HomeMy WebLinkAboutFMC 2024Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10134247 07/10/2024
Jaco #7785 Fastrip #32
3701 Ming Avenue Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
VeederRoot TLS-3XX Technician - C32655 10/11/2024
Vaporless Manufacturing Inc. - #5265 10/21/2024
FFS Phil-Tite Phase I - 1016703714 12/07/2024
07/10/2024 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS-350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 87 Unleaded STP
L2 208 87 Unleaded Fill
L3 303 87 Unleaded ANN
L4 208 91 Premium STP
L5 208 91 Premium Fill
L6 303 91 Premium ANN
L7 208 Diesel STP
L8 208 Diesel Fill
L9 303 Diesel ANN
L10 208 Vent Box
L11 208 Dispenser 1-2 UDC
L12 208 Dispenser 3-4 UDC
L13 208 Dispenser 5-6 UDC
L14 208 Dispenser 7-8 UDC
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 Unleaded
T2 FX1V 91 Premium
T3 FX1DV Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
07/10/2024
NOPARKING
F
STPL1
V
AL3
STPL4AL6
STPL7AL9
FV
F
L2
L5
L8
L1478
L1356
L1234
L1112
L10
EXISTING BUILDING
12,000 GALLON87 UNLEADED
12,000 GALLONPREMIUM
12,000 GALLONDIESEL
W
GH
DUMPSTERW
CATCHBASIN
PRICE SIGNOUTDOOR AREAWITH COVER
BUS STOP
MING AVE.REAL RD.PROPERTY LINE
PROPERTY LINE
N
LEGEND
L1 87 STP
L2 87 FILL
L3 87 ANNULAR
L4 91 STP
L5 91 FILL
L6 91 ANNULAR
L7 DSL STP
L8 DSL FILL
L9 DSL ANNULAR
L10 VENT BOX
L11 UDC 1 - 2
L12 UDC 3 - 4
L13 UDC 5 - 6
L14 UDC 7 - 8
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 3/2 INCH DOUBLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
UST ELECTRICAL PANEL
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
W
G
A
H
P
V
SCALE:
SITE MAP C1
VICINITY MAP
PROJECT DATA
1"=10'-0"
INCHES012
SHEET SIZE 22 X 34
3701 MING AVE.
BAKERSFIELD, CA 93309
PROJECT OWNER:
JAMIESON HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
15-021-003025
CERS ID 10134247
FASTRIP #7785
3701 MING AVE..
BAKERSFIELD, CA 93309
03/18/17 REV.REAL RD.MING AVE.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #7785 Fastrip #323701 Ming AvenueBakersfield10134247Disp 3-4Disp 7-8MPDMPDMPD MPD Disp 1-2Disp 5-6ProductProductProductProductBrandon Nunez
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10134247 07/10/2024
Jaco #7785 Fastrip #32
3701 Ming Avenue Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
FFS Phil-Tite Phase I - 1016703714 12/07/2024
PEI 1200 1 Hour Hydrostatic All Spill Containers
07/10/2024 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1: 87 UNL
Phil-Tite
T2: 91 PNL
Phil-Tite
T3: DSL
Phil-Tite
7785 Jaco System Setup & Alarm History
Responses Received:
200
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
JUL 10, 2024 8:35 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 8578 63.12 0.0 83.6 3104
2 PREMIUM 6855 52.05 0.0 86.8 4827
3 DIESEL 2320 23.01 0.0 82.6 9362
I90500
JUL 10, 2024 8:35 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JUL 10, 2024 8:35 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUL 10, 2024 8:35 AM
SHIFT TIME 1 : 6:00 AM
I50202
JUL 10, 2024 8:36 AM
SHIFT TIME 2 : DISABLED
I50203
JUL 10, 2024 8:36 AM
SHIFT TIME 3 : DISABLED
I50204
JUL 10, 2024 8:36 AM
SHIFT TIME 4 : DISABLED
I54600
JUL 10, 2024 8:36 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUL 10, 2024 8:36 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUL 10, 2024 8:36 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUL 10, 2024 8:36 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUL 10, 2024 8:36 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUL 10, 2024 8:36 AM
PRINT TC VOLUMES
ENABLED
I50E00
JUL 10, 2024 8:36 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUL 10, 2024 8:36 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUL 10, 2024 8:36 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUL 10, 2024 8:36 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUL 10, 2024 8:36 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 1 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUL 10, 2024 8:36 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUL 10, 2024 8:36 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUL 10, 2024 8:36 AM
TANK CHART SECURITY
DISABLED
I5BD00
JUL 10, 2024 8:36 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JUL 10, 2024 8:36 AM
MASS/DENSITY
DISABLED
I88101
JUL 10, 2024 8:36 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JUL 10, 2024 8:36 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
JUL 10, 2024 8:36 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JUL 10, 2024 8:36 AM
I88105
JUL 10, 2024 8:36 AM
I88106
JUL 10, 2024 8:36 AM
I52000
JUL 10, 2024 8:36 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE MAR 9, 2011 DISABLED
2 ON DATE MAR 9, 2011 DISABLED
3 ON DATE MAR 9, 2011 DISABLED
4 ON DATE MAR 9, 2011 DISABLED
5 ON DATE MAR 9, 2011 DISABLED
6 ON DATE MAR 9, 2011 DISABLED
7 ON DATE MAR 9, 2011 DISABLED
8 ON DATE MAR 9, 2011 DISABLED
I60100
JUL 10, 2024 8:36 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 PREMIUM ON
3 DIESEL ON
4 OFF
I60200
JUL 10, 2024 8:36 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4
I60300
JUL 10, 2024 8:36 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL 3
4 4
I60900
JUL 10, 2024 8:36 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 PREMIUM 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
JUL 10, 2024 8:36 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 92.00
2 PREMIUM 92.00
3 DIESEL 92.00
4 0.00
I60A00
JUL 10, 2024 8:36 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
4 PTS 11682 2 PREMIUM 4 PTS 11682 3 DIESEL
4 PTS 11682 4 1 PT 0
I60400
JUL 10, 2024 8:36 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11682
2 PREMIUM 11682
3 DIESEL 11682
4 0
I60500
JUL 10, 2024 8:36 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11682 9433 5882 2319
2 PREMIUM 11682 9433 5882 2319
3 DIESEL 11682 9433 5882 2319
4 0 0 0 0
I60600
JUL 10, 2024 8:36 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11682 0 0 0
0 9433 0 0
0 0 5882 0
0 0 0 2319
0 0 0 0
2 PREMIUM 11682 0 0 0
0 9433 0 0
0 0 5882 0
0 0 0 2319
0 0 0 0
3 DIESEL 11682 0 0 0
0 9433 0 0
0 0 5882 0
0 0 0 2319
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUL 10, 2024 8:36 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 PREMIUM NO
3 DIESEL NO
4 NO
I62F00
JUL 10, 2024 8:36 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN.
2 PREMIUM 4.0 IN.
3 DIESEL 4.0 IN.
I62700
JUL 10, 2024 8:36 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 PREMIUM 2.0
3 DIESEL 2.0
I64200
JUL 10, 2024 8:36 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 PREMIUM LOW
3 DIESEL LOW
I62400
JUL 10, 2024 8:36 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 PREMIUM 3.0
3 DIESEL 3.0
I62800
JUL 10, 2024 8:36 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11682
2 PREMIUM 11682
3 DIESEL 11682
4 0
I62300
JUL 10, 2024 8:36 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10514
2 PREMIUM 10514
3 DIESEL 10514
4 0
I62200
JUL 10, 2024 8:36 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11098
2 PREMIUM 11098
3 DIESEL 11098
4 0
I62900
JUL 10, 2024 8:36 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1752
2 PREMIUM 1752
3 DIESEL 1752
4 0
I62100
JUL 10, 2024 8:36 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1200
2 PREMIUM 1200
3 DIESEL 1200
4 0
I62600
JUL 10, 2024 8:36 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I62500
JUL 10, 2024 8:36 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I60800
JUL 10, 2024 8:36 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 3.00
3 DIESEL 3.00
4 0.00
I60B00
JUL 10, 2024 8:36 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUL 10, 2024 8:36 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 0.00
3 DIESEL 0.00
4 0.00
I61200
JUL 10, 2024 8:36 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 PREMIUM NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
JUL 10, 2024 8:36 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 PREMIUM 120
3 DIESEL 120
4 0
I62A00
JUL 10, 2024 8:36 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 PREMIUM 120
3 DIESEL 120
4 0
I62C00
JUL 10, 2024 8:36 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 PREMIUM STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
JUL 10, 2024 8:36 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUL 10, 2024 8:36 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 PREMIUM OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
JUL 10, 2024 8:36 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I63200
JUL 10, 2024 8:36 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I61000
JUL 10, 2024 8:36 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63A00
JUL 10, 2024 8:36 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 PREMIUM 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
JUL 10, 2024 8:36 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JUL 1, 2009
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
JUL 10, 2024 8:36 AM
CSLD PROBABLITY OF DETECTION
I61400
JUL 10, 2024 8:36 AM
CSLD CLIMATE FACTOR
I61600
JUL 10, 2024 8:36 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 PREMIUM IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
JUL 10, 2024 8:36 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED
2 PREMIUM DISABLED
3 DIESEL DISABLED
4 DISABLED
I61B00
JUL 10, 2024 8:36 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JUL 10, 2024 8:36 AM
CSLD REPORT ONLY
I62B00
JUL 10, 2024 8:36 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 PREMIUM ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
JUL 10, 2024 8:36 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUL 10, 2024 8:36 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 PREMIUM 0
3 DIESEL 0
4 0
I63500
JUL 10, 2024 8:36 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63900
JUL 10, 2024 8:36 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 PREMIUM
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
JUL 10, 2024 8:36 AM
I77700
JUL 10, 2024 8:36 AM
I77800
JUL 10, 2024 8:36 AM
I78C00
JUL 10, 2024 8:36 AM
I78300
JUL 10, 2024 8:36 AM
I78F00
JUL 10, 2024 8:36 AM
I78700
JUL 10, 2024 8:36 AM
I70200
JUL 10, 2024 8:36 AM
LIQUID LABEL
DEVICE LABEL
1 UNL STP
2 UNL FILL
3 UNL ANN
4 PNL STP
5 PNL FILL
6 PNL ANN
7 DSL STP
8 DSL FILL
9 DSL ANN
10 VENT BOX
11 DISP 1-2
12 DISP 3-4
13 DISP 5-6
14 DISP 7-8
15
16
I70300
JUL 10, 2024 8:36 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL STP TRI-STATE (SINGLE FLOAT)
2 UNL FILL TRI-STATE (SINGLE FLOAT)
3 UNL ANN DUAL POINT HYDROSTATIC
4 PNL STP TRI-STATE (SINGLE FLOAT)
5 PNL FILL TRI-STATE (SINGLE FLOAT)
6 PNL ANN DUAL POINT HYDROSTATIC
7 DSL STP TRI-STATE (SINGLE FLOAT)
8 DSL FILL TRI-STATE (SINGLE FLOAT)
9 DSL ANN DUAL POINT HYDROSTATIC
10 VENT BOX TRI-STATE (SINGLE FLOAT)
11 DISP 1-2 TRI-STATE (SINGLE FLOAT)
12 DISP 3-4 TRI-STATE (SINGLE FLOAT)
13 DISP 5-6 TRI-STATE (SINGLE FLOAT)
14 DISP 7-8 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
JUL 10, 2024 8:36 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL STP STP SUMP
2 UNL FILL PIPING SUMP
3 UNL ANN ANNULAR SPACE
4 PNL STP STP SUMP
5 PNL FILL PIPING SUMP
6 PNL ANN ANNULAR SPACE
7 DSL STP STP SUMP
8 DSL FILL PIPING SUMP
9 DSL ANN ANNULAR SPACE
10 VENT BOX PIPING SUMP
11 DISP 1-2 DISPENSER PAN
12 DISP 3-4 DISPENSER PAN
13 DISP 5-6 DISPENSER PAN
14 DISP 7-8 DISPENSER PAN
15 OTHER SENSORS
16 OTHER SENSORS
I74200
JUL 10, 2024 8:36 AM
I74300
JUL 10, 2024 8:36 AM
I74400
JUL 10, 2024 8:36 AM
I74700
JUL 10, 2024 8:36 AM
I74800
JUL 10, 2024 8:36 AM
I74900
JUL 10, 2024 8:36 AM
I7BC00
JUL 10, 2024 8:36 AM
I80200
JUL 10, 2024 8:36 AM
I80300
JUL 10, 2024 8:36 AM
I80400
JUL 10, 2024 8:36 AM
I80700
JUL 10, 2024 8:36 AM
RELAY LABEL
DEVICE LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4 OVERFILL
I80900
JUL 10, 2024 8:36 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNLEADED NORMALLY OPEN
2 PREMIUM NORMALLY OPEN
3 DIESEL NORMALLY CLOSED
4 OVERFILL NORMALLY OPEN
I80B00
JUL 10, 2024 8:36 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL NONE
4 OVERFILL NONE
I80A00
JUL 10, 2024 8:36 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNLEADED PUMP CONTROL OUTPUT
2 PREMIUM PUMP CONTROL OUTPUT
3 DIESEL STANDARD
4 OVERFILL STANDARD
I80C00
JUL 10, 2024 8:36 AM
I80800
JUL 10, 2024 8:36 AM
RELAY SETUP REPORT
R 1:UNLEADED
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 1:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 1:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:PREMIUM
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
LIQUID SENSOR ALMS
L 4:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 4:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 4:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DIESEL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: NONE
LIQUID SENSOR ALMS
L 7:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 7:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
R 4:OVERFILL
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
I79000
JUL 10, 2024 8:37 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
JUL 10, 2024 8:37 AM
I72300
JUL 10, 2024 8:37 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VP 1-2 VAPOR PRESSURE
02 FM 1-2 AIR FLOW METER
03 FM 3-4 AIR FLOW METER
04 FM 5-6 AIR FLOW METER
05 FM 7-8 AIR FLOW METER
06 FM 7-8 AIR FLOW METER
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JUL 10, 2024 8:37 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
JUL 10, 2024 8:37 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JUL 10, 2024 8:37 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
VAPOR PROCESSOR TYPE
NONE
IV4700
JUL 10, 2024 8:37 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JUL 10, 2024 8:37 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
ACCEPT HIGH ORVR: YES
IV4A00
JUL 10, 2024 8:37 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
IV4B00
JUL 10, 2024 8:37 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
IV4900
JUL 10, 2024 8:37 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JUL 10, 2024 8:37 AM
ISD VERSION: 01.07
Pre Alarm History
Responses Received:
I10200
JUL 10, 2024 8:40 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 505223 505070
2 4 PROBE / G.T. 163488 163307
3 INTERSTITIAL BD 201193 201080
4 INTERSTITIAL BD 202259 201786
5 UNUSED 9948674 9803741
6 UNUSED 9940113 9790592
7 UNUSED 9939717 9792265
8 UNUSED 9937733 9786844
9 STP SENSE BOARD 33009 33051
10 RELAY BOARD 14882 14880
11 UNUSED 9943077 9795764
12 UNUSED 9938692 9793753
13 UNUSED 9937147 9790492
14 UNUSED 9938859 9787506
15 UNUSED 9939924 9792334
16 UNUSED 9932282 9780201
COMM 1 ELEC DISP INT. 100832 100901
COMM 2 RS232 SERIAL BD 14944 14965
COMM 3 RS232 SERIAL BD 14882 14880
COMM 4 UNUSED 9944706 9795743
COMM 5 UNUSED 9937022 9792143
COMM 6 UNUSED 9934955 9785600
I90200
JUL 10, 2024 8:40 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 10, 2024 8:40 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-08-24 11:40AM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 7-08-24 11:38AM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 7-08-24 11:36AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-08-24 10:43AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-08-24 8:47AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-07-24 12:00PM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-06-24 2:45PM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-06-24 11:15AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-05-24 1:48PM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-05-24 9:34AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-04-24 2:16PM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-04-24 10:56AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-04-24 5:01AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-04-24 3:30AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-03-24 6:26PM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-03-24 12:32PM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-03-24 5:17AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-02-24 11:55PM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-02-24 9:09PM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-02-24 12:49PM
L10 PIPE VENT BOX FUEL ALARM CLEAR 7-02-24 9:50AM
L10 PIPE VENT BOX FUEL ALARM ALARM 7-02-24 9:50AM
L10 PIPE VENT BOX FUEL ALARM CLEAR 7-02-24 9:50AM
L10 PIPE VENT BOX FUEL ALARM ALARM 7-02-24 9:49AM
L14 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L13 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L12 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L11 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 8 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L10 PIPE VENT BOX SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 9 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 3 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 5 PIPE PNL FILL SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-02-24 9:43AM
L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L 8 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L12 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L11 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L 3 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L10 PIPE VENT BOX SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L 5 PIPE PNL FILL SENSOR OUT ALARM ALARM 7-02-24 9:42AM
L 9 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-02-24 9:42AM
I11200
JUL 10, 2024 8:40 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 7-10-24 8:37AM
SYSTEM PAPER OUT CLEAR 7-10-24 8:37AM
SYSTEM PAPER OUT ALARM 7-10-24 8:36AM
SYSTEM PRINTER ERROR ALARM 7-10-24 8:36AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-23-24 5:29AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-23-24 4:55AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-17-24 10:08PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-17-24 8:53PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-17-24 12:15PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-17-24 10:35AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-11-24 11:21AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-11-24 11:19AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-04-24 10:44AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-04-24 10:31AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-02-24 11:18AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-02-24 9:48AM
SYSTEM PRINTER ERROR CLEAR 5-02-24 6:01AM
SYSTEM PAPER OUT CLEAR 5-02-24 6:01AM
SYSTEM PRINTER ERROR ALARM 5-02-24 6:00AM
SYSTEM PAPER OUT ALARM 5-02-24 6:00AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 4-29-24 6:33AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 4-29-24 4:25AM
OTHER ISD VAPOR LEAK WARN CLEAR 4-26-24 10:06AM
OTHER ISD VAPOR LEAK WARN ALARM 4-22-24 10:01AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 4-16-24 12:07PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 4-16-24 10:53AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 4-12-24 11:24PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 4-12-24 8:36PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 3-29-24 1:26AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 3-28-24 10:31PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 3-02-24 1:26PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 3-02-24 11:10AM
SYSTEM PRINTER ERROR CLEAR 3-01-24 11:03PM
SYSTEM PAPER OUT CLEAR 3-01-24 11:03PM
SYSTEM PRINTER ERROR ALARM 3-01-24 11:03PM
SYSTEM PAPER OUT ALARM 3-01-24 11:03PM
SYSTEM PRINTER ERROR CLEAR 3-01-24 11:03PM
SYSTEM PAPER OUT CLEAR 3-01-24 11:03PM
SYSTEM PRINTER ERROR ALARM 3-01-24 11:03PM
SYSTEM PAPER OUT ALARM 3-01-24 11:03PM
SYSTEM PRINTER ERROR CLEAR 3-01-24 11:03PM
SYSTEM PAPER OUT CLEAR 3-01-24 11:03PM
SYSTEM PRINTER ERROR ALARM 3-01-24 11:02PM
SYSTEM PAPER OUT ALARM 3-01-24 11:02PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 2-24-24 11:53AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 2-24-24 10:51AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 2-16-24 12:11AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 2-15-24 11:46PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 2-13-24 9:55PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 2-13-24 9:39PM
I20600
JUL 10, 2024 8:40 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUN 25, 2024 11:28 PM
JUN 15, 2024 10:59 PM
JUN 5, 2024 11:32 PM
LOW PRODUCT ALARM MAY 17, 2024 12:06 PM
APR 29, 2024 6:15 AM
APR 12, 2024 10:57 PM
HIGH PRODUCT ALARM APR 1, 2023 11:25 PM
INVALID FUEL LEVEL JAN 22, 2024 9:54 AM
OCT 21, 2023 4:28 PM
OCT 9, 2023 7:33 PM
DELIVERY NEEDED JUN 23, 2024 4:55 AM
MAY 17, 2024 8:53 PM
MAY 17, 2024 10:35 AM
TANK 2 PREMIUM
OVERFILL ALARM JUN 7, 2023 1:08 AM
JUN 7, 2023 12:56 AM
FEB 21, 2023 12:46 PM
TANK 3 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 10, 2024 8:40 AM
I30200
JUL 10, 2024 8:40 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL STP
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:15 AM FUEL ALARM
JUL 20, 2023 10:24 AM SENSOR OUT ALARM
2 UNL FILL
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:33 AM FUEL ALARM
APR 9, 2024 11:37 AM FUEL ALARM
3 UNL ANN
JUL 8, 2024 10:43 AM HIGH LIQUID ALARM
JUL 7, 2024 12:00 PM HIGH LIQUID ALARM
JUL 6, 2024 11:15 AM HIGH LIQUID ALARM
4 PNL STP
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:14 AM FUEL ALARM
JUL 20, 2023 10:48 AM FUEL ALARM
5 PNL FILL
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:35 AM FUEL ALARM
MAR 30, 2024 8:56 AM FUEL ALARM
6 PNL ANN
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:33 AM LOW LIQUID ALARM
JUL 2, 2024 9:33 AM HIGH LIQUID ALARM
7 DSL STP
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:28 AM FUEL ALARM
JUL 2, 2024 9:27 AM FUEL ALARM
8 DSL FILL
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:30 AM FUEL ALARM
APR 14, 2024 4:03 PM FUEL ALARM
9 DSL ANN
JUL 8, 2024 11:36 AM LOW LIQUID ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:30 AM LOW LIQUID ALARM
10 VENT BOX
JUL 2, 2024 9:50 AM FUEL ALARM
JUL 2, 2024 9:49 AM FUEL ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
11 DISP 1-2
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:16 AM FUEL ALARM
JUL 20, 2023 10:24 AM SENSOR OUT ALARM
12 DISP 3-4
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:18 AM FUEL ALARM
JUL 20, 2023 10:24 AM SENSOR OUT ALARM
13 DISP 5-6
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:16 AM FUEL ALARM
JUL 20, 2023 10:24 AM SENSOR OUT ALARM
14 DISP 7-8
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
JUL 2, 2024 9:17 AM FUEL ALARM
JUL 20, 2023 10:24 AM SENSOR OUT ALARM
I31600
JUL 10, 2024 8:40 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP 1-2
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
I40200
JUL 10, 2024 8:40 AM
I40300
JUL 10, 2024 8:40 AM
I34200
JUL 10, 2024 8:40 AM
I34700
JUL 10, 2024 8:40 AM
IV0100
JUL 10, 2024 8:40 AM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-04-26 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-04-25 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-04-24 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-04-23 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-04-22 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-01-28 10:01:11 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.51
24-01-10 10:01:32 A/L RATIO DEGRADATION FP 6 BLEND3 0.78
23-10-22 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.82
23-10-09 10:01:36 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.33
23-09-07 10:01:53 A/L RATIO DEGRADATION FP 4 BLEND3 0.81
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-11-21 10:01:51 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-11-21 10:01:51 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-11-21 10:01:51 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-11-21 10:01:51 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
22-02-16 10:01:43 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-02-15 10:01:38 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-02-14 10:01:38 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-02-07 10:01:50 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-02-01 10:01:56 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-01-25 10:01:56 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-06-09 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY
24-06-08 14:04:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-06-08 14:04:30 ISD STARTUP
24-06-08 14:03:16 ISD SHUTDOWN
24-04-26 10:06:44 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
24-03-08 10:02:09 READINESS ISD:PP EVR:PP ISD & EVR READY
24-03-07 11:58:56 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-03-07 11:58:56 ISD STARTUP
24-03-07 11:58:53 ISD SHUTDOWN
24-03-03 03:00:00 TIME CHANGE DETECTED AT: 24-03-03 02:00:13
Post Alarm History
Responses Received:
I10200
JUL 10, 2024 12:32 PM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 505223 505070
2 4 PROBE / G.T. 163488 163307
3 INTERSTITIAL BD 201193 201080
4 INTERSTITIAL BD 202259 201786
5 UNUSED 9948674 9803741
6 UNUSED 9940113 9790592
7 UNUSED 9939717 9792265
8 UNUSED 9937733 9786844
9 STP SENSE BOARD 33009 33051
10 RELAY BOARD 14882 14880
11 UNUSED 9943077 9795764
12 UNUSED 9938692 9793753
13 UNUSED 9937147 9790492
14 UNUSED 9938859 9787506
15 UNUSED 9939924 9792334
16 UNUSED 9932282 9780201
COMM 1 ELEC DISP INT. 100832 100901
COMM 2 RS232 SERIAL BD 14944 14965
COMM 3 RS232 SERIAL BD 14882 14880
COMM 4 UNUSED 9944706 9795743
COMM 5 UNUSED 9937022 9792143
COMM 6 UNUSED 9934955 9785600
I90200
JUL 10, 2024 12:32 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 10, 2024 12:32 PM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 5 PIPE PNL FILL FUEL ALARM CLEAR 7-10-24 12:10PM
L 5 PIPE PNL FILL FUEL ALARM ALARM 7-10-24 12:09PM
L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L 3 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L 8 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L12 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L14 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L13 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L11 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L 5 PIPE PNL FILL SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L10 PIPE VENT BOX SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L 9 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-10-24 10:53AM
L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L 3 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L10 PIPE VENT BOX SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L 9 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L 8 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L 5 PIPE PNL FILL SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L11 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L12 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L14 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L13 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-10-24 10:53AM
L10 PIPE VENT BOX FUEL ALARM CLEAR 7-10-24 10:51AM
L10 PIPE VENT BOX FUEL ALARM ALARM 7-10-24 10:51AM
L 2 PIPE UNL FILL FUEL ALARM CLEAR 7-10-24 10:46AM
L 2 PIPE UNL FILL FUEL ALARM ALARM 7-10-24 10:46AM
L 5 PIPE PNL FILL FUEL ALARM CLEAR 7-10-24 10:45AM
L 5 PIPE PNL FILL FUEL ALARM ALARM 7-10-24 10:45AM
L 8 PIPE DSL FILL FUEL ALARM CLEAR 7-10-24 10:44AM
L 8 PIPE DSL FILL FUEL ALARM ALARM 7-10-24 10:44AM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 7-10-24 10:43AM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 7-10-24 10:43AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 7-10-24 10:43AM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 7-10-24 10:43AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 7-10-24 10:43AM
L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 7-10-24 10:43AM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 7-10-24 10:43AM
L 6 ANNULAR PNL ANN LOW LIQUID ALARM ALARM 7-10-24 10:43AM
L 6 ANNULAR PNL ANN HIGH LIQUID ALARM CLEAR 7-10-24 10:43AM
L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 7-10-24 10:42AM
L 6 ANNULAR PNL ANN HIGH LIQUID ALARM ALARM 7-10-24 10:42AM
L 3 ANNULAR UNL ANN LOW LIQUID ALARM CLEAR 7-10-24 10:42AM
I11200
JUL 10, 2024 12:32 PM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 7-10-24 8:37AM
SYSTEM PAPER OUT CLEAR 7-10-24 8:37AM
SYSTEM PAPER OUT ALARM 7-10-24 8:36AM
SYSTEM PRINTER ERROR ALARM 7-10-24 8:36AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 6-23-24 5:29AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 6-23-24 4:55AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-17-24 10:08PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-17-24 8:53PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-17-24 12:15PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-17-24 10:35AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-11-24 11:21AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-11-24 11:19AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-04-24 10:44AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-04-24 10:31AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 5-02-24 11:18AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 5-02-24 9:48AM
SYSTEM PRINTER ERROR CLEAR 5-02-24 6:01AM
SYSTEM PAPER OUT CLEAR 5-02-24 6:01AM
SYSTEM PRINTER ERROR ALARM 5-02-24 6:00AM
SYSTEM PAPER OUT ALARM 5-02-24 6:00AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 4-29-24 6:33AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 4-29-24 4:25AM
OTHER ISD VAPOR LEAK WARN CLEAR 4-26-24 10:06AM
OTHER ISD VAPOR LEAK WARN ALARM 4-22-24 10:01AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 4-16-24 12:07PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 4-16-24 10:53AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 4-12-24 11:24PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 4-12-24 8:36PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 3-29-24 1:26AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 3-28-24 10:31PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 3-02-24 1:26PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 3-02-24 11:10AM
SYSTEM PRINTER ERROR CLEAR 3-01-24 11:03PM
SYSTEM PAPER OUT CLEAR 3-01-24 11:03PM
SYSTEM PRINTER ERROR ALARM 3-01-24 11:03PM
SYSTEM PAPER OUT ALARM 3-01-24 11:03PM
SYSTEM PRINTER ERROR CLEAR 3-01-24 11:03PM
SYSTEM PAPER OUT CLEAR 3-01-24 11:03PM
SYSTEM PRINTER ERROR ALARM 3-01-24 11:03PM
SYSTEM PAPER OUT ALARM 3-01-24 11:03PM
SYSTEM PRINTER ERROR CLEAR 3-01-24 11:03PM
SYSTEM PAPER OUT CLEAR 3-01-24 11:03PM
SYSTEM PRINTER ERROR ALARM 3-01-24 11:02PM
SYSTEM PAPER OUT ALARM 3-01-24 11:02PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 2-24-24 11:53AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 2-24-24 10:51AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 2-16-24 12:11AM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 2-15-24 11:46PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 2-13-24 9:55PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 2-13-24 9:39PM
I20600
JUL 10, 2024 12:32 PM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUN 25, 2024 11:28 PM
JUN 15, 2024 10:59 PM
JUN 5, 2024 11:32 PM
LOW PRODUCT ALARM MAY 17, 2024 12:06 PM
APR 29, 2024 6:15 AM
APR 12, 2024 10:57 PM
HIGH PRODUCT ALARM APR 1, 2023 11:25 PM
INVALID FUEL LEVEL JAN 22, 2024 9:54 AM
OCT 21, 2023 4:28 PM
OCT 9, 2023 7:33 PM
DELIVERY NEEDED JUN 23, 2024 4:55 AM
MAY 17, 2024 8:53 PM
MAY 17, 2024 10:35 AM
TANK 2 PREMIUM
OVERFILL ALARM JUN 7, 2023 1:08 AM
JUN 7, 2023 12:56 AM
FEB 21, 2023 12:46 PM
TANK 3 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 10, 2024 12:32 PM
I30200
JUL 10, 2024 12:32 PM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL STP
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:41 AM FUEL ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
2 UNL FILL
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:46 AM FUEL ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
3 UNL ANN
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:42 AM LOW LIQUID ALARM
JUL 10, 2024 10:42 AM HIGH LIQUID ALARM
4 PNL STP
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:41 AM FUEL ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
5 PNL FILL
JUL 10, 2024 12:09 PM FUEL ALARM
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:45 AM FUEL ALARM
6 PNL ANN
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:43 AM LOW LIQUID ALARM
JUL 10, 2024 10:42 AM HIGH LIQUID ALARM
7 DSL STP
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:40 AM FUEL ALARM
JUL 10, 2024 10:40 AM FUEL ALARM
8 DSL FILL
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:44 AM FUEL ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
9 DSL ANN
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:43 AM LOW LIQUID ALARM
JUL 10, 2024 10:43 AM HIGH LIQUID ALARM
10 VENT BOX
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:51 AM FUEL ALARM
JUL 2, 2024 9:50 AM FUEL ALARM
11 DISP 1-2
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:36 AM FUEL ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
12 DISP 3-4
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:37 AM FUEL ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
13 DISP 5-6
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:35 AM FUEL ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
14 DISP 7-8
JUL 10, 2024 10:53 AM SENSOR OUT ALARM
JUL 10, 2024 10:37 AM FUEL ALARM
JUL 2, 2024 9:42 AM SENSOR OUT ALARM
I31600
JUL 10, 2024 12:32 PM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP 1-2
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
I40200
JUL 10, 2024 12:32 PM
I40300
JUL 10, 2024 12:32 PM
I34200
JUL 10, 2024 12:32 PM
I34700
JUL 10, 2024 12:32 PM
IV0100
JUL 10, 2024 12:32 PM
FASTRIP 785
3701 MING AVE
BAKERSFIELD 93309
661-397-3699
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-04-26 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-04-25 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-04-24 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-04-23 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-04-22 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.63
24-01-28 10:01:11 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.51
24-01-10 10:01:32 A/L RATIO DEGRADATION FP 6 BLEND3 0.78
23-10-22 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.82
23-10-09 10:01:36 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.33
23-09-07 10:01:53 A/L RATIO DEGRADATION FP 4 BLEND3 0.81
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-11-21 10:01:51 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-11-21 10:01:51 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-11-21 10:01:51 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-11-21 10:01:51 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
22-02-16 10:01:43 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-02-15 10:01:38 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-02-14 10:01:38 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-02-07 10:01:50 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-02-01 10:01:56 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-01-25 10:01:56 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-06-09 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY
24-06-08 14:04:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-06-08 14:04:30 ISD STARTUP
24-06-08 14:03:16 ISD SHUTDOWN
24-04-26 10:06:44 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
24-03-08 10:02:09 READINESS ISD:PP EVR:PP ISD & EVR READY
24-03-07 11:58:56 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-03-07 11:58:56 ISD STARTUP
24-03-07 11:58:53 ISD SHUTDOWN
24-03-03 03:00:00 TIME CHANGE DETECTED AT: 24-03-03 02:00:13