HomeMy WebLinkAboutFairview Rd Bakersfield Final ELD UST System Post Installation Test Report
ELD Test Date:
Customer:
Location:
Tested By: CGRS, Inc.
5444 Dry Creek Road
Sacramento, CA 95838
Project No:61-27879
BSSR Inc.
Independent
6630 Rosedale Hwy #B
Bakersfield, CA 93308
300 Fairview Rd
Bakersfield, CA 93307
January 24, 2024
®
Location:CGRS Project No :
Test Date:
CGRS Techs:
IOTA Tech Signature:
Sergio L. Nunez CA Tank Tester #06-1727
Reviewed by:
Chris Murphy Director of CA Services
Date
Date
Diesel Primary Containment System PASS
Post Installation ELD Test Results
1/24/2024
1/25/2024
Test Certification
Post Installation Enhanced Leak Detection (ELD)
January 24, 2024
61-27879
Independent
300 Fairview Rd
Bakersfield, CA 93307
Sergio L. Nunez
This document certifies that the UST systems listed below at the above referenced location have
been tested and passed the iota®VaporTite V005 tightness test.CGRS further certifies that the
iota®VaporTite V005 meets the post installation testing requirements for post installation testing
for newly installed underground storage tank systems as per the California Health and Safety Code,
Chapter 6.7,section 25290.1(j)(1).
Final Test Date:IOTA Technicians:
Site Information CGRS Project No :61-27879 Installation Contractor Information
Facility:Customer Name:
Address:Address:
City, State, Zip:City, State, Zip:
County:Contact:
CUPA Email:Phone/Email:
Tank No.Capacity (gal.)Product Type Manufacturer Brine Test Result
Tank 1 10,000 Diesel DW Fiberglass Total Containment No N/A
Tank Top Sumps Diameter (in.)Depth (in.)Volume (gal.)Description Test Result
S1 42 50 299.88 DSL TS/FS PASS
Junction Boxes with Tank Connection Description Test Result
S1 Tank Probe and Turbine J-Box Open During Test PASS
UDCs Length (in.)Width (in.)Depth (in.)Volume (gal.)Description Test Result
UDC1 25 18 30 58.44 Bravo PASS
Transition Sump Length (in.)Width (in.)Depth (in.)Volume (gal.)Description Test Result
N/A N/A N/A N/A N/A N/A N/A
Product Piping Manufacturer Type Size (in.)Length (ft.) Test Result
DSL PL NOV DW Fiberglass 2 45 PASS
Vent Piping Manufacturer Type Size (in.)Length (ft.)Test Result
DSL Vent NOV DW Fiberglass 2 30 N/A
Vapor Piping Manufacturer Type Size (in.)Length (ft.)Test Result
N/A N/A N/A N/A N/A N/A
Reviewed By Date IOTA Tech Signature Date
1/24/2024
CA License No.
1/25/2024 06-1727
300 Fairview Rd 6630 Rosedale Hwy #B
Bakersfield, CA 93308
COMPONENTS IN CONTAINMENT
Kern Fidel Carillo
hazmatprogram@co.kern.ca.us; laurelf@kerncounty.com; lpreece@bakersfieldfire.us; mwmoore@bakersfieldfire.us; parmagost@bakersfieldfire.us 661-205-2773/fidelbssr@gmail.com
Leak Logs / Repair
Bakersfield, CA 93307
PIPING
TANKS
Final ELD Test Project Worksheet
1/24/2024
Independent BSSR Inc.
Sergio L. Nunez