Secondary Containment Testing Report Form
CERS = California Environmental Reporting System, ICC = International Code Council,
ID = Identification, NA = Not Applicable, UDC = Under-Dispenser Containment,
Page 1 of 5
TYPE OF ACTION ☐ Installation ☐ Repair ☐ 6 Month X 36 Month
CERS ID
10024420
Test Date
6/27/2024
Facility Name
ARCO California
Facility Address
3125 California Ave
City
Bakersfield
ZIP Code
93304
Company Performing the Test
Advanced Compliance
Phone
6617064321
Mailing Address
4007 Brae Burn Dr Bakersfield Ca 93306
Service Technician Performing Test
Bradley Hinsley
Contractor/Tank Tester License Number
971259 ICC Number
8835007
ICC Expiration Date
8/8/2025
Manufacturer and Test Equipment Training Certifications Expiration Date
ICC Service Techican 8/8/2025
INCON STS 10/20/2025
Test Procedures Used Components Tested
PEI/RP1200-19 Sect. 4. Tank Annular
PEI/RP1200-19 Sect. 5. Line Secondary
PEI/RP1200-19 Sect. 6. Containment Sump
I hereby certify that the secondary containment was tested in accordance with California
Code of Regulations, title 23, division 3, chapter 16, section 2637; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
6/27/2024
Total # of Pages
1. FACILITY INFORMATION
2. SERVICE TECHNICIAN INFORMATION
3. TRAINING AND CERTIFICATIONS
4. TEST PROCEDURE INFORMATION
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
Underground Storage Tank
Secondary Containment Testing Report Form
All tests marked “Fail” and any repairs made before or during the tightness test must be described in
the COMMENTS section.
Page 2 of 5
Test Method Developed by ☐ Manufacturer ☐ Industry Standard X Professional Engineer
Test Type ☐ Pressure X Vacuum ☐ Hydrostatic
Test Equipment Used: Annular Test Setup
Tank ID 87Q 87N 91
Tank Manufacturer Unknown Unknown Unknown
Tank Capacity 19,703 10,369 11,849
Test Start Time 08:50 09:10 11:20
Initial Reading -10.00InHg -10.00InHg -10.00InHg
Test End Time 09:50 10:10 12:20
Final Reading -10.00InHg -10.00InHg -10.00InHg
Change in Reading 0.0InHg 0.0InHg 0.0InHg
Pass/Fail Criteria +/- 0.0 InHg +/- 0.0 InHg +/- 0.0 InHg
Tightness Test Results X Pass ☐ Fail X Pass ☐ Fail X Pass ☐ Fail ☐ Pass ☐ Fail
Test Method Developed by ☐ Manufacturer ☐ Industry Standard X Professional Engineer
Test Type X Pressure ☐ Vacuum ☐ Hydrostatic
Test Equipment Used: Piping Secondary Test Setup
Pipe Run ID 87N Product 87Q Product 91 Product 87N-87S Line
Pipe Manufacturer Unknown Unknown Unknown Unknown
Test Start Time 08:25 08:25 08:50 08:25
Initial Reading 5.0 PSI 5.0 PSI 5.0 PSI 5.0 PSI
Test End Time 09:25 09:25 09:50 09:25
Final Reading 5.0 PSI 3.0 PSI 5.0 PSI 5.0 PSI
Change in Reading 0.0 PSI 2.0 PSI 0.0 PSI 0.0 PSI
Pass/Fail Criteria +/- 0.0 PSI +/- 0.0 PSI +/- 0.0 PSI +/- 0.0 PSI
Tightness Test Results X Pass ☐ Fail ☐ Pass X Fail X Pass ☐ Fail X Pass ☐ Fail
Pipe Run ID
Pipe Manufacturer
Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail
Additional copies of this page may be attached.
6. TANK SECONDARY CONTAINMENT TEST
7. PIPE SECONDARY CONTAINMENT TEST
Underground Storage Tank
Secondary Containment Testing Report Form
All tests marked “Fail” and any repairs made before or during the tightness test must be described in
the COMMENTS section.
Page 3 of 5
Test Method Developed by ☐ Manufacturer ☐ Industry Standard X Professional Engineer
Test Type ☐ Pressure ☐ Vacuum X Hydrostatic
Test Equipment Used: INCON STS
Sump/UDC ID 87Q STP 87N STP 91 STP Disp 1/2
Sump Manufacturer Unknown Unknown Unknown Unknown
Sump Depth (inches) 61 61 61 49
Sump Bottom to Top of
Highest Pipe Penetration
(inches)
52 50 52 27
Test Start Time 09:20 09:04 09:50 11:17
Initial Reading 3.0282 4.1040 2.4561 4.9758
Test End Time 09:36 09:19 10:05 11:32
Final Reading 3.0285 4.1041 2.4559 4.9754
Change in Reading 0.0003 0.0001 0.0002 0.0004
Pass/Fail Criteria +/- 0.0020 +/- 0.0020 +/- 0.0020 +/- 0.0020
Tightness Test Results X Pass ☐ Fail X Pass ☐ Fail X Pass ☐ Fail X Pass ☐ Fail
Sump/UDC ID Disp 3/4 Disp 5/6 Disp 7/8 Disp 9/10
Sump Manufacturer Unknown Unknown Unknown Unknown
Sump Depth (inches) 49 49 49 49
Sump Bottom to Top of
Highest Pipe Penetration
(inches)
27 27 27 27
Test Start Time 10:59 10:29 11:49 11:49
Initial Reading 4.6267 7.5435 5.1977 7.4571
Test End Time 11:14 10:44 12:05 12:05
Final Reading 4.6256 7.5435 5.1950 7.4400
Change in Reading 0.0011 0.0000 0.0027 0.0171
Pass/Fail Criteria +/- 0.0020 +/- 0.0020 +/- 0.0020 +/- 0.0020
Tightness Test Results X Pass ☐ Fail X Pass ☐ Fail ☐ Pass X Fail ☐ Pass X Fail
Additional copies of this page may be attached.
8. SUMP/UDC TEST
Underground Storage Tank
Secondary Containment Testing Report Form
All tests marked “Fail” and any repairs made before or during the tightness test must be described in
the COMMENTS section.
Page 4 of 5
Test Method Developed by ☐ Manufacturer ☐ Industry Standard X Professional Engineer
Test Type ☐ Pressure ☐ Vacuum X Hydrostatic
Test Equipment Used: INCON STS
Sump/UDC ID Disp 11/12 Disp 13/14 Disp 15/16 Disp 17/18
Sump Manufacturer Unknown Unknown Unknown Unknown
Sump Depth (inches) 49 49 49 49
Sump Bottom to Top of
Highest Pipe Penetration
(inches)
27 27 27 27
Test Start Time 10:10 13:38 13:18 14:04
Initial Reading 4.6850 3.7454 3.1874 6.0714
Test End Time 10:25 13:53 13:34 14:19
Final Reading 4.6838 3.7456 3.1889 6.0709
Change in Reading 0.0012 0.0002 0.0015 0.0005
Pass/Fail Criteria +/- 0.0020 +/- 0.0020 +/- 0.0020 +/- 0.0020
Tightness Test Results X Pass ☐ Fail X Pass ☐ Fail X Pass ☐ Fail X Pass ☐ Fail
Sump/UDC ID
Sump Manufacturer
Sump Depth (inches)
Sump Bottom to Top of
Highest Pipe Penetration
(inches)
Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail
Additional copies of this page may be attached.
8. SUMP/UDC TEST (continued)
Underground Storage Tank
Secondary Containment Testing Report Form
All tests marked “Fail” and any repairs made before or during the tightness test must be described in
the COMMENTS section.
Page 5 of 5
87Q Product Line, Disp 7/8-9/10 failed, must be repaired and retested.