HomeMy WebLinkAboutFMC 2024Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10157583 06/25/2024
Avo Shell
5700 Auburn Street Bakersfield 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
VeederRoot TLS-3XX Technician - C32655 10/11/2024
Vaporless Manufacturing Inc. - #5265 10/21/2024
OPW - 1193585 04/14/2025
06/25/2024 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS-350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 303 87 Unleaded Tank ANN
L2 303 91 Premium Tank ANN
L3 303 Diesel Tank ANN
L9 208 Diesel STP
L10 208 Diesel STP ANN
L11 208 87 Unleaded Fill
L12 304 87 Unleaded Fill
L13 304 91 Premium Fill ANN
L14 208 91 Premium Fill
L15 208 Diesel Fill
L16 304 Diesel Fill ANN
L17 208 Dispenser 9-10 UDC
L18 304 Dispenser 9-10 UDC ANN
L19 208 Dispenser 11-12 UDC
L20 304 Dispenser 11-12 UDC ANN
L21 208 87 Unleaded STP
L22 304 87 Unleaded STP ANN
L23 208 91 Premium STP
L24 304 91 Premium STP ANN
L25 208 Dispenser 1-2 UDC
L26 303 Dispenser 1-2 UDC ANN
L27 208 Dispenser 3-4 UDC
L28 304 Dispenser 3-4 UDC ANN
L29 208 Dispenser 5-6 UDC
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L30 304 Dispenser 5-6 UDC ANN
L31 208 Dispenser 7-8 UDC
L32 304 Dispenser 7-8 UDC ANN
S8 363/364 87 Product
S9 363/364 91 Vent
S10 363/364 87-91 Vapor
S11 363/364 87 Vent
S12 363/364 91 Product
S14 363/364 Diesel Product
S15 363/364 Diesel Vent
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 Unleaded
T2 FX1V 91 Premium
T3 FX1DV Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Emergency Shutoff Switch - when compressed kills power to STPs, Dispensers, as well as VeederRoot and Point-Of-Sale.
When testing the ESO, a power breaker switch labeled "Panel FC" must be reset in order to restore power to all applications.
Reset switches and breakers are located in the back room of the building. All electrical site components and breaker panels
are located in said room.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Avo Shell5700 Auburn StreetBakersfield10157583Disp 3-4Disp 7-8 Disp 11-12MPDMPDMPDMPDMPDMPDDisp 1-2Disp 5-6Disp 9-10ProductProductProductProductProductProductBrandon Nunez
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10157583 06/25/2024
Avo Shell
5700 Auburn Street Bakersfield 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
OPW - 1193585 04/14/2025
PEI 1200 1 Hour Hydrostatic All Spill Containers
06/25/2024 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1: 87 UNL
OPW
T2: 91 PNL
OPW
T3: DSL
OPW
Avo Shell System Setup & Alarm History
Responses Received:
200
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
06-25-24 2:23 PM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 9657 57.50 0.0 88.2 10046
2 PREMIUM 4604 37.48 0.0 84.9 6923
3 DIESEL 4464 36.62 0.0 89.0 7063
I90500
06-25-24 2:23 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
06-25-24 2:23 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MM-DD-YY HH:MM:SS xM
I50201
06-25-24 2:23 PM
SHIFT TIME 1 : 6:00 AM
I50202
06-25-24 2:23 PM
SHIFT TIME 2 : DISABLED
I50203
06-25-24 2:23 PM
SHIFT TIME 3 : DISABLED
I50204
06-25-24 2:23 PM
SHIFT TIME 4 : DISABLED
I54600
06-25-24 2:23 PM
TANK PER TST NEEDED WRN: DISABLED
I54900
06-25-24 2:23 PM
TANK ANN TST NEEDED WRN: DISABLED
I55300
06-25-24 2:23 PM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
06-25-24 2:23 PM
LINE PER TST NEEDED WRN: DISABLED
I55900
06-25-24 2:23 PM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
06-25-24 2:23 PM
PRINT TC VOLUMES
ENABLED
I50E00
06-25-24 2:23 PM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
06-25-24 2:23 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
06-25-24 2:23 PM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
06-25-24 2:23 PM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
06-25-24 2:23 PM
DAYLIGHT SAVING TIME
START DATE APR WEEK 1 SUN 2:00 AM
END DATE OCT WEEK 6 SUN 2:00 AM
I51600
06-25-24 2:23 PM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
06-25-24 2:23 PM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
06-25-24 2:23 PM
TANK CHART SECURITY
DISABLED
I5BD00
06-25-24 2:23 PM
CUSTOM ALARM LABELS
DISABLED
I56000
06-25-24 2:23 PM
MASS/DENSITY
DISABLED
I88101
06-25-24 2:23 PM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
06-25-24 2:23 PM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
06-25-24 2:23 PM
I88104
06-25-24 2:23 PM
I88105
06-25-24 2:23 PM
I88106
06-25-24 2:23 PM
I52000
06-25-24 2:23 PM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE MAR 11, 2012 DISABLED
2 ON DATE MAR 11, 2012 DISABLED
3 ON DATE MAR 11, 2012 DISABLED
4 ON DATE MAR 11, 2012 DISABLED
5 ON DATE MAR 11, 2012 DISABLED
6 ON DATE MAR 11, 2012 DISABLED
7 ON DATE MAR 11, 2012 DISABLED
8 ON DATE MAR 11, 2012 DISABLED
I60100
06-25-24 2:23 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 PREMIUM ON
3 DIESEL ON
4 OFF
I60200
06-25-24 2:23 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4
I60300
06-25-24 2:23 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL 3
4 4
I60900
06-25-24 2:23 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 PREMIUM 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
06-25-24 2:23 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 117.75
2 PREMIUM 89.75
3 DIESEL 89.75
4 0.00
I60A00
06-25-24 2:23 PM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
4 PTS 19703 2 PREMIUM 4 PTS 11527 3 DIESEL
4 PTS 11527 4 1 PT 0
I60400
06-25-24 2:23 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 19703
2 PREMIUM 11527
3 DIESEL 11527
4 0
I60500
06-25-24 2:23 PM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 19703 16062 9961 3824
2 PREMIUM 11527 9379 5836 2271
3 DIESEL 11527 9379 5836 2271
4 0 0 0 0
I60600
06-25-24 2:23 PM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 19703 0 0 0
0 16062 0 0
0 0 9961 0
0 0 0 3824
0 0 0 0
2 PREMIUM 11527 0 0 0
0 9379 0 0
0 0 5836 0
0 0 0 2271
0 0 0 0
3 DIESEL 11527 0 0 0
0 9379 0 0
0 0 5836 0
0 0 0 2271
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
06-25-24 2:23 PM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 PREMIUM NO
3 DIESEL NO
4 NO
I62F00
06-25-24 2:23 PM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 3.0 IN.
2 PREMIUM 3.0 IN.
3 DIESEL 3.0 IN.
I62700
06-25-24 2:23 PM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 PREMIUM 2.0
3 DIESEL 2.0
I64200
06-25-24 2:23 PM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 PREMIUM LOW
3 DIESEL LOW
I62400
06-25-24 2:23 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 PREMIUM 3.0
3 DIESEL 3.0
I62800
06-25-24 2:23 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 19703
2 PREMIUM 11527
3 DIESEL 11527
4 0
I62300
06-25-24 2:23 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 18718
2 PREMIUM 10374
3 DIESEL 10374
4 0
I62200
06-25-24 2:23 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 18718
2 PREMIUM 10951
3 DIESEL 10951
4 0
I62900
06-25-24 2:23 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 2000
2 PREMIUM 1200
3 DIESEL 1200
4 0
I62100
06-25-24 2:23 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1500
2 PREMIUM 1000
3 DIESEL 1000
4 0
I62600
06-25-24 2:23 PM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I62500
06-25-24 2:23 PM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 50
2 PREMIUM 50
3 DIESEL 50
4 99
I60800
06-25-24 2:23 PM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 0.00
3 DIESEL 0.00
4 0.00
I60B00
06-25-24 2:23 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
06-25-24 2:23 PM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 0.00
3 DIESEL 0.00
4 0.00
I61200
06-25-24 2:23 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 PREMIUM NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
06-25-24 2:23 PM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 2000
2 PREMIUM 1200
3 DIESEL 1200
4 0
I62A00
06-25-24 2:23 PM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 2000
2 PREMIUM 1200
3 DIESEL 1200
4 0
I62C00
06-25-24 2:23 PM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 PREMIUM STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
06-25-24 2:23 PM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
06-25-24 2:23 PM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 PREMIUM OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
06-25-24 2:23 PM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I63200
06-25-24 2:23 PM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I61000
06-25-24 2:23 PM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63A00
06-25-24 2:23 PM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 PREMIUM 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
06-25-24 2:24 PM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ANNUALLY: ALL TANK
DEC WEEK 1 SUN
START TIME : 2:30 AM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
06-25-24 2:24 PM
CSLD PROBABLITY OF DETECTION
I61400
06-25-24 2:24 PM
CSLD CLIMATE FACTOR
I61600
06-25-24 2:24 PM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 PREMIUM IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
06-25-24 2:24 PM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED
2 PREMIUM DISABLED
3 DIESEL DISABLED
4 DISABLED
I61B00
06-25-24 2:24 PM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
06-25-24 2:24 PM
CSLD REPORT ONLY
I62B00
06-25-24 2:24 PM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED 00-00-00
2 PREMIUM 00-00-00
3 DIESEL 00-00-00
4 00-00-00
I63300
06-25-24 2:24 PM
LEAK TEST REPORT FORMAT: NORMAL
I63400
06-25-24 2:24 PM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 PREMIUM 0
3 DIESEL 0
4 0
I63500
06-25-24 2:24 PM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63900
06-25-24 2:24 PM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 PREMIUM
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
06-25-24 2:24 PM
I77700
06-25-24 2:24 PM
I77800
06-25-24 2:24 PM
I78C00
06-25-24 2:24 PM
I78300
06-25-24 2:24 PM
I78F00
06-25-24 2:24 PM
I78700
06-25-24 2:24 PM
I70200
06-25-24 2:24 PM
LIQUID LABEL
DEVICE LABEL
1 UNL TANK ANN
2 PREM TANK ANN
3 DIESEL TANK ANN
4
5
6
7
8
9 DIESEL STP
10 DIESEL STP ANN
11 UNL FILL
12 UNL FILL ANN
13 PREM FILL ANN
14 PREM FILL
15 DIESEL FILL
16 DIESEL FILL ANN
17 DIS 9-10
18 DIS 9-10 ANN
19 DIS 11-12
20 DIS 11-12 ANN
21 UNL STP
22 UNL STP ANN
23 PREM STP
24 PREM STP ANN
25 DIS 1-2
26 DIS 1-2 ANN
27 DIS 3-4
28 DIS 3-4 ANN
29 DIS 5-6
30 DIS 5-6 ANN
31 DIS 7-8
32 DIS 7-8 ANN
I70300
06-25-24 2:24 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL TANK ANN DUAL POINT HYDROSTATIC
2 PREM TANK ANN DUAL POINT HYDROSTATIC
3 DIESEL TANK ANN DUAL POINT HYDROSTATIC
4 TRI-STATE (SINGLE FLOAT)
5 TRI-STATE (SINGLE FLOAT)
6 TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
9 DIESEL STP TRI-STATE (SINGLE FLOAT)
10 DIESEL STP ANN TRI-STATE (SINGLE FLOAT)
11 UNL FILL TRI-STATE (SINGLE FLOAT)
12 UNL FILL ANN TRI-STATE (SINGLE FLOAT)
13 PREM FILL ANN TRI-STATE (SINGLE FLOAT)
14 PREM FILL TRI-STATE (SINGLE FLOAT)
15 DIESEL FILL TRI-STATE (SINGLE FLOAT)
16 DIESEL FILL ANN TRI-STATE (SINGLE FLOAT)
17 DIS 9-10 TRI-STATE (SINGLE FLOAT)
18 DIS 9-10 ANN TRI-STATE (SINGLE FLOAT)
19 DIS 11-12 TRI-STATE (SINGLE FLOAT)
20 DIS 11-12 ANN TRI-STATE (SINGLE FLOAT)
21 UNL STP TRI-STATE (SINGLE FLOAT)
22 UNL STP ANN TRI-STATE (SINGLE FLOAT)
23 PREM STP TRI-STATE (SINGLE FLOAT)
24 PREM STP ANN TRI-STATE (SINGLE FLOAT)
25 DIS 1-2 TRI-STATE (SINGLE FLOAT)
26 DIS 1-2 ANN TRI-STATE (SINGLE FLOAT)
27 DIS 3-4 TRI-STATE (SINGLE FLOAT)
28 DIS 3-4 ANN TRI-STATE (SINGLE FLOAT)
29 DIS 5-6 TRI-STATE (SINGLE FLOAT)
30 DIS 5-6 ANN TRI-STATE (SINGLE FLOAT)
31 DIS 7-8 TRI-STATE (SINGLE FLOAT)
32 DIS 7-8 ANN TRI-STATE (SINGLE FLOAT)
I70400
06-25-24 2:24 PM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL TANK ANN ANNULAR SPACE
2 PREM TANK ANN ANNULAR SPACE
3 DIESEL TANK ANN ANNULAR SPACE
4 OTHER SENSORS
5 OTHER SENSORS
6 OTHER SENSORS
7 OTHER SENSORS
8 OTHER SENSORS
9 DIESEL STP STP SUMP
10 DIESEL STP ANN ANNULAR SPACE
11 UNL FILL PIPING SUMP
12 UNL FILL ANN ANNULAR SPACE
13 PREM FILL ANN ANNULAR SPACE
14 PREM FILL PIPING SUMP
15 DIESEL FILL PIPING SUMP
16 DIESEL FILL ANN ANNULAR SPACE
17 DIS 9-10 DISPENSER PAN
18 DIS 9-10 ANN ANNULAR SPACE
19 DIS 11-12 DISPENSER PAN
20 DIS 11-12 ANN ANNULAR SPACE
21 UNL STP STP SUMP
22 UNL STP ANN ANNULAR SPACE
23 PREM STP STP SUMP
24 PREM STP ANN ANNULAR SPACE
25 DIS 1-2 DISPENSER PAN
26 DIS 1-2 ANN ANNULAR SPACE
27 DIS 3-4 DISPENSER PAN
28 DIS 3-4 ANN ANNULAR SPACE
29 DIS 5-6 DISPENSER PAN
30 DIS 5-6 ANN ANNULAR SPACE
31 DIS 7-8 DISPENSER PAN
32 DIS 7-8 ANN ANNULAR SPACE
I74200
06-25-24 2:24 PM
I74300
06-25-24 2:24 PM
I74400
06-25-24 2:24 PM
I74700
06-25-24 2:24 PM
I74800
06-25-24 2:24 PM
I74900
06-25-24 2:24 PM
I7BC00
06-25-24 2:24 PM
I80200
06-25-24 2:24 PM
I80300
06-25-24 2:24 PM
I80400
06-25-24 2:24 PM
I80700
06-25-24 2:24 PM
RELAY LABEL
DEVICE LABEL
1 87 STP
2 91 STP
3 DIESEL STP
4 OVERFILL ALARM
I80900
06-25-24 2:24 PM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 87 STP NORMALLY OPEN
2 91 STP NORMALLY OPEN
3 DIESEL STP NORMALLY OPEN
4 OVERFILL ALARM NORMALLY OPEN
I80B00
06-25-24 2:24 PM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 87 STP 1
2 91 STP 2
3 DIESEL STP 3
4 OVERFILL ALARM NONE
I80A00
06-25-24 2:24 PM
RELAY TYPE
RELAY DESIGNATION TYPE
1 87 STP PUMP CONTROL OUTPUT
2 91 STP PUMP CONTROL OUTPUT
3 DIESEL STP PUMP CONTROL OUTPUT
4 OVERFILL ALARM STANDARD
I80C00
06-25-24 2:24 PM
I80800
06-25-24 2:24 PM
RELAY SETUP REPORT
R 1:87 STP
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L17:FUEL ALARM
L19:FUEL ALARM
L21:FUEL ALARM
L25:FUEL ALARM
L27:FUEL ALARM
L29:FUEL ALARM
L31:FUEL ALARM
L17:SENSOR OUT ALARM
L19:SENSOR OUT ALARM
L21:SENSOR OUT ALARM
L25:SENSOR OUT ALARM
L27:SENSOR OUT ALARM
L29:SENSOR OUT ALARM
L31:SENSOR OUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 2:91 STP
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
LIQUID SENSOR ALMS
L17:FUEL ALARM
L19:FUEL ALARM
L23:FUEL ALARM
L25:FUEL ALARM
L27:FUEL ALARM
L29:FUEL ALARM
L31:FUEL ALARM
L17:SENSOR OUT ALARM
L19:SENSOR OUT ALARM
L23:SENSOR OUT ALARM
L25:SENSOR OUT ALARM
L27:SENSOR OUT ALARM
L29:SENSOR OUT ALARM
L31:SENSOR OUT ALARM
L17:SHORT ALARM
L19:SHORT ALARM
L23:SHORT ALARM
L25:SHORT ALARM
L27:SHORT ALARM
L29:SHORT ALARM
L31:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 3:DIESEL STP
TYPE:
PUMP CONTROL OUTPUT
TANK #: 3
LIQUID SENSOR ALMS
L 9:FUEL ALARM
L17:FUEL ALARM
L19:FUEL ALARM
L25:FUEL ALARM
L27:FUEL ALARM
L 9:SENSOR OUT ALARM
L17:SENSOR OUT ALARM
L19:SENSOR OUT ALARM
L25:SENSOR OUT ALARM
L27:SENSOR OUT ALARM
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
I79000
06-25-24 2:25 PM
EDIM:1 VR:349643-001-B TD:97.10.27.11.25
I79100
06-25-24 2:25 PM
I72300
06-25-24 2:25 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 PRESS DISP 1-2 VAPOR PRESSURE
02 FM DISP 1-2 AIR FLOW METER
03 FM DISP 3-4 AIR FLOW METER
04 FM DISP 5-6 AIR FLOW METER
05 FM DISP 7-8 AIR FLOW METER
06 FM DISP 9-10 AIR FLOW METER
07 FM DISP 11-12 AIR FLOW METER
08 87 PROD VAC SENSOR
09 91 VENT VAC SENSOR
10 87-91 VAPOR VAC SENSOR
11 87 VENT VAC SENSOR
12 91 PROD VAC SENSOR
13 91 VENT VAC SENSOR
14 DIESEL PROD VAC SENSOR
15 DIESEL VENT VAC SENSOR
16 ATM PRESS ATM P SENSOR
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
06-25-24 2:25 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
06-25-24 2:25 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
06-25-24 2:25 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
VAPOR PROCESSOR TYPE
NONE
IV4700
06-25-24 2:25 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
06-25-24 2:25 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
ACCEPT HIGH ORVR: YES
IV4A00
06-25-24 2:25 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
09 09 09 05 02 BLEND3
10 16 10 05 02 BLEND3
11 17 11 06 02 BLEND3
12 18 12 06 02 BLEND3
IV4B00
06-25-24 2:25 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 01/01 09/01 xx/xx
02 01 02/02 01/02 09/02 xx/xx
03 02 02/03 01/03 09/03 xx/xx
04 02 02/04 01/04 09/04 xx/xx
05 03 02/05 01/05 09/05 xx/xx
06 03 02/06 01/06 09/06 xx/xx
07 04 02/07 01/07 09/07 xx/xx
08 04 02/08 01/08 09/08 xx/xx
09 05 02/09 01/09 09/09 xx/xx
16 05 02/10 01/10 09/10 xx/xx
17 06 02/11 01/11 09/11 xx/xx
18 06 02/12 01/12 09/12 xx/xx
IV4900
06-25-24 2:25 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
06-25-24 2:25 PM
ISD VERSION: 01.07
Pre Alarm History
Responses Received:
I10200
06-25-24 2:26 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39536 39433
2 7SMARTSENSOR BD 507076 505098
3 UNUSED 4977997 4977679
4 4 PROBE / G.T. 162746 162696
5 INTERSTITIAL BD 201384 201059
6 INTERSTITIAL BD 201595 201229
7 INTERSTITIAL BD 201173 200930
8 INTERSTITIAL BD 201363 200973
9 RELAY BOARD 14935 14941
10 STP SENSE BOARD 33180 33147
11 UNUSED 4980403 4975840
12 UNUSED 4974185 4974321
13 UNUSED 4972177 4975426
14 UNUSED 4970890 4973354
15 UNUSED 4969838 4973019
16 UNUSED 4973444 4970770
COMM 1 ELEC DISP INT. 101010 100907
COMM 2 RS232 SERIAL BD 14955 14961
COMM 3 UNUSED 4975744 4974597
COMM 4 UNUSED 4973580 4970514
COMM 5 UNUSED 4969584 4969784
COMM 6 UNUSED 4969467 4974716
I90200
06-25-24 2:26 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
06-25-24 2:26 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
E 1 OTHER COMMUNICATION ALARM CLEAR 06-24-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM ALARM 06-24-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 06-17-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM ALARM 06-17-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 06-07-24 9:38 PM
E 1 OTHER COMMUNICATION ALARM ALARM 06-07-24 9:38 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 06-07-24 6:40 AM
E 1 OTHER COMMUNICATION ALARM ALARM 06-07-24 6:40 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 06-03-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM ALARM 06-03-24 2:07 AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT FAIL CLEAR 06-02-24 10:19 AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT FAIL ALARM 06-02-24 10:03 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 05-27-24 2:08 AM
E 1 OTHER COMMUNICATION ALARM ALARM 05-27-24 2:08 AM
L14 PIPE PREM FILL FUEL ALARM CLEAR 05-24-24 11:40 AM
L14 PIPE PREM FILL FUEL ALARM ALARM 05-24-24 11:39 AM
L14 PIPE PREM FILL FUEL ALARM CLEAR 05-24-24 11:39 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT FAIL CLEAR 05-24-24 10:08 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT FAIL ALARM 05-24-24 10:03 AM
L14 PIPE PREM FILL FUEL ALARM ALARM 05-23-24 4:48 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 05-20-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM ALARM 05-20-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 05-05-24 12:27 AM
E 1 OTHER COMMUNICATION ALARM ALARM 05-05-24 12:27 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 05-04-24 10:32 PM
E 1 OTHER COMMUNICATION ALARM ALARM 05-04-24 10:32 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 05-04-24 9:50 PM
E 1 OTHER COMMUNICATION ALARM ALARM 05-04-24 9:50 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 04-29-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM ALARM 04-29-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 04-28-24 12:37 PM
E 1 OTHER COMMUNICATION ALARM ALARM 04-28-24 12:37 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 04-28-24 6:48 AM
E 1 OTHER COMMUNICATION ALARM ALARM 04-28-24 6:48 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 04-28-24 6:36 AM
E 1 OTHER COMMUNICATION ALARM ALARM 04-28-24 6:36 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 04-22-24 2:07 AM
E 1 OTHER COMMUNICATION ALARM ALARM 04-22-24 2:07 AM
s12 OTHER 91 PROD NO VACUUM ALARM CLEAR 04-18-24 11:33 AM
s12 OTHER 91 PROD NO VACUUM ALARM ALARM 04-18-24 11:21 AM
s12 OTHER 91 PROD NO VACUUM ALARM CLEAR 04-18-24 11:21 AM
s12 OTHER 91 PROD HIGH LIQUID ALARM CLEAR 04-18-24 11:21 AM
s12 OTHER 91 PROD HIGH LIQUID ALARM ALARM 04-18-24 11:20 AM
s12 OTHER 91 PROD NO VACUUM ALARM ALARM 04-18-24 11:19 AM
s12 OTHER 91 PROD NO VACUUM ALARM CLEAR 04-18-24 11:13 AM
s12 OTHER 91 PROD NO VACUUM ALARM ALARM 04-18-24 11:06 AM
s12 OTHER 91 PROD NO VACUUM ALARM CLEAR 04-18-24 9:54 AM
s12 OTHER 91 PROD COMMUNICATION ALARM CLEAR 04-18-24 9:41 AM
s12 OTHER 91 PROD COMMUNICATION ALARM ALARM 04-18-24 9:36 AM
L14 PIPE PREM FILL FUEL ALARM CLEAR 04-18-24 9:07 AM
I11200
06-25-24 2:26 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 06-15-24 9:26 AM
SYSTEM PAPER OUT CLEAR 06-15-24 9:26 AM
SYSTEM PRINTER ERROR ALARM 06-15-24 9:26 AM
SYSTEM PAPER OUT ALARM 06-15-24 9:26 AM
SYSTEM PRINTER ERROR CLEAR 06-15-24 9:26 AM
SYSTEM PAPER OUT CLEAR 06-15-24 9:26 AM
SYSTEM PRINTER ERROR ALARM 06-15-24 9:26 AM
SYSTEM PAPER OUT ALARM 06-15-24 9:26 AM
h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 06-12-24 10:00 AM
h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 06-11-24 10:04 AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 06-08-24 10:00 AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 06-02-24 10:00 AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 06-02-24 10:00 AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 06-01-24 10:03 AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 05-31-24 10:03 AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 05-26-24 10:04 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 05-24-24 10:00 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 05-24-24 10:00 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 05-22-24 10:04 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 05-21-24 10:00 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 05-18-24 10:03 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 05-17-24 10:03 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 05-16-24 10:00 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 05-15-24 10:02 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 05-09-24 10:00 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 05-08-24 10:02 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 05-07-24 10:00 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 05-06-24 10:01 AM
SYSTEM PRINTER ERROR CLEAR 04-26-24 10:29 AM
SYSTEM PAPER OUT CLEAR 04-26-24 10:29 AM
SYSTEM PRINTER ERROR ALARM 04-26-24 10:28 AM
SYSTEM PAPER OUT ALARM 04-26-24 10:28 AM
s12 OTHER 91 PROD VACUUM WARNING CLEAR 04-18-24 11:19 AM
s12 OTHER 91 PROD VACUUM WARNING ALARM 04-18-24 11:13 AM
s12 OTHER 91 PROD VACUUM WARNING CLEAR 04-18-24 11:06 AM
s12 OTHER 91 PROD VACUUM WARNING ALARM 04-18-24 10:04 AM
OTHER ISD GROSS PRES WARN CLEAR 03-28-24 11:38 AM
OTHER ISD GROSS PRES WARN ALARM 03-24-24 10:02 AM
SYSTEM PRINTER ERROR CLEAR 03-16-24 10:56 AM
SYSTEM PAPER OUT CLEAR 03-16-24 10:56 AM
SYSTEM PRINTER ERROR ALARM 03-16-24 10:56 AM
SYSTEM PAPER OUT ALARM 03-16-24 10:56 AM
OTHER ISD GROSS PRES WARN CLEAR 03-14-24 10:00 AM
OTHER ISD GROSS PRES WARN ALARM 03-11-24 10:03 AM
OTHER ISD GROSS PRES WARN CLEAR 03-04-24 5:21 PM
OTHER ISD GROSS PRES WARN ALARM 03-03-24 10:03 AM
OTHER ISD DEGRD PRES WARN CLEAR 02-28-24 10:00 AM
OTHER ISD DEGRD PRES WARN ALARM 02-26-24 10:03 AM
OTHER ISD GROSS PRES WARN CLEAR 02-12-24 10:00 AM
OTHER ISD GROSS PRES WARN ALARM 02-07-24 10:02 AM
I20600
06-25-24 2:26 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
TANK ALARM HISTORY
TANK 1 UNLEADED
TANK 2 PREMIUM
LOW PRODUCT ALARM 08-25-23 11:02 AM
SUDDEN LOSS ALARM 12-01-23 11:09 AM
11-14-23 3:05 PM
INVALID FUEL LEVEL 08-25-23 11:02 AM
07-27-23 5:35 PM
PROBE OUT 12-01-23 4:46 PM
11-14-23 7:42 AM
09-01-23 7:26 AM
HIGH WATER WARNING 07-24-23 4:51 AM
DELIVERY NEEDED 12-04-23 9:22 PM
08-04-23 10:01 AM
07-27-23 5:27 PM
TANK 3 DIESEL
OVERFILL ALARM 01-31-23 7:29 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
06-25-24 2:26 PM
I30200
06-25-24 2:26 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL TANK ANN
11-14-23 6:08 PM SENSOR OUT ALARM
11-14-23 5:08 PM LOW LIQUID ALARM
11-14-23 2:42 PM LOW LIQUID ALARM
2 PREM TANK ANN
11-30-23 9:25 AM LOW LIQUID ALARM
11-30-23 9:24 AM HIGH LIQUID ALARM
11-30-23 9:24 AM LOW LIQUID ALARM
3 DIESEL TANK ANN
11-14-23 6:09 PM SENSOR OUT ALARM
11-14-23 3:55 PM LOW LIQUID ALARM
11-14-23 3:54 PM LOW LIQUID ALARM
9 DIESEL STP
11-14-23 6:09 PM SENSOR OUT ALARM
06-21-23 11:02 AM SENSOR OUT ALARM
06-21-23 10:30 AM FUEL ALARM
10 DIESEL STP ANN
11-14-23 6:09 PM SENSOR OUT ALARM
06-21-23 11:02 AM SENSOR OUT ALARM
06-21-23 10:03 AM FUEL ALARM
11 UNL FILL
11-14-23 6:09 PM SENSOR OUT ALARM
06-21-23 11:02 AM SENSOR OUT ALARM
06-21-23 10:10 AM FUEL ALARM
12 UNL FILL ANN
11-14-23 6:09 PM SENSOR OUT ALARM
06-21-23 11:02 AM SENSOR OUT ALARM
06-21-23 10:01 AM FUEL ALARM
13 PREM FILL ANN
11-30-23 9:23 AM FUEL ALARM
11-14-23 6:09 PM SENSOR OUT ALARM
11-14-23 6:01 PM FUEL ALARM
14 PREM FILL
05-24-24 11:39 AM FUEL ALARM
05-23-24 4:48 PM FUEL ALARM
04-13-24 6:32 PM FUEL ALARM
15 DIESEL FILL
11-14-23 6:09 PM SENSOR OUT ALARM
06-21-23 11:02 AM SENSOR OUT ALARM
06-21-23 10:08 AM FUEL ALARM
16 DIESEL FILL ANN
11-14-23 6:09 PM SENSOR OUT ALARM
06-21-23 11:02 AM SENSOR OUT ALARM
06-21-23 10:00 AM FUEL ALARM
17 DIS 9-10
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:08 AM SENSOR OUT ALARM
06-21-23 11:06 AM SENSOR OUT ALARM
18 DIS 9-10 ANN
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:09 AM SENSOR OUT ALARM
06-21-23 11:07 AM SENSOR OUT ALARM
19 DIS 11-12
11-14-23 6:10 PM SENSOR OUT ALARM
09-28-23 5:36 PM FUEL ALARM
06-21-23 11:09 AM SENSOR OUT ALARM
20 DIS 11-12 ANN
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:09 AM SENSOR OUT ALARM
06-21-23 11:07 AM SENSOR OUT ALARM
21 UNL STP
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:09 AM SENSOR OUT ALARM
06-21-23 11:07 AM SENSOR OUT ALARM
22 UNL STP ANN
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:09 AM SENSOR OUT ALARM
06-21-23 11:04 AM FUEL ALARM
23 PREM STP
02-29-24 5:43 AM FUEL ALARM
11-30-23 9:17 AM FUEL ALARM
11-14-23 6:07 PM FUEL ALARM
24 PREM STP ANN
04-12-24 8:28 AM FUEL ALARM
04-12-24 8:24 AM FUEL ALARM
11-30-23 9:21 AM FUEL ALARM
25 DIS 1-2
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:11 AM SENSOR OUT ALARM
06-21-23 11:11 AM FUEL ALARM
26 DIS 1-2 ANN
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:07 AM SENSOR OUT ALARM
06-21-23 10:07 AM FUEL ALARM
27 DIS 3-4
06-21-23 11:07 AM SENSOR OUT ALARM
06-21-23 10:07 AM FUEL ALARM
07-06-22 10:29 AM SENSOR OUT ALARM
28 DIS 3-4 ANN
06-21-23 11:07 AM SENSOR OUT ALARM
06-21-23 10:46 AM FUEL ALARM
07-06-22 10:29 AM SENSOR OUT ALARM
29 DIS 5-6
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:11 AM SENSOR OUT ALARM
06-21-23 11:09 AM FUEL ALARM
30 DIS 5-6 ANN
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:12 AM SENSOR OUT ALARM
06-21-23 11:09 AM FUEL ALARM
31 DIS 7-8
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:12 AM SENSOR OUT ALARM
06-21-23 11:09 AM FUEL ALARM
32 DIS 7-8 ANN
11-14-23 6:10 PM SENSOR OUT ALARM
06-21-23 11:12 AM SENSOR OUT ALARM
06-21-23 11:09 AM FUEL ALARM
I31600
06-25-24 2:26 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PRESS DISP 1-2
2 FM DISP 1-2
3 FM DISP 3-4
4 FM DISP 5-6
5 FM DISP 7-8
6 FM DISP 9-10
7 FM DISP 11-12
8 87 PROD
09-28-23 6:09 PM HIGH LIQUID ALARM
09-28-23 6:08 PM NO VACUUM ALARM
09-28-23 5:57 PM HIGH LIQUID ALARM
9 91 VENT
02-22-24 2:15 AM NO VACUUM ALARM
11-30-23 9:36 AM NO VACUUM ALARM
11-30-23 9:36 AM HIGH LIQUID ALARM
10 87-91 VAPOR
11-14-23 1:42 PM COMMUNICATION ALARM
10-22-23 6:42 PM COMMUNICATION ALARM
10-22-23 12:02 AM COMMUNICATION ALARM
11 87 VENT
11-14-23 4:24 PM NO VACUUM ALARM
09-28-23 6:08 PM HIGH LIQUID ALARM
09-28-23 6:08 PM NO VACUUM ALARM
12 91 PROD
04-18-24 11:21 AM NO VACUUM ALARM
04-18-24 11:20 AM HIGH LIQUID ALARM
04-18-24 11:19 AM NO VACUUM ALARM
14 DIESEL PROD
06-21-23 11:29 AM NO VACUUM ALARM
06-21-23 11:28 AM HIGH LIQUID ALARM
07-06-22 11:00 AM NO VACUUM ALARM
15 DIESEL VENT
11-14-23 4:24 PM NO VACUUM ALARM
06-21-23 11:31 AM NO VACUUM ALARM
06-21-23 11:28 AM HIGH LIQUID ALARM
16 ATM PRESS
I40200
06-25-24 2:26 PM
I40300
06-25-24 2:26 PM
I34200
06-25-24 2:26 PM
I34700
06-25-24 2:26 PM
IV0100
06-25-24 2:26 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-06-11 10:04:26 A/L RATIO DEGRADATION FP12 BLEND3 0.80
24-06-07 10:04:25 A/L RATIO DEGRADATION FP 7 BLEND3 0.77
24-06-06 10:04:21 A/L RATIO DEGRADATION FP 7 BLEND3 0.76
24-06-05 10:03:21 A/L RATIO DEGRADATION FP 7 BLEND3 0.76
24-06-04 10:03:28 A/L RATIO DEGRADATION FP 7 BLEND3 0.77
24-06-03 10:03:55 A/L RATIO DEGRADATION FP 7 BLEND3 0.80
24-06-02 10:03:26 A/L RATIO DEGRADATION FP 7 BLEND3 0.78
24-06-01 10:03:52 A/L RATIO DEGRADATION FP 7 BLEND3 0.79
24-06-01 10:03:52 A/L RATIO DEGRADATION FP 6 BLEND3 0.80
24-06-01 10:03:52 A/L RATIO DEGRADATION FP 1 BLEND3 0.78
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
24-06-02 10:03:26 A/L RATIO DEGRADATION FP 1 BLEND3 0.78
24-05-24 10:03:29 A/L RATIO DEGRADATION FP 2 BLEND3 0.79
23-11-13 10:02:33 SENSOR OUT SELFTEST T 2
23-11-12 10:02:36 SENSOR OUT SELFTEST T 2
23-11-11 10:02:33 SENSOR OUT SELFTEST T 2
23-11-10 10:02:58 SENSOR OUT SELFTEST T 2
23-11-09 10:03:34 SENSOR OUT SELFTEST T 2
23-11-08 10:04:13 SENSOR OUT SELFTEST T 2
23-11-08 10:04:13 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-11-07 10:04:02 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 3:FM DISP 5-6
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-06-02 10:19:24 COLLECTION TEST HH01 GRADE TEST MANUALLY CLEARED
24-06-02 10:16:35 PUMPS MANUALLY RE-ENABLED
24-06-02 10:03:26 A/L RATIO GROSS DEGRADATION DISABLED FP 01 BLEND3
24-05-24 10:08:04 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
24-05-24 10:07:45 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-05-24 10:04:13 PUMPS MANUALLY RE-ENABLED
24-05-24 10:03:29 A/L RATIO GROSS DEGRADATION DISABLED FP 02 BLEND3
24-04-10 10:25:00 TIME CHANGE DETECTED AT: 24-04-10 11:22:13
24-04-07 03:00:00 TIME CHANGE DETECTED AT: 24-04-07 02:00:13
24-03-28 11:38:16 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
Post Alarm History
Responses Received:
I10200
06-25-24 5:07 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39536 39637
2 7SMARTSENSOR BD 507076 509991
3 UNUSED 4977997 5004872
4 4 PROBE / G.T. 162746 163108
5 INTERSTITIAL BD 201384 202053
6 INTERSTITIAL BD 201595 201677
7 INTERSTITIAL BD 201173 201677
8 INTERSTITIAL BD 201363 201907
9 RELAY BOARD 14935 14949
10 STP SENSE BOARD 33180 33211
11 UNUSED 4980403 4998150
12 UNUSED 4974185 4990542
13 UNUSED 4972177 4990214
14 UNUSED 4970890 4985900
15 UNUSED 4969838 4987152
16 UNUSED 4973444 4987364
COMM 1 ELEC DISP INT. 101010 101105
COMM 2 RS232 SERIAL BD 14955 14949
COMM 3 UNUSED 4975744 4999999
COMM 4 UNUSED 4973580 4993720
COMM 5 UNUSED 4969584 4993527
COMM 6 UNUSED 4969467 4994259
I90200
06-25-24 5:07 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
06-25-24 5:07 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 3 ANNULAR DIESEL TANK ANN HIGH LIQUID ALARM CLEAR 06-25-24 3:21 PM
L 1 ANNULAR UNL TANK ANN LOW LIQUID ALARM CLEAR 06-25-24 3:21 PM
L 1 ANNULAR UNL TANK ANN LOW LIQUID ALARM ALARM 06-25-24 3:21 PM
L 1 ANNULAR UNL TANK ANN HIGH LIQUID ALARM CLEAR 06-25-24 3:21 PM
L 2 ANNULAR PREM TANK ANN HIGH LIQUID ALARM CLEAR 06-25-24 3:21 PM
L 1 ANNULAR UNL TANK ANN LOW LIQUID ALARM CLEAR 06-25-24 3:21 PM
L 1 ANNULAR UNL TANK ANN HIGH LIQUID ALARM ALARM 06-25-24 3:21 PM
L 2 ANNULAR PREM TANK ANN LOW LIQUID ALARM CLEAR 06-25-24 3:21 PM
L 2 ANNULAR PREM TANK ANN HIGH LIQUID ALARM ALARM 06-25-24 3:21 PM
L 3 ANNULAR DIESEL TANK ANN LOW LIQUID ALARM CLEAR 06-25-24 3:21 PM
L 3 ANNULAR DIESEL TANK ANN HIGH LIQUID ALARM ALARM 06-25-24 3:21 PM
s14 OTHER DIESEL PROD HIGH LIQUID ALARM CLEAR 06-25-24 3:18 PM
s15 OTHER DIESEL VENT HIGH LIQUID ALARM CLEAR 06-25-24 3:18 PM
s15 OTHER DIESEL VENT NO VACUUM ALARM CLEAR 06-25-24 3:18 PM
L 1 ANNULAR UNL TANK ANN LOW LIQUID ALARM ALARM 06-25-24 3:17 PM
s15 OTHER DIESEL VENT NO VACUUM ALARM ALARM 06-25-24 3:17 PM
s14 OTHER DIESEL PROD NO VACUUM ALARM CLEAR 06-25-24 3:17 PM
L 2 ANNULAR PREM TANK ANN LOW LIQUID ALARM ALARM 06-25-24 3:16 PM
s14 OTHER DIESEL PROD NO VACUUM ALARM ALARM 06-25-24 3:16 PM
L 3 ANNULAR DIESEL TANK ANN LOW LIQUID ALARM ALARM 06-25-24 3:16 PM
s15 OTHER DIESEL VENT HIGH LIQUID ALARM ALARM 06-25-24 3:15 PM
s14 OTHER DIESEL PROD HIGH LIQUID ALARM ALARM 06-25-24 3:15 PM
s11 OTHER 87 VENT HIGH LIQUID ALARM CLEAR 06-25-24 3:14 PM
s 8 OTHER 87 PROD HIGH LIQUID ALARM CLEAR 06-25-24 3:14 PM
s10 OTHER 87-91 VAPOR HIGH LIQUID ALARM CLEAR 06-25-24 3:14 PM
s11 OTHER 87 VENT NO VACUUM ALARM CLEAR 06-25-24 3:13 PM
s12 OTHER 91 PROD HIGH LIQUID ALARM CLEAR 06-25-24 3:13 PM
s 9 OTHER 91 VENT HIGH LIQUID ALARM CLEAR 06-25-24 3:13 PM
s 9 OTHER 91 VENT NO VACUUM ALARM CLEAR 06-25-24 3:13 PM
s 9 OTHER 91 VENT NO VACUUM ALARM ALARM 06-25-24 3:12 PM
s12 OTHER 91 PROD NO VACUUM ALARM CLEAR 06-25-24 3:12 PM
s11 OTHER 87 VENT NO VACUUM ALARM ALARM 06-25-24 3:12 PM
s12 OTHER 91 PROD NO VACUUM ALARM ALARM 06-25-24 3:12 PM
s10 OTHER 87-91 VAPOR NO VACUUM ALARM CLEAR 06-25-24 3:11 PM
s12 OTHER 91 PROD HIGH LIQUID ALARM ALARM 06-25-24 3:11 PM
s 9 OTHER 91 VENT HIGH LIQUID ALARM ALARM 06-25-24 3:11 PM
s 9 OTHER 91 VENT HIGH LIQUID ALARM CLEAR 06-25-24 3:11 PM
s12 OTHER 91 PROD HIGH LIQUID ALARM CLEAR 06-25-24 3:11 PM
s12 OTHER 91 PROD NO VACUUM ALARM CLEAR 06-25-24 3:11 PM
s10 OTHER 87-91 VAPOR NO VACUUM ALARM ALARM 06-25-24 3:10 PM
s 8 OTHER 87 PROD NO VACUUM ALARM CLEAR 06-25-24 3:10 PM
s12 OTHER 91 PROD NO VACUUM ALARM ALARM 06-25-24 3:10 PM
s12 OTHER 91 PROD HIGH LIQUID ALARM ALARM 06-25-24 3:10 PM
s 9 OTHER 91 VENT HIGH LIQUID ALARM ALARM 06-25-24 3:10 PM
s 8 OTHER 87 PROD NO VACUUM ALARM ALARM 06-25-24 3:09 PM
s10 OTHER 87-91 VAPOR HIGH LIQUID ALARM ALARM 06-25-24 3:09 PM
s11 OTHER 87 VENT HIGH LIQUID ALARM ALARM 06-25-24 3:09 PM
s 8 OTHER 87 PROD HIGH LIQUID ALARM ALARM 06-25-24 3:09 PM
L16 ANNULAR DIESEL FILL ANN SENSOR OUT ALARM CLEAR 06-25-24 3:05 PM
L 3 ANNULAR DIESEL TANK ANN SENSOR OUT ALARM CLEAR 06-25-24 3:05 PM
I11200
06-25-24 5:07 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 06-15-24 9:26 AM
SYSTEM PAPER OUT CLEAR 06-15-24 9:26 AM
SYSTEM PRINTER ERROR ALARM 06-15-24 9:26 AM
SYSTEM PAPER OUT ALARM 06-15-24 9:26 AM
SYSTEM PRINTER ERROR CLEAR 06-15-24 9:26 AM
SYSTEM PAPER OUT CLEAR 06-15-24 9:26 AM
SYSTEM PRINTER ERROR ALARM 06-15-24 9:26 AM
SYSTEM PAPER OUT ALARM 06-15-24 9:26 AM
h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 06-12-24 10:00 AM
h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 06-11-24 10:04 AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 06-08-24 10:00 AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 06-02-24 10:00 AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 06-02-24 10:00 AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 06-01-24 10:03 AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 05-31-24 10:03 AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 05-26-24 10:04 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 05-24-24 10:00 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 05-24-24 10:00 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 05-22-24 10:04 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 05-21-24 10:00 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 05-18-24 10:03 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 05-17-24 10:03 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 05-16-24 10:00 AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 05-15-24 10:02 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 05-09-24 10:00 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 05-08-24 10:02 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 05-07-24 10:00 AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 05-06-24 10:01 AM
SYSTEM PRINTER ERROR CLEAR 04-26-24 10:29 AM
SYSTEM PAPER OUT CLEAR 04-26-24 10:29 AM
SYSTEM PRINTER ERROR ALARM 04-26-24 10:28 AM
SYSTEM PAPER OUT ALARM 04-26-24 10:28 AM
s12 OTHER 91 PROD VACUUM WARNING CLEAR 04-18-24 11:19 AM
s12 OTHER 91 PROD VACUUM WARNING ALARM 04-18-24 11:13 AM
s12 OTHER 91 PROD VACUUM WARNING CLEAR 04-18-24 11:06 AM
s12 OTHER 91 PROD VACUUM WARNING ALARM 04-18-24 10:04 AM
OTHER ISD GROSS PRES WARN CLEAR 03-28-24 11:38 AM
OTHER ISD GROSS PRES WARN ALARM 03-24-24 10:02 AM
SYSTEM PRINTER ERROR CLEAR 03-16-24 10:56 AM
SYSTEM PAPER OUT CLEAR 03-16-24 10:56 AM
SYSTEM PRINTER ERROR ALARM 03-16-24 10:56 AM
SYSTEM PAPER OUT ALARM 03-16-24 10:56 AM
OTHER ISD GROSS PRES WARN CLEAR 03-14-24 10:00 AM
OTHER ISD GROSS PRES WARN ALARM 03-11-24 10:03 AM
OTHER ISD GROSS PRES WARN CLEAR 03-04-24 5:21 PM
OTHER ISD GROSS PRES WARN ALARM 03-03-24 10:03 AM
OTHER ISD DEGRD PRES WARN CLEAR 02-28-24 10:00 AM
OTHER ISD DEGRD PRES WARN ALARM 02-26-24 10:03 AM
OTHER ISD GROSS PRES WARN CLEAR 02-12-24 10:00 AM
OTHER ISD GROSS PRES WARN ALARM 02-07-24 10:02 AM
I20600
06-25-24 5:07 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
TANK ALARM HISTORY
TANK 1 UNLEADED
TANK 2 PREMIUM
LOW PRODUCT ALARM 08-25-23 11:02 AM
SUDDEN LOSS ALARM 12-01-23 11:09 AM
11-14-23 3:05 PM
INVALID FUEL LEVEL 08-25-23 11:02 AM
07-27-23 5:35 PM
PROBE OUT 12-01-23 4:46 PM
11-14-23 7:42 AM
09-01-23 7:26 AM
HIGH WATER WARNING 07-24-23 4:51 AM
DELIVERY NEEDED 12-04-23 9:22 PM
08-04-23 10:01 AM
07-27-23 5:27 PM
TANK 3 DIESEL
OVERFILL ALARM 01-31-23 7:29 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
06-25-24 5:07 PM
I30200
06-25-24 5:07 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL TANK ANN
06-25-24 3:21 PM LOW LIQUID ALARM
06-25-24 3:21 PM HIGH LIQUID ALARM
06-25-24 3:17 PM LOW LIQUID ALARM
2 PREM TANK ANN
06-25-24 3:21 PM HIGH LIQUID ALARM
06-25-24 3:16 PM LOW LIQUID ALARM
06-25-24 3:03 PM SENSOR OUT ALARM
3 DIESEL TANK ANN
06-25-24 3:21 PM HIGH LIQUID ALARM
06-25-24 3:16 PM LOW LIQUID ALARM
06-25-24 3:03 PM SENSOR OUT ALARM
9 DIESEL STP
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:41 PM FUEL ALARM
11-14-23 6:09 PM SENSOR OUT ALARM
10 DIESEL STP ANN
06-25-24 3:03 PM SENSOR OUT ALARM
11-14-23 6:09 PM SENSOR OUT ALARM
06-21-23 11:02 AM SENSOR OUT ALARM
11 UNL FILL
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:47 PM FUEL ALARM
11-14-23 6:09 PM SENSOR OUT ALARM
12 UNL FILL ANN
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:47 PM FUEL ALARM
06-25-24 2:47 PM FUEL ALARM
13 PREM FILL ANN
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:44 PM FUEL ALARM
11-30-23 9:23 AM FUEL ALARM
14 PREM FILL
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:44 PM FUEL ALARM
05-24-24 11:39 AM FUEL ALARM
15 DIESEL FILL
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:42 PM FUEL ALARM
11-14-23 6:09 PM SENSOR OUT ALARM
16 DIESEL FILL ANN
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:42 PM FUEL ALARM
11-14-23 6:09 PM SENSOR OUT ALARM
17 DIS 9-10
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:52 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
18 DIS 9-10 ANN
06-25-24 3:04 PM SENSOR OUT ALARM
06-25-24 2:58 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
19 DIS 11-12
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:53 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
20 DIS 11-12 ANN
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:53 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
21 UNL STP
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:37 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
22 UNL STP ANN
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:38 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
23 PREM STP
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:40 PM FUEL ALARM
02-29-24 5:43 AM FUEL ALARM
24 PREM STP ANN
06-25-24 3:03 PM SENSOR OUT ALARM
06-25-24 2:40 PM FUEL ALARM
04-12-24 8:28 AM FUEL ALARM
25 DIS 1-2
06-25-24 3:04 PM SENSOR OUT ALARM
06-25-24 2:49 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
26 DIS 1-2 ANN
06-25-24 3:04 PM SENSOR OUT ALARM
06-25-24 2:49 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
27 DIS 3-4
06-25-24 3:04 PM SENSOR OUT ALARM
06-25-24 2:50 PM FUEL ALARM
06-21-23 11:07 AM SENSOR OUT ALARM
28 DIS 3-4 ANN
06-25-24 3:04 PM SENSOR OUT ALARM
06-25-24 2:50 PM FUEL ALARM
06-21-23 11:07 AM SENSOR OUT ALARM
29 DIS 5-6
06-25-24 3:04 PM SENSOR OUT ALARM
06-25-24 2:51 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
30 DIS 5-6 ANN
06-25-24 3:04 PM SENSOR OUT ALARM
06-25-24 2:51 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
31 DIS 7-8
06-25-24 3:04 PM SENSOR OUT ALARM
06-25-24 2:51 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
32 DIS 7-8 ANN
06-25-24 3:04 PM SENSOR OUT ALARM
06-25-24 2:52 PM FUEL ALARM
11-14-23 6:10 PM SENSOR OUT ALARM
I31600
06-25-24 5:07 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PRESS DISP 1-2
2 FM DISP 1-2
3 FM DISP 3-4
4 FM DISP 5-6
5 FM DISP 7-8
6 FM DISP 9-10
7 FM DISP 11-12
8 87 PROD
06-25-24 3:09 PM NO VACUUM ALARM
06-25-24 3:09 PM HIGH LIQUID ALARM
09-28-23 6:09 PM HIGH LIQUID ALARM
9 91 VENT
06-25-24 3:12 PM NO VACUUM ALARM
06-25-24 3:11 PM HIGH LIQUID ALARM
06-25-24 3:10 PM HIGH LIQUID ALARM
10 87-91 VAPOR
06-25-24 3:10 PM NO VACUUM ALARM
06-25-24 3:09 PM HIGH LIQUID ALARM
11-14-23 1:42 PM COMMUNICATION ALARM
11 87 VENT
06-25-24 3:12 PM NO VACUUM ALARM
06-25-24 3:09 PM HIGH LIQUID ALARM
11-14-23 4:24 PM NO VACUUM ALARM
12 91 PROD
06-25-24 3:12 PM NO VACUUM ALARM
06-25-24 3:11 PM HIGH LIQUID ALARM
06-25-24 3:10 PM NO VACUUM ALARM
14 DIESEL PROD
06-25-24 3:16 PM NO VACUUM ALARM
06-25-24 3:15 PM HIGH LIQUID ALARM
06-21-23 11:29 AM NO VACUUM ALARM
15 DIESEL VENT
06-25-24 3:17 PM NO VACUUM ALARM
06-25-24 3:15 PM HIGH LIQUID ALARM
11-14-23 4:24 PM NO VACUUM ALARM
16 ATM PRESS
I40200
06-25-24 5:07 PM
I40300
06-25-24 5:08 PM
I34200
06-25-24 5:08 PM
I34700
06-25-24 5:08 PM
IV0100
06-25-24 5:08 PM
FAIRFAX SHELL MART
5700 AUBURN ST
BAKERSFIELD CA 93306
661 873 7730
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-06-11 10:04:26 A/L RATIO DEGRADATION FP12 BLEND3 0.80
24-06-07 10:04:25 A/L RATIO DEGRADATION FP 7 BLEND3 0.77
24-06-06 10:04:21 A/L RATIO DEGRADATION FP 7 BLEND3 0.76
24-06-05 10:03:21 A/L RATIO DEGRADATION FP 7 BLEND3 0.76
24-06-04 10:03:28 A/L RATIO DEGRADATION FP 7 BLEND3 0.77
24-06-03 10:03:55 A/L RATIO DEGRADATION FP 7 BLEND3 0.80
24-06-02 10:03:26 A/L RATIO DEGRADATION FP 7 BLEND3 0.78
24-06-01 10:03:52 A/L RATIO DEGRADATION FP 7 BLEND3 0.79
24-06-01 10:03:52 A/L RATIO DEGRADATION FP 6 BLEND3 0.80
24-06-01 10:03:52 A/L RATIO DEGRADATION FP 1 BLEND3 0.78
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
24-06-02 10:03:26 A/L RATIO DEGRADATION FP 1 BLEND3 0.78
24-05-24 10:03:29 A/L RATIO DEGRADATION FP 2 BLEND3 0.79
23-11-13 10:02:33 SENSOR OUT SELFTEST T 2
23-11-12 10:02:36 SENSOR OUT SELFTEST T 2
23-11-11 10:02:33 SENSOR OUT SELFTEST T 2
23-11-10 10:02:58 SENSOR OUT SELFTEST T 2
23-11-09 10:03:34 SENSOR OUT SELFTEST T 2
23-11-08 10:04:13 SENSOR OUT SELFTEST T 2
23-11-08 10:04:13 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-11-07 10:04:02 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 3:FM DISP 5-6
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-06-25 17:05:19 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-06-25 17:05:19 ISD STARTUP
24-06-25 16:20:03 ISD SHUTDOWN
24-06-25 16:19:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-06-25 16:19:39 ISD STARTUP
24-06-25 16:07:41 ISD SHUTDOWN
24-06-02 10:19:24 COLLECTION TEST HH01 GRADE TEST MANUALLY CLEARED
24-06-02 10:16:35 PUMPS MANUALLY RE-ENABLED
24-06-02 10:03:26 A/L RATIO GROSS DEGRADATION DISABLED FP 01 BLEND3
24-05-24 10:08:04 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED