HomeMy WebLinkAboutFMC 2024IMPACT VALVE LEAK DETECTOR MONITOR CERTIFICATION SPILL BUCKET TEST 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 4/28/2024 BAKERSFIELD FIRE DEPARTMENT OFFICE OF ENVIRONMENTAL SERVICES INSPECTOR KRIS KARNS 1501 TRUXTUN AVE. BAKERSFIELD, CA 93301 Test Date: 4/4/2024 Order Number: 3468258 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 7-ELEVEN 37942/59987 3225 BUCK OWENS BLVD., HWY 99/HWY 58 BAKERSFIELD, CA 93301 In an effort to keep all our record keeping and reporting requirements as current as possible, Tanknology kindly requests you notify Dawn Kohlmeyer in writing at dkohlmeyer@tanknology.com when your CUPA requires all records to be submitted electronically via the CERS database. Your assistance in this endeavor is greatly appreciated. Testing performed: Sincerely, Dawn Kohlmeyer Manager, Field Reporting LDT 5000 Field Test Apparatus Line Leak Detector Test Page 1 of 1 Work Order:3468258 Date:4/4/2024 Site Name / ID:7-ELEVEN 37942/59987 / 37942/59987 Address:3225 BUCK OWENS BLVD., HWY 99/HWY 58 City:BAKERSFIELD State:CA Zip:93301 Tank ID Product Product Line Tested From Existing/New Mechanical/Electronic Manufacturer/Model Serial No. Pump Operating Pressure (psi) Calibrated Leak (ml/min) Calibrated Leak (gph) Holding PSI *N/A for Electronic LD's Resiliency (ml) *N/A for Electronic LD's Metering PSI *N/A for Electronic LD's Opening Time (sec) *N/A for Electronic LD's Test Results T-1 REGULAR 1 6 Existing Mechanical Veeder Root FX1V 20508-3195 28.00 189.0 3.00 15.00 100.00 10 7 Pass T-2 PREMIUM 1 6 Existing Mechanical Veeder Root FX1V 30208-9410 27.00 189.0 3.00 25.00 120.00 10 6 Pass T-4 Diesel 1 9 Existing Mechanical Veeder Root FX1DV 412209911 Not Tested Technician Comments: Unable to test diesel line leak detector due to excessive bleed back, greater than five gallons and continued to flow. Troubleshooting required. Technician Name:Steven Lantz Certification #:175337 Technician Signature:Expire Date:5/5/2024 Environmental Compliance for Petroleum Systems © 2024 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Impact Valve Inspection Impact Valve Operational Inspection Work Order:3468258 Date:4/4/2024 Site Name/ID:7-ELEVEN 37942/59987 Address:3225 BUCK OWENS BLVD., HWY 99/HWY 58 City:BAKERSFIELD State:CA Zip:93301 How Inspected: Line Test NFPA 30A PEI RP1200 Other Dispenser Number Grade Secure Mount? Valve Lock?Pass/ Fail Comments 1/2 87 Pass Fail Not Tested 1/2 91 Pass Fail Not Tested 3/4 87 Pass Fail Not Tested 3/4 91 Pass Fail Not Tested 5/6 87 Pass Fail Not Tested 5/6 91 Pass Fail Not Tested 7/8 87 Pass Fail Not Tested 7/8 91 Pass Fail Not Tested 9/ 40 Pass Fail Not Tested none/ 40 Pass Fail Not Tested 9 Sat/10 40 Pass Fail Not Tested 10 Sat/11 40 Pass Fail Not Tested 11 Sat/12 40 Pass Fail Not Tested 12 Sat/13 40 Pass Fail Not Tested 13 Sat/ 40 Pass Fail Not Tested Technician Comments: Technician Name:Steven Lantz Signature: Environmental Compliance for Petroleum Systems ©2024 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Tanknology, Inc.800-964-1250 11000 N Mopac Expy #500 Austin, Tx 78759 Steven Lantz 10134880 04/04/2024 7-ELEVEN 37942/59987 3225 BUCK OWENS BLVD., HWY 99/HWY 58 BAKERSFIELD 93301 Class A General Engineering 743160 8358929 05/08/2025 08/16/2024 04/25/2025 04/04/2024 6 Veeder Root:ATG Technician (B46717) VMI:TLDT-5000 Tester (5375) Gilbarco EMC 334.00 L1 91 STP SUMP L2 L3 87 INT L4 L5 L6 L7 FILTER SUMP L8 L9 91 FVR SUMP L10 UDC UDC UDC 3/4 UDC UDC 5/6 UDC UDC 7/8 UDC 9 DIESEL UDC 9 SAT-10 DIESEL UDC 10 SAT-11 DIESEL UDC 11 SAT-12 DIESEL UDC UDC 13 SAT DIESEL 794380-205 87 STP SUMP 91 INT DSL STP SUMP DSL INT 87 FVR SUMP DSL FVR SUMP UDC 1/2 12 SAT-13 DIESEL 794380-208 794390-420 794390-420 794380-208 794390-460 794380-208 794380-208 794380-208 794380-208 847990-001 847990-001 847990-001 847990-001 847990-001 847990-001 847990-001 847990-001 847990-001 847990-001 T1 RUL T2 T4 DSL - Not Tested - See Comments Red Jacket FX1V PULRed Jacket FX1V Red Jacket FX1DV Unable to test diesel line leak detector due to excessive bleed back, greater than five gallons and continued to flow. Troubleshooting required. All UDCs have Veeder Root 001 standalone sensors. 04/04/2024 10134880 04/04/2024 7-ELEVEN 37942/59987 3225 BUCK OWENS BLVD., HWY 99/HWY 58 BAKERSFIELD 93301 Tanknology, Inc.800-964-1250 11000 N Mopac Expy #500 Austin, TX 78759 Steven Lantz 743160 8358929 05/08/2025 06/05/2025 Per PEI RP1200: 1 Hr Lake Test Spill Buckets 04/04/2024 2 Franklin Fueling:Phil-Tite EVR Ph 1 Systems T1 RUL T2 PUL T4 DSL Phil Tite Phil Tite Phil Tite SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 7-ELEVEN 37942/59987 Date of Testing: 4/4/2024 Facility Address: 3225 BUCK OWENS BLVD., HWY 99/HWY 58 , BAKERSFIELD, CA 93301 Facility Contact: Joel Phone: 661-229-9416 Date Local Agency Was Notified of Testing: 3/5/2024 Name of Local Agency Inspector (if present during testing): Luke Preece 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY INC. Technician Conducting Test: Steven Lantz Credentials1: CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s): 8358929 3. SPILL BUCKET TESTING INFORMATION Test Method Used By: Hydrostatic Vacuum Other Test Equipment Used: LAKE TEST Equipment Resolution: 0.0625 in. Identify Spill Bucket (By Tank Number, Stored Product, etc.) Bucket Installation Type: Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test Test Start Time (TI): Initial Reading (RI): Test End Time(TF): Final Reading (RF): Test Duration(TF–TI): Change in Reading (RF–RI) : Pass/Fail Threshold or Criteria: Test Result: Spill Box # Tank T-1 REGULAR - Fill 1 - Direct - Grade level in containment sump Direct Bury Contained in Sump 11.00 13.00 15 min 09:30:00 12.50 in. 10:30:00 12.50 in. 1 hr 0.00 in. +/- 0.00 Pass Spill Box # Tank T-2 PREMIUM - Fill 1 - Direct - Below Grade in containment sump Direct Bury Contained in Sump 11.00 13.00 15 min 09:30:00 12.50 in. 10:30:00 12.50 in. 1 hr 0.00 in. +/- 0.00 Pass Spill Box # Tank T-4 Diesel - Fill 1 - Direct - Grade level in containment sump Direct Bury Contained in Sump 11.00 13.00 15 min 10:00:00 12.50 in. 11:00:00 12.50 in. 1 hr 0.00 in. +/- 0.00 Pass Spill Box # Direct Bury Contained in Sump min +/- Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature:Date:4/4/2024 1State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. WO: 3468258 Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:3468258 Site ID / Name:37942/59987 / 7-ELEVEN 37942/59987 Address:3225 BUCK OWENS BLVD., HWY 99/HWY 58 City:BAKERSFIELD State:CA Zip:93301 Test Duration Test Pressure P/F Threshold Tank Annular - Vacuum 1 hr, 20k or less tank 10" hg 0 loss, int dry before and after test Tank Annular - Vacuum 2 hr, >20k tank 10" hg 0 loss, int dry before and after test Line Annular - Pressure 1 hr 5 psi 0 loss STP Sump - Hydro 1 hr 4" above highest penetration or sidewall seam less than 1/8" over hour, settle time of 15 minutes minimum prior to starting the test UDC Sump - Hydro 1 hr 4" above highest penetration or sidewall seam less than 1/8" over hour, settle time of 15 minutes minimum prior to starting the test Spill Bucket - SW Vac 1 min 30" wc no greater than 4" wc vaccum decay - bucket must be dry Spill Bucket - SW Hydro 1 hr within 1.5" of top of the bucket less than 1/8" over hour, settle time of 5 minutest minimum prior to starting the test Spill Bucket - DW Vac 1 min 15" wc no greater than 3" wc vaccum decay - int must be dry  I10100 APR 4, 2024 12:00 PM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 SYSTEM STATUS REPORT ALL FUNCTIONS NORMAL     I20100 APR 4, 2024 12:00 PM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 IN-TANK INVENTORY TANK PRODUCT VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP 1 RUL 11953 11849 2177 75.31 0.00 72.38 2 PUL 2177 2157 7963 25.52 0.00 73.01 4 DSL 14287 14193 5781 85.40 0.00 74.53     I30100 APR 4, 2024 12:00 PM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 LIQUID STATUS REPORT SENSOR LOCATION STATUS 1 91 STP SUMP SENSOR NORMAL 2 87 STP SUMP SENSOR NORMAL 3 87 INT SENSOR NORMAL 4 91 INT SENSOR NORMAL 5 DSL STP SUMP SENSOR NORMAL 6 DSL INT SENSOR NORMAL 7 FILTER SUMP SENSOR NORMAL 8 87 FVR SUMP SENSOR NORMAL 9 91 FVR SUMP SENSOR NORMAL 10 DSL FVR SUMP SENSOR NORMAL     I50301 APR 4, 2024 12:00 PM # 1:860169 7-11 37942     I50302 APR 4, 2024 12:00 PM # 2:3225 BUCK OWENS     I50303 APR 4, 2024 12:00 PM # 3:BAKERSFIELD,CA 933O8     I50304 APR 4, 2024 12:00 PM # 4:41031663305001    I51700 APR 4, 2024 12:00 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM     I50F00 APR 4, 2024 12:00 PM MON DD YYYY HH:MM:SS xM     I60100 APR 4, 2024 12:00 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 RUL ON 2 PUL ON 3 OFF 4 DSL ON     I60200 APR 4, 2024 12:00 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 RUL 2 PUL 3 4 DSL    I60300 APR 4, 2024 12:00 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 RUL 1 2 PUL 2 3 3 4 DSL 4     I60400 APR 4, 2024 12:00 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 RUL 14130 2 PUL 10140 3 0 4 DSL 20068     I60700 APR 4, 2024 12:00 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 RUL 95.50 2 PUL 95.50 3 0.00 4 DSL 127.50  I60900 APR 4, 2024 12:00 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 RUL 0.000700 2 PUL 0.000700 3 0.000000 4 DSL 0.000450     I61200 APR 4, 2024 12:00 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 RUL NONE NONE 2 PUL NONE NONE 3 NONE NONE 4 DSL NONE NONE     I62100 APR 4, 2024 12:00 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 0 2 PUL 0 3 0 4 DSL 0    I62200 APR 4, 2024 12:00 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 13424 2 PUL 9633 3 0 4 DSL 19065    I62300 APR 4, 2024 12:00 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 12717 2 PUL 9126 3 0 4 DSL 18061    I62400 APR 4, 2024 12:00 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 RUL 1.5 2 PUL 1.5 4 DSL 2.0   I62800 APR 4, 2024 12:00 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 14130 2 PUL 10140 3 0 4 DSL 20068     I62900 APR 4, 2024 12:00 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 141 2 PUL 101 3 0 4 DSL 201     I70300 APR 4, 2024 12:00 PM LIQUID TYPE SENSOR LOCATION TYPE 1 91 STP SUMP TRI-STATE (SINGLE FLOAT) 2 87 STP SUMP TRI-STATE (SINGLE FLOAT) 3 87 INT TRI-STATE (SINGLE FLOAT) 4 91 INT TRI-STATE (SINGLE FLOAT) 5 DSL STP SUMP TRI-STATE (SINGLE FLOAT) 6 DSL INT TRI-STATE (SINGLE FLOAT) 7 FILTER SUMP TRI-STATE (SINGLE FLOAT) 8 87 FVR SUMP TRI-STATE (SINGLE FLOAT) 9 91 FVR SUMP TRI-STATE (SINGLE FLOAT) 10 DSL FVR SUMP TRI-STATE (SINGLE FLOAT) 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT)     I90200 APR 4, 2024 12:00 PM SOFTWARE REVISION LEVEL VERSION 334.00 SOFTWARE# 346334-100-A CREATED - 15.05.29.10.36 S-MODULE# 330160-100-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR    I30200 APR 4, 2024 12:00 PM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 91 STP SUMP APR 4, 2024 9:56 AM SENSOR OUT ALARM APR 4, 2024 9:31 AM FUEL ALARM APR 10, 2023 1:00 PM SENSOR OUT ALARM 2 87 STP SUMP APR 4, 2024 9:56 AM SENSOR OUT ALARM APR 4, 2024 9:33 AM FUEL ALARM JUN 14, 2023 9:20 AM FUEL ALARM 3 87 INT APR 4, 2024 9:56 AM SENSOR OUT ALARM APR 4, 2024 9:32 AM FUEL ALARM APR 10, 2023 1:00 PM SENSOR OUT ALARM 4 91 INT APR 4, 2024 9:56 AM SENSOR OUT ALARM APR 4, 2024 9:32 AM FUEL ALARM APR 10, 2023 1:00 PM SENSOR OUT ALARM 5 DSL STP SUMP APR 4, 2024 10:16 AM FUEL ALARM APR 4, 2024 10:13 AM FUEL ALARM APR 4, 2024 9:56 AM SENSOR OUT ALARM 6 DSL INT APR 4, 2024 10:13 AM FUEL ALARM APR 4, 2024 9:56 AM SENSOR OUT ALARM APR 10, 2023 1:00 PM SENSOR OUT ALARM 7 FILTER SUMP APR 4, 2024 10:14 AM FUEL ALARM APR 4, 2024 9:56 AM SENSOR OUT ALARM DEC 30, 2023 6:10 AM FUEL ALARM 8 87 FVR SUMP APR 4, 2024 9:56 AM SENSOR OUT ALARM APR 4, 2024 9:32 AM FUEL ALARM APR 10, 2023 1:00 PM SENSOR OUT ALARM 9 91 FVR SUMP APR 4, 2024 9:56 AM SENSOR OUT ALARM APR 4, 2024 9:31 AM FUEL ALARM APR 10, 2023 1:00 PM SENSOR OUT ALARM 10 DSL FVR SUMP APR 4, 2024 10:13 AM FUEL ALARM APR 4, 2024 9:56 AM SENSOR OUT ALARM FEB 19, 2024 1:09 AM FUEL ALARM    I80800 APR 4, 2024 12:01 PM RELAY SETUP REPORT R 1:87 STP TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS L 2:FUEL ALARM L 3:FUEL ALARM L 8:FUEL ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 8:SHORT ALARM R 2:89 STP TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS L 1:FUEL ALARM L 4:FUEL ALARM L 9:FUEL ALARM L 1:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L 1:SHORT ALARM L 4:SHORT ALARM L 9:SHORT ALARM R 3:DSL 1,2,3 TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS L 5:FUEL ALARM L 6:FUEL ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM R 4:DSL STP 4,5 TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L10:FUEL ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L10:SHORT ALARM R 5:DSL OVERFILL TYPE: STANDARD NORMALLY OPEN IN-TANK ALARMS T 1:OVERFILL ALARM T 4:HIGH PRODUCT ALARM T 4:MAX PRODUCT ALARM LIQUID SENSOR ALMS ALL:FUEL ALARM R 6:GAS OVERFILL TYPE: STANDARD NORMALLY OPEN IN-TANK ALARMS T 1:OVERFILL ALARM T 2:OVERFILL ALARM T 1:HIGH PRODUCT ALARM T 2:HIGH PRODUCT ALARM T 1:MAX PRODUCT ALARM T 2:MAX PRODUCT ALARM R 7: TYPE: STANDARD NORMALLY OPEN - NO ALARM ASSIGNMENTS -R 8: TYPE: STANDARD NORMALLY OPEN - NO ALARM ASSIGNMENTS -