HomeMy WebLinkAboutFMC 2024Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10134205 7-22-24 Jaco #3362 Fastrip #633 6401 South H Street Bakersfield 93304 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Rockland Kirk 1073967 10241356 9-29-24 GVR C32654 9-28-24 VMI #5254 #5255 10-3-24 7-22-24 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder-Root EMC 336.02 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 UNL STP L2 208 UNL FILL L3 303 UNL ANN L4 208 PNL STP L5 208 PNL FILL L6 303 PNL ANN L7 208 DSL STP L8 208 DSL FILL L9 303 DSL ANN L10 208 DISP 1-2 L11 208 DISP 3-4 L12 208 DISP 5-6 L13 208 DISP 7-8 Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V UNLEADED T2 FX1V PREMIUM T3 FX1DV DIESEL Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. FVAL3 STPL1L212,000 GALLON87 UNLEADED AL6 STPL4L5 AL9 STPL7L8 V F F 12L1056L12 34L1178L13 NOPARKING EXISTING BUILDING 12,000 GALLONPREMIUM 12,000 GALLONDIESEL PRICE SIGNDUMPSTERCATCHBASIN W G H W SOUTH H ST.PANAMA LN.PROPERTY LINE STORAGE CONTAINER130'130'109.98'110.11' N LEGEND L1 87 STP L2 87 FILL L3 87 ANNULAR L4 91 STP L5 91 FILL L6 91 ANNULAR L7 DSL STP L8 DSL FILL L9 DSL ANNULAR L10 UDC 1 - 2 L11 UDC 3 - 4 L12 UDC 5 - 6 L13 UDC 7 - 8 87 GAS 3/2 INCH DBL WALLED PIPE 91 GAS 3/2 INCH DBL WALLED PIPE DIESEL 3/2 INCH DBL WALLED PIPE VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE VAPOR VENT 2 INCH SINGLE WALLED PIPE PRODUCT SPILL CONTAINER VAPOR SPILL CONTAINER ANNULAR EMERGENCY SHUT-OFF OVERFILL ALARM FIRE EXTINGUISHER GAS METER SHUT-OFF WATER METER SHUT-SHUT OFF HEALY CAS EVACUATION MEETING POINT AUTOMATIC TANK GAUGE CIRCUIT BREAKER UST ELECTRICAL PANEL AIR AND WATER HAZWASTE DRUM W G A H P V SCALE: SITE MAP C1 VICINITY MAP PROJECT DATA 1"=10'-0" INCHES012 SHEET SIZE 22 X 34 6401 S H ST. BAKERSFIELD, CA 93304 PROJECT OWNER: JACO HILL PO. BOX 82515 BAKERSFIELD, CA 93380 CONTACT: SITE PLOT PLAN FOR: FACILITY ID 15-021-003024 CERS ID 10134205 FASTRIP #3362 6401 S H ST. BAKERSFIELD, CA 93304 01/23/17 REV.S H ST.PANAMA LN. APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Jaco #3362 Fastrip #6336401 South H StreetBakersfield101342051-23-4 5-687918791DSL879187911-23-43-45-67-87-8ProductProductProductProductProductProductProductProductProductRockland Kirk APPENDIX C-10 7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBDSL7-8ProductRockland Kirk Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10134205 7-22-24 Jaco #3362 Fastrip #633 6401 South H Street Bakersfield 93304 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Rockland Kirk 1073967 10241356 9-29-24 FFS EVR Phase 1- VR-101 #1016693714 10-16-24 RP1200 Spill buckets 7-22-24 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1 87 PhilTite T2 91 PhilTite T3 DSL PhilTite Responses Received: 200 FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 JUL 22, 2024 8:31 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 7738 57.86 0.8 85.2 3944 2 PREMIUM 7928 59.08 0.0 89.8 3754 3 DIESEL 4851 39.86 0.8 88.8 6831 I90500 JUL 22, 2024 8:31 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JUL 22, 2024 8:31 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JUL 22, 2024 8:31 AM SHIFT TIME 1 : 6:00 AM I50202 JUL 22, 2024 8:31 AM SHIFT TIME 2 : DISABLED I50203 JUL 22, 2024 8:31 AM SHIFT TIME 3 : DISABLED I50204 JUL 22, 2024 8:31 AM SHIFT TIME 4 : DISABLED I54600 JUL 22, 2024 8:31 AM TANK PER TST NEEDED WRN: DISABLED I54900 JUL 22, 2024 8:31 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JUL 22, 2024 8:31 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JUL 22, 2024 8:31 AM LINE PER TST NEEDED WRN: DISABLED I55900 JUL 22, 2024 8:31 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JUL 22, 2024 8:31 AM PRINT TC VOLUMES ENABLED I50E00 JUL 22, 2024 8:31 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JUL 22, 2024 8:31 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JUL 22, 2024 8:31 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JUL 22, 2024 8:31 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 JUL 22, 2024 8:31 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 1 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 JUL 22, 2024 8:31 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JUL 22, 2024 8:31 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JUL 22, 2024 8:31 AM TANK CHART SECURITY DISABLED I5BD00 JUL 22, 2024 8:31 AM CUSTOM ALARM LABELS DISABLED I56000 JUL 22, 2024 8:31 AM MASS/DENSITY DISABLED I88101 JUL 22, 2024 8:31 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88102 JUL 22, 2024 8:31 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JUL 22, 2024 8:31 AM PORT SETTINGS: COMM BOARD : 3 (EDIM ) RS-232 SECURITY CODE : DISABLED I88104 JUL 22, 2024 8:31 AM I88105 JUL 22, 2024 8:31 AM I88106 JUL 22, 2024 8:31 AM I52000 JUL 22, 2024 8:31 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE JUN 24, 2019 DISABLED 2 ON DATE JUN 24, 2019 DISABLED 3 ON DATE JUN 24, 2019 DISABLED 4 ON DATE JUN 24, 2019 DISABLED 5 ON DATE JUN 24, 2019 DISABLED 6 ON DATE JUN 24, 2019 DISABLED 7 ON DATE JUN 24, 2019 DISABLED 8 ON DATE JUN 24, 2019 DISABLED I60100 JUL 22, 2024 8:31 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED ON 2 PREMIUM ON 3 DIESEL ON 4 OFF I60200 JUL 22, 2024 8:31 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 2 PREMIUM 3 DIESEL 4 I60300 JUL 22, 2024 8:31 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 2 3 DIESEL 3 4 4 I60900 JUL 22, 2024 8:31 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 0.000700 2 PREMIUM 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 JUL 22, 2024 8:31 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 92.00 2 PREMIUM 92.00 3 DIESEL 92.00 4 0.00 I60A00 JUL 22, 2024 8:31 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 PT 11682 2 PREMIUM 1 PT 11682 3 DIESEL 1 PT 11682 4 1 PT 0 I60400 JUL 22, 2024 8:31 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 11682 2 PREMIUM 11682 3 DIESEL 11682 4 0 I60500 JUL 22, 2024 8:31 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 11682 0 0 0 2 PREMIUM 11682 0 0 0 3 DIESEL 11682 0 0 0 4 0 0 0 0 I60600 JUL 22, 2024 8:31 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 11682 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PREMIUM 11682 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 11682 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JUL 22, 2024 8:31 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED NO 2 PREMIUM NO 3 DIESEL NO 4 NO I62F00 JUL 22, 2024 8:31 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 4.0 IN. 2 PREMIUM 4.0 IN. 3 DIESEL 4.0 IN. I62700 JUL 22, 2024 8:31 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 2.0 2 PREMIUM 2.0 3 DIESEL 2.0 I64200 JUL 22, 2024 8:31 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED LOW 2 PREMIUM LOW 3 DIESEL LOW I62400 JUL 22, 2024 8:31 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 3.0 2 PREMIUM 3.0 3 DIESEL 3.0 I62800 JUL 22, 2024 8:31 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11682 2 PREMIUM 11682 3 DIESEL 11682 4 0 I62300 JUL 22, 2024 8:31 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 10514 2 PREMIUM 10514 3 DIESEL 10514 4 0 I62200 JUL 22, 2024 8:31 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11098 2 PREMIUM 11098 3 DIESEL 11098 4 0 I62900 JUL 22, 2024 8:31 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1168 2 PREMIUM 1168 3 DIESEL 1168 4 0 I62100 JUL 22, 2024 8:31 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1200 2 PREMIUM 1200 3 DIESEL 1200 4 0 I62600 JUL 22, 2024 8:31 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I62500 JUL 22, 2024 8:31 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I60800 JUL 22, 2024 8:31 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 9.00 2 PREMIUM 8.00 3 DIESEL 6.00 4 0.00 I60B00 JUL 22, 2024 8:31 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JUL 22, 2024 8:31 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 PREMIUM 0.00 3 DIESEL 0.00 4 0.00 I61200 JUL 22, 2024 8:31 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NONE NONE 2 PREMIUM NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 JUL 22, 2024 8:31 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 PREMIUM 120 3 DIESEL 120 4 0 I62A00 JUL 22, 2024 8:31 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 PREMIUM 120 3 DIESEL 120 4 0 I62C00 JUL 22, 2024 8:31 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED STANDARD 2 PREMIUM STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 JUL 22, 2024 8:31 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JUL 22, 2024 8:31 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED OFF OFF 2 PREMIUM OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 JUL 22, 2024 8:31 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I63200 JUL 22, 2024 8:31 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I61000 JUL 22, 2024 8:31 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63A00 JUL 22, 2024 8:31 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 10.00% 2 PREMIUM 10.00% 3 DIESEL 10.00% 4 10.00% I61100 JUL 22, 2024 8:31 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK FEB 6, 2007 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JUL 22, 2024 8:31 AM CSLD PROBABLITY OF DETECTION I61400 JUL 22, 2024 8:31 AM CSLD CLIMATE FACTOR I61600 JUL 22, 2024 8:31 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED IMMEDIATE 2 PREMIUM IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 JUL 22, 2024 8:31 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED DISABLED 2 PREMIUM DISABLED 3 DIESEL DISABLED 4 DISABLED I61B00 JUL 22, 2024 8:31 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JUL 22, 2024 8:31 AM CSLD REPORT ONLY I62B00 JUL 22, 2024 8:31 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED ??? 0, 0 2 PREMIUM ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 JUL 22, 2024 8:31 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JUL 22, 2024 8:31 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 0 2 PREMIUM 0 3 DIESEL 0 4 0 I63500 JUL 22, 2024 8:31 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63900 JUL 22, 2024 8:32 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED END FACTOR: NONE 2 PREMIUM END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 JUL 22, 2024 8:32 AM I77700 JUL 22, 2024 8:32 AM I77800 JUL 22, 2024 8:32 AM I78C00 JUL 22, 2024 8:32 AM I78300 JUL 22, 2024 8:32 AM I78F00 JUL 22, 2024 8:32 AM I78700 JUL 22, 2024 8:32 AM I70200 JUL 22, 2024 8:32 AM LIQUID LABEL DEVICE LABEL 1 UNL STP 2 UNL FILL 3 UNL ANN 4 PNL STP 5 PNL FILL 6 PNL ANN 7 DSL STP 8 DSL FILL 9 DSL ANN 10 DISP 1-2 11 DISP 3-4 12 DISP 5-6 13 DISP 7-8 14 15 16 I70300 JUL 22, 2024 8:32 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL STP TRI-STATE (SINGLE FLOAT) 2 UNL FILL TRI-STATE (SINGLE FLOAT) 3 UNL ANN DUAL POINT HYDROSTATIC 4 PNL STP TRI-STATE (SINGLE FLOAT) 5 PNL FILL TRI-STATE (SINGLE FLOAT) 6 PNL ANN DUAL POINT HYDROSTATIC 7 DSL STP TRI-STATE (SINGLE FLOAT) 8 DSL FILL TRI-STATE (SINGLE FLOAT) 9 DSL ANN DUAL POINT HYDROSTATIC 10 DISP 1-2 TRI-STATE (SINGLE FLOAT) 11 DISP 3-4 TRI-STATE (SINGLE FLOAT) 12 DISP 5-6 TRI-STATE (SINGLE FLOAT) 13 DISP 7-8 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JUL 22, 2024 8:32 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL STP STP SUMP 2 UNL FILL PIPING SUMP 3 UNL ANN ANNULAR SPACE 4 PNL STP STP SUMP 5 PNL FILL PIPING SUMP 6 PNL ANN ANNULAR SPACE 7 DSL STP STP SUMP 8 DSL FILL PIPING SUMP 9 DSL ANN ANNULAR SPACE 10 DISP 1-2 DISPENSER PAN 11 DISP 3-4 DISPENSER PAN 12 DISP 5-6 DISPENSER PAN 13 DISP 7-8 DISPENSER PAN 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 JUL 22, 2024 8:32 AM I74300 JUL 22, 2024 8:32 AM I74400 JUL 22, 2024 8:32 AM I74700 JUL 22, 2024 8:32 AM I74800 JUL 22, 2024 8:32 AM I74900 JUL 22, 2024 8:32 AM I7BC00 JUL 22, 2024 8:32 AM I80200 JUL 22, 2024 8:32 AM I80300 JUL 22, 2024 8:32 AM I80400 JUL 22, 2024 8:32 AM I80700 JUL 22, 2024 8:32 AM RELAY LABEL DEVICE LABEL 1 POS SHUT DOWN 2 OVERFILL ALARM 3 4 I80900 JUL 22, 2024 8:32 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 POS SHUT DOWN NORMALLY CLOSED 2 OVERFILL ALARM NORMALLY OPEN 3 NORMALLY OPEN 4 NORMALLY OPEN I80B00 JUL 22, 2024 8:32 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 POS SHUT DOWN 1 2 OVERFILL ALARM NONE 3 NONE 4 NONE I80A00 JUL 22, 2024 8:32 AM RELAY TYPE RELAY DESIGNATION TYPE 1 POS SHUT DOWN STANDARD 2 OVERFILL ALARM STANDARD 3 STANDARD 4 STANDARD I80C00 JUL 22, 2024 8:32 AM I80800 JUL 22, 2024 8:32 AM RELAY SETUP REPORT R 1:POS SHUT DOWN TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 4:FUEL ALARM L 7:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L 1:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 1:SHORT ALARM L 4:SHORT ALARM L 7:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM R 3: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 JUL 22, 2024 8:32 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 JUL 22, 2024 8:32 AM I72300 JUL 22, 2024 8:32 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 PS 1-2 VAPOR PRESSURE 02 FM 1-2 AIR FLOW METER 03 FM 3-4 AIR FLOW METER 04 F-M 5-6 AIR FLOW METER 05 FM 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JUL 22, 2024 8:32 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JUL 22, 2024 8:32 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JUL 22, 2024 8:32 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 VAPOR PROCESSOR TYPE NONE IV4700 JUL 22, 2024 8:32 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 JUL 22, 2024 8:32 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ACCEPT HIGH ORVR: YES IV4A00 JUL 22, 2024 8:32 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 17 01 01 01 BLEND3 02 18 02 01 01 BLEND3 03 19 03 02 01 BLEND3 04 20 04 02 01 BLEND3 05 21 05 03 01 BLEND3 06 22 06 03 01 BLEND3 07 23 07 04 01 BLEND3 08 24 08 04 01 BLEND3 IV4B00 JUL 22, 2024 8:32 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 17 01 02/01 03/01 09/01 xx/xx 18 01 02/02 03/02 09/02 xx/xx 19 02 02/03 03/03 09/03 xx/xx 20 02 02/04 03/04 09/04 xx/xx 21 03 02/05 03/05 09/05 xx/xx 22 03 02/06 03/06 09/06 xx/xx 23 04 02/07 03/07 09/07 xx/xx 24 04 02/08 03/08 09/08 xx/xx IV4900 JUL 22, 2024 8:32 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JUL 22, 2024 8:32 AM ISD VERSION: 01.07 Responses Received: I10200 JUL 22, 2024 8:27 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39650 39558 2 4 PROBE / G.T. 164808 164594 3 INTERSTITIAL BD 202695 202471 4 INTERSTITIAL BD 202877 202655 5 UNUSED 10023974 9956237 6 UNUSED 10003811 9945932 7 UNUSED 9999355 9943632 8 UNUSED 10000403 9944008 9 UNUSED 9995811 9947529 10 RELAY BOARD 14992 14985 11 UNUSED 10000180 9950227 12 UNUSED 9998170 9943018 13 UNUSED 9999372 9947065 14 UNUSED 9991508 9943394 15 UNUSED 9998345 9942885 16 UNUSED 9995178 9946645 COMM 1 RS232 SERIAL BD 14992 15007 COMM 2 RS232 SERIAL BD 15102 15096 COMM 3 ELEC DISP INT. 101715 101683 COMM 4 UNUSED 10002059 9952837 COMM 5 UNUSED 9996204 9941448 COMM 6 UNUSED 9995483 9947994 I90200 JUL 22, 2024 8:27 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUL 22, 2024 8:27 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 7-22-24 1:11AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 7-22-24 1:04AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 7-12-24 7:29AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 7-12-24 7:23AM L 2 PIPE UNL FILL FUEL ALARM CLEAR 7-11-24 10:03AM L11 DISP PAN DISP 3-4 FUEL ALARM CLEAR 7-11-24 10:00AM L11 DISP PAN DISP 3-4 FUEL ALARM ALARM 7-11-24 10:00AM L10 DISP PAN DISP 1-2 FUEL ALARM CLEAR 7-11-24 9:59AM L10 DISP PAN DISP 1-2 FUEL ALARM ALARM 7-11-24 9:59AM L12 DISP PAN DISP 5-6 FUEL ALARM CLEAR 7-11-24 9:57AM L12 DISP PAN DISP 5-6 FUEL ALARM ALARM 7-11-24 9:57AM L13 DISP PAN DISP 7-8 FUEL ALARM CLEAR 7-11-24 9:55AM L13 DISP PAN DISP 7-8 FUEL ALARM ALARM 7-11-24 9:54AM L13 DISP PAN DISP 7-8 FUEL ALARM CLEAR 7-11-24 9:54AM L13 DISP PAN DISP 7-8 FUEL ALARM ALARM 7-11-24 9:54AM L13 DISP PAN DISP 7-8 FUEL ALARM CLEAR 7-11-24 9:54AM L13 DISP PAN DISP 7-8 FUEL ALARM ALARM 7-11-24 9:54AM L 4 STP SUMP PNL STP FUEL ALARM CLEAR 7-11-24 9:50AM L 7 STP SUMP DSL STP FUEL ALARM CLEAR 7-11-24 9:50AM L 7 STP SUMP DSL STP FUEL ALARM ALARM 7-11-24 9:50AM L 4 STP SUMP PNL STP FUEL ALARM ALARM 7-11-24 9:49AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 7-11-24 9:36AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 7-11-24 9:35AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 7-11-24 9:35AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 7-11-24 9:35AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 7-11-24 9:35AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 7-11-24 9:35AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 7-11-24 9:34AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM ALARM 7-11-24 9:34AM L 6 ANNULAR PNL ANN HIGH LIQUID ALARM CLEAR 7-11-24 9:34AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 7-11-24 9:34AM L 6 ANNULAR PNL ANN HIGH LIQUID ALARM ALARM 7-11-24 9:34AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM ALARM 7-11-24 9:34AM L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-11-24 9:33AM L 3 ANNULAR UNL ANN LOW LIQUID ALARM CLEAR 7-11-24 9:33AM L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-11-24 9:33AM L 3 ANNULAR UNL ANN LOW LIQUID ALARM ALARM 7-11-24 9:33AM L 8 PIPE DSL FILL FUEL ALARM CLEAR 7-11-24 9:31AM L 8 PIPE DSL FILL FUEL ALARM ALARM 7-11-24 9:31AM L 5 PIPE PNL FILL FUEL ALARM CLEAR 7-11-24 9:30AM L 5 PIPE PNL FILL FUEL ALARM ALARM 7-11-24 9:30AM L 2 PIPE UNL FILL FUEL ALARM ALARM 7-11-24 9:28AM L 2 PIPE UNL FILL FUEL ALARM CLEAR 7-11-24 9:28AM L 2 PIPE UNL FILL FUEL ALARM ALARM 7-11-24 9:28AM L 7 STP SUMP DSL STP FUEL ALARM CLEAR 7-05-24 5:37PM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 7-05-24 5:33PM L 7 STP SUMP DSL STP FUEL ALARM ALARM 7-05-24 5:17PM T 3 TANK DIESEL PROBE OUT CLEAR 7-05-24 5:14PM T 3 TANK DIESEL PROBE OUT ALARM 7-05-24 4:59PM T 3 TANK DIESEL PROBE OUT CLEAR 7-05-24 4:57PM I11200 JUL 22, 2024 8:27 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 7-19-24 2:01PM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 7-17-24 10:01AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PAPER OUT CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PAPER OUT ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PAPER OUT CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PAPER OUT ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PAPER OUT CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PAPER OUT ALARM 7-13-24 9:51AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 7-11-24 8:51AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 7-10-24 10:01AM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 7-05-24 5:13PM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 7-05-24 5:13PM T 3 TANK DIESEL LOW TEMP WARNING CLEAR 7-03-24 4:29PM T 3 TANK DIESEL LOW TEMP WARNING ALARM 7-03-24 4:29PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 7-01-24 1:05PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 6-30-24 10:19PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 6-29-24 7:09PM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 6-29-24 7:07PM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 6-29-24 1:11PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 6-29-24 1:04PM SYSTEM PRINTER ERROR CLEAR 6-26-24 2:40PM SYSTEM PAPER OUT CLEAR 6-26-24 2:40PM SYSTEM PRINTER ERROR ALARM 6-26-24 2:38PM SYSTEM PAPER OUT ALARM 6-26-24 2:38PM I20600 JUL 22, 2024 8:27 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JUN 23, 2024 11:26 PM FEB 18, 2024 10:16 AM JAN 7, 2024 6:57 AM INVALID FUEL LEVEL JUN 21, 2024 5:48 PM JUN 17, 2024 5:29 PM MAY 29, 2024 12:45 AM TANK 2 PREMIUM OVERFILL ALARM JUL 2, 2023 5:16 PM OCT 3, 2022 4:31 PM TANK 3 DIESEL LOW PRODUCT ALARM JUN 30, 2024 9:09 PM JUN 29, 2024 1:04 PM INVALID FUEL LEVEL JUL 5, 2024 5:13 PM JUN 29, 2024 1:11 PM PROBE OUT JUL 5, 2024 4:59 PM JUL 5, 2024 4:52 PM JUL 3, 2024 4:25 PM DELIVERY NEEDED JUN 30, 2024 10:19 PM JUN 29, 2024 1:04 PM LOW TEMP WARNING JUL 3, 2024 4:29 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUL 22, 2024 8:27 AM I30200 JUL 22, 2024 8:27 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP OCT 20, 2023 7:10 PM FUEL ALARM OCT 20, 2023 5:32 PM FUEL ALARM OCT 20, 2023 12:04 PM FUEL ALARM 2 UNL FILL JUL 11, 2024 9:28 AM FUEL ALARM JUL 11, 2024 9:28 AM FUEL ALARM JUN 4, 2024 6:11 AM FUEL ALARM 3 UNL ANN JUL 11, 2024 9:33 AM HIGH LIQUID ALARM JUL 11, 2024 9:33 AM LOW LIQUID ALARM JUL 27, 2023 9:20 AM SENSOR OUT ALARM 4 PNL STP JUL 11, 2024 9:49 AM FUEL ALARM JUL 27, 2023 9:20 AM SENSOR OUT ALARM JUL 27, 2023 9:15 AM FUEL ALARM 5 PNL FILL JUL 11, 2024 9:30 AM FUEL ALARM APR 5, 2024 10:14 AM FUEL ALARM FEB 22, 2024 1:12 PM FUEL ALARM 6 PNL ANN JUL 11, 2024 9:34 AM LOW LIQUID ALARM JUL 11, 2024 9:34 AM HIGH LIQUID ALARM JUL 11, 2024 9:34 AM LOW LIQUID ALARM 7 DSL STP JUL 11, 2024 9:50 AM FUEL ALARM JUL 5, 2024 5:17 PM FUEL ALARM JUN 12, 2024 6:13 AM FUEL ALARM 8 DSL FILL JUL 11, 2024 9:31 AM FUEL ALARM MAR 30, 2024 4:16 AM FUEL ALARM FEB 7, 2024 1:02 AM FUEL ALARM 9 DSL ANN JUL 22, 2024 1:04 AM HIGH LIQUID ALARM JUL 12, 2024 7:23 AM HIGH LIQUID ALARM JUL 11, 2024 9:35 AM LOW LIQUID ALARM 10 DISP 1-2 JUL 11, 2024 9:59 AM FUEL ALARM JUL 27, 2023 9:20 AM SENSOR OUT ALARM JUL 27, 2023 9:17 AM FUEL ALARM 11 DISP 3-4 JUL 11, 2024 10:00 AM FUEL ALARM JUL 27, 2023 9:20 AM SENSOR OUT ALARM JUL 27, 2023 9:17 AM FUEL ALARM 12 DISP 5-6 JUL 11, 2024 9:57 AM FUEL ALARM JUL 27, 2023 9:20 AM SENSOR OUT ALARM JUL 27, 2023 9:17 AM FUEL ALARM 13 DISP 7-8 JUL 11, 2024 9:54 AM FUEL ALARM JUL 11, 2024 9:54 AM FUEL ALARM JUL 11, 2024 9:54 AM FUEL ALARM I31600 JUL 22, 2024 8:27 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PS 1-2 JUN 12, 2023 2:45 PM COMMUNICATION ALARM 2 FM 1-2 JUN 12, 2023 2:46 PM COMMUNICATION ALARM 3 FM 3-4 4 F-M 5-6 5 FM 7-8 I40200 JUL 22, 2024 8:27 AM I40300 JUL 22, 2024 8:27 AM I34200 JUL 22, 2024 8:27 AM I34700 JUL 22, 2024 8:27 AM IV0100 JUL 22, 2024 8:27 AM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-07-19 10:01:09 A/L RATIO DEGRADATION FP 3 BLEND3 0.80 24-07-18 10:01:09 A/L RATIO DEGRADATION FP 3 BLEND3 0.80 24-07-17 10:01:09 A/L RATIO DEGRADATION FP 3 BLEND3 0.80 24-07-10 10:01:24 A/L RATIO DEGRADATION FP 3 BLEND3 0.77 24-02-01 10:01:59 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.98 24-01-13 10:01:53 A/L RATIO DEGRADATION FP 8 BLEND3 0.80 23-10-24 10:01:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.46 23-10-23 10:01:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.46 23-10-22 10:01:41 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.48 23-10-21 10:01:48 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.25 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-11-27 10:01:48 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 22-11-02 10:01:09 A/L RATIO DEGRADATION FP 2 BLEND3 1.43 21-06-20 10:01:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 21-05-31 10:01:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 21-05-31 10:01:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 21-03-31 10:01:34 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.75 19-09-26 10:01:23 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 19-09-05 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 19-07-13 09:22:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 19-03-06 09:54:16 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-07-19 14:01:38 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 24-07-11 08:51:48 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 24-07-11 08:51:41 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED 24-07-11 08:51:37 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-04-14 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 24-04-13 16:01:46 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-04-13 16:01:46 ISD STARTUP 24-04-13 16:01:21 ISD SHUTDOWN 24-04-13 15:53:22 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-04-13 15:53:22 ISD STARTUP Responses Received: I10200 JUL 22, 2024 12:14 PM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39650 39540 2 4 PROBE / G.T. 164808 164593 3 INTERSTITIAL BD 202695 202427 4 INTERSTITIAL BD 202877 202658 5 UNUSED 10023974 9944360 6 UNUSED 10003811 9937976 7 UNUSED 9999355 9939772 8 UNUSED 10000403 9930150 9 UNUSED 9995811 9933855 10 RELAY BOARD 14992 14992 11 UNUSED 10000180 9939020 12 UNUSED 9998170 9936227 13 UNUSED 9999372 9930685 14 UNUSED 9991508 9936338 15 UNUSED 9998345 9929532 16 UNUSED 9995178 9933855 COMM 1 RS232 SERIAL BD 14992 15014 COMM 2 RS232 SERIAL BD 15102 15103 COMM 3 ELEC DISP INT. 101715 101703 COMM 4 UNUSED 10002059 9936515 COMM 5 UNUSED 9996204 9935008 COMM 6 UNUSED 9995483 9933168 I90200 JUL 22, 2024 12:14 PM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUL 22, 2024 12:14 PM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 8 PIPE DSL FILL FUEL ALARM CLEAR 7-22-24 11:23AM L 8 PIPE DSL FILL FUEL ALARM ALARM 7-22-24 11:22AM L 2 PIPE UNL FILL FUEL ALARM CLEAR 7-22-24 10:52AM L 2 PIPE UNL FILL FUEL ALARM ALARM 7-22-24 10:37AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 7-22-24 10:29AM L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 7-22-24 10:29AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 7-22-24 10:29AM L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 7-22-24 10:29AM L 3 ANNULAR UNL ANN LOW LIQUID ALARM CLEAR 7-22-24 10:28AM L 3 ANNULAR UNL ANN LOW LIQUID ALARM ALARM 7-22-24 10:28AM L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 7-22-24 10:28AM L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 7-22-24 10:27AM L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 7-22-24 10:25AM L 3 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-22-24 10:25AM L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L 8 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L 5 PIPE PNL FILL SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L12 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L11 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L10 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L 9 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L13 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-22-24 10:24AM L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-22-24 10:24AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 7-22-24 10:24AM L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 7-22-24 10:24AM L 3 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-22-24 10:24AM L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-22-24 10:24AM L 8 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-22-24 10:24AM L 5 PIPE PNL FILL SENSOR OUT ALARM ALARM 7-22-24 10:24AM L12 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-22-24 10:24AM L11 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 7-22-24 10:24AM L10 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-22-24 10:24AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-22-24 10:24AM L13 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-22-24 10:24AM L 9 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-22-24 10:24AM L 8 PIPE DSL FILL FUEL ALARM CLEAR 7-22-24 10:21AM L 8 PIPE DSL FILL FUEL ALARM ALARM 7-22-24 10:21AM L 5 PIPE PNL FILL FUEL ALARM CLEAR 7-22-24 10:21AM L 5 PIPE PNL FILL FUEL ALARM ALARM 7-22-24 10:21AM L 2 PIPE UNL FILL FUEL ALARM CLEAR 7-22-24 10:20AM L 2 PIPE UNL FILL FUEL ALARM ALARM 7-22-24 10:20AM L12 DISP PAN DISP 5-6 FUEL ALARM CLEAR 7-22-24 10:20AM L12 DISP PAN DISP 5-6 FUEL ALARM ALARM 7-22-24 10:20AM L13 DISP PAN DISP 7-8 FUEL ALARM CLEAR 7-22-24 10:19AM L13 DISP PAN DISP 7-8 FUEL ALARM ALARM 7-22-24 10:19AM L11 DISP PAN DISP 3-4 FUEL ALARM CLEAR 7-22-24 10:19AM L11 DISP PAN DISP 3-4 FUEL ALARM ALARM 7-22-24 10:19AM I11200 JUL 22, 2024 12:14 PM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 7-19-24 2:01PM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 7-17-24 10:01AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PAPER OUT CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PAPER OUT ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PAPER OUT CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PAPER OUT ALARM 7-13-24 9:51AM SYSTEM PRINTER ERROR CLEAR 7-13-24 9:51AM SYSTEM PAPER OUT CLEAR 7-13-24 9:51AM SYSTEM PRINTER ERROR ALARM 7-13-24 9:51AM SYSTEM PAPER OUT ALARM 7-13-24 9:51AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 7-11-24 8:51AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 7-10-24 10:01AM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 7-05-24 5:13PM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 7-05-24 5:13PM T 3 TANK DIESEL LOW TEMP WARNING CLEAR 7-03-24 4:29PM T 3 TANK DIESEL LOW TEMP WARNING ALARM 7-03-24 4:29PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 7-01-24 1:05PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 6-30-24 10:19PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 6-29-24 7:09PM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 6-29-24 7:07PM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 6-29-24 1:11PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 6-29-24 1:04PM SYSTEM PRINTER ERROR CLEAR 6-26-24 2:40PM SYSTEM PAPER OUT CLEAR 6-26-24 2:40PM SYSTEM PRINTER ERROR ALARM 6-26-24 2:38PM SYSTEM PAPER OUT ALARM 6-26-24 2:38PM I20600 JUL 22, 2024 12:14 PM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JUN 23, 2024 11:26 PM FEB 18, 2024 10:16 AM JAN 7, 2024 6:57 AM INVALID FUEL LEVEL JUN 21, 2024 5:48 PM JUN 17, 2024 5:29 PM MAY 29, 2024 12:45 AM TANK 2 PREMIUM OVERFILL ALARM JUL 2, 2023 5:16 PM OCT 3, 2022 4:31 PM TANK 3 DIESEL LOW PRODUCT ALARM JUN 30, 2024 9:09 PM JUN 29, 2024 1:04 PM INVALID FUEL LEVEL JUL 5, 2024 5:13 PM JUN 29, 2024 1:11 PM PROBE OUT JUL 5, 2024 4:59 PM JUL 5, 2024 4:52 PM JUL 3, 2024 4:25 PM DELIVERY NEEDED JUN 30, 2024 10:19 PM JUN 29, 2024 1:04 PM LOW TEMP WARNING JUL 3, 2024 4:29 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUL 22, 2024 12:14 PM I30200 JUL 22, 2024 12:14 PM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:18 AM FUEL ALARM OCT 20, 2023 7:10 PM FUEL ALARM 2 UNL FILL JUL 22, 2024 10:37 AM FUEL ALARM JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:20 AM FUEL ALARM 3 UNL ANN JUL 22, 2024 10:28 AM LOW LIQUID ALARM JUL 22, 2024 10:27 AM HIGH LIQUID ALARM JUL 22, 2024 10:24 AM SENSOR OUT ALARM 4 PNL STP JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:17 AM FUEL ALARM JUL 11, 2024 9:49 AM FUEL ALARM 5 PNL FILL JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:21 AM FUEL ALARM JUL 11, 2024 9:30 AM FUEL ALARM 6 PNL ANN JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:16 AM LOW LIQUID ALARM JUL 22, 2024 10:15 AM HIGH LIQUID ALARM 7 DSL STP JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:17 AM FUEL ALARM JUL 11, 2024 9:50 AM FUEL ALARM 8 DSL FILL JUL 22, 2024 11:22 AM FUEL ALARM JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:21 AM FUEL ALARM 9 DSL ANN JUL 22, 2024 10:29 AM LOW LIQUID ALARM JUL 22, 2024 10:29 AM HIGH LIQUID ALARM JUL 22, 2024 10:24 AM SENSOR OUT ALARM 10 DISP 1-2 JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:18 AM FUEL ALARM JUL 11, 2024 9:59 AM FUEL ALARM 11 DISP 3-4 JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:19 AM FUEL ALARM JUL 11, 2024 10:00 AM FUEL ALARM 12 DISP 5-6 JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:20 AM FUEL ALARM JUL 11, 2024 9:57 AM FUEL ALARM 13 DISP 7-8 JUL 22, 2024 10:24 AM SENSOR OUT ALARM JUL 22, 2024 10:19 AM FUEL ALARM JUL 11, 2024 9:54 AM FUEL ALARM I31600 JUL 22, 2024 12:14 PM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PS 1-2 JUN 12, 2023 2:45 PM COMMUNICATION ALARM 2 FM 1-2 JUN 12, 2023 2:46 PM COMMUNICATION ALARM 3 FM 3-4 4 F-M 5-6 5 FM 7-8 I40200 JUL 22, 2024 12:14 PM I40300 JUL 22, 2024 12:14 PM I34200 JUL 22, 2024 12:14 PM I34700 JUL 22, 2024 12:14 PM IV0100 JUL 22, 2024 12:14 PM FASTRIP 3362 6401 S H ST BAKERSFIELD,CA93304 661-831-4709 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-07-19 10:01:09 A/L RATIO DEGRADATION FP 3 BLEND3 0.80 24-07-18 10:01:09 A/L RATIO DEGRADATION FP 3 BLEND3 0.80 24-07-17 10:01:09 A/L RATIO DEGRADATION FP 3 BLEND3 0.80 24-07-10 10:01:24 A/L RATIO DEGRADATION FP 3 BLEND3 0.77 24-02-01 10:01:59 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.98 24-01-13 10:01:53 A/L RATIO DEGRADATION FP 8 BLEND3 0.80 23-10-24 10:01:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.46 23-10-23 10:01:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.46 23-10-22 10:01:41 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.48 23-10-21 10:01:48 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.25 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-11-27 10:01:48 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 22-11-02 10:01:09 A/L RATIO DEGRADATION FP 2 BLEND3 1.43 21-06-20 10:01:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 21-05-31 10:01:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 21-05-31 10:01:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 21-03-31 10:01:34 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.75 19-09-26 10:01:23 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 19-09-05 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 19-07-13 09:22:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 19-03-06 09:54:16 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-07-22 10:23:28 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-07-22 10:23:28 ISD STARTUP 24-07-22 10:23:08 ISD SHUTDOWN 24-07-19 14:01:38 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 24-07-11 08:51:48 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED 24-07-11 08:51:41 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED 24-07-11 08:51:37 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-04-14 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 24-04-13 16:01:46 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-04-13 16:01:46 ISD STARTUP