Loading...
HomeMy WebLinkAboutFairview Rd Bakersfield Final ELD UST System Post Installation Test Report ELD Test Date: Customer: Location: Tested By: CGRS, Inc. 5444 Dry Creek Road Sacramento, CA 95838 Project No:61-27879 BSSR Inc. Independent 6630 Rosedale Hwy #B Bakersfield, CA 93308 300 Fairview Rd Bakersfield, CA 93307 January 24, 2024 ® Location:CGRS Project No : Test Date: CGRS Techs: IOTA Tech Signature: Sergio L. Nunez CA Tank Tester #06-1727 Reviewed by: Chris Murphy Director of CA Services Date Date Diesel Primary Containment System PASS Post Installation ELD Test Results 1/24/2024 1/25/2024 Test Certification Post Installation Enhanced Leak Detection (ELD) January 24, 2024 61-27879 Independent 300 Fairview Rd Bakersfield, CA 93307 Sergio L. Nunez This document certifies that the UST systems listed below at the above referenced location have been tested and passed the iota®VaporTite V005 tightness test.CGRS further certifies that the iota®VaporTite V005 meets the post installation testing requirements for post installation testing for newly installed underground storage tank systems as per the California Health and Safety Code, Chapter 6.7,section 25290.1(j)(1). Final Test Date:IOTA Technicians: Site Information CGRS Project No :61-27879 Installation Contractor Information Facility:Customer Name: Address:Address: City, State, Zip:City, State, Zip: County:Contact: CUPA Email:Phone/Email: Tank No.Capacity (gal.)Product Type Manufacturer Brine Test Result Tank 1 10,000 Diesel DW Fiberglass Total Containment No N/A Tank Top Sumps Diameter (in.)Depth (in.)Volume (gal.)Description Test Result S1 42 50 299.88 DSL TS/FS PASS Junction Boxes with Tank Connection Description Test Result S1 Tank Probe and Turbine J-Box Open During Test PASS UDCs Length (in.)Width (in.)Depth (in.)Volume (gal.)Description Test Result UDC1 25 18 30 58.44 Bravo PASS Transition Sump Length (in.)Width (in.)Depth (in.)Volume (gal.)Description Test Result N/A N/A N/A N/A N/A N/A N/A Product Piping Manufacturer Type Size (in.)Length (ft.) Test Result DSL PL NOV DW Fiberglass 2 45 PASS Vent Piping Manufacturer Type Size (in.)Length (ft.)Test Result DSL Vent NOV DW Fiberglass 2 30 N/A Vapor Piping Manufacturer Type Size (in.)Length (ft.)Test Result N/A N/A N/A N/A N/A N/A Reviewed By Date IOTA Tech Signature Date 1/24/2024 CA License No. 1/25/2024 06-1727 300 Fairview Rd 6630 Rosedale Hwy #B Bakersfield, CA 93308 COMPONENTS IN CONTAINMENT Kern Fidel Carillo hazmatprogram@co.kern.ca.us; laurelf@kerncounty.com; lpreece@bakersfieldfire.us; mwmoore@bakersfieldfire.us; parmagost@bakersfieldfire.us 661-205-2773/fidelbssr@gmail.com Leak Logs / Repair Bakersfield, CA 93307 PIPING TANKS Final ELD Test Project Worksheet 1/24/2024 Independent BSSR Inc. Sergio L. Nunez