HomeMy WebLinkAbout2024 ELD (INSTALLATION)Providers for MDleak® MSleak® DPleak®, MCleak® and
PHDleak® Testing Technologies
Page 1 of 2
Test Type: Job #: 5335
Facility Name: PO #:
Prepared For:
Site Address:
City:
State and Zip: CA 93311
Start Date:End Date:
SYSTEM Test MDL TK-1 87 TK-2 91 TK-3 DSL VR
Product Primary MDleak:0.005 GPH PASS PASS PASS
Vent Primary MDleak:0.005 GPH PASS PASS PASS
VR Primary MDleak:0.005 GPH PASS PASS NA
MDleak Tank:0.005 GPH PASS PASS PASS
Turbine Sump Fittings:0.005 GPH PASS PASS PASS
Fill/Vapor Sump Fittings:0.005 GPH PASS PASS PASS
UDC Fittings:0.005 GPH PASS PASS PASS
Fill Bucket:0.005 GPH PASS PASS PASS
Vapor Bucket:0.005 GPH PASS PASS NA
Vent Box Fittings 0.005 GPH PASS PASS PASS
Fill Spill Bucket Hydro:0.1 GPH PASS PASS PASS
Vapor Bucket Hydro:0.1 GPH PASS PASS NA
16101 Stockdale Highway
Bakersfield
5/9/20245/8/2024
Sunset Mechanical
Facility Certification CONFIDENTIAL
California ELD New Construction Test w/out Fuel
Sully's
Providers for MDleak® MSleak® DPleak®, MCleak® and
PHDleak® Testing Technologies
Page 2 of 2
Test Type:
Facility Name: Job #: 5335
Prepared For: PO #:
Site Address:
City:
State and Zip: CA 93311
Start Date:End Date:
SYSTEM TK-1 87 TK-2 91 TK-3 DSL VR
20000 12000 8000
Modern Modern Modern
Dry Dry Dry
63"63"65"
10 ft 10 ft 10 ft
No Fuel No Fuel No Fuel
Tank Sump Boots Turbine
Bravo Bravo
8.00 0 0 0
Manufacture
EVR:
Certifying Field Technician: State Lic. # :
Certification Leak Rate: 0.005.gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date:
16101 Stockdale Highway
Bakersfield
5/8/2024 5/9/2024
Ricardo Gonzalez
Tank Volume in Gallons:
UST Manufacture:
Type of Interstice:
Depth To Top Tank:
Tank Diameter:
OPW
Bravo
Smith
Smith
Unisource
Spill Buckets:
Healgy
Gilbarco
Office use only
5/16/2024
Depth to Ground Water:
Component Manufacture:
UDC/Dispensers Information
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Containment Boots:
Piping Information
Product Lines:
Vapor Return / Vent:
Depth of Liquid Within Tank:
5/9/2024
Facility Certification CONFIDENTIAL
California ELD New Construction Test w/out Fuel
Sully's
Sunset Mechanical
Flex:
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National
Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is
true and correct to the best of my knowledge.
This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak
sensitivity listed above by using one or more of the following DPleak®,MDleak®,MCleak and PHDleak®EPA aproved
Methods.These Methods are the most versatile and comprehensive testing procedures offered to the petroleum
industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®,MCleak,and PHDleak®Method can
be assured that their facility has passed the Nation's highest standard in preventative leak detection.
04-1695
PhilTite