HomeMy WebLinkAboutFMC 2024Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10134244 08/07/2024
Jaco #3360 Farrell's Fastrip
6401 White Lane Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fisher
1073967
10278702 03/10/2025
Veeder Root - C33847 07/24/2025
Vaporless Manufacturing LLC #5346 03/14/2025
08/07/2024 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 Unleaded STP
L3 208 Unleaded Fill
L4 208 Premium STP
L5 208 Premium Fill
L6 303 Premium Annular
L7 208 Diesel STP
L9 303 Diesel Annular
L10 208 Dispenser 1/2
L11 208 Dispenser 3/4
L12 208 Dispenser 5/6
L13 208 Dispenser 7/8
L14 303 Unleaded Annular
L15 208 Diesel Fill
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 Unleaded
T2 FX1V 91 Premium
T3 FX1DV Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
08/07/2024
EXISTING BUILDING
78L13
12,000 GALLON87 UNLEADED
34L11
56L1212L10
STPL1 AL2
12,000 GALLONPREMIUM
12,000 GALLONDIESEL
FV
FV
F
AL5
AL16
STPL4
STPL7
L3
L6
L8
NOPARKING
NOPARKING
DUMPSTERDRAINAGE WAYDRAINAGE WAY
DRAINAGE WAYDRAINAGE WAY
DRAINAGE WAY
DRAINAGE WAYDUMPSTER
H
W
W
G
WHITE LN.
PROPERTY LINE
ASHE RD.PRICE SIGNPLAZA SIGNPRICE SIGN
N
PROPERTY LINE
LEGEND
L1 87 STP
L2 87 ANNULAR
L3 87 FILL
L4 91 STP
L5 91 ANNULAR
L6 91 FILL
L7 DSL STP
L8 DSL FILL
L10 UDC 1 - 2
L11 UDC 3 - 4
L12 UDC 5 - 6
L13 UDC 7 - 8
L16 DSL ANNULAR
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
WATER SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
AUTOMATIC TANK GAUGE
UST ELECTRICAL PANEL
CIRCUIT BREAKER
AIR AND WATER DISPENSER
FIRE PREVENTION SYSTEM
G
A
H
P
V
W
SCALE:
SITE MAP C1
VICINITY MAP
PROJECT DATA
1"=20'-0"
INCHES012
SHEET SIZE 22 X 34
6401 WHITE LN.
BAKERSFIELD, CA 93309
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACITILY ID 15-021-003021
CERS ID 10134202
FASTRIP #3360
6401 WHITE LN.
BAKERSFIELD, CA 93309
01/16/17 REV.ASHE RD.WHITE LN.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #3360 Farrell's Fastrip6401 White LaneBakersfield101342443/47/8MPDMPDMPDMPD1/25/6ProductProductProductProductMark Fisher
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10134244 08/07/2024
Jaco #3360 Farrell's Fastrip
6401 White Lane Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fisher
1073967
10278702 03/10/2025
FFS - 1022293714 11/10/2024
PEI1200, 1 hour hydrostatic test All Spill Buckets
08/07/2024 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
87
Phil-Tite
91
Phil-Tite
Diesel
Phil-Tite
JACO #3360 SYSTEM SETUP
Responses Received:
200
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
AUG 7, 2024 10:02 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNL 3076 28.46 0.0 88.4 8606
2 PNL 7165 54.24 0.8 88.1 4517
3 DIESEL 3448 30.93 0.0 89.0 8234
I90500
AUG 7, 2024 10:02 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
AUG 7, 2024 10:02 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
AUG 7, 2024 10:02 AM
SHIFT TIME 1 : 7:00 AM
I50202
AUG 7, 2024 10:02 AM
SHIFT TIME 2 : DISABLED
I50203
AUG 7, 2024 10:02 AM
SHIFT TIME 3 : DISABLED
I50204
AUG 7, 2024 10:02 AM
SHIFT TIME 4 : DISABLED
I54600
AUG 7, 2024 10:02 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
AUG 7, 2024 10:02 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
AUG 7, 2024 10:02 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
AUG 7, 2024 10:02 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
AUG 7, 2024 10:02 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
AUG 7, 2024 10:02 AM
PRINT TC VOLUMES
ENABLED
I50E00
AUG 7, 2024 10:02 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
AUG 7, 2024 10:02 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
AUG 7, 2024 10:02 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
AUG 7, 2024 10:02 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
AUG 7, 2024 10:02 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
AUG 7, 2024 10:02 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
AUG 7, 2024 10:02 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
AUG 7, 2024 10:02 AM
TANK CHART SECURITY
DISABLED
I5BD00
AUG 7, 2024 10:02 AM
CUSTOM ALARM LABELS
DISABLED
I56000
AUG 7, 2024 10:02 AM
MASS/DENSITY
DISABLED
I88101
AUG 7, 2024 10:02 AM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88102
AUG 7, 2024 10:02 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
AUG 7, 2024 10:02 AM
PORT SETTINGS:
COMM BOARD : 3 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88104
AUG 7, 2024 10:02 AM
I88105
AUG 7, 2024 10:02 AM
I88106
AUG 7, 2024 10:02 AM
I52000
AUG 7, 2024 10:02 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE ??? 7, 2024 DISABLED
2 ON DATE ??? 7, 2024 DISABLED
3 ON DATE ??? 7, 2024 DISABLED
4 ON DATE ??? 7, 2024 DISABLED
5 ON DATE ??? 7, 2024 DISABLED
6 ON DATE ??? 7, 2024 DISABLED
7 ON DATE ??? 7, 2024 DISABLED
8 ON DATE ??? 7, 2024 DISABLED
I60100
AUG 7, 2024 10:02 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNL ON
2 PNL ON
3 DIESEL ON
4 OFF
I60200
AUG 7, 2024 10:02 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNL
2 PNL
3 DIESEL
4
I60300
AUG 7, 2024 10:02 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNL 1
2 PNL 2
3 DIESEL 3
4 4
I60900
AUG 7, 2024 10:02 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNL 0.000700
2 PNL 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
AUG 7, 2024 10:02 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNL 92.00
2 PNL 92.00
3 DIESEL 92.00
4 0.00
I60A00
AUG 7, 2024 10:02 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL 1 PT
11682 2 PNL 1 PT 11682 3 DIESEL
1 PT 11682 4 1 PT 0
I60400
AUG 7, 2024 10:02 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 11682
2 PNL 11682
3 DIESEL 11682
4 0
I60500
AUG 7, 2024 10:02 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNL 11682 0 0 0
2 PNL 11682 0 0 0
3 DIESEL 11682 0 0 0
4 0 0 0 0
I60600
AUG 7, 2024 10:02 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNL 11682 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 PNL 11682 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DIESEL 11682 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
AUG 7, 2024 10:02 AM
TANK PRODUCT LABEL METER DATA
1 UNL NO
2 PNL NO
3 DIESEL NO
4 NO
I62F00
AUG 7, 2024 10:02 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNL 4.0 IN.
2 PNL 4.0 IN.
3 DIESEL 4.0 IN.
I62700
AUG 7, 2024 10:02 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNL 2.0
2 PNL 2.0
3 DIESEL 2.0
I64200
AUG 7, 2024 10:02 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNL LOW
2 PNL LOW
3 DIESEL LOW
I62400
AUG 7, 2024 10:02 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNL 3.0
2 PNL 3.0
3 DIESEL 3.0
I62800
AUG 7, 2024 10:02 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 11682
2 PNL 11682
3 DIESEL 11682
4 0
I62300
AUG 7, 2024 10:02 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 10800
2 PNL 10800
3 DIESEL 10800
4 0
I62200
AUG 7, 2024 10:02 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 11400
2 PNL 11400
3 DIESEL 11400
4 0
I62900
AUG 7, 2024 10:02 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1800
2 PNL 1800
3 DIESEL 1800
4 0
I62100
AUG 7, 2024 10:02 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 500
2 PNL 500
3 DIESEL 500
4 0
I62600
AUG 7, 2024 10:03 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 99
2 PNL 99
3 DIESEL 99
4 99
I62500
AUG 7, 2024 10:03 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 99
2 PNL 99
3 DIESEL 99
4 99
I60800
AUG 7, 2024 10:03 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNL 8.00
2 PNL 6.00
3 DIESEL 10.00
4 0.00
I60B00
AUG 7, 2024 10:03 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
AUG 7, 2024 10:03 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNL 0.00
2 PNL 0.00
3 DIESEL 0.00
4 0.00
I61200
AUG 7, 2024 10:03 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNL NONE NONE
2 PNL NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
AUG 7, 2024 10:03 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 120
2 PNL 120
3 DIESEL 120
4 0
I62A00
AUG 7, 2024 10:03 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 120
2 PNL 120
3 DIESEL 120
4 0
I62C00
AUG 7, 2024 10:03 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNL STANDARD
2 PNL STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
AUG 7, 2024 10:03 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 PNL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
AUG 7, 2024 10:03 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNL OFF OFF
2 PNL OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
AUG 7, 2024 10:03 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNL OFF
2 PNL OFF
3 DIESEL OFF
4 OFF
I63200
AUG 7, 2024 10:03 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNL OFF
2 PNL OFF
3 DIESEL OFF
4 OFF
I61000
AUG 7, 2024 10:03 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNL 1
2 PNL 1
3 DIESEL 1
4 1
I63A00
AUG 7, 2024 10:03 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNL 10.00%
2 PNL 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
AUG 7, 2024 10:03 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
MAR 22, 2011
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
AUG 7, 2024 10:03 AM
CSLD PROBABLITY OF DETECTION
I61400
AUG 7, 2024 10:03 AM
CSLD CLIMATE FACTOR
I61600
AUG 7, 2024 10:03 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNL IMMEDIATE
2 PNL IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
AUG 7, 2024 10:03 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNL DISABLED
2 PNL DISABLED
3 DIESEL DISABLED
4 DISABLED
I61B00
AUG 7, 2024 10:03 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
AUG 7, 2024 10:03 AM
CSLD REPORT ONLY
I62B00
AUG 7, 2024 10:03 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNL ??? 0, 0
2 PNL ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
AUG 7, 2024 10:03 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
AUG 7, 2024 10:03 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 0
2 PNL 0
3 DIESEL 0
4 0
I63500
AUG 7, 2024 10:03 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1
2 PNL 1
3 DIESEL 1
4 1
I63900
AUG 7, 2024 10:03 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNL
END FACTOR: NONE
2 PNL
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
AUG 7, 2024 10:03 AM
I77700
AUG 7, 2024 10:03 AM
I77800
AUG 7, 2024 10:03 AM
I78C00
AUG 7, 2024 10:03 AM
I78300
AUG 7, 2024 10:03 AM
I78F00
AUG 7, 2024 10:03 AM
I78700
AUG 7, 2024 10:03 AM
I70200
AUG 7, 2024 10:03 AM
LIQUID LABEL
DEVICE LABEL
1 UNL STP
2 UNL ANN
3 UNL FILL
4 PNL STP
5 PNL FILL
6 PNL ANN
7 DIE STP
8 DIE FILL
9 DIE ANN
10 DIS 1-2
11 DIS 3-4
12 DIS 5-6
13 DIS 7-8
14 UNL ANN
15 DSL FILL
16 DIE ANN
I70300
AUG 7, 2024 10:03 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL STP TRI-STATE (SINGLE FLOAT)
2 UNL ANN DUAL POINT HYDROSTATIC
3 UNL FILL TRI-STATE (SINGLE FLOAT)
4 PNL STP TRI-STATE (SINGLE FLOAT)
5 PNL FILL TRI-STATE (SINGLE FLOAT)
6 PNL ANN DUAL POINT HYDROSTATIC
7 DIE STP TRI-STATE (SINGLE FLOAT)
8 DIE FILL TRI-STATE (SINGLE FLOAT)
9 DIE ANN DUAL POINT HYDROSTATIC
10 DIS 1-2 TRI-STATE (SINGLE FLOAT)
11 DIS 3-4 TRI-STATE (SINGLE FLOAT)
12 DIS 5-6 TRI-STATE (SINGLE FLOAT)
13 DIS 7-8 TRI-STATE (SINGLE FLOAT)
14 UNL ANN DUAL POINT HYDROSTATIC
15 DSL FILL TRI-STATE (SINGLE FLOAT)
16 DIE ANN DUAL POINT HYDROSTATIC
I70400
AUG 7, 2024 10:03 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL STP STP SUMP
2 UNL ANN ANNULAR SPACE
3 UNL FILL OTHER SENSORS
4 PNL STP STP SUMP
5 PNL FILL OTHER SENSORS
6 PNL ANN ANNULAR SPACE
7 DIE STP STP SUMP
8 DIE FILL OTHER SENSORS
9 DIE ANN ANNULAR SPACE
10 DIS 1-2 DISPENSER PAN
11 DIS 3-4 DISPENSER PAN
12 DIS 5-6 DISPENSER PAN
13 DIS 7-8 DISPENSER PAN
14 UNL ANN ANNULAR SPACE
15 DSL FILL OTHER SENSORS
16 DIE ANN ANNULAR SPACE
I74200
AUG 7, 2024 10:03 AM
I74300
AUG 7, 2024 10:03 AM
I74400
AUG 7, 2024 10:03 AM
I74700
AUG 7, 2024 10:03 AM
I74800
AUG 7, 2024 10:03 AM
I74900
AUG 7, 2024 10:03 AM
I7BC00
AUG 7, 2024 10:03 AM
I80200
AUG 7, 2024 10:03 AM
I80300
AUG 7, 2024 10:03 AM
I80400
AUG 7, 2024 10:03 AM
I80700
AUG 7, 2024 10:03 AM
RELAY LABEL
DEVICE LABEL
1 UNL
2 PNL
3 DSL
4 OVERFILL
I80900
AUG 7, 2024 10:03 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNL NORMALLY CLOSED
2 PNL NORMALLY CLOSED
3 DSL NORMALLY CLOSED
4 OVERFILL NORMALLY OPEN
I80B00
AUG 7, 2024 10:03 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNL 1
2 PNL 2
3 DSL 3
4 OVERFILL 1
I80A00
AUG 7, 2024 10:03 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNL STANDARD
2 PNL STANDARD
3 DSL STANDARD
4 OVERFILL STANDARD
I80C00
AUG 7, 2024 10:03 AM
I80800
AUG 7, 2024 10:03 AM
RELAY SETUP REPORT
R 1:UNL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L 1:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 1:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:PNL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
LIQUID SENSOR ALMS
L 4:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L 4:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 4:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DSL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 3
LIQUID SENSOR ALMS
L 7:FUEL ALARM
L10:FUEL ALARM
L12:FUEL ALARM
L 7:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 7:SHORT ALARM
L10:SHORT ALARM
L12:SHORT ALARM
R 4:OVERFILL
TYPE:
STANDARD
NORMALLY OPEN
TANK #: 1
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
I79000
AUG 7, 2024 10:04 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
AUG 7, 2024 10:04 AM
I72300
AUG 7, 2024 10:04 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VP SENSOR DIS 3-4 VAPOR PRESSURE
02 FM DIS 1-2 AIR FLOW METER
03 FM DIS 3-4 AIR FLOW METER
04 FM DIS 5-6 AIR FLOW METER
05 FM DIS 7-8 AIR FLOW METER
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
AUG 7, 2024 10:04 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
AUG 7, 2024 10:04 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
AUG 7, 2024 10:04 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
VAPOR PROCESSOR TYPE
NONE
IV4700
AUG 7, 2024 10:04 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
ASSESSMENT TIME
START TIME: 10:01 AM
TIME DELAY MINUTES: 1
IV5200
AUG 7, 2024 10:04 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
ACCEPT HIGH ORVR: NO
IV4A00
AUG 7, 2024 10:04 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
IV4B00
AUG 7, 2024 10:04 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
IV4900
AUG 7, 2024 10:04 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
AUG 7, 2024 10:04 AM
ISD VERSION: 01.07
JACO #3360 ALARM HISTORY
BEFORE:
Responses Received:
I10200
AUG 7, 2024 10:00 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39576 39506
2 4 PROBE / G.T. 164189 164101
3 INTERSTITIAL BD 202921 202716
4 INTERSTITIAL BD 202609 202524
5 UNUSED 9839353 9805355
6 UNUSED 9834213 9803350
7 UNUSED 9832507 9802359
8 UNUSED 9831816 9802543
9 STP SENSE BOARD 33074 33074
10 RELAY BOARD 15053 15030
11 UNUSED 9835996 9805317
12 UNUSED 9830763 9803104
13 UNUSED 9836987 9805824
14 UNUSED 9826200 9806931
15 UNUSED 9830072 9794576
16 UNUSED 9824655 9804165
COMM 1 RS232 SERIAL BD 15030 15030
COMM 2 RS232 SERIAL BD 15099 15099
COMM 3 ELEC DISP INT. 101796 101775
COMM 4 UNUSED 9842657 9806032
COMM 5 UNUSED 9829519 9803727
COMM 6 UNUSED 9828274 9801099
I90200
AUG 7, 2024 10:00 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 7, 2024 10:00 AM
FASTRIP
6401 WHITE LANE
BAKERSFIELD,CA 93309
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 6 ANNULAR PNL ANN HIGH LIQUID ALARM ALARM 8-06-24 9:13PM
L12 DISP PAN DIS 5-6 FUEL ALARM CLEAR 8-01-24 9:52AM
L12 DISP PAN DIS 5-6 FUEL ALARM ALARM 8-01-24 9:37AM
L 7 STP SUMP DIE STP SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L 3 OTHER UNL FILL SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L10 DISP PAN DIS 1-2 SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L15 OTHER DSL FILL SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L 5 OTHER PNL FILL SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L14 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L12 DISP PAN DIS 5-6 SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L11 DISP PAN DIS 3-4 SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L 9 ANNULAR DIE ANN SENSOR OUT ALARM CLEAR 8-01-24 9:35AM
L13 DISP PAN DIS 7-8 SENSOR OUT ALARM CLEAR 8-01-24 9:35AM