02AM
s14 OTHER DIESEL TANK HIGH LIQUID ALARM CLEAR 4-18-24 10:02AM
s14 OTHER DIESEL TANK HIGH LIQUID ALARM ALARM 4-18-24 10:01AM
I11200
APR 18, 2024 11:21 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 4-14-24 5:09PM
SYSTEM PAPER OUT CLEAR 4-14-24 5:09PM
SYSTEM PAPER OUT ALARM 4-14-24 5:08PM
SYSTEM PRINTER ERROR ALARM 4-14-24 5:08PM
OTHER ISD SENSOR OUT WARN CLEAR 3-29-24 9:21AM
OTHER ISD SENSOR OUT WARN ALARM 3-28-24 10:08AM
OTHER ISD SENSOR OUT WARN CLEAR 3-26-24 3:05PM
OTHER ISD SENSOR OUT WARN ALARM 3-26-24 10:07AM
OTHER ISD SENSOR OUT WARN CLEAR 3-25-24 10:11AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 3-25-24 10:10AM
OTHER ISD SENSOR OUT WARN ALARM 3-25-24 10:07AM
h 7 OTHER FP7: BLEND3 GROSS COLLECT WARN CLEAR 3-25-24 10:05AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 3-24-24 10:07AM
h 7 OTHER FP7: BLEND3 GROSS COLLECT WARN ALARM 3-24-24 10:07AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 3-18-24 11:03AM
T 1 TANK 87-1 UNLEADED INVALID FUEL LEVEL CLEAR 3-18-24 11:02AM
T 1 TANK 87-1 UNLEADED INVALID FUEL LEVEL ALARM 3-18-24 7:33AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 3-17-24 7:54PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 3-15-24 6:06PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 3-15-24 7:53AM
SYSTEM PRINTER ERROR CLEAR 3-12-24 6:37PM
SYSTEM PAPER OUT CLEAR 3-12-24 6:37PM
SYSTEM PAPER OUT ALARM 3-12-24 6:34PM
SYSTEM PRINTER ERROR ALARM 3-12-24 6:33PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 3-09-24 10:42PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 3-09-24 10:08PM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 3-07-24 8:43PM
T 4 TANK DIESEL DELIVERY NEEDED ALARM 3-07-24 3:32PM
OTHER ISD GROSS PRES WARN CLEAR 3-04-24 2:11PM
OTHER ISD GROSS PRES WARN ALARM 3-02-24 10:11AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 2-27-24 12:19AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 2-26-24 6:34PM
OTHER ISD VAPOR LEAK WARN CLEAR 2-26-24 12:30PM
T 3 TANK 91 PREMIUM DELIVERY NEEDED CLEAR 2-26-24 12:04PM
T 3 TANK 91 PREMIUM INVALID FUEL LEVEL CLEAR 2-26-24 12:04PM
T 3 TANK 91 PREMIUM INVALID FUEL LEVEL ALARM 2-26-24 11:40AM
T 3 TANK 91 PREMIUM DELIVERY NEEDED ALARM 2-26-24 11:39AM
OTHER ISD VAPOR LEAK WARN ALARM 2-22-24 10:08AM
OTHER ISD VAPOR LEAK WARN CLEAR 2-16-24 1:05PM
OTHER ISD VAPOR LEAK WARN ALARM 2-15-24 10:08AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 2-11-24 12:16AM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 2-10-24 11:50PM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED ALARM 2-10-24 5:53PM
T 4 TANK DIESEL DELIVERY NEEDED ALARM 2-10-24 9:37AM
OTHER ISD GROSS PRES WARN CLEAR 2-05-24 9:07AM
OTHER ISD GROSS PRES WARN ALARM 2-01-24 10:09AM
OTHER ISD GROSS PRES WARN CLEAR 1-25-24 1:53PM
OTHER ISD GROSS PRES WARN ALARM 1-24-24 10:08AM
T 1 TANK 87-1 UNLEADED DELIVERY NEEDED CLEAR 1-18-24 10:12PM
T 1 TANK 87-1 UNLEADED INVALID FUEL LEVEL CLEAR 1-18-24 10:11PM
I20600
APR 18, 2024 11:21 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
TANK ALARM HISTORY
TANK 1 87-1 UNLEADED
OVERFILL ALARM JAN 10, 2024 9:10 AM
DEC 3, 2023 1:01 AM
DEC 29, 2022 12:20 PM
LOW PRODUCT ALARM MAR 18, 2024 7:54 AM
JAN 18, 2024 5:52 PM
HIGH PRODUCT ALARM JAN 10, 2024 9:10 AM
AUG 15, 2022 2:05 PM
INVALID FUEL LEVEL MAR 18, 2024 7:33 AM
JAN 18, 2024 4:33 PM
PROBE OUT JAN 10, 2024 9:57 AM
JAN 10, 2024 8:48 AM
AUG 15, 2022 2:06 PM
DELIVERY NEEDED MAR 17, 2024 7:54 PM
MAR 15, 2024 7:53 AM
MAR 9, 2024 10:08 PM
TANK 2 87-2 UNLEADED
OVERFILL ALARM JAN 10, 2024 9:44 AM
JAN 10, 2024 9:11 AM
JAN 5, 2024 12:34 AM
HIGH PRODUCT ALARM JAN 10, 2024 9:12 AM
AUG 15, 2022 2:03 PM
JUN 10, 2022 9:12 AM
PROBE OUT JAN 10, 2024 9:55 AM
JAN 10, 2024 9:04 AM
JAN 10, 2024 8:52 AM
HIGH WATER WARNING JAN 10, 2024 8:56 AM
MAX PRODUCT ALARM JUN 10, 2022 9:12 AM
APR 9, 2022 5:56 AM
LOW TEMP WARNING JAN 10, 2024 9:57 AM
AUG 15, 2022 2:04 PM
TANK 3 91 PREMIUM
HIGH WATER ALARM JAN 10, 2024 9:17 AM
OVERFILL ALARM JAN 10, 2024 9:45 AM
JAN 10, 2024 9:13 AM
AUG 15, 2022 2:02 PM
LOW PRODUCT ALARM FEB 26, 2024 11:39 AM
JAN 10, 2024 8:54 AM
DEC 18, 2022 9:40 PM
SUDDEN LOSS ALARM FEB 26, 2024 11:40 AM
HIGH PRODUCT ALARM JAN 10, 2024 9:45 AM
JAN 10, 2024 9:13 AM
JUN 10, 2022 9:13 AM
INVALID FUEL LEVEL FEB 26, 2024 11:40 AM
DEC 18, 2022 7:44 PM
PROBE OUT FEB 28, 2024 2:15 PM
FEB 28, 2024 2:02 PM
FEB 26, 2024 11:41 AM
HIGH WATER WARNING JAN 10, 2024 9:17 AM
DELIVERY NEEDED FEB 26, 2024 11:39 AM
JAN 10, 2024 8:54 AM
NOV 13, 2023 9:07 AM
MAX PRODUCT ALARM JAN 10, 2024 9:13 AM
JUN 10, 2022 9:13 AM
JUN 10, 2022 8:05 AM
LOW TEMP WARNING JAN 10, 2024 9:52 AM
TANK 4 DIESEL
HIGH WATER ALARM FEB 23, 2023 12:19 PM
FEB 23, 2023 11:57 AM
FEB 22, 2023 6:00 PM
OVERFILL ALARM JAN 10, 2024 9:46 AM
JAN 10, 2024 9:15 AM
FEB 23, 2023 12:13 PM
LOW PRODUCT ALARM JAN 10, 2024 8:56 AM
SUDDEN LOSS ALARM DEC 25, 2023 5:43 PM
HIGH PRODUCT ALARM JAN 10, 2024 9:46 AM
JAN 10, 2024 9:15 AM
FEB 23, 2023 12:13 PM
INVALID FUEL LEVEL JAN 10, 2024 8:57 AM
FEB 23, 2023 12:30 PM
FEB 23, 2023 12:28 PM
PROBE OUT JAN 10, 2024 9:48 AM
JAN 10, 2024 8:57 AM
FEB 23, 2023 1:44 PM
HIGH WATER WARNING FEB 23, 2023 12:19 PM
FEB 23, 2023 11:57 AM
FEB 22, 2023 6:00 PM
DELIVERY NEEDED MAR 7, 2024 3:32 PM
FEB 10, 2024 9:37 AM
JAN 10, 2024 8:56 AM
MAX PRODUCT ALARM JAN 10, 2024 9:15 AM
FEB 23, 2023 12:13 PM
JUN 10, 2022 9:14 AM
LOW TEMP WARNING FEB 23, 2023 1:47 PM
FEB 23, 2023 12:44 PM
FEB 23, 2023 11:53 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
APR 18, 2024 11:22 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1:87 UNLEADED
APR 18, 2024 10:47 AM PLLD SHUTDOWN ALARM
APR 18, 2024 10:47 AM GROSS LINE FAIL
APR 18, 2024 10:36 AM PLLD SHUTDOWN ALARM
APR 18, 2024 10:36 AM GROSS LINE FAIL
APR 18, 2024 9:57 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:45 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:44 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:43 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:42 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:37 AM PLLD SHUTDOWN ALARM
Q 2:91 PREMIUM
APR 18, 2024 10:28 AM PLLD SHUTDOWN ALARM
APR 18, 2024 10:28 AM GROSS LINE FAIL
APR 18, 2024 9:57 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:45 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:44 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:43 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:42 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:35 AM PLLD SHUTDOWN ALARM
APR 4, 2024 12:36 PM PLLD SHUTDOWN ALARM
APR 4, 2024 12:36 PM GROSS LINE FAIL
Q 3:DIESEL
APR 18, 2024 10:14 AM PLLD SHUTDOWN ALARM
APR 18, 2024 10:14 AM GROSS LINE FAIL
APR 18, 2024 9:57 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:45 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:44 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:43 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:42 AM PLLD SHUTDOWN ALARM
APR 18, 2024 9:33 AM PLLD SHUTDOWN ALARM
APR 4, 2024 12:27 PM PLLD SHUTDOWN ALARM
APR 4, 2024 12:27 PM GROSS LINE FAIL
I30200
APR 18, 2024 11:22 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87-1 STP
APR 18, 2024 9:57 AM SENSOR OUT ALARM
APR 18, 2024 9:37 AM LOW LIQUID ALARM
APR 18, 2024 9:36 AM FUEL ALARM
2 87-1 FILL
APR 18, 2024 9:58 AM SENSOR OUT ALARM
APR 18, 2024 9:42 AM LOW LIQUID ALARM
APR 18, 2024 9:41 AM FUEL ALARM
3 87-2 STP
APR 18, 2024 9:57 AM SENSOR OUT ALARM
APR 18, 2024 9:37 AM LOW LIQUID ALARM
APR 18, 2024 9:37 AM FUEL ALARM
4 87-2 FILL
APR 18, 2024 9:58 AM SENSOR OUT ALARM
APR 18, 2024 9:41 AM LOW LIQUID ALARM
APR 18, 2024 9:40 AM FUEL ALARM
5 91 STP
APR 18, 2024 9:58 AM SENSOR OUT ALARM
APR 18, 2024 9:36 AM LOW LIQUID ALARM
APR 18, 2024 9:35 AM FUEL ALARM
6 91 FILL
APR 18, 2024 9:58 AM SENSOR OUT ALARM
APR 18, 2024 9:40 AM LOW LIQUID ALARM
APR 18, 2024 9:39 AM FUEL ALARM
7 DIESEL STP
APR 18, 2024 9:58 AM SENSOR OUT ALARM
APR 18, 2024 9:34 AM LOW LIQUID ALARM
APR 18, 2024 9:33 AM FUEL ALARM
8 DIESEL FILL
APR 18, 2024 9:58 AM SENSOR OUT ALARM
APR 18, 2024 9:39 AM LOW LIQUID ALARM
APR 18, 2024 9:38 AM FUEL ALARM
9 DISP 1-2
APR 18, 2024 9:57 AM SENSOR OUT ALARM
APR 18, 2024 9:44 AM LOW LIQUID ALARM
APR 18, 2024 9:43 AM FUEL ALARM
10 DISP 3-4
APR 18, 2024 9:58 AM SENSOR OUT ALARM
APR 18, 2024 9:44 AM LOW LIQUID ALARM
APR 18, 2024 9:44 AM FUEL ALARM
11 DISP 5-6
APR 18, 2024 9:57 AM SENSOR OUT ALARM
APR 18, 2024 9:43 AM LOW LIQUID ALARM
APR 18, 2024 9:42 AM FUEL ALARM
12 DISP 7-8
APR 18, 2024 9:57 AM SENSOR OUT ALARM
APR 18, 2024 9:45 AM LOW LIQUID ALARM
APR 18, 2024 9:45 AM FUEL ALARM
13 VENT BOX
APR 18, 2024 9:57 AM SENSOR OUT ALARM
APR 18, 2024 9:47 AM LOW LIQUID ALARM
APR 18, 2024 9:46 AM FUEL ALARM
I31600
APR 18, 2024 11:22 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 87-1 PRODUCT
APR 18, 2024 9:48 AM HIGH LIQUID ALARM
APR 4, 2024 10:43 AM HIGH LIQUID ALARM
APR 4, 2024 10:42 AM NO VACUUM ALARM
2 87-1 VENT
APR 18, 2024 9:48 AM HIGH LIQUID ALARM
APR 4, 2024 10:43 AM HIGH LIQUID ALARM
APR 4, 2024 10:42 AM NO VACUUM ALARM
3 87-1 TANK
APR 18, 2024 9:50 AM NO VACUUM ALARM
APR 4, 2024 10:44 AM HIGH LIQUID ALARM
APR 4, 2024 10:44 AM NO VACUUM ALARM
4 87-2 PRODUCT
APR 18, 2024 10:48 AM HIGH LIQUID ALARM
APR 18, 2024 9:45 AM HIGH LIQUID ALARM
APR 4, 2024 10:48 AM HIGH LIQUID ALARM
5 87-2 VENT
APR 18, 2024 10:48 AM HIGH LIQUID ALARM
APR 18, 2024 9:45 AM HIGH LIQUID ALARM
APR 4, 2024 10:48 AM HIGH LIQUID ALARM
6 87-2 TANK
APR 18, 2024 9:51 AM NO VACUUM ALARM
APR 4, 2024 2:41 PM NO VACUUM ALARM
APR 4, 2024 10:54 AM HIGH LIQUID ALARM
7 87-2 VAPOR
APR 18, 2024 10:48 AM HIGH LIQUID ALARM
APR 18, 2024 9:45 AM HIGH LIQUID ALARM
APR 4, 2024 10:48 AM HIGH LIQUID ALARM
8 ATM
9 91 PRODUCT
APR 18, 2024 10:08 AM NO VACUUM ALARM
APR 18, 2024 10:07 AM HIGH LIQUID ALARM
APR 18, 2024 9:42 AM HIGH LIQUID ALARM
10 91 VENT
APR 18, 2024 10:18 AM NO VACUUM ALARM
APR 18, 2024 10:07 AM HIGH LIQUID ALARM
APR 18, 2024 9:42 AM HIGH LIQUID ALARM
11 91 TANK
APR 18, 2024 9:53 AM HIGH LIQUID ALARM
APR 18, 2024 9:53 AM NO VACUUM ALARM
APR 4, 2024 11:00 AM HIGH LIQUID ALARM
12 DIESEL PRODUCT
APR 18, 2024 10:02 AM NO VACUUM ALARM
APR 18, 2024 10:02 AM HIGH LIQUID ALARM
APR 18, 2024 9:39 AM HIGH LIQUID ALARM
13 DIESEL VENT
APR 18, 2024 10:03 AM NO VACUUM ALARM
APR 18, 2024 10:02 AM HIGH LIQUID ALARM
APR 18, 2024 9:39 AM HIGH LIQUID ALARM
14 DIESEL TANK
APR 18, 2024 11:11 AM HIGH LIQUID ALARM
APR 18, 2024 11:04 AM NO VACUUM ALARM
APR 18, 2024 10:28 AM HIGH LIQUID ALARM
17 DISP 1-2 FM
18 DISP 3-4 FM
19 DISP 5-6 FM
20 DISP 7-8 FM
21 DISP 1-2 PRES SENSR
JUN 1, 2023 2:23 PM COMMUNICATION ALARM
I40200
APR 18, 2024 11:22 AM
I40300
APR 18, 2024 11:22 AM
I34200
APR 18, 2024 11:22 AM
I34700
APR 18, 2024 11:22 AM
IV0100
APR 18, 2024 11:22 AM
3351 HOWARDS
3200 PANAMA LN
BAKERSFIELD CA
93313
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-03-28 10:08:38 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 3:DISP 5-6 FM
24-03-26 10:07:18 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:DISP 7-8 FM
24-03-25 10:07:54 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:DISP 7-8 FM
24-03-25 10:07:54 A/L RATIO DEGRADATION FP 7 BLEND3 BLKD
24-03-24 10:07:11 A/L RATIO DEGRADATION FP 7 BLEND3 BLKD
24-03-24 10:07:11 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
24-03-04 10:09:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07
24-03-03 10:09:22 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07
24-03-02 10:11:44 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07
24-02-26 10:08:12 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 186.73
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
24-03-25 10:07:54 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
23-09-12 10:10:10 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-11 10:09:46 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-10 10:09:47 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-04 10:09:14 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-03 10:09:07 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-09-02 10:09:23 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-10-18 10:10:20 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.02
19-12-18 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
19-11-25 10:02:24 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-04-10 19:08:58 VAPOR PROCESSOR TEST MANUALLY CLEARED
24-04-10 19:08:50 ISD SELFTEST TEST MANUALLY CLEARED
24-04-10 19:08:26 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
24-04-10 19:08:02 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-04-05 10:07:42 READINESS ISD:PP EVR:PP ISD & EVR READY
24-04-04 11:33:38 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-04-04 11:33:38 ISD STARTUP
24-04-04 11:33:32 ISD SHUTDOWN
24-03-29 09:21:54 SENSOR OUT TEST MANUALLY CLEARED
24-03-26 15:05:23 SENSOR OUT TEST MANUALLY CLEARED