November 6, 2020 File: [727-01-03]
Manpreet Behl
1501 Truxtun Ave
Bakersfield, CA 93301
RE: 2800 and 2816 Calloway Stormwater Runoff
The purpose of this letter is to evaluate the runoff from the development of Parcel A of
Lot Line Adjustment 02-0204 (LLA). The project area is located on the southeast corner
of Calloway Drive and Flushing Quail Road. The project runoff area consists of three
parcels; parcels A, B and C of the LLA. Two of these, parcels B and C are fully
developed and are referenced in the attached Storm Drain Master Plan done by Porter
Robertson Engineering (2005). These parcels are already developed and the storm
water runoff flowing to the existing catch basin at Node181 in the PR study, located on
the north side of the project site, on the south side of Flushing Quail. As Parcel A will be
improved, we have reviewed and updated the drainage calculations completed by Porter
Robertson Engineering. We have determined that the existing catch basin and
downstream pipe have sufficient capacity to handle the incremental runoff from the
development of Parcel A.
Existing Condition:
The existing catch basin on Flushing Quail (node 181) is a standard catch basin with a
3.5 ft opening. According the PR study this catch basin has a capacity of 6.5 cfs and the
existing Q5 at basin 181 is 3.64 cfs. Downstream of the catch basin is an 18’ SD pipe.
The existing pipe flow (Q10) is 4.20 cfs.
Proposed condition:
The addition of Parcel A to the existing condition will result in a total flow to the catch
basin of (Q5) of 5.27 cfs and a total flow in the SD pipe of (Q10) of 6.1 cfs.
Catch Basin: The catch basin 181 has an inlet capacity of 5.6 cfs per the PR study. The
proposed Q5 to the catch basin is 5.27 cfs. The catch basin is properly sized for the
additional runoff.
Downstream Pipe:
Factoring in the additional runoff from the Parcel A results in the addition of 1.9 cfs to the
downstream pipe network. This raises the HGL at basin 181 by a total of 1.05’ which
reduces the available freeboard to 1.66’. The additional flow to the network does not
adversely affect the collection pipe system. The impact on the rest of the system is
negligible because all but 0.09’ of HGL rise is in the last two 18” pipe runs. The overall
rise in the rest of the collection system is only 0.09’.
Attached you will find the following exhibits to support these conclusions:
Runoff drainage calcs for the Parcel A, B and C study area.
HGL analysis with revisions to the PR study.
5509 Young Street
Bakersfield, CA 93311
Tel: 661.325.9474 - Fax 661.322.0129
www.cornerstoneeng.com
Attachments
Exhibit of Parcels
Drainage Calculations for Parcels B & C of LLA 02-0204
5509 Young Street
Bakersfield, CA 93311
Tel: 661.325.9474 - Fax 661.322.0129
www.cornerstoneeng.com
Parcel Exhibit
1.54 Acres
Calculations
Existing Conditions:
A= 3.46 Acres
C=0.9
Per attached Porter Robertson Engineering Drainage Calculation for Parcel B &
C of LLA 02-0204:
C*A = 3.11
Tc = 17 min
I5 = 1.17
I10 = 1.35
Proposed Conditions
A = 3.46 + 1.54 = 5.00 Acres
Q5 = (0.9)(1.17)(5.00) = 5.27 cfs
Q10 = (0.9)(1.35)(5.0) = 6.1 cfs (proposed)
Per attached Porter Robertson Engineering Drainage Calculation for Parcel B &
C of LLA 02-0204:
Existing CB full capacity is 1.6 cfs/ft * 3.5 ft wide = 5.6 cfs
Proposed Runoff = 5.27 cfs
Existing Pipe per the Drainage Calculations for Parcel A, B & C of LLA 02-0204:
See attached HGL calculations with additional 1.9 cfs to the pipe system