HomeMy WebLinkAboutFMC 2024Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10137943 7-18-24
Jaco #3366 Fastrip (West)
8001 White Lane Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Rockland Kirk
1073967
10241356 9-29-24
GVR C32654 9-28-24
VMI #5255 #5254 10-3-24
7-18-24 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder-Root TLS-350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 420 UNL ANN
L2 208 UNL FILL
L3 208 UNL STP
L4 420 UNL 2 ANN
L5 208 UNL 2 FILL
L6 208 UNL 2 STP
L7 420 PREM ANN
L8 208 PREM FILL
L9 208 PREM STP
L10 420 DSL ANN
L11 208 DSL FILL
L12 208 DSL STP
L13 208 DISP 1-2
L14 208 DISP 3-4
L15 208 DISP 5-6
L16 208 DISP 7-8
L17 208 DISP 9-10
L18 208 DISP 11-12
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87
T3 FX1V 91
T4 FX1DV DSL
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted. NO PARKINGNO PAR
KING
EXISTING BUILDING
L13
L14
L15L16
L17
L18
L12STP
L9STP
L6STP
L3STP
L10
L7
L4
L1
L11
L8
L5
L2
87-2 UNLEADED
12,000 GALLON87-1 UNLEADED
12,000 GALLON DIESEL12,000 GALLON
1/2
43
65
910
78
12/11
#3-366
#3-367
N
91 PREMIUM12,000 GALLON
V F
87-1 UNLEADED12,000 GALLON
87-2 UNLEADED12,000 GALLON91 PREMIUM12,000 GALLON
DIESEL12,000 GALLON
L5STP
L2STP
L11STP
L14STP
AL6
L1
L10
L13
L7/L8
L3
L12
L15
L9
L18
L17
L16L19
L20
L21
18/17
1516
1314
2122
1920
25/24
L22
PROPERTY LINE
PROPERTY LINEH
W
W
H
PRICE SIGN
PRICE SIGNDIESEL PRICE SIGN
#367
#366
NO PARKINGACCESS RAMPS ACCESSRAMPDUMPSTER
G
A
A
A
V F
V F
F
A A
A
A
A
F
F
F
F
V
V
V
366 LEGEND
L1 87-1 ANNULAR
L2 87-1 FILL
L3 87-1 STP
L4 87-2 ANNULAR
L5 87-2 FILL
L6 87-2 STP
L7 91 ANNULAR
L8 91 FILL
L9 91 STP
L10 DSL ANNULAR
L11 DSL FILL
L12 DSL STP
L13 UDC 1 - 2
L14 UDC 3 - 4
L15 UDC 5 - 6
L16 UDC 7 - 8
L17 UDC 9 - 10
L18 UDC 11 -12
367 LEGEND
L1 87-1 ANNULAR
L2 87-1 STP ANNULAR AND SUMP SENSOR 2-TO-1
L3 87-1 FILL
L5 87-2 STP
L6 87- 2 STP ANNULAR
L7 87-2 FILL
L8 87-2 ANNULAR FILL
L9 87-2 ANNULAR
L10 91 ANNULAR
L11 91 STP
L12 91 FILL
L13 DSL ANNULAR
L14 DSL STP
L15 DSL FILL
L16 UDC 13 - 14
L17 UDC 15 - 16
L18 UDC 17 - 18
L19 UDC 19 -20
L20 UDC 21 -22
L21 UDC 23 - 24
L22 VENT BOX ANNULAR AND SUMP SENSOR 2-TO-1
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3/2 INCH DOUBLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
S1: 87-2 UNLEADED VENT LINE
S2: PRODUCT SIPHON LINE AND VACUUM CHASE
S3: VAPOR RETURN LINE
EMERGENCY SHUT-OFF
OVERFILL ALARM
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
FIRE EXTINGUISHER
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
WH
A
F
V
SITE MAP
DATE REVISIONS
DATE:
DRAWN BY:
CHECKED:
APPROVED:
RAC CADFILE:
SHEET NO.
A.P.N.:385-013-21-4
SCALE:
CONVENIENCE MARKET FOR:
3101 STATE RDBAKERSFIELD, CA 93308
PROJECT OWNER:
DRAWING:
CD
FASTRIPS - 3-366-3-367 3366-MSP
FASTRIP FOOD STORE
BAKERSFIELD, CALIFORNIA 933098001 WHITE LN.
JACO HILL
SITE PLAN
C1
TAB:CERS
1"=15'-0"
INCHES012
SHEET SIZE 22 X 34
01/07/2022
8001 WHITE LN.
BAKERSFIELD, CA 93309
GOSFORD RD.
WHITE LN.
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-097250
CERS ID 10137946
FASTRIPS 3-366 / 3-367
8001 WHITE LN.
BAKERSFIELD, CA 93309
02/12/2021 REV.
VICINITY MAP
PROJECT DATA
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #3366 Fastrip (West)8001 White LaneBakersfield101379431-23-4 5-68791DSL8791879187911-21-23-45-67-87-8ProductProductProductProductProductProductProductProductProductRockland Kirk
APPENDIX C-10
7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB9111-12ProductProduct11-1287919-10ProductProduct9-1087DSL7-8ProductRockland Kirk
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10137943 7-18-24
Jaco #3366 Fastrip (West)
8001 White Lane Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Rockland Kirk
1073967
10241356 9-29-24
OPW 1193547 2-15-25
RP1200 Spill buckets
7-18-24 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1 87
OPW
T2 87-2
OPW
T3 91
OPW
T4 DSL
OPW
Responses Received:
200
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
JUL 18, 2024 9:17 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 9604 82.42 1.5 82.3 2458
2 UNLEADED 2 9728 83.45 0.0 82.8 2334
3 PREMIUM 7342 65.02 0.0 82.8 4720
4 DIESEL 4319 43.02 1.2 85.9 7743
I90500
JUL 18, 2024 9:17 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JUL 18, 2024 9:17 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUL 18, 2024 9:17 AM
SHIFT TIME 1 : DISABLED
I50202
JUL 18, 2024 9:17 AM
SHIFT TIME 2 : DISABLED
I50203
JUL 18, 2024 9:17 AM
SHIFT TIME 3 : DISABLED
I50204
JUL 18, 2024 9:17 AM
SHIFT TIME 4 : DISABLED
I54600
JUL 18, 2024 9:17 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUL 18, 2024 9:17 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUL 18, 2024 9:17 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUL 18, 2024 9:17 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUL 18, 2024 9:17 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUL 18, 2024 9:17 AM
PRINT TC VOLUMES
ENABLED
I50E00
JUL 18, 2024 9:17 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUL 18, 2024 9:17 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUL 18, 2024 9:17 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUL 18, 2024 9:17 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUL 18, 2024 9:17 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUL 18, 2024 9:17 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUL 18, 2024 9:18 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUL 18, 2024 9:18 AM
TANK CHART SECURITY
DISABLED
I5BD00
JUL 18, 2024 9:18 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JUL 18, 2024 9:18 AM
MASS/DENSITY
DISABLED
I88101
JUL 18, 2024 9:18 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JUL 18, 2024 9:18 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
JUL 18, 2024 9:18 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JUL 18, 2024 9:18 AM
I88105
JUL 18, 2024 9:18 AM
I88106
JUL 18, 2024 9:18 AM
I52000
JUL 18, 2024 9:18 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE FEB 23, 2012 DISABLED
2 ON DATE FEB 23, 2012 DISABLED
3 ON DATE FEB 23, 2012 DISABLED
4 ON DATE FEB 23, 2012 DISABLED
5 ON DATE FEB 23, 2012 DISABLED
6 ON DATE FEB 23, 2012 DISABLED
7 ON DATE FEB 23, 2012 DISABLED
8 ON DATE FEB 23, 2012 DISABLED
I60100
JUL 18, 2024 9:18 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 UNLEADED 2 ON
3 PREMIUM ON
4 DIESEL ON
I60200
JUL 18, 2024 9:18 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 UNLEADED 2
3 PREMIUM
4 DIESEL
I60300
JUL 18, 2024 9:18 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 UNLEADED 2 2
3 PREMIUM 3
4 DIESEL 4
I60900
JUL 18, 2024 9:18 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 UNLEADED 2 0.000700
3 PREMIUM 0.000700
4 DIESEL 0.000450
I60700
JUL 18, 2024 9:18 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 111.00
2 UNLEADED 2 111.00
3 PREMIUM 111.00
4 DIESEL 111.00
I60A00
JUL 18, 2024 9:18 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
1 PT 12062 2 UNLEADED 2 1 PT 12062 3
PREMIUM 1 PT 12062 4 DIESEL 1 PT
12062
I60400
JUL 18, 2024 9:18 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062
2 UNLEADED 2 12062
3 PREMIUM 12062
4 DIESEL 12062
I60500
JUL 18, 2024 9:18 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062 0 0 0
2 UNLEADED 2 12062 0 0 0
3 PREMIUM 12062 0 0 0
4 DIESEL 12062 0 0 0
I60600
JUL 18, 2024 9:18 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 UNLEADED 2 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 PREMIUM 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 DIESEL 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUL 18, 2024 9:18 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 UNLEADED 2 NO
3 PREMIUM NO
4 DIESEL NO
I62F00
JUL 18, 2024 9:18 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN.
2 UNLEADED 2 3.0 IN.
3 PREMIUM 4.0 IN.
4 DIESEL 4.0 IN.
I62700
JUL 18, 2024 9:18 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 UNLEADED 2 2.0
3 PREMIUM 2.0
4 DIESEL 2.0
I64200
JUL 18, 2024 9:18 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 UNLEADED 2 LOW
3 PREMIUM LOW
4 DIESEL LOW
I62400
JUL 18, 2024 9:18 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 UNLEADED 2 3.0
3 PREMIUM 3.0
4 DIESEL 4.0
I62800
JUL 18, 2024 9:18 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062
2 UNLEADED 2 12062
3 PREMIUM 12062
4 DIESEL 12062
I62300
JUL 18, 2024 9:18 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10856
2 UNLEADED 2 10856
3 PREMIUM 10856
4 DIESEL 10856
I62200
JUL 18, 2024 9:18 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11459
2 UNLEADED 2 11459
3 PREMIUM 11459
4 DIESEL 11459
I62900
JUL 18, 2024 9:18 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 482
2 UNLEADED 2 1800
3 PREMIUM 1689
4 DIESEL 1800
I62100
JUL 18, 2024 9:18 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 500
2 UNLEADED 2 500
3 PREMIUM 500
4 DIESEL 500
I62600
JUL 18, 2024 9:18 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 UNLEADED 2 99
3 PREMIUM 99
4 DIESEL 99
I62500
JUL 18, 2024 9:18 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 UNLEADED 2 99
3 PREMIUM 99
4 DIESEL 99
I60800
JUL 18, 2024 9:18 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 UNLEADED 2 0.00
3 PREMIUM 0.00
4 DIESEL 0.00
I60B00
JUL 18, 2024 9:18 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUL 18, 2024 9:18 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 UNLEADED 2 0.00
3 PREMIUM 0.00
4 DIESEL 0.00
I61200
JUL 18, 2024 9:18 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED 2 NONE
2 UNLEADED 2 1 NONE
3 PREMIUM NONE NONE
4 DIESEL NONE NONE
I63600
JUL 18, 2024 9:18 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 UNLEADED 2 120
3 PREMIUM 120
4 DIESEL 120
I62A00
JUL 18, 2024 9:18 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 UNLEADED 2 120
3 PREMIUM 120
4 DIESEL 120
I62C00
JUL 18, 2024 9:18 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 UNLEADED 2 STANDARD
3 PREMIUM STANDARD
4 DIESEL STANDARD
I62D00
JUL 18, 2024 9:18 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 UNLEADED 2 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUL 18, 2024 9:18 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 UNLEADED 2 OFF OFF
3 PREMIUM OFF OFF
4 DIESEL OFF OFF
I63000
JUL 18, 2024 9:18 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 UNLEADED 2 OFF
3 PREMIUM OFF
4 DIESEL OFF
I63200
JUL 18, 2024 9:18 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 UNLEADED 2 OFF
3 PREMIUM OFF
4 DIESEL OFF
I61000
JUL 18, 2024 9:18 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 UNLEADED 2 1
3 PREMIUM 1
4 DIESEL 1
I63A00
JUL 18, 2024 9:18 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 UNLEADED 2 10.00%
3 PREMIUM 10.00%
4 DIESEL 10.00%
I61100
JUL 18, 2024 9:18 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JUL 23, 2010
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
JUL 18, 2024 9:18 AM
CSLD PROBABLITY OF DETECTION
I61400
JUL 18, 2024 9:18 AM
CSLD CLIMATE FACTOR
I61600
JUL 18, 2024 9:18 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 UNLEADED 2 IMMEDIATE
3 PREMIUM IMMEDIATE
4 DIESEL IMMEDIATE
I61A00
JUL 18, 2024 9:18 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED
2 UNLEADED 2 DISABLED
3 PREMIUM DISABLED
4 DIESEL DISABLED
I61B00
JUL 18, 2024 9:18 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JUL 18, 2024 9:18 AM
CSLD REPORT ONLY
I62B00
JUL 18, 2024 9:18 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 UNLEADED 2 ??? 0, 0
3 PREMIUM ??? 0, 0
4 DIESEL ??? 0, 0
I63300
JUL 18, 2024 9:18 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUL 18, 2024 9:18 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 UNLEADED 2 0
3 PREMIUM 0
4 DIESEL 0
I63500
JUL 18, 2024 9:18 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 UNLEADED 2 1
3 PREMIUM 1
4 DIESEL 1
I63900
JUL 18, 2024 9:18 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 UNLEADED 2
END FACTOR: NONE
3 PREMIUM
END FACTOR: NONE
4 DIESEL
END FACTOR: NONE
I78000
JUL 18, 2024 9:18 AM
I77700
JUL 18, 2024 9:18 AM
I77800
JUL 18, 2024 9:18 AM
I78C00
JUL 18, 2024 9:18 AM
I78300
JUL 18, 2024 9:18 AM
I78F00
JUL 18, 2024 9:18 AM
I78700
JUL 18, 2024 9:18 AM
I70200
JUL 18, 2024 9:18 AM
LIQUID LABEL
DEVICE LABEL
1 UNL ANN
2 UNL FILL
3 UNL STP
4 UNL 2 ANN
5 UNLD 2 FILL
6 UNL 2 STP
7 PREM ANN
8 PREM FILL
9 PREM STP
10 DSL ANN
11 DSL FILL
12 DSL STP
13 DISP 1-2
14 DISP 3 4
15 DISP 5-6
16 DISP 7-8
17 DISP 9-10
18 DISP 11-12
19
20
21
22
23
24
I70300
JUL 18, 2024 9:18 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL ANN TRI-STATE (SINGLE FLOAT)
2 UNL FILL TRI-STATE (SINGLE FLOAT)
3 UNL STP TRI-STATE (SINGLE FLOAT)
4 UNL 2 ANN TRI-STATE (SINGLE FLOAT)
5 UNLD 2 FILL TRI-STATE (SINGLE FLOAT)
6 UNL 2 STP TRI-STATE (SINGLE FLOAT)
7 PREM ANN TRI-STATE (SINGLE FLOAT)
8 PREM FILL TRI-STATE (SINGLE FLOAT)
9 PREM STP TRI-STATE (SINGLE FLOAT)
10 DSL ANN TRI-STATE (SINGLE FLOAT)
11 DSL FILL TRI-STATE (SINGLE FLOAT)
12 DSL STP TRI-STATE (SINGLE FLOAT)
13 DISP 1-2 TRI-STATE (SINGLE FLOAT)
14 DISP 3 4 TRI-STATE (SINGLE FLOAT)
15 DISP 5-6 TRI-STATE (SINGLE FLOAT)
16 DISP 7-8 TRI-STATE (SINGLE FLOAT)
17 DISP 9-10 TRI-STATE (SINGLE FLOAT)
18 DISP 11-12 TRI-STATE (SINGLE FLOAT)
19 TRI-STATE (SINGLE FLOAT)
20 TRI-STATE (SINGLE FLOAT)
21 TRI-STATE (SINGLE FLOAT)
22 TRI-STATE (SINGLE FLOAT)
23 TRI-STATE (SINGLE FLOAT)
24 TRI-STATE (SINGLE FLOAT)
I70400
JUL 18, 2024 9:18 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL ANN ANNULAR SPACE
2 UNL FILL PIPING SUMP
3 UNL STP STP SUMP
4 UNL 2 ANN ANNULAR SPACE
5 UNLD 2 FILL PIPING SUMP
6 UNL 2 STP STP SUMP
7 PREM ANN ANNULAR SPACE
8 PREM FILL PIPING SUMP
9 PREM STP STP SUMP
10 DSL ANN ANNULAR SPACE
11 DSL FILL PIPING SUMP
12 DSL STP STP SUMP
13 DISP 1-2 DISPENSER PAN
14 DISP 3 4 DISPENSER PAN
15 DISP 5-6 DISPENSER PAN
16 DISP 7-8 DISPENSER PAN
17 DISP 9-10 DISPENSER PAN
18 DISP 11-12 DISPENSER PAN
19 OTHER SENSORS
20 OTHER SENSORS
21 OTHER SENSORS
22 OTHER SENSORS
23 OTHER SENSORS
24 OTHER SENSORS
I74200
JUL 18, 2024 9:18 AM
I74300
JUL 18, 2024 9:18 AM
I74400
JUL 18, 2024 9:18 AM
I74700
JUL 18, 2024 9:18 AM
I74800
JUL 18, 2024 9:18 AM
I74900
JUL 18, 2024 9:18 AM
I7BC00
JUL 18, 2024 9:18 AM
I80200
JUL 18, 2024 9:18 AM
I80300
JUL 18, 2024 9:18 AM
I80400
JUL 18, 2024 9:18 AM
I80700
JUL 18, 2024 9:18 AM
RELAY LABEL
DEVICE LABEL
1 SHUTDOWN
2 OVERFILL ALARM
3 INTERNAL ALARM
4
I80900
JUL 18, 2024 9:18 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 SHUTDOWN NORMALLY CLOSED
2 OVERFILL ALARM NORMALLY OPEN
3 INTERNAL ALARM NORMALLY OPEN
4 NORMALLY OPEN
I80B00
JUL 18, 2024 9:18 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 SHUTDOWN 3
2 OVERFILL ALARM NONE
3 INTERNAL ALARM NONE
4 NONE
I80A00
JUL 18, 2024 9:18 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 SHUTDOWN STANDARD
2 OVERFILL ALARM STANDARD
3 INTERNAL ALARM MOMENTARY
4 STANDARD
I80C00
JUL 18, 2024 9:18 AM
I80800
JUL 18, 2024 9:18 AM
RELAY SETUP REPORT
R 1:SHUTDOWN
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 3
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 6:FUEL ALARM
L 9:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L15:FUEL ALARM
L16:FUEL ALARM
L17:FUEL ALARM
L18:FUEL ALARM
L 3:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L16:SENSOR OUT ALARM
L17:SENSOR OUT ALARM
L18:SENSOR OUT ALARM
L 3:SHORT ALARM
L 6:SHORT ALARM
L 9:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
L15:SHORT ALARM
L16:SHORT ALARM
L17:SHORT ALARM
L18:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 3:INTERNAL ALARM
TYPE:
MOMENTARY
NORMALLY OPEN
IN-TANK ALARMS
ALL:LEAK ALARM
ALL:HIGH WATER ALARM
ALL:OVERFILL ALARM
ALL:LOW PRODUCT ALARM
ALL:SUDDEN LOSS ALARM
ALL:HIGH PRODUCT ALARM
ALL:INVALID FUEL LEVEL
ALL:PROBE OUT
ALL:HIGH WATER WARNING
ALL:DELIVERY NEEDED
ALL:MAX PRODUCT ALARM
ALL:GROSS TEST FAIL
ALL:PERIODIC TEST FAIL
ALL:ANNUAL TEST FAIL
ALL:PER TST NEEDED WRN
ALL:ANN TST NEEDED WRN
ALL:PER TST NEEDED ALM
ALL:ANN TST NEEDED ALM
ALL:TANK TEST ACTIVE
ALL:NO CSLD IDLE TIME
ALL:TANK SIPHON BREAK
ALL:LOW TEMP WARNING
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
SMARTSENSOR ALARMS
ALL:SETUP DATA WARNING
ALL:COMMUNICATION ALARM
ALL:SENSOR FAULT ALARM
ALL:FUEL WARNING
ALL:FUEL ALARM
ALL:WATER WARNING
ALL:WATER ALARM
ALL:HIGH LIQUID WARNING
ALL:HIGH LIQUID ALARM
ALL:LOW LIQUID WARNING
ISD SITE ALARMS
ISD STAGE I WARN
ISD GROSS PRES WARN
ISD GROSS PRES FAIL
ISD DEGRD PRES WARN
ISD DEGRD PRES FAIL
ISD VAPOR LEAK WARN
ISD VAPOR LEAK FAIL
ISD VP PRES WARN
ISD VP PRES FAIL
ISD VP STATUS WARN
ISD VP STATUS FAIL
MISSING RELAY SETUP
MISSING HOSE SETUP
MISSING TANK SETUP
MISS VAPOR FLOW MTR
MISS VAPOR PRES SEN
MISSING VP INPUT
ISD SETUP WARN
ISD SETUP FAIL
ISD SENSOR OUT WARN
ISD SENSOR OUT FAIL
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
JUL 18, 2024 9:19 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
JUL 18, 2024 9:19 AM
I72300
JUL 18, 2024 9:19 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 PS 11-12 VAPOR PRESSURE
02 FM 1-2 AIR FLOW METER
03 FM 3-4 AIR FLOW METER
04 FM 5-6 AIR FLOW METER
05 FM 7-8 AIR FLOW METER
06 FM 9-10 AIR FLOW METER
07 FM 11-12 AIR FLOW METER
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JUL 18, 2024 9:19 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
JUL 18, 2024 9:19 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JUL 18, 2024 9:19 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
VAPOR PROCESSOR TYPE
NONE
IV4700
JUL 18, 2024 9:19 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JUL 18, 2024 9:19 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ACCEPT HIGH ORVR: NO
IV4A00
JUL 18, 2024 9:19 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 01 BLEND3
02 02 02 01 01 BLEND3
03 03 03 02 01 BLEND3
04 04 04 02 01 BLEND3
05 05 05 03 01 BLEND3
06 06 06 03 01 BLEND3
07 07 07 04 01 BLEND3
08 08 08 04 01 BLEND3
09 09 09 05 01 BLEND3
10 10 10 05 01 BLEND3
11 11 11 06 01 BLEND3
12 12 12 06 01 BLEND3
IV4B00
JUL 18, 2024 9:19 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
09 05 02/09 03/09 09/09 xx/xx
10 05 02/10 03/10 09/10 xx/xx
11 06 02/11 03/11 09/11 xx/xx
12 06 02/12 03/12 09/12 xx/xx
IV4900
JUL 18, 2024 9:19 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JUL 18, 2024 9:19 AM
ISD VERSION: 01.07
Responses Received:
I10200
JUL 18, 2024 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39395 39266
2 4 PROBE / G.T. 163529 162792
3 INTERSTITIAL BD 201924 201056
4 INTERSTITIAL BD 201901 201101
5 INTERSTITIAL BD 201060 200245
6 UNUSED 9661155 9385646
7 UNUSED 9644453 9380208
8 UNUSED 9643221 9381438
9 UNUSED 9638633 9381576
10 RELAY BOARD 14922 14891
11 UNUSED 9641842 9382957
12 UNUSED 9636678 9386151
13 UNUSED 9641927 9380583
14 UNUSED 9635913 9376505
15 UNUSED 9631239 9380648
16 UNUSED 9633619 9379137
COMM 1 ELEC DISP INT. 100982 100656
COMM 2 RS232 SERIAL BD 15007 14978
COMM 3 RS232 SERIAL BD 15007 14978
COMM 4 UNUSED 9648981 9383885
COMM 5 UNUSED 9632131 9377584
COMM 6 UNUSED 9631664 9380885
I90200
JUL 18, 2024 9:16 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 18, 2024 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 1 ANNULAR UNL ANN FUEL ALARM CLEAR 7-10-24 1:20PM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 3 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 8 PIPE PREM FILL SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 7 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 6 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L10 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 1 ANNULAR UNL ANN FUEL ALARM ALARM 7-10-24 1:12PM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 5 PIPE UNLD 2 FILL SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L14 DISP PAN DISP 3 4 SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L11 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L12 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 9 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L13 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-10-24 1:12PM
L 8 PIPE PREM FILL SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L 7 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L 6 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L 3 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L10 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L14 DISP PAN DISP 3 4 SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L 5 PIPE UNLD 2 FILL SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L12 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L11 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L 9 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-10-24 1:12PM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-10-24 1:11PM
L 1 ANNULAR UNL ANN FUEL ALARM CLEAR 7-10-24 1:11PM
L13 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-10-24 1:11PM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-10-24 1:11PM
L 1 ANNULAR UNL ANN FUEL ALARM ALARM 7-10-24 12:56PM
L13 DISP PAN DISP 1-2 FUEL ALARM CLEAR 7-10-24 12:31PM
L13 DISP PAN DISP 1-2 FUEL ALARM ALARM 7-10-24 11:53AM
L13 DISP PAN DISP 1-2 FUEL ALARM CLEAR 7-10-24 11:28AM
L13 DISP PAN DISP 1-2 FUEL ALARM ALARM 7-10-24 11:15AM
L 2 PIPE UNL FILL FUEL ALARM CLEAR 7-10-24 11:00AM
L 2 PIPE UNL FILL FUEL ALARM ALARM 7-10-24 10:57AM
L 5 PIPE UNLD 2 FILL FUEL ALARM CLEAR 7-10-24 10:57AM
L 5 PIPE UNLD 2 FILL FUEL ALARM ALARM 7-10-24 10:57AM
L 8 PIPE PREM FILL FUEL ALARM CLEAR 7-10-24 10:57AM
L 8 PIPE PREM FILL FUEL ALARM ALARM 7-10-24 10:55AM
I11200
JUL 18, 2024 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM CLEAR 6-19-24 6:11AM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM ALARM 6-19-24 6:01AM
SYSTEM PRINTER ERROR CLEAR 6-04-24 4:46AM
SYSTEM PAPER OUT CLEAR 6-04-24 4:46AM
SYSTEM PAPER OUT ALARM 6-04-24 4:45AM
SYSTEM PRINTER ERROR ALARM 6-04-24 4:45AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 5-08-24 12:22PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 5-06-24 10:02AM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM CLEAR 4-20-24 6:44PM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM ALARM 4-20-24 6:23PM
OTHER ISD GROSS PRES WARN CLEAR 4-15-24 2:04PM
OTHER ISD GROSS PRES WARN ALARM 4-15-24 10:01AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 4-11-24 2:35PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 4-11-24 2:35PM
OTHER ISD GROSS PRES WARN CLEAR 4-08-24 10:20AM
SYSTEM PRINTER ERROR CLEAR 4-08-24 4:06AM
SYSTEM PAPER OUT CLEAR 4-08-24 4:06AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 4-07-24 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 4-07-24 10:01AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 4-06-24 10:00AM
SYSTEM PRINTER ERROR ALARM 4-06-24 5:37AM
SYSTEM PAPER OUT ALARM 4-06-24 5:37AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 4-05-24 10:01AM
OTHER ISD GROSS PRES WARN ALARM 4-03-24 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 3-27-24 10:51AM
OTHER ISD GROSS PRES WARN ALARM 3-27-24 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 3-20-24 10:00AM
OTHER ISD GROSS PRES WARN ALARM 3-13-24 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 3-06-24 11:08AM
OTHER ISD GROSS PRES WARN ALARM 3-06-24 10:01AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 2-24-24 10:00AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 2-21-24 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 1-25-24 10:27AM
OTHER ISD GROSS PRES WARN ALARM 1-25-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 1-17-24 10:07AM
OTHER ISD GROSS PRES WARN ALARM 1-17-24 10:02AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 1-11-24 10:49AM
SYSTEM PRINTER ERROR CLEAR 1-09-24 10:02AM
SYSTEM PAPER OUT CLEAR 1-09-24 10:02AM
SYSTEM PRINTER ERROR ALARM 1-09-24 10:02AM
SYSTEM PAPER OUT ALARM 1-09-24 10:02AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 1-07-24 10:02AM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM CLEAR 1-01-24 9:03AM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM ALARM 1-01-24 8:58AM
OTHER ISD GROSS PRES WARN CLEAR 12-21-23 10:08AM
OTHER ISD GROSS PRES WARN ALARM 12-21-23 10:02AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 10:00AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 12-06-23 10:03AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 10:00AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 11-22-23 10:02AM
I20600
JUL 18, 2024 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUN 21, 2024 5:16 AM
MAY 17, 2024 5:13 AM
MAY 14, 2024 1:14 AM
HIGH PRODUCT ALARM OCT 5, 2023 12:28 AM
TANK 2 UNLEADED 2
OVERFILL ALARM JUN 21, 2024 5:23 AM
JUN 19, 2024 5:59 AM
JUN 15, 2024 2:17 PM
HIGH PRODUCT ALARM JUN 19, 2024 6:01 AM
APR 20, 2024 6:23 PM
JAN 1, 2024 8:58 AM
PROBE OUT MAR 7, 2024 5:44 AM
MAR 6, 2024 12:57 PM
MAR 6, 2024 12:56 PM
TANK 3 PREMIUM
OVERFILL ALARM APR 9, 2024 6:00 AM
NOV 5, 2022 2:16 AM
TANK 4 DIESEL
LOW PRODUCT ALARM FEB 13, 2021 8:05 AM
DELIVERY NEEDED SEP 3, 2022 8:31 AM
MAY 24, 2022 9:25 AM
FEB 13, 2021 8:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 18, 2024 9:16 AM
I30200
JUL 18, 2024 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL ANN
JUL 10, 2024 1:12 PM FUEL ALARM
JUL 10, 2024 1:11 PM SENSOR OUT ALARM
JUL 10, 2024 12:56 PM FUEL ALARM
2 UNL FILL
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:57 AM FUEL ALARM
MAR 20, 2024 11:40 AM FUEL ALARM
3 UNL STP
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:42 AM FUEL ALARM
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
4 UNL 2 ANN
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:47 AM FUEL ALARM
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
5 UNLD 2 FILL
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:57 AM FUEL ALARM
MAR 19, 2024 8:08 PM FUEL ALARM
6 UNL 2 STP
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:42 AM FUEL ALARM
MAR 5, 2024 12:18 PM FUEL ALARM
7 PREM ANN
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:48 AM FUEL ALARM
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
8 PREM FILL
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:55 AM FUEL ALARM
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
9 PREM STP
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:43 AM FUEL ALARM
MAR 5, 2024 6:49 PM FUEL ALARM
10 DSL ANN
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:49 AM FUEL ALARM
JUL 25, 2023 9:52 AM SENSOR OUT ALARM
11 DSL FILL
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:53 AM FUEL ALARM
FEB 2, 2024 1:27 AM FUEL ALARM
12 DSL STP
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:43 AM FUEL ALARM
JUL 10, 2024 10:37 AM FUEL ALARM
13 DISP 1-2
JUL 10, 2024 1:11 PM SENSOR OUT ALARM
JUL 10, 2024 11:53 AM FUEL ALARM
JUL 10, 2024 11:15 AM FUEL ALARM
14 DISP 3 4
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:44 AM FUEL ALARM
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
15 DISP 5-6
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:45 AM FUEL ALARM
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
16 DISP 7-8
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:45 AM FUEL ALARM
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
17 DISP 9-10
JUL 10, 2024 1:11 PM SENSOR OUT ALARM
JUL 10, 2024 10:46 AM FUEL ALARM
JUL 25, 2023 9:52 AM SENSOR OUT ALARM
18 DISP 11-12
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
JUL 10, 2024 10:46 AM FUEL ALARM
JUL 25, 2023 9:52 AM SENSOR OUT ALARM
I31600
JUL 18, 2024 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 11-12
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
JUN 23, 2024 12:44 PM COMMUNICATION ALARM
6 FM 9-10
JUL 20, 2022 5:02 PM COMMUNICATION ALARM
JUL 20, 2022 3:11 PM COMMUNICATION ALARM
JUL 20, 2022 12:29 PM COMMUNICATION ALARM
7 FM 11-12
I40200
JUL 18, 2024 9:16 AM
I40300
JUL 18, 2024 9:16 AM
I34200
JUL 18, 2024 9:16 AM
I34700
JUL 18, 2024 9:16 AM
IV0100
JUL 18, 2024 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-05-08 10:01:40 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
24-05-07 10:01:35 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
24-05-06 10:02:00 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
24-04-15 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
24-04-11 10:01:09 A/L RATIO DEGRADATION FP 9 BLEND3 0.78
24-04-11 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 1.48
24-04-10 10:01:09 A/L RATIO DEGRADATION FP 9 BLEND3 0.77
24-04-10 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 1.48
24-04-09 10:01:09 A/L RATIO DEGRADATION FP 9 BLEND3 0.76
24-04-09 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 1.46
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
24-03-20 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-03-31 10:02:22 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
22-08-06 10:01:53 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-08-03 10:01:09 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-02-13 10:01:35 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
21-04-19 10:02:18 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
20-10-23 10:01:58 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD
20-10-23 10:01:58 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD
20-10-17 10:02:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
20-06-14 10:01:09 A/L RATIO GROSS BLOCKAGE FP10 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-07-11 10:03:35 READINESS ISD:PP EVR:PP ISD & EVR READY
24-07-10 13:11:20 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-07-10 13:11:20 ISD STARTUP
24-07-10 13:11:06 ISD SHUTDOWN
24-05-08 12:22:04 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED
24-04-15 14:04:45 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-04-15 13:54:45 PUMPS MANUALLY RE-ENABLED
24-04-11 14:35:32 COLLECTION TEST HH09 GRADE TEST MANUALLY CLEARED
24-04-11 14:35:17 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED
24-04-08 10:20:15 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
Responses Received:
I10200
JUL 18, 2024 12:03 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39395 39309
2 4 PROBE / G.T. 163529 163074
3 INTERSTITIAL BD 201924 201426
4 INTERSTITIAL BD 201901 201358
5 INTERSTITIAL BD 201060 200413
6 UNUSED 9661155 9419261
7 UNUSED 9644453 9412679
8 UNUSED 9643221 9412895
9 UNUSED 9638633 9413960
10 RELAY BOARD 14922 14891
11 UNUSED 9641842 9414715
12 UNUSED 9636678 9417391
13 UNUSED 9641927 9414888
14 UNUSED 9635913 9414758
15 UNUSED 9631239 9414629
16 UNUSED 9633619 9410874
COMM 1 ELEC DISP INT. 100982 100874
COMM 2 RS232 SERIAL BD 15007 14999
COMM 3 RS232 SERIAL BD 15007 14978
COMM 4 UNUSED 9648981 9413830
COMM 5 UNUSED 9632131 9413571
COMM 6 UNUSED 9631664 9415945
I90200
JUL 18, 2024 12:03 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 18, 2024 12:03 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L13 DISP PAN DISP 1-2 FUEL ALARM CLEAR 7-18-24 11:06AM
L13 DISP PAN DISP 1-2 FUEL ALARM ALARM 7-18-24 10:56AM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L 3 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L 8 PIPE PREM FILL SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L 7 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L 6 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L 5 PIPE UNLD 2 FILL SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L14 DISP PAN DISP 3 4 SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L12 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L11 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L10 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-18-24 10:00AM
L13 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-18-24 9:59AM
L 9 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-18-24 9:59AM
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-18-24 9:59AM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-18-24 9:59AM
L14 DISP PAN DISP 3 4 SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L 8 PIPE PREM FILL SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L 7 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L 6 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L12 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L11 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L 3 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L10 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L 5 PIPE UNLD 2 FILL SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L13 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-18-24 9:59AM
L 9 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-18-24 9:58AM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-18-24 9:58AM
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-18-24 9:58AM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-18-24 9:58AM
L 7 ANNULAR PREM ANN FUEL ALARM CLEAR 7-18-24 9:50AM
L10 ANNULAR DSL ANN FUEL ALARM CLEAR 7-18-24 9:50AM
L10 ANNULAR DSL ANN FUEL ALARM ALARM 7-18-24 9:50AM
L 7 ANNULAR PREM ANN FUEL ALARM ALARM 7-18-24 9:50AM
L 7 ANNULAR PREM ANN FUEL ALARM CLEAR 7-18-24 9:50AM
L10 ANNULAR DSL ANN FUEL ALARM CLEAR 7-18-24 9:50AM
L 7 ANNULAR PREM ANN FUEL ALARM ALARM 7-18-24 9:50AM
L10 ANNULAR DSL ANN FUEL ALARM ALARM 7-18-24 9:50AM
L 7 ANNULAR PREM ANN FUEL ALARM CLEAR 7-18-24 9:50AM
L 7 ANNULAR PREM ANN FUEL ALARM ALARM 7-18-24 9:49AM
L 1 ANNULAR UNL ANN FUEL ALARM CLEAR 7-18-24 9:48AM
L 1 ANNULAR UNL ANN FUEL ALARM ALARM 7-18-24 9:48AM
I11200
JUL 18, 2024 12:03 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM CLEAR 6-19-24 6:11AM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM ALARM 6-19-24 6:01AM
SYSTEM PRINTER ERROR CLEAR 6-04-24 4:46AM
SYSTEM PAPER OUT CLEAR 6-04-24 4:46AM
SYSTEM PAPER OUT ALARM 6-04-24 4:45AM
SYSTEM PRINTER ERROR ALARM 6-04-24 4:45AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 5-08-24 12:22PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 5-06-24 10:02AM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM CLEAR 4-20-24 6:44PM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM ALARM 4-20-24 6:23PM
OTHER ISD GROSS PRES WARN CLEAR 4-15-24 2:04PM
OTHER ISD GROSS PRES WARN ALARM 4-15-24 10:01AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 4-11-24 2:35PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 4-11-24 2:35PM
OTHER ISD GROSS PRES WARN CLEAR 4-08-24 10:20AM
SYSTEM PRINTER ERROR CLEAR 4-08-24 4:06AM
SYSTEM PAPER OUT CLEAR 4-08-24 4:06AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 4-07-24 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 4-07-24 10:01AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 4-06-24 10:00AM
SYSTEM PRINTER ERROR ALARM 4-06-24 5:37AM
SYSTEM PAPER OUT ALARM 4-06-24 5:37AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 4-05-24 10:01AM
OTHER ISD GROSS PRES WARN ALARM 4-03-24 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 3-27-24 10:51AM
OTHER ISD GROSS PRES WARN ALARM 3-27-24 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 3-20-24 10:00AM
OTHER ISD GROSS PRES WARN ALARM 3-13-24 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 3-06-24 11:08AM
OTHER ISD GROSS PRES WARN ALARM 3-06-24 10:01AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 2-24-24 10:00AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 2-21-24 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 1-25-24 10:27AM
OTHER ISD GROSS PRES WARN ALARM 1-25-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 1-17-24 10:07AM
OTHER ISD GROSS PRES WARN ALARM 1-17-24 10:02AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 1-11-24 10:49AM
SYSTEM PRINTER ERROR CLEAR 1-09-24 10:02AM
SYSTEM PAPER OUT CLEAR 1-09-24 10:02AM
SYSTEM PRINTER ERROR ALARM 1-09-24 10:02AM
SYSTEM PAPER OUT ALARM 1-09-24 10:02AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 1-07-24 10:02AM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM CLEAR 1-01-24 9:03AM
T 2 TANK UNLEADED 2 HIGH PRODUCT ALARM ALARM 1-01-24 8:58AM
OTHER ISD GROSS PRES WARN CLEAR 12-21-23 10:08AM
OTHER ISD GROSS PRES WARN ALARM 12-21-23 10:02AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 10:00AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 12-06-23 10:03AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 10:00AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 11-22-23 10:02AM
I20600
JUL 18, 2024 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUN 21, 2024 5:16 AM
MAY 17, 2024 5:13 AM
MAY 14, 2024 1:14 AM
HIGH PRODUCT ALARM OCT 5, 2023 12:28 AM
TANK 2 UNLEADED 2
OVERFILL ALARM JUN 21, 2024 5:23 AM
JUN 19, 2024 5:59 AM
JUN 15, 2024 2:17 PM
HIGH PRODUCT ALARM JUN 19, 2024 6:01 AM
APR 20, 2024 6:23 PM
JAN 1, 2024 8:58 AM
PROBE OUT MAR 7, 2024 5:44 AM
MAR 6, 2024 12:57 PM
MAR 6, 2024 12:56 PM
TANK 3 PREMIUM
OVERFILL ALARM APR 9, 2024 6:00 AM
NOV 5, 2022 2:16 AM
TANK 4 DIESEL
LOW PRODUCT ALARM FEB 13, 2021 8:05 AM
DELIVERY NEEDED SEP 3, 2022 8:31 AM
MAY 24, 2022 9:25 AM
FEB 13, 2021 8:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 18, 2024 12:04 PM
I30200
JUL 18, 2024 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL ANN
JUL 18, 2024 9:58 AM SENSOR OUT ALARM
JUL 18, 2024 9:48 AM FUEL ALARM
JUL 18, 2024 9:48 AM FUEL ALARM
2 UNL FILL
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:44 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
3 UNL STP
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:47 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
4 UNL 2 ANN
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:48 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
5 UNLD 2 FILL
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:45 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
6 UNL 2 STP
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:47 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
7 PREM ANN
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:50 AM FUEL ALARM
JUL 18, 2024 9:50 AM FUEL ALARM
8 PREM FILL
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:45 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
9 PREM STP
JUL 18, 2024 9:58 AM SENSOR OUT ALARM
JUL 18, 2024 9:46 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
10 DSL ANN
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:50 AM FUEL ALARM
JUL 18, 2024 9:50 AM FUEL ALARM
11 DSL FILL
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:45 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
12 DSL STP
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:46 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
13 DISP 1-2
JUL 18, 2024 10:56 AM FUEL ALARM
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:41 AM FUEL ALARM
14 DISP 3 4
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:44 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
15 DISP 5-6
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:43 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
16 DISP 7-8
JUL 18, 2024 9:59 AM SENSOR OUT ALARM
JUL 18, 2024 9:43 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
17 DISP 9-10
JUL 18, 2024 9:58 AM SENSOR OUT ALARM
JUL 18, 2024 9:42 AM FUEL ALARM
JUL 10, 2024 1:11 PM SENSOR OUT ALARM
18 DISP 11-12
JUL 18, 2024 9:58 AM SENSOR OUT ALARM
JUL 18, 2024 9:42 AM FUEL ALARM
JUL 10, 2024 1:12 PM SENSOR OUT ALARM
I31600
JUL 18, 2024 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 11-12
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
JUN 23, 2024 12:44 PM COMMUNICATION ALARM
6 FM 9-10
JUL 20, 2022 5:02 PM COMMUNICATION ALARM
JUL 20, 2022 3:11 PM COMMUNICATION ALARM
JUL 20, 2022 12:29 PM COMMUNICATION ALARM
7 FM 11-12
I40200
JUL 18, 2024 12:04 PM
I40300
JUL 18, 2024 12:04 PM
I34200
JUL 18, 2024 12:04 PM
I34700
JUL 18, 2024 12:04 PM
IV0100
JUL 18, 2024 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-05-08 10:01:40 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
24-05-07 10:01:35 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
24-05-06 10:02:00 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
24-04-15 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
24-04-11 10:01:09 A/L RATIO DEGRADATION FP 9 BLEND3 0.78
24-04-11 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 1.48
24-04-10 10:01:09 A/L RATIO DEGRADATION FP 9 BLEND3 0.77
24-04-10 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 1.48
24-04-09 10:01:09 A/L RATIO DEGRADATION FP 9 BLEND3 0.76
24-04-09 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 1.46
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
24-03-20 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-03-31 10:02:22 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
22-08-06 10:01:53 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-08-03 10:01:09 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-02-13 10:01:35 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
21-04-19 10:02:18 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
20-10-23 10:01:58 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD
20-10-23 10:01:58 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD
20-10-17 10:02:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
20-06-14 10:01:09 A/L RATIO GROSS BLOCKAGE FP10 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-07-18 10:02:29 READINESS ISD:PP EVR:PP ISD & EVR READY
24-07-18 09:58:01 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-07-18 09:58:01 ISD STARTUP
24-07-18 09:57:38 ISD SHUTDOWN
24-07-11 10:03:35 READINESS ISD:PP EVR:PP ISD & EVR READY
24-07-10 13:11:20 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-07-10 13:11:20 ISD STARTUP
24-07-10 13:11:06 ISD SHUTDOWN
24-05-08 12:22:04 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED
24-04-15 14:04:45 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED