HomeMy WebLinkAboutFMC 2024Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10120951 06/19/2024
Mesa Marin Chevron
11101 Highway 178 Bakersfield 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
VeederRoot TLS-3XX Technician - C32655 10/11/2024
Vaporless Manufacturing Inc. - #5265 10/24/2024
OPW - 1193585 04/14/2025
06/19/2024 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS-350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208/304 Dispenser 1-2 UDC
L2 208/304 Dispenser 3-4 UDC
L3 208/304 Dispenser 5-6 UDC
L4 208/304 Dispenser 7-8 UDC
L5 208/304 Dispenser 9-10 UDC
L6 208/304 Dispenser 11-12 UDC
L7 208/304 87 Unleaded STP
L8 208/304 87 Unleaded Fill
L9 208/304 91 Supreme STP
L10 208/304 91 Supreme Fill
L11 208/304 Diesel STP
L12 208/304 Diesel Fill
L13 208/304 Vent Box
S9 463/464 / 420 Unleaded Tank
S10 463/464 Unleaded Product
S11 463/464 Vapor Return
S12 463/464 / 420 Supreme Tank
S13 463/464 Supreme Product
S14 463/464 Unleaded-Supreme Vent
S15 463/464 / 420 Diesel Tank
S16 463/464 Diesel Product
S17 463/464 Diesel Vent
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 Unleaded
T2 FX1V 91 Supreme
T3 FX1DV Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
All liquid sensors utilize a VR 2 to 1 Sensor Input Box connecting 208 and 304 sensors together.
Audible visual alarms include Fuel Alarm & High Liquid Alarm
All Tank Annular sensors are 420 sensors monitored under vacuum via 463/464 sensor.
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
06/19/2024
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Mesa Marin Chevron11101 Highway 178Bakersfield10120951Disp 3-4Disp 7-8 Disp 11-12MPDMPDMPDMPDMPDMPDDisp 1-2Disp 5-6Disp 9-10ProductProductProductProductProductProductBrandon Nunez
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10120951 06/19/2024
Mesa Marin Chevron
11101 Highway 178 Bakersfield 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
OPW - 1193585 04/14/2025
PEI 1200 1 Hour Hydrostatic All Spill Containers
06/19/2024 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1: 87 UNL
OPW
T2: 91 SUP
OPW
T3: DSL
OPW
Mesa Marin Chevron System Setup & Alarm History
Responses Received:
200
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
JUN 19, 2024 8:47 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 9178 68.27 0.0 84.7 2854
2 SUPREME 5123 42.28 0.0 84.7 6909
3 DIESEL 4319 37.08 0.0 86.5 7756
I90500
JUN 19, 2024 8:47 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JUN 19, 2024 8:47 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUN 19, 2024 8:47 AM
SHIFT TIME 1 : 1:00 AM
I50202
JUN 19, 2024 8:47 AM
SHIFT TIME 2 : DISABLED
I50203
JUN 19, 2024 8:47 AM
SHIFT TIME 3 : DISABLED
I50204
JUN 19, 2024 8:47 AM
SHIFT TIME 4 : DISABLED
I54600
JUN 19, 2024 8:47 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUN 19, 2024 8:47 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUN 19, 2024 8:47 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUN 19, 2024 8:47 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUN 19, 2024 8:47 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUN 19, 2024 8:47 AM
PRINT TC VOLUMES
ENABLED
I50E00
JUN 19, 2024 8:47 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUN 19, 2024 8:47 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUN 19, 2024 8:47 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUN 19, 2024 8:47 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUN 19, 2024 8:47 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUN 19, 2024 8:47 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUN 19, 2024 8:47 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUN 19, 2024 8:47 AM
TANK CHART SECURITY
DISABLED
I5BD00
JUN 19, 2024 8:47 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JUN 19, 2024 8:47 AM
MASS/DENSITY
DISABLED
I88101
JUN 19, 2024 8:47 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JUN 19, 2024 8:47 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
JUN 19, 2024 8:47 AM
PORT SETTINGS:
COMM BOARD : 3 (S-SAT )
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 2 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
DTR NORMAL STATE: HIGH
I88104
JUN 19, 2024 8:47 AM
I88105
JUN 19, 2024 8:47 AM
I88106
JUN 19, 2024 8:47 AM
I52000
JUN 19, 2024 8:47 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 WEEKLY FRI 4:51 PM
2 WEEKLY FRI 4:51 PM
3 WEEKLY FRI 4:51 PM
4 WEEKLY FRI 4:51 PM
5 WEEKLY FRI 4:51 PM
6 WEEKLY FRI 4:51 PM
7 WEEKLY FRI 4:51 PM
8 VEEDER ROOT (FMS) WEEKLY FRI 4:51 PM
I60100
JUN 19, 2024 8:47 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 SUPREME ON
3 DIESEL ON
4 OFF
I60200
JUN 19, 2024 8:47 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 SUPREME
3 DIESEL
4
I60300
JUN 19, 2024 8:47 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 SUPREME 2
3 DIESEL 3
4 4
I60900
JUN 19, 2024 8:47 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 SUPREME 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
JUN 19, 2024 8:47 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 95.75
2 SUPREME 95.75
3 DIESEL 95.75
4 0.00
I60A00
JUN 19, 2024 8:47 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 PT
12032 2 SUPREME 1 PT 12032 3 DIESEL
1 PT 12075 4 1 PT 0
I60400
JUN 19, 2024 8:47 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032
2 SUPREME 12032
3 DIESEL 12075
4 0
I60500
JUN 19, 2024 8:47 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032 0 0 0
2 SUPREME 12032 0 0 0
3 DIESEL 12075 0 0 0
4 0 0 0 0
I60600
JUN 19, 2024 8:47 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 SUPREME 12032 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DIESEL 12075 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUN 19, 2024 8:47 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 SUPREME NO
3 DIESEL NO
4 NO
I62F00
JUN 19, 2024 8:47 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN. PS
2 SUPREME 4.0 IN. PS
3 DIESEL 4.0 IN.
I62700
JUN 19, 2024 8:47 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 SUPREME 2.0
3 DIESEL 2.0
I64200
JUN 19, 2024 8:47 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 SUPREME LOW
3 DIESEL LOW
I62400
JUN 19, 2024 8:47 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 SUPREME 3.0
3 DIESEL 3.0
I62800
JUN 19, 2024 8:47 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032
2 SUPREME 12032
3 DIESEL 12075
4 0
I62300
JUN 19, 2024 8:47 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10829
2 SUPREME 10829
3 DIESEL 10868
4 0
I62200
JUN 19, 2024 8:47 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11430
2 SUPREME 11430
3 DIESEL 11471
4 0
I62900
JUN 19, 2024 8:47 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 SUPREME 120
3 DIESEL 121
4 0
I62100
JUN 19, 2024 8:47 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 500
2 SUPREME 500
3 DIESEL 500
4 0
I62600
JUN 19, 2024 8:47 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 SUPREME 99
3 DIESEL 99
4 99
I62500
JUN 19, 2024 8:47 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 SUPREME 99
3 DIESEL 99
4 99
I60800
JUN 19, 2024 8:47 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 SUPREME 0.00
3 DIESEL 0.00
4 0.00
I60B00
JUN 19, 2024 8:47 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUN 19, 2024 8:47 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 SUPREME 0.00
3 DIESEL 0.00
4 0.00
I61200
JUN 19, 2024 8:47 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 SUPREME NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
JUN 19, 2024 8:47 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 SUPREME 120
3 DIESEL 120
4 0
I62A00
JUN 19, 2024 8:47 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 SUPREME 120
3 DIESEL 120
4 0
I62C00
JUN 19, 2024 8:47 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 SUPREME STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
JUN 19, 2024 8:47 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 SUPREME GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUN 19, 2024 8:47 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 SUPREME OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
JUN 19, 2024 8:47 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 SUPREME OFF
3 DIESEL OFF
4 OFF
I63200
JUN 19, 2024 8:47 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 SUPREME OFF
3 DIESEL OFF
4 OFF
I61000
JUN 19, 2024 8:47 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 SUPREME 1
3 DIESEL 1
4 1
I63A00
JUN 19, 2024 8:47 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 SUPREME 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
JUN 19, 2024 8:47 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JAN 2, 2019
START TIME : 2:00 AM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:ENABLED
I61300
JUN 19, 2024 8:47 AM
CSLD PROBABLITY OF DETECTION
I61400
JUN 19, 2024 8:47 AM
CSLD CLIMATE FACTOR
I61600
JUN 19, 2024 8:47 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 SUPREME IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
JUN 19, 2024 8:47 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED ENABLED
2 SUPREME ENABLED
3 DIESEL ENABLED
4 ENABLED
I61B00
JUN 19, 2024 8:47 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JUN 19, 2024 8:47 AM
CSLD REPORT ONLY
I62B00
JUN 19, 2024 8:47 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 SUPREME ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
JUN 19, 2024 8:47 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUN 19, 2024 8:47 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 SUPREME 0
3 DIESEL 0
4 0
I63500
JUN 19, 2024 8:47 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 SUPREME 1
3 DIESEL 1
4 1
I63900
JUN 19, 2024 8:47 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 SUPREME
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
JUN 19, 2024 8:47 AM
I77700
JUN 19, 2024 8:47 AM
I77800
JUN 19, 2024 8:47 AM
I78C00
JUN 19, 2024 8:47 AM
I78300
JUN 19, 2024 8:47 AM
I78F00
JUN 19, 2024 8:47 AM
I78700
JUN 19, 2024 8:47 AM
I70200
JUN 19, 2024 8:47 AM
LIQUID LABEL
DEVICE LABEL
1 DISP 1-2
2 DISP 3-4
3 DISP 5-6
4 DISP 7-8
5 DISP 9-10
6 DISP 11-12
7 UNL STP
8 UNL FILL
9 SUPREME STP
10 SUPREME FILL
11 DIESEL STP
12 DIESEL FILL
13 VENT BOX
14
15
16
I70300
JUN 19, 2024 8:47 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 DISP 1-2 DW SUMP 2-1
2 DISP 3-4 DW SUMP 2-1
3 DISP 5-6 DW SUMP 2-1
4 DISP 7-8 DW SUMP 2-1
5 DISP 9-10 DW SUMP 2-1
6 DISP 11-12 DW SUMP 2-1
7 UNL STP DW SUMP 2-1
8 UNL FILL DW SUMP 2-1
9 SUPREME STP DW SUMP 2-1
10 SUPREME FILL DW SUMP 2-1
11 DIESEL STP DW SUMP 2-1
12 DIESEL FILL DW SUMP 2-1
13 VENT BOX DW SUMP 2-1
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
JUN 19, 2024 8:47 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 DISP 1-2 DISPENSER PAN
2 DISP 3-4 DISPENSER PAN
3 DISP 5-6 DISPENSER PAN
4 DISP 7-8 DISPENSER PAN
5 DISP 9-10 DISPENSER PAN
6 DISP 11-12 DISPENSER PAN
7 UNL STP STP SUMP
8 UNL FILL OTHER SENSORS
9 SUPREME STP STP SUMP
10 SUPREME FILL OTHER SENSORS
11 DIESEL STP STP SUMP
12 DIESEL FILL OTHER SENSORS
13 VENT BOX OTHER SENSORS
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
JUN 19, 2024 8:47 AM
I74300
JUN 19, 2024 8:47 AM
I74400
JUN 19, 2024 8:47 AM
I74700
JUN 19, 2024 8:47 AM
I74800
JUN 19, 2024 8:47 AM
I74900
JUN 19, 2024 8:47 AM
I7BC00
JUN 19, 2024 8:47 AM
I80200
JUN 19, 2024 8:47 AM
I80300
JUN 19, 2024 8:47 AM
I80400
JUN 19, 2024 8:48 AM
I80700
JUN 19, 2024 8:48 AM
RELAY LABEL
DEVICE LABEL
1 UNL
2 SUPREME
3 DIESEL
4 OVERFILL ALARM
I80900
JUN 19, 2024 8:48 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNL NORMALLY OPEN
2 SUPREME NORMALLY OPEN
3 DIESEL NORMALLY OPEN
4 OVERFILL ALARM NORMALLY OPEN
I80B00
JUN 19, 2024 8:48 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNL 1
2 SUPREME 2
3 DIESEL 3
4 OVERFILL ALARM NONE
I80A00
JUN 19, 2024 8:48 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNL PUMP CONTROL OUTPUT
2 SUPREME PUMP CONTROL OUTPUT
3 DIESEL PUMP CONTROL OUTPUT
4 OVERFILL ALARM STANDARD
I80C00
JUN 19, 2024 8:48 AM
I80800
JUN 19, 2024 8:48 AM
RELAY SETUP REPORT
R 1:UNL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:SUPREME
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DIESEL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 3
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 6:FUEL ALARM
L11:FUEL ALARM
L 2:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L 2:SHORT ALARM
L 6:SHORT ALARM
L11:SHORT ALARM
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
I79000
JUN 19, 2024 8:48 AM
EDIM:1 VR:349867-001-D TD:17.02.14.08.38
I79100
JUN 19, 2024 8:48 AM
I72300
JUN 19, 2024 8:48 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 DISP 1-2 FM AIR FLOW METER
02 DISP 3-4 FM AIR FLOW METER
03 DISP 5-6 FM AIR FLOW METER
04 DISP 7-8 FM AIR FLOW METER
05 DISP 9-10 FM AIR FLOW METER
06 DISP 11-12 FM AIR FLOW METER
07 DISP 5-6 PS VAPOR PRESSURE
08 ATM ATM P SENSOR
09 UNL TANK VAC SENSOR
10 UNL PRODUCT VAC SENSOR
11 VAPOR RETURN VAC SENSOR
12 SUPREME TANK VAC SENSOR
13 SUPREME PRODUCT VAC SENSOR
14 UNL-SUP VENT VAC SENSOR
15 DIESEL TANK VAC SENSOR
16 DIESEL PRODUCT VAC SENSOR
17 DIESEL VENT VAC SENSOR
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JUN 19, 2024 8:48 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
JUN 19, 2024 8:48 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JUN 19, 2024 8:48 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
VAPOR PROCESSOR TYPE
NONE
IV4700
JUN 19, 2024 8:48 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JUN 19, 2024 8:48 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ACCEPT HIGH ORVR: YES
IV4A00
JUN 19, 2024 8:48 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
09 09 09 05 02 BLEND3
10 16 10 05 02 BLEND3
11 17 11 06 02 BLEND3
12 18 12 06 02 BLEND3
IV4B00
JUN 19, 2024 8:48 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 09/01 01/01 xx/xx
02 01 02/02 09/02 01/02 xx/xx
03 02 02/03 09/03 01/03 xx/xx
04 02 02/04 09/04 01/04 xx/xx
05 03 02/05 09/05 01/05 xx/xx
06 03 02/06 09/06 01/06 xx/xx
07 04 02/07 09/07 01/07 xx/xx
08 04 02/08 09/08 01/08 xx/xx
09 05 02/09 09/09 01/09 xx/xx
16 05 02/10 09/10 01/10 xx/xx
17 06 02/11 09/11 01/11 xx/xx
18 06 02/12 09/12 01/12 xx/xx
IV4900
JUN 19, 2024 8:48 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JUN 19, 2024 8:48 AM
ISD VERSION: 01.06
Pre Alarm History
Responses Received:
I10200
JUN 19, 2024 8:49 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164126 164723
2 7SMARTSENSOR BD 505360 506774
3 8SMARTSENSOR BD 39330 39412
4 8SMARTSENSOR BD 39396 39456
5 INTERSTITIAL BD 201541 201891
6 INTERSTITIAL BD 201257 201520
7 UNUSED 4846706 4910091
8 UNUSED 4839908 4894164
9 RELAY BOARD 14963 14978
10 STP SENSE BOARD 33096 33131
11 UNUSED 4852892 4899328
12 UNUSED 4850212 4901485
13 UNUSED 4844743 4897898
14 UNUSED 4843327 4898346
15 UNUSED 4848970 4893222
16 UNUSED 4850147 4890404
COMM 1 ELEC DISP INT. 101203 101515
COMM 2 RS232 SERIAL BD 14897 14935
COMM 3 SERIAL SAT BD 480489 480938
COMM 4 UNUSED 4852979 4895571
COMM 5 UNUSED 4849885 4896275
COMM 6 UNUSED 4842259 4893649
I90200
JUN 19, 2024 8:49 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUN 19, 2024 8:49 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
E 1 OTHER COMMUNICATION ALARM CLEAR 6-17-24 4:23PM
E 1 OTHER COMMUNICATION ALARM ALARM 6-17-24 4:23PM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-17-24 4:23PM
E 1 OTHER COMMUNICATION ALARM ALARM 6-17-24 4:23PM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-17-24 2:04AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-17-24 2:04AM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-10-24 2:04AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-10-24 2:04AM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-07-24 10:42AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-07-24 10:41AM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-07-24 10:32AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-07-24 10:32AM
L 9 STP SUMP SUPREME STP FUEL ALARM CLEAR 6-07-24 7:54AM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-07-24 7:05AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-07-24 7:05AM
L 9 STP SUMP SUPREME STP FUEL ALARM ALARM 6-07-24 2:44AM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-04-24 3:41PM
E 1 OTHER COMMUNICATION ALARM ALARM 6-04-24 3:41PM
E 1 OTHER COMMUNICATION ALARM CLEAR 6-03-24 2:05AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-03-24 2:04AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-27-24 2:05AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-27-24 2:04AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-20-24 9:11AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-20-24 9:10AM
E 1 OTHER COMMUNICATION ALARM CLEAR 5-20-24 8:53AM
E 1 OTHER COMMUNICATION ALARM ALARM 5-20-24 8:52AM
L10 OTHER SUPREME FILL SENSOR OUT ALARM CLEAR 5-20-24 8:17AM
L 9 STP SUMP SUPREME STP LOW LIQUID ALARM CLEAR 5-20-24 8:16AM
L 9 STP SUMP SUPREME STP LOW LIQUID ALARM ALARM 5-20-24 8:16AM
L10 OTHER SUPREME FILL SENSOR OUT ALARM ALARM 5-20-24 8:14AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM CLEAR 5-20-24 8:13AM
L 9 STP SUMP SUPREME STP LOW LIQUID ALARM CLEAR 5-20-24 8:08AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM ALARM 5-20-24 8:06AM
L10 OTHER SUPREME FILL FUEL ALARM CLEAR 5-20-24 8:06AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM CLEAR 5-20-24 8:06AM
L10 OTHER SUPREME FILL FUEL ALARM ALARM 5-20-24 8:06AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM ALARM 5-20-24 8:03AM
L10 OTHER SUPREME FILL FUEL ALARM CLEAR 5-20-24 8:03AM
L10 OTHER SUPREME FILL SENSOR OUT ALARM CLEAR 5-20-24 8:02AM
L10 OTHER SUPREME FILL FUEL ALARM ALARM 5-20-24 8:02AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM CLEAR 5-20-24 8:01AM
L10 OTHER SUPREME FILL SENSOR OUT ALARM ALARM 5-20-24 8:01AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM ALARM 5-20-24 8:01AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM CLEAR 5-20-24 7:59AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM ALARM 5-20-24 7:53AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM CLEAR 5-20-24 7:51AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM ALARM 5-20-24 7:47AM
L10 OTHER SUPREME FILL FUEL ALARM CLEAR 5-20-24 7:47AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM CLEAR 5-20-24 7:46AM
L10 OTHER SUPREME FILL FUEL ALARM ALARM 5-20-24 7:46AM
I11200
JUN 19, 2024 8:49 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h12 OTHER FP12: BLEND3 FLOW COLLECT WARN CLEAR 6-07-24 8:14AM
h12 OTHER FP12: BLEND3 FLOW COLLECT WARN ALARM 6-06-24 10:08AM
SYSTEM PRINTER ERROR CLEAR 5-28-24 8:00AM
SYSTEM PAPER OUT CLEAR 5-28-24 8:00AM
SYSTEM PRINTER ERROR ALARM 5-28-24 8:00AM
SYSTEM PAPER OUT ALARM 5-28-24 8:00AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 5-17-24 2:15PM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 5-17-24 10:06AM
SYSTEM PRINTER ERROR CLEAR 5-08-24 1:03AM
SYSTEM PAPER OUT CLEAR 5-08-24 1:03AM
SYSTEM PAPER OUT ALARM 5-08-24 1:03AM
SYSTEM PRINTER ERROR ALARM 5-08-24 1:03AM
SYSTEM PRINTER ERROR CLEAR 5-08-24 1:02AM
SYSTEM PAPER OUT CLEAR 5-08-24 1:02AM
SYSTEM PRINTER ERROR ALARM 5-08-24 1:02AM
SYSTEM PRINTER ERROR CLEAR 5-08-24 1:02AM
SYSTEM PRINTER ERROR ALARM 5-08-24 1:01AM
SYSTEM PAPER OUT ALARM 5-08-24 1:00AM
SYSTEM PRINTER ERROR CLEAR 4-17-24 11:49PM
SYSTEM PAPER OUT CLEAR 4-17-24 11:49PM
SYSTEM PAPER OUT ALARM 4-17-24 11:49PM
SYSTEM PRINTER ERROR ALARM 4-17-24 11:49PM
SYSTEM PRINTER ERROR CLEAR 4-17-24 11:49PM
SYSTEM PAPER OUT CLEAR 4-17-24 11:49PM
SYSTEM PAPER OUT ALARM 4-17-24 11:49PM
SYSTEM PAPER OUT CLEAR 4-17-24 11:49PM
SYSTEM PRINTER ERROR ALARM 4-17-24 11:48PM
SYSTEM PAPER OUT ALARM 4-17-24 11:48PM
SYSTEM PRINTER ERROR CLEAR 4-11-24 2:27PM
SYSTEM PAPER OUT CLEAR 4-11-24 2:26PM
SYSTEM PRINTER ERROR ALARM 4-11-24 2:26PM
SYSTEM PAPER OUT ALARM 4-11-24 2:22PM
SYSTEM PRINTER ERROR CLEAR 3-23-24 12:24AM
SYSTEM PAPER OUT CLEAR 3-23-24 12:24AM
SYSTEM PAPER OUT ALARM 3-23-24 12:24AM
SYSTEM PRINTER ERROR ALARM 3-23-24 12:24AM
SYSTEM PRINTER ERROR CLEAR 3-03-24 4:27AM
SYSTEM PRINTER ERROR ALARM 3-03-24 4:27AM
SYSTEM PAPER OUT CLEAR 3-03-24 4:27AM
SYSTEM PAPER OUT ALARM 3-03-24 4:27AM
SYSTEM PRINTER ERROR CLEAR 3-03-24 4:27AM
SYSTEM PAPER OUT CLEAR 3-03-24 4:26AM
SYSTEM PAPER OUT ALARM 3-03-24 4:26AM
SYSTEM PAPER OUT CLEAR 3-03-24 4:26AM
SYSTEM PAPER OUT ALARM 3-03-24 4:26AM
SYSTEM PAPER OUT CLEAR 3-03-24 4:26AM
SYSTEM PAPER OUT ALARM 3-03-24 4:26AM
SYSTEM PAPER OUT CLEAR 3-03-24 4:26AM
SYSTEM PAPER OUT ALARM 3-03-24 4:26AM
SYSTEM PAPER OUT CLEAR 3-03-24 4:26AM
I20600
JUN 19, 2024 8:50 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
TANK ALARM HISTORY
TANK 1 UNLEADED
TANK 2 SUPREME
TANK 3 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUN 19, 2024 8:50 AM
I30200
JUN 19, 2024 8:50 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2
JUL 24, 2023 2:03 PM FUEL ALARM
JUL 24, 2023 2:03 PM LOW LIQUID ALARM
FEB 13, 2021 8:05 AM SENSOR OUT ALARM
2 DISP 3-4
JUL 24, 2023 2:05 PM FUEL ALARM
JUL 24, 2023 2:04 PM LOW LIQUID ALARM
FEB 13, 2021 8:05 AM SENSOR OUT ALARM
3 DISP 5-6
JUL 24, 2023 2:05 PM FUEL ALARM
JUL 24, 2023 2:05 PM LOW LIQUID ALARM
4 DISP 7-8
JUL 24, 2023 2:06 PM FUEL ALARM
JUL 24, 2023 2:05 PM LOW LIQUID ALARM
FEB 13, 2021 8:05 AM SENSOR OUT ALARM
5 DISP 9-10
JUL 24, 2023 2:04 PM FUEL ALARM
JUL 24, 2023 2:03 PM LOW LIQUID ALARM
FEB 13, 2021 8:05 AM SENSOR OUT ALARM
6 DISP 11-12
JUL 24, 2023 2:05 PM FUEL ALARM
JUL 24, 2023 2:04 PM LOW LIQUID ALARM
FEB 13, 2021 8:05 AM SENSOR OUT ALARM
7 UNL STP
JUL 24, 2023 1:54 PM FUEL ALARM
JUL 24, 2023 1:52 PM LOW LIQUID ALARM
8 UNL FILL
APR 1, 2024 9:12 AM FUEL ALARM
MAR 11, 2024 5:59 PM FUEL ALARM
JUL 24, 2023 2:17 PM LOW LIQUID ALARM
9 SUPREME STP
JUN 7, 2024 2:44 AM FUEL ALARM
MAY 20, 2024 8:16 AM LOW LIQUID ALARM
MAY 17, 2024 2:11 PM LOW LIQUID ALARM
10 SUPREME FILL
MAY 20, 2024 8:14 AM SENSOR OUT ALARM
MAY 20, 2024 8:06 AM LOW LIQUID ALARM
MAY 20, 2024 8:06 AM FUEL ALARM
11 DIESEL STP
JUL 24, 2023 1:51 PM LOW LIQUID ALARM
JUL 24, 2023 1:51 PM FUEL ALARM
FEB 13, 2021 8:05 AM SENSOR OUT ALARM
12 DIESEL FILL
JUL 24, 2023 2:15 PM FUEL ALARM
JUL 24, 2023 2:12 PM FUEL ALARM
JUL 24, 2023 2:12 PM LOW LIQUID ALARM
13 VENT BOX
NOV 26, 2023 3:37 AM LOW LIQUID ALARM
NOV 25, 2023 6:13 AM LOW LIQUID ALARM
JUL 24, 2023 2:12 PM FUEL ALARM
I31600
JUN 19, 2024 8:50 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2 FM
2 DISP 3-4 FM
3 DISP 5-6 FM
4 DISP 7-8 FM
5 DISP 9-10 FM
6 DISP 11-12 FM
7 DISP 5-6 PS
8 ATM
9 UNL TANK
JUL 24, 2023 1:56 PM NO VACUUM ALARM
10 UNL PRODUCT
JUL 24, 2023 1:56 PM HIGH LIQUID ALARM
JUL 24, 2023 1:56 PM NO VACUUM ALARM
JUL 24, 2023 1:55 PM NO VACUUM ALARM
11 VAPOR RETURN
AUG 11, 2023 7:15 AM HIGH LIQUID ALARM
AUG 11, 2023 5:49 AM HIGH LIQUID ALARM
AUG 11, 2023 5:48 AM HIGH LIQUID ALARM
12 SUPREME TANK
JUL 24, 2023 1:55 PM NO VACUUM ALARM
13 SUPREME PRODUCT
JUL 24, 2023 2:08 PM HIGH LIQUID ALARM
JUL 24, 2023 1:56 PM NO VACUUM ALARM
14 UNL-SUP VENT
JUL 24, 2023 2:08 PM HIGH LIQUID ALARM
JUL 24, 2023 1:56 PM HIGH LIQUID ALARM
JUL 24, 2023 1:56 PM NO VACUUM ALARM
15 DIESEL TANK
SEP 25, 2023 11:50 AM NO VACUUM ALARM
SEP 25, 2023 11:46 AM NO VACUUM ALARM
SEP 25, 2023 11:45 AM NO VACUUM ALARM
16 DIESEL PRODUCT
JUL 24, 2023 1:53 PM HIGH LIQUID ALARM
JUL 24, 2023 1:53 PM NO VACUUM ALARM
17 DIESEL VENT
JUL 24, 2023 1:53 PM HIGH LIQUID ALARM
JUL 24, 2023 1:53 PM NO VACUUM ALARM
I40200
JUN 19, 2024 8:50 AM
I40300
JUN 19, 2024 8:50 AM
I34200
JUN 19, 2024 8:50 AM
I34700
JUN 19, 2024 8:50 AM
IV0100
JUN 19, 2024 8:50 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 97%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-06-06 10:08:04 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 0.59
24-05-17 10:06:44 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.60
24-01-25 10:03:54 SENSOR OUT SELFTEST E 1
23-12-08 10:03:55 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3 0.60
23-11-12 10:03:35 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.28
23-11-11 10:03:26 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.28
23-11-10 10:03:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.28
23-11-09 10:04:12 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.20
23-10-30 10:01:14 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 104.90
23-10-29 10:01:10 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 106.07
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-12-09 10:03:46 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3
23-10-31 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 104.56
22-10-09 10:03:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 43.37
22-10-08 10:03:42 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.44
22-10-07 10:03:44 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.38
22-06-11 10:07:00 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3
22-03-05 10:07:15 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3
21-09-07 10:07:55 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
21-08-18 10:08:51 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
21-07-26 10:05:35 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-06-18 10:06:53 READINESS ISD:PP EVR:PP ISD & EVR READY
24-06-17 16:21:31 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-06-17 16:21:31 ISD STARTUP
24-06-17 15:47:10 ISD SHUTDOWN
24-06-07 10:59:05 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
24-06-07 08:14:35 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED
24-05-17 14:15:48 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED
24-05-12 10:06:01 READINESS ISD:PP EVR:PP ISD & EVR READY
24-05-11 16:28:55 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-05-11 16:28:55 ISD STARTUP
Post Alarm History
Responses Received:
I10200
JUN 19, 2024 2:40 PM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164126 163649
2 7SMARTSENSOR BD 505360 504405
3 8SMARTSENSOR BD 39330 39266
4 8SMARTSENSOR BD 39396 39310
5 INTERSTITIAL BD 201541 201244
6 INTERSTITIAL BD 201257 200818
7 UNUSED 4846706 4817162
8 UNUSED 4839908 4808523
9 RELAY BOARD 14963 14955
10 STP SENSE BOARD 33096 33067
11 UNUSED 4852892 4809305
12 UNUSED 4850212 4812010
13 UNUSED 4844743 4811617
14 UNUSED 4843327 4810047
15 UNUSED 4848970 4803328
16 UNUSED 4850147 4806404
COMM 1 ELEC DISP INT. 101203 101385
COMM 2 RS232 SERIAL BD 14897 14889
COMM 3 SERIAL SAT BD 480489 480315
COMM 4 UNUSED 4852979 4809131
COMM 5 UNUSED 4849885 4810178
COMM 6 UNUSED 4842259 4815348
I90200
JUN 19, 2024 2:40 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUN 19, 2024 2:40 PM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
s15 OTHER DIESEL TANK NO VACUUM ALARM CLEAR 6-19-24 12:23PM
s12 OTHER SUPREME TANK NO VACUUM ALARM CLEAR 6-19-24 12:18PM
s 9 OTHER UNL TANK NO VACUUM ALARM CLEAR 6-19-24 12:11PM
L 3 DISP PAN DISP 5-6 LOW LIQUID ALARM CLEAR 6-19-24 11:39AM
L 3 DISP PAN DISP 5-6 LOW LIQUID ALARM ALARM 6-19-24 11:39AM
L 4 DISP PAN DISP 7-8 LOW LIQUID ALARM CLEAR 6-19-24 11:38AM
L 4 DISP PAN DISP 7-8 LOW LIQUID ALARM ALARM 6-19-24 11:38AM
L 2 DISP PAN DISP 3-4 LOW LIQUID ALARM CLEAR 6-19-24 11:38AM
L 2 DISP PAN DISP 3-4 LOW LIQUID ALARM ALARM 6-19-24 11:37AM
L13 OTHER VENT BOX LOW LIQUID ALARM CLEAR 6-19-24 11:07AM
L13 OTHER VENT BOX LOW LIQUID ALARM ALARM 6-19-24 11:07AM
L13 OTHER VENT BOX LOW LIQUID ALARM CLEAR 6-19-24 11:06AM
L13 OTHER VENT BOX LOW LIQUID ALARM ALARM 6-19-24 11:06AM
L13 OTHER VENT BOX FUEL ALARM CLEAR 6-19-24 11:06AM
L13 OTHER VENT BOX FUEL ALARM ALARM 6-19-24 11:06AM
L 6 DISP PAN DISP 11-12 FUEL ALARM CLEAR 6-19-24 10:59AM
L 6 DISP PAN DISP 11-12 FUEL ALARM ALARM 6-19-24 10:56AM
L11 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L10 OTHER SUPREME FILL SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L12 OTHER DIESEL FILL SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 9 STP SUMP SUPREME STP SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L13 OTHER VENT BOX SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 2 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 4 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 3 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 7 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 6 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 1 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 5 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 8 OTHER UNL FILL SENSOR OUT ALARM CLEAR 6-19-24 10:25AM
L 7 STP SUMP UNL STP SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L 4 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L 3 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L 2 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L 1 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L 6 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L 8 OTHER UNL FILL SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L 5 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L10 OTHER SUPREME FILL SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L12 OTHER DIESEL FILL SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L11 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L 9 STP SUMP SUPREME STP SENSOR OUT ALARM ALARM 6-19-24 10:24AM
L13 OTHER VENT BOX SENSOR OUT ALARM ALARM 6-19-24 10:24AM
s 9 OTHER UNL TANK NO VACUUM ALARM ALARM 6-19-24 10:17AM
s 9 OTHER UNL TANK HIGH LIQUID ALARM CLEAR 6-19-24 10:16AM
s 9 OTHER UNL TANK HIGH LIQUID ALARM ALARM 6-19-24 10:15AM
s12 OTHER SUPREME TANK HIGH LIQUID ALARM CLEAR 6-19-24 10:11AM
s12 OTHER SUPREME TANK HIGH LIQUID ALARM ALARM 6-19-24 10:10AM
s12 OTHER SUPREME TANK NO VACUUM ALARM ALARM 6-19-24 10:10AM
s15 OTHER DIESEL TANK HIGH LIQUID ALARM CLEAR 6-19-24 10:05AM
I11200
JUN 19, 2024 2:40 PM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h11 OTHER FP11: BLEND3 FLOW COLLECT WARN ALARM 6-19-24 10:06AM
SYSTEM PRINTER ERROR CLEAR 6-19-24 9:22AM
SYSTEM PAPER OUT CLEAR 6-19-24 9:21AM
SYSTEM PAPER OUT ALARM 6-19-24 9:21AM
SYSTEM PAPER OUT CLEAR 6-19-24 9:21AM
SYSTEM PAPER OUT ALARM 6-19-24 9:21AM
SYSTEM PAPER OUT CLEAR 6-19-24 9:21AM
SYSTEM PAPER OUT ALARM 6-19-24 9:21AM
SYSTEM PAPER OUT CLEAR 6-19-24 9:21AM
SYSTEM PAPER OUT ALARM 6-19-24 9:21AM
SYSTEM PRINTER ERROR ALARM 6-19-24 9:21AM
h12 OTHER FP12: BLEND3 FLOW COLLECT WARN CLEAR 6-07-24 8:14AM
h12 OTHER FP12: BLEND3 FLOW COLLECT WARN ALARM 6-06-24 10:08AM
SYSTEM PRINTER ERROR CLEAR 5-28-24 8:00AM
SYSTEM PAPER OUT CLEAR 5-28-24 8:00AM
SYSTEM PRINTER ERROR ALARM 5-28-24 8:00AM
SYSTEM PAPER OUT ALARM 5-28-24 8:00AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 5-17-24 2:15PM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 5-17-24 10:06AM
SYSTEM PRINTER ERROR CLEAR 5-08-24 1:03AM
SYSTEM PAPER OUT CLEAR 5-08-24 1:03AM
SYSTEM PAPER OUT ALARM 5-08-24 1:03AM
SYSTEM PRINTER ERROR ALARM 5-08-24 1:03AM
SYSTEM PRINTER ERROR CLEAR 5-08-24 1:02AM
SYSTEM PAPER OUT CLEAR 5-08-24 1:02AM
SYSTEM PRINTER ERROR ALARM 5-08-24 1:02AM
SYSTEM PRINTER ERROR CLEAR 5-08-24 1:02AM
SYSTEM PRINTER ERROR ALARM 5-08-24 1:01AM
SYSTEM PAPER OUT ALARM 5-08-24 1:00AM
SYSTEM PRINTER ERROR CLEAR 4-17-24 11:49PM
SYSTEM PAPER OUT CLEAR 4-17-24 11:49PM
SYSTEM PAPER OUT ALARM 4-17-24 11:49PM
SYSTEM PRINTER ERROR ALARM 4-17-24 11:49PM
SYSTEM PRINTER ERROR CLEAR 4-17-24 11:49PM
SYSTEM PAPER OUT CLEAR 4-17-24 11:49PM
SYSTEM PAPER OUT ALARM 4-17-24 11:49PM
SYSTEM PAPER OUT CLEAR 4-17-24 11:49PM
SYSTEM PRINTER ERROR ALARM 4-17-24 11:48PM
SYSTEM PAPER OUT ALARM 4-17-24 11:48PM
SYSTEM PRINTER ERROR CLEAR 4-11-24 2:27PM
SYSTEM PAPER OUT CLEAR 4-11-24 2:26PM
SYSTEM PRINTER ERROR ALARM 4-11-24 2:26PM
SYSTEM PAPER OUT ALARM 4-11-24 2:22PM
SYSTEM PRINTER ERROR CLEAR 3-23-24 12:24AM
SYSTEM PAPER OUT CLEAR 3-23-24 12:24AM
SYSTEM PAPER OUT ALARM 3-23-24 12:24AM
SYSTEM PRINTER ERROR ALARM 3-23-24 12:24AM
SYSTEM PRINTER ERROR CLEAR 3-03-24 4:27AM
SYSTEM PRINTER ERROR ALARM 3-03-24 4:27AM
SYSTEM PAPER OUT CLEAR 3-03-24 4:27AM
I20600
JUN 19, 2024 2:40 PM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
TANK ALARM HISTORY
TANK 1 UNLEADED
TANK 2 SUPREME
TANK 3 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUN 19, 2024 2:41 PM
I30200
JUN 19, 2024 2:41 PM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:45 AM LOW LIQUID ALARM
JUN 19, 2024 9:44 AM FUEL ALARM
2 DISP 3-4
JUN 19, 2024 11:37 AM LOW LIQUID ALARM
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:44 AM LOW LIQUID ALARM
3 DISP 5-6
JUN 19, 2024 11:39 AM LOW LIQUID ALARM
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:42 AM LOW LIQUID ALARM
4 DISP 7-8
JUN 19, 2024 11:38 AM LOW LIQUID ALARM
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:42 AM LOW LIQUID ALARM
5 DISP 9-10
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:41 AM LOW LIQUID ALARM
JUN 19, 2024 9:40 AM FUEL ALARM
6 DISP 11-12
JUN 19, 2024 10:56 AM FUEL ALARM
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:39 AM LOW LIQUID ALARM
7 UNL STP
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:31 AM LOW LIQUID ALARM
JUN 19, 2024 9:30 AM LOW LIQUID ALARM
8 UNL FILL
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:34 AM LOW LIQUID ALARM
JUN 19, 2024 9:34 AM FUEL ALARM
9 SUPREME STP
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:27 AM LOW LIQUID ALARM
JUN 19, 2024 9:27 AM FUEL ALARM
10 SUPREME FILL
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:36 AM LOW LIQUID ALARM
JUN 19, 2024 9:35 AM FUEL ALARM
11 DIESEL STP
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:26 AM LOW LIQUID ALARM
JUN 19, 2024 9:25 AM FUEL ALARM
12 DIESEL FILL
JUN 19, 2024 10:24 AM SENSOR OUT ALARM
JUN 19, 2024 9:37 AM LOW LIQUID ALARM
JUN 19, 2024 9:36 AM FUEL ALARM
13 VENT BOX
JUN 19, 2024 11:07 AM LOW LIQUID ALARM
JUN 19, 2024 11:06 AM LOW LIQUID ALARM
JUN 19, 2024 11:06 AM FUEL ALARM
I31600
JUN 19, 2024 2:41 PM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2 FM
2 DISP 3-4 FM
3 DISP 5-6 FM
4 DISP 7-8 FM
5 DISP 9-10 FM
6 DISP 11-12 FM
7 DISP 5-6 PS
8 ATM
9 UNL TANK
JUN 19, 2024 10:17 AM NO VACUUM ALARM
JUN 19, 2024 10:15 AM HIGH LIQUID ALARM
JUL 24, 2023 1:56 PM NO VACUUM ALARM
10 UNL PRODUCT
JUN 19, 2024 9:52 AM NO VACUUM ALARM
JUN 19, 2024 9:51 AM HIGH LIQUID ALARM
JUL 24, 2023 1:56 PM HIGH LIQUID ALARM
11 VAPOR RETURN
JUN 19, 2024 9:53 AM NO VACUUM ALARM
JUN 19, 2024 9:51 AM HIGH LIQUID ALARM
AUG 11, 2023 7:15 AM HIGH LIQUID ALARM
12 SUPREME TANK
JUN 19, 2024 10:10 AM HIGH LIQUID ALARM
JUN 19, 2024 10:10 AM NO VACUUM ALARM
JUL 24, 2023 1:55 PM NO VACUUM ALARM
13 SUPREME PRODUCT
JUN 19, 2024 9:48 AM NO VACUUM ALARM
JUN 19, 2024 9:48 AM HIGH LIQUID ALARM
JUL 24, 2023 2:08 PM HIGH LIQUID ALARM
14 UNL-SUP VENT
JUN 19, 2024 9:49 AM NO VACUUM ALARM
JUN 19, 2024 9:48 AM HIGH LIQUID ALARM
JUL 24, 2023 2:08 PM HIGH LIQUID ALARM
15 DIESEL TANK
JUN 19, 2024 10:04 AM HIGH LIQUID ALARM
JUN 19, 2024 9:54 AM NO VACUUM ALARM
SEP 25, 2023 11:50 AM NO VACUUM ALARM
16 DIESEL PRODUCT
JUN 19, 2024 9:54 AM NO VACUUM ALARM
JUN 19, 2024 9:52 AM HIGH LIQUID ALARM
JUL 24, 2023 1:53 PM HIGH LIQUID ALARM
17 DIESEL VENT
JUN 19, 2024 9:53 AM NO VACUUM ALARM
JUN 19, 2024 9:52 AM HIGH LIQUID ALARM
JUL 24, 2023 1:53 PM HIGH LIQUID ALARM
I40200
JUN 19, 2024 2:41 PM
I40300
JUN 19, 2024 2:41 PM
I34200
JUN 19, 2024 2:41 PM
I34700
JUN 19, 2024 2:41 PM
IV0100
JUN 19, 2024 2:41 PM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-06-19 10:06:10 FLOW PERFORMANCE HOSE BLOCKAGE FP11 BLEND3 0.57
24-06-06 10:08:04 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 0.59
24-05-17 10:06:44 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.60
24-01-25 10:03:54 SENSOR OUT SELFTEST E 1
23-12-08 10:03:55 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3 0.60
23-11-12 10:03:35 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.28
23-11-11 10:03:26 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.28
23-11-10 10:03:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.28
23-11-09 10:04:12 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.20
23-10-30 10:01:14 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 104.90
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-12-09 10:03:46 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3
23-10-31 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 104.56
22-10-09 10:03:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 43.37
22-10-08 10:03:42 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.44
22-10-07 10:03:44 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.38
22-06-11 10:07:00 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3
22-03-05 10:07:15 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3
21-09-07 10:07:55 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
21-08-18 10:08:51 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
21-07-26 10:05:35 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-06-19 10:27:32 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-06-19 10:27:32 ISD STARTUP
24-06-19 10:27:27 ISD SHUTDOWN
24-06-18 10:06:53 READINESS ISD:PP EVR:PP ISD & EVR READY
24-06-17 16:21:31 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-06-17 16:21:31 ISD STARTUP
24-06-17 15:47:10 ISD SHUTDOWN
24-06-07 10:59:05 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
24-06-07 08:14:35 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED
24-05-17 14:15:48 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED