HomeMy WebLinkAbout2024 FMCAppendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10134226 06/13/2024 Jaco #3346 Fastrip #621 805 -34th- Street Bakersfield 93301 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fisher 1073967 10278702 Veeder Root - C33847 07/24/2025 Vaporless Manfacturing LLC #5346 03/14/2025 OPW - 1193587 08/04/2025 06/13/2024 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder Root TLS350 336.02 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 Unleaded 1 STP L2 420 Unleaded 1 Annular L3 208 Unleaded 2 STP L4 420 Unleaded 2 Annular L5 208 Premium STP L6 420 Premium Annular L7 208 Diesel STP L8 420 Diesel Annular L9 208 Dispenser 1/2 L10 208 Dispenser 3/4 L11 208 Dispenser 5/6 L12 208 Dispenser 7/8 L13 208 E. Trans Sump L14 208 W. Trans Sump Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V 87-1 Unleaded T2 FX1V 87-2 Unleaded T3 FX1V 91 Premium T4 FX1DV Diesel Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. 06/13/2024 VFFN PRIC E S I G N PROPERTY LINE PROPERTY LINE141.50'125'EXISTING BUILDING W H G W 34TH ST.Q ST.VFSTPL112,000 GALLON87-1 UNLEADED12,000 GALLON87-2 UNLEADED12,000 GALLON91 PREMIUM12,000 GALLONDIESELVFSTPL3STPL5STPL7AL2AL4AL6AL8L9L11L12L10L13L1465874321L12L10DUMPSTER NOPARKINGLEGEND L1 87-1 STP L2 87-1 ANNULAR L3 87-2 STP L4 87-2 ANNULAR L5 91 STP L6 91 ANNULAR L7 DSL STP L8 DSL ANNULAR L9 UDC 1 -2 L10 UDC 3 - 4 L11 UDC 5 - 6 L12 UDC 7 - 8 L13 E. TRANS SUMP L14 W. TRANS SUMP 87 GAS 2 INCH SINGLE WALLED PIPE 91 GAS 2 INCH SINGLE WALLED PIPE DIESEL 2 INCH SINGLE WALLED PIPE VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIP VAPOR VENT 2 INCH SINGLE WALLED PIPE PRODUCT SPILL CONTAINER VAPOR SPILL CONTAINER ANNULAR EMERGENCY SHUT-OFF OVERFILL ALARM FIRE EXTINGUISHER GAS METER SHUT-OFF EVACUATION MEETING POINT AUTOMATIC TANK GAUGE UST ELECTRICAL PANEL AIR AND WATER DISPENSER HAZ-WASTE DRUMS G A P V SITE MAP SITE PLAN C1 TAB:CERS 1"=10'-0" INCHES012 SHEET SIZE 22 X 34 DATE REVISIONS DATE: DRAWN BY: CHECKED: APPROVED: RAC FASTRIP - 3-346 CADFILE: SHEET NO.3346-MSP A.P.N.: 002-032-14-00-8 SCALE: FASTRIP OIL COMPANYCONVENIENCE MARKET FOR: BAKERSFIELD, CALIFORNIA 93301 JACO HILL 805 34TH ST. 3101 STATE RDBAKERSFIELD, CA 93308 PROJECT OWNER: DRAWING: CD 03/25/2021 805 34TH ST. BAKERSFIELD, CA 93301 Q ST. 34TH ST. PROJECT OWNER: JACO HILL PO. BOX 82515 BAKERSFIELD, CA 93380 CONTACT: SITE PLOT PLAN FOR: FACILITY ID 15-021-03017 CERS ID 10134226 FASTRIP #3346 805 34TH ST. BAKERSFIELD, CA 93301 03/05/2021 REV. VICINITY MAP PROJECT DATA APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Jaco #3346 Fastrip #621805 -34th- StreetBakersfield101342263/47/8MPDMPDMPDMPD1/25/6ProductProductProductProductMark Fisher Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10134226 06/13/2024 Jaco #3346 Fastrip #621 805 -34th- Street Bakersfield 93301 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fisher 1073967 10278702 OPW - 1193587 08/04/2025 OPW - 1193587 PEI1200, 1 hour hydrostatic test 06/13/2024 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. 87-1 OPW 87-2 OPW 91 OPW Diesel OPW FASTRIP #3346 SYSTEM SETUP Responses Received: 200 FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 JUN 13, 2024 8:39 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 1 8103 60.80 0.0 81.2 3959 2 UNLEADEDED 2 8120 60.91 0.8 83.0 3942 3 PREMIUM 5629 45.25 0.0 80.1 6433 4 DIESEL 3568 32.15 0.8 80.9 8494 I90500 JUN 13, 2024 8:39 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JUN 13, 2024 8:39 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JUN 13, 2024 8:39 AM SHIFT TIME 1 : 6:00 AM I50202 JUN 13, 2024 8:39 AM SHIFT TIME 2 : DISABLED I50203 JUN 13, 2024 8:39 AM SHIFT TIME 3 : DISABLED I50204 JUN 13, 2024 8:39 AM SHIFT TIME 4 : DISABLED I54600 JUN 13, 2024 8:39 AM TANK PER TST NEEDED WRN: DISABLED I54900 JUN 13, 2024 8:39 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JUN 13, 2024 8:39 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JUN 13, 2024 8:39 AM LINE PER TST NEEDED WRN: DISABLED I55900 JUN 13, 2024 8:39 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JUN 13, 2024 8:39 AM PRINT TC VOLUMES ENABLED I50E00 JUN 13, 2024 8:39 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JUN 13, 2024 8:39 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JUN 13, 2024 8:39 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JUN 13, 2024 8:39 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 JUN 13, 2024 8:39 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 JUN 13, 2024 8:39 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JUN 13, 2024 8:39 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JUN 13, 2024 8:39 AM TANK CHART SECURITY DISABLED I5BD00 JUN 13, 2024 8:39 AM CUSTOM ALARM LABELS DISABLED I56000 JUN 13, 2024 8:39 AM MASS/DENSITY DISABLED I88101 JUN 13, 2024 8:39 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JUN 13, 2024 8:39 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JUN 13, 2024 8:39 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 JUN 13, 2024 8:39 AM I88105 JUN 13, 2024 8:39 AM I88106 JUN 13, 2024 8:39 AM I52000 JUN 13, 2024 8:39 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE JAN 28, 2022 DISABLED 2 ON DATE JAN 28, 2022 DISABLED 3 ON DATE JAN 28, 2022 DISABLED 4 ON DATE JAN 28, 2022 DISABLED 5 ON DATE JAN 28, 2022 DISABLED 6 ON DATE JAN 28, 2022 DISABLED 7 ON DATE JAN 28, 2022 DISABLED 8 ON DATE JAN 28, 2022 DISABLED I60100 JUN 13, 2024 8:39 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED 1 ON 2 UNLEADEDED 2 ON 3 PREMIUM ON 4 DIESEL ON I60200 JUN 13, 2024 8:39 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 1 2 UNLEADEDED 2 3 PREMIUM 4 DIESEL I60300 JUN 13, 2024 8:39 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 1 2 UNLEADEDED 2 2 3 PREMIUM 3 4 DIESEL 4 I60900 JUN 13, 2024 8:39 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 1 0.000700 2 UNLEADEDED 2 0.000700 3 PREMIUM 0.000700 4 DIESEL 0.000450 I60700 JUN 13, 2024 8:39 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 1 95.50 2 UNLEADEDED 2 95.50 3 PREMIUM 95.50 4 DIESEL 95.50 I60A00 JUN 13, 2024 8:39 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 1 PT 12062 2 UNLEADEDED 2 1 PT 12062 3 PREMIUM 1 PT 12062 4 DIESEL 1 PT 12062 I60400 JUN 13, 2024 8:39 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12062 2 UNLEADEDED 2 12062 3 PREMIUM 12062 4 DIESEL 12062 I60500 JUN 13, 2024 8:39 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12062 0 0 0 2 UNLEADEDED 2 12062 0 0 0 3 PREMIUM 12062 0 0 0 4 DIESEL 12062 0 0 0 I60600 JUN 13, 2024 8:39 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 UNLEADEDED 2 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 PREMIUM 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 DIESEL 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JUN 13, 2024 8:39 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED 1 NO 2 UNLEADEDED 2 NO 3 PREMIUM NO 4 DIESEL NO I62F00 JUN 13, 2024 8:39 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 1 4.0 IN. 2 UNLEADEDED 2 4.0 IN. 3 PREMIUM 4.0 IN. 4 DIESEL 4.0 IN. I62700 JUN 13, 2024 8:39 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 2.0 2 UNLEADEDED 2 2.0 3 PREMIUM 2.0 4 DIESEL 2.0 I64200 JUN 13, 2024 8:39 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED 1 LOW 2 UNLEADEDED 2 LOW 3 PREMIUM LOW 4 DIESEL LOW I62400 JUN 13, 2024 8:39 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 3.0 2 UNLEADEDED 2 3.0 3 PREMIUM 3.0 4 DIESEL 3.0 I62800 JUN 13, 2024 8:39 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 12062 2 UNLEADEDED 2 12062 3 PREMIUM 12062 4 DIESEL 12062 I62300 JUN 13, 2024 8:39 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 10856 2 UNLEADEDED 2 10856 3 PREMIUM 10856 4 DIESEL 10856 I62200 JUN 13, 2024 8:39 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 11459 2 UNLEADEDED 2 11459 3 PREMIUM 11459 4 DIESEL 11459 I62900 JUN 13, 2024 8:39 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 1809 2 UNLEADEDED 2 1809 3 PREMIUM 1809 4 DIESEL 1809 I62100 JUN 13, 2024 8:39 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 500 2 UNLEADEDED 2 500 3 PREMIUM 500 4 DIESEL 500 I62600 JUN 13, 2024 8:39 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 99 2 UNLEADEDED 2 99 3 PREMIUM 99 4 DIESEL 99 I62500 JUN 13, 2024 8:39 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 99 2 UNLEADEDED 2 99 3 PREMIUM 99 4 DIESEL 99 I60800 JUN 13, 2024 8:39 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 2.50 2 UNLEADEDED 2 0.00 3 PREMIUM 1.40 4 DIESEL 0.20 I60B00 JUN 13, 2024 8:39 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JUN 13, 2024 8:39 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 1 0.00 2 UNLEADEDED 2 0.00 3 PREMIUM 0.00 4 DIESEL 0.00 I61200 JUN 13, 2024 8:39 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED 1 NONE 2 2 UNLEADEDED 2 NONE 1 3 PREMIUM NONE NONE 4 DIESEL NONE NONE I63600 JUN 13, 2024 8:39 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 120 2 UNLEADEDED 2 120 3 PREMIUM 120 4 DIESEL 120 I62A00 JUN 13, 2024 8:39 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 0 2 UNLEADEDED 2 0 3 PREMIUM 0 4 DIESEL 0 I62C00 JUN 13, 2024 8:39 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED 1 STANDARD 2 UNLEADEDED 2 STANDARD 3 PREMIUM STANDARD 4 DIESEL STANDARD I62D00 JUN 13, 2024 8:39 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED 1 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 2 UNLEADEDED 2 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 3 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 4 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JUN 13, 2024 8:39 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED 1 OFF OFF 2 UNLEADEDED 2 OFF OFF 3 PREMIUM OFF OFF 4 DIESEL OFF OFF I63000 JUN 13, 2024 8:39 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED 1 OFF 2 UNLEADEDED 2 OFF 3 PREMIUM OFF 4 DIESEL OFF I63200 JUN 13, 2024 8:40 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED 1 OFF 2 UNLEADEDED 2 OFF 3 PREMIUM OFF 4 DIESEL OFF I61000 JUN 13, 2024 8:40 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 1 2 UNLEADEDED 2 1 3 PREMIUM 1 4 DIESEL 1 I63A00 JUN 13, 2024 8:40 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 1 10.00% 2 UNLEADEDED 2 10.00% 3 PREMIUM 10.00% 4 DIESEL 10.00% I61100 JUN 13, 2024 8:40 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK JUL 1, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JUN 13, 2024 8:40 AM CSLD PROBABLITY OF DETECTION I61400 JUN 13, 2024 8:40 AM CSLD CLIMATE FACTOR I61600 JUN 13, 2024 8:40 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED 1 IMMEDIATE 2 UNLEADEDED 2 IMMEDIATE 3 PREMIUM IMMEDIATE 4 DIESEL IMMEDIATE I61A00 JUN 13, 2024 8:40 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED 1 DISABLED 2 UNLEADEDED 2 DISABLED 3 PREMIUM DISABLED 4 DIESEL DISABLED I61B00 JUN 13, 2024 8:40 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JUN 13, 2024 8:40 AM CSLD REPORT ONLY I62B00 JUN 13, 2024 8:40 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED 1 ??? 0, 0 2 UNLEADEDED 2 ??? 0, 0 3 PREMIUM ??? 0, 0 4 DIESEL ??? 0, 0 I63300 JUN 13, 2024 8:40 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JUN 13, 2024 8:40 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 0 2 UNLEADEDED 2 0 3 PREMIUM 0 4 DIESEL 0 I63500 JUN 13, 2024 8:40 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 1 2 UNLEADEDED 2 1 3 PREMIUM 1 4 DIESEL 1 I63900 JUN 13, 2024 8:40 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED 1 END FACTOR: NONE 2 UNLEADEDED 2 END FACTOR: NONE 3 PREMIUM END FACTOR: NONE 4 DIESEL END FACTOR: NONE I78000 JUN 13, 2024 8:40 AM I77700 JUN 13, 2024 8:40 AM I77800 JUN 13, 2024 8:40 AM I78C00 JUN 13, 2024 8:40 AM I78300 JUN 13, 2024 8:40 AM I78F00 JUN 13, 2024 8:40 AM I78700 JUN 13, 2024 8:40 AM I70200 JUN 13, 2024 8:40 AM LIQUID LABEL DEVICE LABEL 1 UNL 1 STP 2 UNL 1 ANN 3 UNL 2 STP 4 UNL 2 ANN 5 PREM STP 6 PREM ANN 7 DSL STP 8 DSL ANN 9 DISP 1-2 10 DISP 3-4 11 DISP 5-6 12 DISP 7-8 13 E TRANS SUMP 14 W TRANS SUMP 15 16 I70300 JUN 13, 2024 8:40 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL 1 STP TRI-STATE (SINGLE FLOAT) 2 UNL 1 ANN TRI-STATE (SINGLE FLOAT) 3 UNL 2 STP TRI-STATE (SINGLE FLOAT) 4 UNL 2 ANN TRI-STATE (SINGLE FLOAT) 5 PREM STP TRI-STATE (SINGLE FLOAT) 6 PREM ANN TRI-STATE (SINGLE FLOAT) 7 DSL STP TRI-STATE (SINGLE FLOAT) 8 DSL ANN TRI-STATE (SINGLE FLOAT) 9 DISP 1-2 TRI-STATE (SINGLE FLOAT) 10 DISP 3-4 TRI-STATE (SINGLE FLOAT) 11 DISP 5-6 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT) 13 E TRANS SUMP TRI-STATE (SINGLE FLOAT) 14 W TRANS SUMP TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JUN 13, 2024 8:40 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL 1 STP STP SUMP 2 UNL 1 ANN ANNULAR SPACE 3 UNL 2 STP STP SUMP 4 UNL 2 ANN ANNULAR SPACE 5 PREM STP STP SUMP 6 PREM ANN ANNULAR SPACE 7 DSL STP STP SUMP 8 DSL ANN ANNULAR SPACE 9 DISP 1-2 DISPENSER PAN 10 DISP 3-4 DISPENSER PAN 11 DISP 5-6 DISPENSER PAN 12 DISP 7-8 DISPENSER PAN 13 E TRANS SUMP PIPING SUMP 14 W TRANS SUMP PIPING SUMP 15 OTHER SENSORS 16 OTHER SENSORS I74200 JUN 13, 2024 8:40 AM I74300 JUN 13, 2024 8:40 AM I74400 JUN 13, 2024 8:40 AM I74700 JUN 13, 2024 8:40 AM I74800 JUN 13, 2024 8:40 AM I74900 JUN 13, 2024 8:40 AM I7BC00 JUN 13, 2024 8:40 AM I80200 JUN 13, 2024 8:40 AM I80300 JUN 13, 2024 8:40 AM I80400 JUN 13, 2024 8:40 AM I80700 JUN 13, 2024 8:40 AM RELAY LABEL DEVICE LABEL 1 UNL 1 2 UNLD 2 3 PREM 4 DIESEL 5 OVERFILL ALARMS 6 7 8 I80900 JUN 13, 2024 8:40 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL 1 NORMALLY OPEN 2 UNLD 2 NORMALLY OPEN 3 PREM NORMALLY OPEN 4 DIESEL NORMALLY CLOSED 5 OVERFILL ALARMS NORMALLY OPEN 6 NORMALLY OPEN 7 NORMALLY OPEN 8 NORMALLY OPEN I80B00 JUN 13, 2024 8:40 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNL 1 1 2 UNLD 2 2 3 PREM 3 4 DIESEL 4 5 OVERFILL ALARMS NONE 6 NONE 7 NONE 8 NONE I80A00 JUN 13, 2024 8:40 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNL 1 PUMP CONTROL OUTPUT 2 UNLD 2 PUMP CONTROL OUTPUT 3 PREM PUMP CONTROL OUTPUT 4 DIESEL STANDARD 5 OVERFILL ALARMS STANDARD 6 STANDARD 7 STANDARD 8 STANDARD I80C00 JUN 13, 2024 8:40 AM I80800 JUN 13, 2024 8:40 AM RELAY SETUP REPORT R 1:UNL 1 TYPE: PUMP CONTROL OUTPUT TANK #: 1 IN-TANK ALARMS T 1:HIGH WATER ALARM T 1:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 3:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 3:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL R 2:UNLD 2 TYPE: PUMP CONTROL OUTPUT TANK #: 2 IN-TANK ALARMS T 2:HIGH WATER ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 3:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 3:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL R 3:PREM TYPE: PUMP CONTROL OUTPUT TANK #: 3 IN-TANK ALARMS T 3:HIGH WATER ALARM T 3:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 5:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL R 4:DIESEL TYPE: STANDARD NORMALLY CLOSED TANK #: 4 IN-TANK ALARMS T 3:HIGH WATER ALARM T 3:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 7:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 7:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L 7:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM R 5:OVERFILL ALARMS TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM R 6: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 7: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 8: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 JUN 13, 2024 8:41 AM EDIM:1 VR:349634-003-E TD:09.05.18.15.18 I79100 JUN 13, 2024 8:41 AM I72300 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VP 1-2 VAPOR PRESSURE 02 FM 1-2 AIR FLOW METER 03 FM 3-4 AIR FLOW METER 04 FM 5-6 AIR FLOW METER 05 FM 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 VAPOR PROCESSOR TYPE NONE IV4700 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 ASSESSMENT TIME START TIME: 10:09 AM TIME DELAY MINUTES: 1 IV5200 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 ACCEPT HIGH ORVR: YES IV4A00 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 03 BLEND3 02 02 02 01 03 BLEND3 03 03 03 02 03 BLEND3 04 04 04 02 03 BLEND3 05 05 05 03 03 BLEND3 06 06 06 03 03 BLEND3 07 07 07 04 03 BLEND3 08 08 08 04 03 BLEND3 IV4B00 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 03/01 09/01 xx/xx 02 01 02/02 03/02 09/02 xx/xx 03 02 02/03 03/03 09/03 xx/xx 04 02 02/04 03/04 09/04 xx/xx 05 03 02/05 03/05 09/05 xx/xx 06 03 02/06 03/06 09/06 xx/xx 07 04 02/07 03/07 09/07 xx/xx 08 04 02/08 03/08 09/08 xx/xx IV4900 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JUN 13, 2024 8:41 AM ISD VERSION: 01.07 FASTRIP #3346 ALARM HISTORY BEFORE: Responses Received: I10200 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 503758 503652 2 4 PROBE / G.T. 161433 161328 3 INTERSTITIAL BD 201851 201708 4 INTERSTITIAL BD 200531 200405 5 UNUSED 4915838 4792406 6 UNUSED 4916524 4788919 7 UNUSED 4915594 4789643 8 UNUSED 4912981 4792270 9 STP SENSE BOARD 33065 33089 10 RELAY BOARD 15044 15044 11 RELAY BOARD 15089 15113 12 UNUSED 4917790 4790733 13 UNUSED 4914114 4791344 14 UNUSED 4913406 4795012 15 UNUSED 4914490 4790371 16 UNUSED 4912874 4792635 COMM 1 ELEC DISP INT. 101268 100592 COMM 2 RS232 SERIAL BD 15066 15067 COMM 3 RS232 SERIAL BD 14910 14953 COMM 4 UNUSED 4917081 4793043 COMM 5 UNUSED 4912298 4789261 COMM 6 UNUSED 4913937 4791933 I90200 JUN 13, 2024 8:41 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 3 STP SUMP UNL 2 STP FUEL ALARM CLEAR 6-06-24 11:13AM L 3 STP SUMP UNL 2 STP FUEL ALARM ALARM 6-06-24 11:13AM L 6 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L 8 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L 5 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L14 PIPE W TRANS SUMP SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L13 PIPE E TRANS SUMP SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 6-06-24 9:51AM L 8 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 6-06-24 9:50AM L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 6-06-24 9:50AM L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 6-06-24 9:49AM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM ALARM 6-06-24 9:49AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 6-06-24 9:49AM L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 6-06-24 9:49AM L 6 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 6-06-24 9:49AM L14 PIPE W TRANS SUMP SENSOR OUT ALARM ALARM 6-06-24 9:49AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 6-06-24 9:49AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 6-06-24 9:49AM L 5 STP SUMP PREM STP SENSOR OUT ALARM ALARM 6-06-24 9:49AM L13 PIPE E TRANS SUMP SENSOR OUT ALARM ALARM 6-06-24 9:49AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 6-06-24 9:49AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 6-06-24 9:49AM L14 PIPE W TRANS SUMP FUEL ALARM CLEAR 6-06-24 9:35AM L14 PIPE W TRANS SUMP FUEL ALARM ALARM 6-06-24 9:35AM L14 PIPE W TRANS SUMP FUEL ALARM CLEAR 6-06-24 9:34AM L14 PIPE W TRANS SUMP FUEL ALARM ALARM 6-06-24 9:34AM L13 PIPE E TRANS SUMP FUEL ALARM CLEAR 6-06-24 9:33AM L13 PIPE E TRANS SUMP FUEL ALARM ALARM 6-06-24 9:32AM L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 6-06-24 9:31AM L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 6-06-24 9:30AM L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 6-06-24 9:30AM L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 6-06-24 9:30AM L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 6-06-24 9:29AM L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 6-06-24 9:29AM L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 6-06-24 9:29AM L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 6-06-24 9:28AM L 8 ANNULAR DSL ANN FUEL ALARM CLEAR 6-06-24 9:27AM L 8 ANNULAR DSL ANN FUEL ALARM ALARM 6-06-24 9:26AM L 6 ANNULAR PREM ANN FUEL ALARM CLEAR 6-06-24 9:18AM L 6 ANNULAR PREM ANN FUEL ALARM ALARM 6-06-24 9:17AM L 4 ANNULAR UNL 2 ANN FUEL ALARM CLEAR 6-06-24 9:17AM L 4 ANNULAR UNL 2 ANN FUEL ALARM ALARM 6-06-24 9:17AM I11200 JUN 13, 2024 8:41 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 6-12-24 8:58AM SYSTEM PRINTER ERROR ALARM 6-12-24 8:57AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 6-11-24 10:09AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 6-09-24 10:11AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 6-02-24 10:09AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 5-31-24 10:11AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 5-27-24 10:09AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 5-24-24 10:12AM OTHER ISD VAPOR LEAK WARN CLEAR 5-08-24 10:11AM OTHER ISD VAPOR LEAK WARN ALARM 5-06-24 10:11AM SYSTEM PRINTER ERROR CLEAR 4-21-24 2:06PM SYSTEM PAPER OUT CLEAR 4-21-24 2:06PM SYSTEM PRINTER ERROR ALARM 4-21-24 2:06PM SYSTEM PAPER OUT ALARM 4-21-24 2:06PM SYSTEM PRINTER ERROR CLEAR 4-21-24 2:06PM SYSTEM PRINTER ERROR ALARM 4-21-24 2:06PM SYSTEM PAPER OUT CLEAR 4-21-24 2:06PM SYSTEM PRINTER ERROR CLEAR 4-21-24 2:05PM SYSTEM PAPER OUT ALARM 4-21-24 2:05PM SYSTEM PRINTER ERROR ALARM 4-21-24 2:05PM SYSTEM PAPER OUT CLEAR 4-21-24 2:05PM SYSTEM PRINTER ERROR CLEAR 4-21-24 2:04PM SYSTEM PRINTER ERROR ALARM 4-21-24 2:04PM SYSTEM PAPER OUT ALARM 4-21-24 2:03PM SYSTEM PRINTER ERROR CLEAR 4-21-24 6:58AM SYSTEM PAPER OUT CLEAR 4-21-24 6:58AM SYSTEM PAPER OUT ALARM 4-21-24 6:58AM SYSTEM PRINTER ERROR ALARM 4-21-24 6:58AM SYSTEM PRINTER ERROR CLEAR 4-21-24 6:02AM SYSTEM PRINTER ERROR ALARM 4-21-24 6:02AM SYSTEM PAPER OUT CLEAR 4-21-24 6:02AM SYSTEM PRINTER ERROR CLEAR 4-21-24 6:02AM SYSTEM PRINTER ERROR ALARM 4-21-24 6:02AM SYSTEM PAPER OUT ALARM 4-21-24 6:00AM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 3-12-24 2:43PM T 2 TANK UNLEADEDED 2 DELIVERY NEEDED CLEAR 3-12-24 2:42PM T 2 TANK UNLEADEDED 2 DELIVERY NEEDED ALARM 3-12-24 2:24PM T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 3-12-24 2:07PM OTHER ISD GROSS PRES WARN CLEAR 3-11-24 7:05AM OTHER ISD GROSS PRES WARN ALARM 3-10-24 10:10AM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 3-05-24 2:15PM T 2 TANK UNLEADEDED 2 DELIVERY NEEDED CLEAR 3-05-24 2:13PM T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 3-05-24 1:16PM T 2 TANK UNLEADEDED 2 DELIVERY NEEDED ALARM 3-05-24 1:01PM OTHER ISD GROSS PRES WARN CLEAR 3-04-24 9:24AM OTHER ISD GROSS PRES WARN ALARM 3-01-24 10:10AM OTHER ISD GROSS PRES WARN CLEAR 2-23-24 10:14AM OTHER ISD GROSS PRES WARN ALARM 2-23-24 10:10AM OTHER ISD GROSS PRES WARN CLEAR 2-16-24 10:30AM OTHER ISD GROSS PRES WARN ALARM 2-16-24 10:10AM I20600 JUN 13, 2024 8:42 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 TANK ALARM HISTORY TANK 1 UNLEADED 1 OVERFILL ALARM NOV 12, 2023 11:09 AM SEP 3, 2023 4:15 PM AUG 21, 2023 5:39 AM HIGH PRODUCT ALARM JUN 25, 2023 9:41 AM JUN 21, 2023 5:57 PM MAY 16, 2022 6:30 AM INVALID FUEL LEVEL AUG 1, 2023 10:23 PM PROBE OUT SEP 10, 2022 12:38 PM DELIVERY NEEDED MAR 12, 2024 2:07 PM MAR 5, 2024 1:16 PM FEB 1, 2024 1:12 PM MAX PRODUCT ALARM JUN 26, 2023 9:07 AM TANK 2 UNLEADEDED 2 OVERFILL ALARM MAY 11, 2024 1:29 PM MAY 11, 2024 1:21 PM APR 17, 2024 12:54 PM LOW PRODUCT ALARM JUN 26, 2023 9:09 AM JUN 23, 2023 1:49 PM JUN 23, 2023 12:09 PM INVALID FUEL LEVEL AUG 1, 2023 11:51 PM JUN 26, 2023 8:59 AM JUN 24, 2023 11:38 PM PROBE OUT SEP 10, 2022 12:39 PM DELIVERY NEEDED MAR 12, 2024 2:24 PM MAR 5, 2024 1:01 PM FEB 1, 2024 1:06 PM TANK 3 PREMIUM DELIVERY NEEDED DEC 28, 2022 5:42 PM DEC 18, 2022 7:19 PM NOV 30, 2022 5:51 AM TANK 4 DIESEL LOW PRODUCT ALARM DEC 5, 2022 5:33 PM INVALID FUEL LEVEL DEC 5, 2022 3:41 PM DELIVERY NEEDED DEC 20, 2023 12:29 PM MAY 9, 2023 5:43 PM JAN 11, 2023 6:44 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUN 13, 2024 8:42 AM I30200 JUN 13, 2024 8:42 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL 1 STP JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:15 AM FUEL ALARM JUN 26, 2023 10:41 AM SENSOR OUT ALARM 2 UNL 1 ANN JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:16 AM FUEL ALARM JUN 26, 2023 12:12 PM FUEL ALARM 3 UNL 2 STP JUN 6, 2024 11:13 AM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:14 AM FUEL ALARM 4 UNL 2 ANN JUN 6, 2024 9:50 AM SENSOR OUT ALARM JUN 6, 2024 9:17 AM FUEL ALARM JUN 26, 2023 12:13 PM FUEL ALARM 5 PREM STP JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:14 AM FUEL ALARM JUN 26, 2023 10:41 AM SENSOR OUT ALARM 6 PREM ANN JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:17 AM FUEL ALARM MAY 21, 2024 9:15 PM SENSOR OUT ALARM 7 DSL STP JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:13 AM FUEL ALARM APR 13, 2024 5:26 PM FUEL ALARM 8 DSL ANN JUN 6, 2024 9:50 AM SENSOR OUT ALARM JUN 6, 2024 9:26 AM FUEL ALARM JUN 26, 2023 12:14 PM FUEL ALARM 9 DISP 1-2 JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:28 AM FUEL ALARM JUN 26, 2023 10:41 AM SENSOR OUT ALARM 10 DISP 3-4 JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:29 AM FUEL ALARM JUN 26, 2023 10:41 AM SENSOR OUT ALARM 11 DISP 5-6 JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:30 AM FUEL ALARM JUN 26, 2023 10:41 AM SENSOR OUT ALARM 12 DISP 7-8 JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:30 AM FUEL ALARM JUN 26, 2023 10:41 AM SENSOR OUT ALARM 13 E TRANS SUMP JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:32 AM FUEL ALARM DEC 9, 2023 7:16 PM FUEL ALARM 14 W TRANS SUMP JUN 6, 2024 9:49 AM SENSOR OUT ALARM JUN 6, 2024 9:35 AM FUEL ALARM JUN 6, 2024 9:34 AM FUEL ALARM I31600 JUN 13, 2024 8:42 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP 1-2 2 FM 1-2 3 FM 3-4 JAN 28, 2022 12:38 PM COMMUNICATION ALARM 4 FM 5-6 JAN 28, 2022 12:38 PM COMMUNICATION ALARM 5 FM 7-8 JAN 28, 2022 12:38 PM COMMUNICATION ALARM I40200 JUN 13, 2024 8:42 AM I40300 JUN 13, 2024 8:42 AM I34200 JUN 13, 2024 8:42 AM I34700 JUN 13, 2024 8:42 AM IV0100 JUN 13, 2024 8:42 AM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-06-10 10:12:08 A/L RATIO DEGRADATION FP 8 BLEND3 0.79 24-06-09 10:11:44 A/L RATIO DEGRADATION FP 8 BLEND3 0.79 24-06-01 10:11:14 A/L RATIO DEGRADATION FP 2 BLEND3 0.80 24-05-31 10:11:26 A/L RATIO DEGRADATION FP 2 BLEND3 0.81 24-05-26 10:12:09 A/L RATIO DEGRADATION FP 8 BLEND3 0.79 24-05-25 10:11:53 A/L RATIO DEGRADATION FP 8 BLEND3 0.79 24-05-24 10:12:03 A/L RATIO DEGRADATION FP 8 BLEND3 0.80 24-05-07 10:11:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.00 24-05-06 10:11:51 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.74 24-03-10 10:10:39 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.03 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-09-06 10:10:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 23-09-06 10:10:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 23-01-18 10:10:09 SENSOR OUT SELFTEST E 1 23-01-17 10:10:09 SENSOR OUT SELFTEST E 1 23-01-16 10:10:09 SENSOR OUT SELFTEST E 1 23-01-15 10:10:09 SENSOR OUT SELFTEST E 1 23-01-14 10:10:09 SENSOR OUT SELFTEST E 1 23-01-13 10:10:09 SENSOR OUT SELFTEST E 1 23-01-12 10:10:09 SENSOR OUT SELFTEST E 1 23-01-11 10:10:09 SENSOR OUT SELFTEST E 1 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-06-06 10:11:12 READINESS ISD:PP EVR:PP ISD & EVR READY 24-06-06 09:54:28 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-06-06 09:54:28 ISD STARTUP 24-06-06 09:54:20 ISD SHUTDOWN 24-06-02 10:11:41 READINESS ISD:PP EVR:PP ISD & EVR READY 24-06-01 10:11:14 READINESS ISD:PP EVR:NP EVR READINESS PENDING 24-05-31 10:11:26 READINESS ISD:PP EVR:NP EVR READINESS PENDING 24-05-30 21:48:34 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-05-30 21:48:34 ISD STARTUP 24-05-30 21:48:09 ISD SHUTDOWN AFTER: Responses Received: I10200 JUN 13, 2024 3:23 PM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 503758 504258 2 4 PROBE / G.T. 161433 161492 3 INTERSTITIAL BD 201851 201938 4 INTERSTITIAL BD 200531 200612 5 UNUSED 4915838 4811987 6 UNUSED 4916524 4807396 7 UNUSED 4915594 4810381 8 UNUSED 4912981 4809929 9 STP SENSE BOARD 33065 33096 10 RELAY BOARD 15044 15052 11 RELAY BOARD 15089 15075 12 UNUSED 4917790 4809910 13 UNUSED 4914114 4806948 14 UNUSED 4913406 4808757 15 UNUSED 4914490 4810860 16 UNUSED 4912874 4811109 COMM 1 ELEC DISP INT. 101268 100603 COMM 2 RS232 SERIAL BD 15066 15052 COMM 3 RS232 SERIAL BD 14910 14916 COMM 4 UNUSED 4917081 4812828 COMM 5 UNUSED 4912298 4806744 COMM 6 UNUSED 4913937 4808440 I90200 JUN 13, 2024 3:23 PM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUN 13, 2024 3:23 PM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 8 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L 6 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L14 PIPE W TRANS SUMP SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L 5 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L13 PIPE E TRANS SUMP SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 6-13-24 1:58PM L 8 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 6-13-24 1:56PM L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 6-13-24 1:56PM L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 6-13-24 1:56PM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM ALARM 6-13-24 1:56PM L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 6-13-24 1:56PM L14 PIPE W TRANS SUMP SENSOR OUT ALARM ALARM 6-13-24 1:56PM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 6-13-24 1:56PM L13 PIPE E TRANS SUMP SENSOR OUT ALARM ALARM 6-13-24 1:56PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 6-13-24 1:56PM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 6-13-24 1:56PM L 6 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 6-13-24 1:56PM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 6-13-24 1:56PM L 5 STP SUMP PREM STP SENSOR OUT ALARM ALARM 6-13-24 1:56PM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 6-13-24 1:56PM L14 PIPE W TRANS SUMP FUEL ALARM CLEAR 6-13-24 1:47PM L14 PIPE W TRANS SUMP FUEL ALARM ALARM 6-13-24 1:46PM L13 PIPE E TRANS SUMP FUEL ALARM CLEAR 6-13-24 1:46PM L13 PIPE E TRANS SUMP FUEL ALARM ALARM 6-13-24 1:45PM L13 PIPE E TRANS SUMP FUEL ALARM CLEAR 6-13-24 1:45PM L13 PIPE E TRANS SUMP FUEL ALARM ALARM 6-13-24 1:45PM L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 6-13-24 1:43PM L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 6-13-24 1:43PM L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 6-13-24 1:41PM L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 6-13-24 1:41PM L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 6-13-24 1:40PM L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 6-13-24 1:39PM L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 6-13-24 1:38PM L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 6-13-24 1:37PM L 1 STP SUMP UNL 1 STP FUEL ALARM CLEAR 6-13-24 1:33PM L 1 STP SUMP UNL 1 STP FUEL ALARM ALARM 6-13-24 1:33PM L 3 STP SUMP UNL 2 STP FUEL ALARM CLEAR 6-13-24 1:32PM L 3 STP SUMP UNL 2 STP FUEL ALARM ALARM 6-13-24 1:32PM L 5 STP SUMP PREM STP FUEL ALARM CLEAR 6-13-24 1:32PM L 5 STP SUMP PREM STP FUEL ALARM ALARM 6-13-24 1:32PM L 7 STP SUMP DSL STP FUEL ALARM CLEAR 6-13-24 1:31PM L 7 STP SUMP DSL STP FUEL ALARM ALARM 6-13-24 1:31PM I11200 JUN 13, 2024 3:23 PM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 6-12-24 8:58AM SYSTEM PRINTER ERROR ALARM 6-12-24 8:57AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 6-11-24 10:09AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 6-09-24 10:11AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 6-02-24 10:09AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 5-31-24 10:11AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 5-27-24 10:09AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 5-24-24 10:12AM OTHER ISD VAPOR LEAK WARN CLEAR 5-08-24 10:11AM OTHER ISD VAPOR LEAK WARN ALARM 5-06-24 10:11AM SYSTEM PRINTER ERROR CLEAR 4-21-24 2:06PM SYSTEM PAPER OUT CLEAR 4-21-24 2:06PM SYSTEM PRINTER ERROR ALARM 4-21-24 2:06PM SYSTEM PAPER OUT ALARM 4-21-24 2:06PM SYSTEM PRINTER ERROR CLEAR 4-21-24 2:06PM SYSTEM PRINTER ERROR ALARM 4-21-24 2:06PM SYSTEM PAPER OUT CLEAR 4-21-24 2:06PM SYSTEM PRINTER ERROR CLEAR 4-21-24 2:05PM SYSTEM PAPER OUT ALARM 4-21-24 2:05PM SYSTEM PRINTER ERROR ALARM 4-21-24 2:05PM SYSTEM PAPER OUT CLEAR 4-21-24 2:05PM SYSTEM PRINTER ERROR CLEAR 4-21-24 2:04PM SYSTEM PRINTER ERROR ALARM 4-21-24 2:04PM SYSTEM PAPER OUT ALARM 4-21-24 2:03PM SYSTEM PRINTER ERROR CLEAR 4-21-24 6:58AM SYSTEM PAPER OUT CLEAR 4-21-24 6:58AM SYSTEM PAPER OUT ALARM 4-21-24 6:58AM SYSTEM PRINTER ERROR ALARM 4-21-24 6:58AM SYSTEM PRINTER ERROR CLEAR 4-21-24 6:02AM SYSTEM PRINTER ERROR ALARM 4-21-24 6:02AM SYSTEM PAPER OUT CLEAR 4-21-24 6:02AM SYSTEM PRINTER ERROR CLEAR 4-21-24 6:02AM SYSTEM PRINTER ERROR ALARM 4-21-24 6:02AM SYSTEM PAPER OUT ALARM 4-21-24 6:00AM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 3-12-24 2:43PM T 2 TANK UNLEADEDED 2 DELIVERY NEEDED CLEAR 3-12-24 2:42PM T 2 TANK UNLEADEDED 2 DELIVERY NEEDED ALARM 3-12-24 2:24PM T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 3-12-24 2:07PM OTHER ISD GROSS PRES WARN CLEAR 3-11-24 7:05AM OTHER ISD GROSS PRES WARN ALARM 3-10-24 10:10AM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 3-05-24 2:15PM T 2 TANK UNLEADEDED 2 DELIVERY NEEDED CLEAR 3-05-24 2:13PM T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 3-05-24 1:16PM T 2 TANK UNLEADEDED 2 DELIVERY NEEDED ALARM 3-05-24 1:01PM OTHER ISD GROSS PRES WARN CLEAR 3-04-24 9:24AM OTHER ISD GROSS PRES WARN ALARM 3-01-24 10:10AM OTHER ISD GROSS PRES WARN CLEAR 2-23-24 10:14AM OTHER ISD GROSS PRES WARN ALARM 2-23-24 10:10AM OTHER ISD GROSS PRES WARN CLEAR 2-16-24 10:30AM OTHER ISD GROSS PRES WARN ALARM 2-16-24 10:10AM I20600 JUN 13, 2024 3:23 PM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 TANK ALARM HISTORY TANK 1 UNLEADED 1 OVERFILL ALARM NOV 12, 2023 11:09 AM SEP 3, 2023 4:15 PM AUG 21, 2023 5:39 AM HIGH PRODUCT ALARM JUN 25, 2023 9:41 AM JUN 21, 2023 5:57 PM MAY 16, 2022 6:30 AM INVALID FUEL LEVEL AUG 1, 2023 10:23 PM PROBE OUT SEP 10, 2022 12:38 PM DELIVERY NEEDED MAR 12, 2024 2:07 PM MAR 5, 2024 1:16 PM FEB 1, 2024 1:12 PM MAX PRODUCT ALARM JUN 26, 2023 9:07 AM TANK 2 UNLEADEDED 2 OVERFILL ALARM MAY 11, 2024 1:29 PM MAY 11, 2024 1:21 PM APR 17, 2024 12:54 PM LOW PRODUCT ALARM JUN 26, 2023 9:09 AM JUN 23, 2023 1:49 PM JUN 23, 2023 12:09 PM INVALID FUEL LEVEL AUG 1, 2023 11:51 PM JUN 26, 2023 8:59 AM JUN 24, 2023 11:38 PM PROBE OUT SEP 10, 2022 12:39 PM DELIVERY NEEDED MAR 12, 2024 2:24 PM MAR 5, 2024 1:01 PM FEB 1, 2024 1:06 PM TANK 3 PREMIUM DELIVERY NEEDED DEC 28, 2022 5:42 PM DEC 18, 2022 7:19 PM NOV 30, 2022 5:51 AM TANK 4 DIESEL LOW PRODUCT ALARM DEC 5, 2022 5:33 PM INVALID FUEL LEVEL DEC 5, 2022 3:41 PM DELIVERY NEEDED DEC 20, 2023 12:29 PM MAY 9, 2023 5:43 PM JAN 11, 2023 6:44 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUN 13, 2024 3:23 PM I30200 JUN 13, 2024 3:23 PM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL 1 STP JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:33 PM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM 2 UNL 1 ANN JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:16 PM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM 3 UNL 2 STP JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:32 PM FUEL ALARM JUN 13, 2024 8:57 AM FUEL ALARM 4 UNL 2 ANN JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:18 PM FUEL ALARM JUN 6, 2024 9:50 AM SENSOR OUT ALARM 5 PREM STP JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:32 PM FUEL ALARM JUN 13, 2024 1:27 PM FUEL ALARM 6 PREM ANN JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:19 PM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM 7 DSL STP JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:31 PM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM 8 DSL ANN JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:23 PM FUEL ALARM JUN 6, 2024 9:50 AM SENSOR OUT ALARM 9 DISP 1-2 JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:37 PM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM 10 DISP 3-4 JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:43 PM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM 11 DISP 5-6 JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:39 PM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM 12 DISP 7-8 JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:41 PM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM 13 E TRANS SUMP JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:45 PM FUEL ALARM JUN 13, 2024 1:45 PM FUEL ALARM 14 W TRANS SUMP JUN 13, 2024 1:56 PM SENSOR OUT ALARM JUN 13, 2024 1:46 PM FUEL ALARM JUN 6, 2024 9:49 AM SENSOR OUT ALARM I31600 JUN 13, 2024 3:23 PM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP 1-2 2 FM 1-2 3 FM 3-4 JAN 28, 2022 12:38 PM COMMUNICATION ALARM 4 FM 5-6 JAN 28, 2022 12:38 PM COMMUNICATION ALARM 5 FM 7-8 JAN 28, 2022 12:38 PM COMMUNICATION ALARM I40200 JUN 13, 2024 3:23 PM I40300 JUN 13, 2024 3:23 PM I34200 JUN 13, 2024 3:23 PM I34700 JUN 13, 2024 3:23 PM IV0100 JUN 13, 2024 3:23 PM FASTRIP 346 805 34TH BAKERSFIELD CA 661-325-0110 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-06-10 10:12:08 A/L RATIO DEGRADATION FP 8 BLEND3 0.79 24-06-09 10:11:44 A/L RATIO DEGRADATION FP 8 BLEND3 0.79 24-06-01 10:11:14 A/L RATIO DEGRADATION FP 2 BLEND3 0.80 24-05-31 10:11:26 A/L RATIO DEGRADATION FP 2 BLEND3 0.81 24-05-26 10:12:09 A/L RATIO DEGRADATION FP 8 BLEND3 0.79 24-05-25 10:11:53 A/L RATIO DEGRADATION FP 8 BLEND3 0.79 24-05-24 10:12:03 A/L RATIO DEGRADATION FP 8 BLEND3 0.80 24-05-07 10:11:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.00 24-05-06 10:11:51 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.74 24-03-10 10:10:39 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.03 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-09-06 10:10:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 23-09-06 10:10:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 23-01-18 10:10:09 SENSOR OUT SELFTEST E 1 23-01-17 10:10:09 SENSOR OUT SELFTEST E 1 23-01-16 10:10:09 SENSOR OUT SELFTEST E 1 23-01-15 10:10:09 SENSOR OUT SELFTEST E 1 23-01-14 10:10:09 SENSOR OUT SELFTEST E 1 23-01-13 10:10:09 SENSOR OUT SELFTEST E 1 23-01-12 10:10:09 SENSOR OUT SELFTEST E 1 23-01-11 10:10:09 SENSOR OUT SELFTEST E 1 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-06-13 14:02:08 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-06-13 14:02:08 ISD STARTUP 24-06-13 14:01:26 ISD SHUTDOWN 24-06-06 10:11:12 READINESS ISD:PP EVR:PP ISD & EVR READY 24-06-06 09:54:28 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-06-06 09:54:28 ISD STARTUP 24-06-06 09:54:20 ISD SHUTDOWN 24-06-02 10:11:41 READINESS ISD:PP EVR:PP ISD & EVR READY 24-06-01 10:11:14 READINESS ISD:PP EVR:NP EVR READINESS PENDING 24-05-31 10:11:26 READINESS ISD:PP EVR:NP EVR READINESS PENDING