HomeMy WebLinkAboutFMC 2024Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10023037 08/13/2024
Jaco #3347 Fastrip #26
2698 Oswell Street Bakersfield 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fsiher
1073967
10278702 03/10/2025
Veeder Root - C33847 07/24/2025
Vaporless Manufacturing LLC #5346 03/14/2025
08/13/2024 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 Unleaded 1 STP
L2 420 Unleaded 1 Annular
L3 208 Diesel STP
L4 420 Diesel Annular
L6 420 Premium Annular
L7 208 Unleaded 2 STP
L8 420 Unleaded 2 Annular
L9 208 Dispenser 1/2
L10 208 Dispenser 3/4
L11 208 Dispenser 5/6
L12 208 Dispenser 7/8
L13 208 Trans Sump N.
L14 208 Trans Sump S.
L15 208 Premium STP
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 Unleaded
T2 FX1V 91 Premium
T3 FX1DV Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
08/13/2024
PRICE SIG
N NOPARKING
EXISTING BUILDING
G H
CATCHBASIN
W
W
SLOPE
RETAINING WALL
DRAINAGE WAY
SLOPE
AL6AL4AL2AL8 F V F V F V F12,000 GALLONPREMIUM12,000 GALLONDEISEL12,000 GALLON87-1 UNLEADED12,000 GALLON87-2 UNLEADEDSTPL7STPL1STPL3STPL15L10 34L912L13L1278L1156L14N
AUBURN ST.
PROPERTY LINE
OSWELL ST.DUMPSTERCOLUMN SUPPORTINGRESTAURANT SIGN (2x)
STORAGE CONTAINER
LEGEND
L1 87-1 STP
L2 87-1 ANNULAR
L3 DSL STP
L4 DSL ANNULAR
L6 91 ANNULAR
L7 87-2 STP
L8 87-2 ANNULAR
L9 UDC 1 - 2
L10 UDC 3 - 4
L11 UDC 5 - 6
L12 UDC 7 - 8
L13 N TRANS SUMP
L14 S TRANS SUMP
L15 91 STP
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
AUTOMATIC TANK GUAGE
CIRCUIT BREAKER
UST ELECTRICAL PANEL
AIR AND WATER
HAZ-WASTE DRUM
W
G
A
H
P
V
SCALE:
SITE MAP C1
VICINITY MAP
PROJECT DATA
1"=10'-0"
INCHES012
SHEET SIZE 22 X 34
2698 OSWELL ST.
BAKERSFIELD, CA 93306
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID: 15-021-00300
CERS ID 10023037
FASTRIP #3347
2698 OSWELL ST.
BAKERSFIELD, CA 93306
01/10/17 REV.OSWELL ST.HWY 178
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #3347 Fastrip #262698 Oswell StreetBakersfield100230373/47/8MPDMPDMPDMPD1/25/6ProductProductProductProductMark Fisher
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10023037 08/13/2024
Jaco #3347 Fastrip #26
2698 Oswell Street Bakersfield 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fsiher
1073967
10278702 03/10/2025
OPW - 1193587 08/04/2025
PEI1200, 1 hour hydrostatic test All Spill Buckets
08/13/2024 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
87-1
OPW
87-2
OPW
91
OPW
Diesel
OPW
JACO #3347 SYSTEM SETUP
Responses Received:
200
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
AUG 13, 2024 10:04 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNL 1 5743 46.38 0.0 87.4 6257
2 DIESEL 2875 27.74 0.8 87.0 9125
3 PNL 4649 39.47 0.0 88.0 7351
4 UNL 2 6020 48.13 0.7 85.7 5980
I90500
AUG 13, 2024 10:04 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
AUG 13, 2024 10:04 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
AUG 13, 2024 10:04 AM
SHIFT TIME 1 : 6:00 AM
I50202
AUG 13, 2024 10:04 AM
SHIFT TIME 2 : DISABLED
I50203
AUG 13, 2024 10:04 AM
SHIFT TIME 3 : DISABLED
I50204
AUG 13, 2024 10:04 AM
SHIFT TIME 4 : DISABLED
I54600
AUG 13, 2024 10:04 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
AUG 13, 2024 10:04 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
AUG 13, 2024 10:04 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
AUG 13, 2024 10:04 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
AUG 13, 2024 10:04 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
AUG 13, 2024 10:04 AM
PRINT TC VOLUMES
ENABLED
I50E00
AUG 13, 2024 10:04 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
AUG 13, 2024 10:04 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
AUG 13, 2024 10:04 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
AUG 13, 2024 10:04 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
AUG 13, 2024 10:04 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
AUG 13, 2024 10:04 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
AUG 13, 2024 10:04 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
AUG 13, 2024 10:04 AM
TANK CHART SECURITY
DISABLED
I5BD00
AUG 13, 2024 10:04 AM
CUSTOM ALARM LABELS
DISABLED
I56000
AUG 13, 2024 10:04 AM
MASS/DENSITY
DISABLED
I88101
AUG 13, 2024 10:04 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
AUG 13, 2024 10:04 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
AUG 13, 2024 10:04 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
AUG 13, 2024 10:04 AM
I88105
AUG 13, 2024 10:04 AM
I88106
AUG 13, 2024 10:04 AM
I52000
AUG 13, 2024 10:04 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE ??? 13, 2024 DISABLED
2 ON DATE ??? 13, 2024 DISABLED
3 ON DATE ??? 13, 2024 DISABLED
4 ON DATE ??? 13, 2024 DISABLED
5 ON DATE ??? 13, 2024 DISABLED
6 ON DATE ??? 13, 2024 DISABLED
7 ON DATE ??? 13, 2024 DISABLED
8 ON DATE ??? 13, 2024 DISABLED
I60100
AUG 13, 2024 10:04 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNL 1 ON
2 DIESEL ON
3 PNL ON
4 UNL 2 ON
I60200
AUG 13, 2024 10:04 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNL 1
2 DIESEL
3 PNL
4 UNL 2
I60300
AUG 13, 2024 10:04 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNL 1 1
2 DIESEL 2
3 PNL 3
4 UNL 2 4
I60900
AUG 13, 2024 10:04 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNL 1 0.000700
2 DIESEL 0.000450
3 PNL 0.000700
4 UNL 2 0.000700
I60700
AUG 13, 2024 10:04 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNL 1 96.00
2 DIESEL 96.00
3 PNL 96.00
4 UNL 2 96.00
I60A00
AUG 13, 2024 10:04 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL 1 1 PT
12000 2 DIESEL 1 PT 12000 3 PNL
1 PT 12000 4 UNL 2 1 PT 12000
I60400
AUG 13, 2024 10:04 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 1 12000
2 DIESEL 12000
3 PNL 12000
4 UNL 2 12000
I60500
AUG 13, 2024 10:04 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNL 1 12000 0 0 0
2 DIESEL 12000 0 0 0
3 PNL 12000 0 0 0
4 UNL 2 12000 0 0 0
I60600
AUG 13, 2024 10:04 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNL 1 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 DIESEL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 PNL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 UNL 2 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
AUG 13, 2024 10:04 AM
TANK PRODUCT LABEL METER DATA
1 UNL 1 NO
2 DIESEL NO
3 PNL NO
4 UNL 2 NO
I62F00
AUG 13, 2024 10:04 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNL 1 4.0 IN.
2 DIESEL 4.0 IN.
3 PNL 4.0 IN.
4 UNL 2 3.0 IN.
I62700
AUG 13, 2024 10:04 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNL 1 2.0
2 DIESEL 2.0
3 PNL 2.0
4 UNL 2 2.0
I64200
AUG 13, 2024 10:04 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNL 1 LOW
2 DIESEL LOW
3 PNL LOW
4 UNL 2 LOW
I62400
AUG 13, 2024 10:04 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNL 1 3.0
2 DIESEL 3.0
3 PNL 3.0
4 UNL 2 3.0
I62800
AUG 13, 2024 10:04 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1 12000
2 DIESEL 12000
3 PNL 12000
4 UNL 2 12000
I62300
AUG 13, 2024 10:04 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1 10800
2 DIESEL 10800
3 PNL 10800
4 UNL 2 10800
I62200
AUG 13, 2024 10:04 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1 11400
2 DIESEL 11400
3 PNL 11400
4 UNL 2 11400
I62900
AUG 13, 2024 10:04 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1 1200
2 DIESEL 1200
3 PNL 1200
4 UNL 2 1200
I62100
AUG 13, 2024 10:04 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1 1200
2 DIESEL 1200
3 PNL 1200
4 UNL 2 1200
I62600
AUG 13, 2024 10:04 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1 99
2 DIESEL 99
3 PNL 99
4 UNL 2 99
I62500
AUG 13, 2024 10:04 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1 99
2 DIESEL 99
3 PNL 99
4 UNL 2 99
I60800
AUG 13, 2024 10:04 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNL 1 0.00
2 DIESEL 0.00
3 PNL 0.00
4 UNL 2 0.00
I60B00
AUG 13, 2024 10:04 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
AUG 13, 2024 10:04 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNL 1 0.00
2 DIESEL 0.00
3 PNL 0.00
4 UNL 2 0.00
I61200
AUG 13, 2024 10:04 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNL 1 4 NONE
2 DIESEL NONE NONE
3 PNL NONE NONE
4 UNL 2 1 NONE
I63600
AUG 13, 2024 10:04 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 1 120
2 DIESEL 120
3 PNL 120
4 UNL 2 120
I62A00
AUG 13, 2024 10:04 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 1 0
2 DIESEL 0
3 PNL 0
4 UNL 2 0
I62C00
AUG 13, 2024 10:04 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNL 1 STANDARD
2 DIESEL STANDARD
3 PNL STANDARD
4 UNL 2 STANDARD
I62D00
AUG 13, 2024 10:04 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNL 1 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
2 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
3 PNL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
4 UNL 2 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
AUG 13, 2024 10:05 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNL 1 OFF OFF
2 DIESEL OFF OFF
3 PNL OFF OFF
4 UNL 2 OFF OFF
I63000
AUG 13, 2024 10:05 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNL 1 OFF
2 DIESEL OFF
3 PNL OFF
4 UNL 2 OFF
I63200
AUG 13, 2024 10:05 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNL 1 OFF
2 DIESEL OFF
3 PNL OFF
4 UNL 2 OFF
I61000
AUG 13, 2024 10:05 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNL 1 1
2 DIESEL 1
3 PNL 1
4 UNL 2 1
I63A00
AUG 13, 2024 10:05 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNL 1 10.00%
2 DIESEL 10.00%
3 PNL 10.00%
4 UNL 2 10.00%
I61100
AUG 13, 2024 10:05 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JUL 23, 2010
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
AUG 13, 2024 10:05 AM
CSLD PROBABLITY OF DETECTION
I61400
AUG 13, 2024 10:05 AM
CSLD CLIMATE FACTOR
I61600
AUG 13, 2024 10:05 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNL 1 IMMEDIATE
2 DIESEL IMMEDIATE
3 PNL IMMEDIATE
4 UNL 2 IMMEDIATE
I61A00
AUG 13, 2024 10:05 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNL 1 DISABLED
2 DIESEL DISABLED
3 PNL DISABLED
4 UNL 2 DISABLED
I61B00
AUG 13, 2024 10:05 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
AUG 13, 2024 10:05 AM
CSLD REPORT ONLY
I62B00
AUG 13, 2024 10:05 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNL 1 ??? 0, 0
2 DIESEL ??? 0, 0
3 PNL ??? 0, 0
4 UNL 2 ??? 0, 0
I63300
AUG 13, 2024 10:05 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
AUG 13, 2024 10:05 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1 0
2 DIESEL 0
3 PNL 0
4 UNL 2 0
I63500
AUG 13, 2024 10:05 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1 1
2 DIESEL 1
3 PNL 1
4 UNL 2 1
I63900
AUG 13, 2024 10:05 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNL 1
END FACTOR: NONE
2 DIESEL
END FACTOR: NONE
3 PNL
END FACTOR: NONE
4 UNL 2
END FACTOR: NONE
I78000
AUG 13, 2024 10:05 AM
I77700
AUG 13, 2024 10:05 AM
I77800
AUG 13, 2024 10:05 AM
I78C00
AUG 13, 2024 10:05 AM
I78300
AUG 13, 2024 10:05 AM
I78F00
AUG 13, 2024 10:05 AM
I78700
AUG 13, 2024 10:05 AM
I70200
AUG 13, 2024 10:05 AM
LIQUID LABEL
DEVICE LABEL
1 UNL 1 STP
2 UNL 1 ANN
3 DSL STP
4 DSL ANN
5
6 PNL ANN
7 UNL 2 STP
8 UNL 2 ANN
9 DISP 1-2
10 DISP 3-4
11 DISP 5-6
12 DISP 7-8
13 TRANS SUMP NO
14 TRANS SUMP SO
15 PNL STP
16 UNL 1 ANN
I70300
AUG 13, 2024 10:05 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL 1 STP TRI-STATE (SINGLE FLOAT)
2 UNL 1 ANN TRI-STATE (SINGLE FLOAT)
3 DSL STP TRI-STATE (SINGLE FLOAT)
4 DSL ANN TRI-STATE (SINGLE FLOAT)
5 TRI-STATE (SINGLE FLOAT)
6 PNL ANN TRI-STATE (SINGLE FLOAT)
7 UNL 2 STP TRI-STATE (SINGLE FLOAT)
8 UNL 2 ANN TRI-STATE (SINGLE FLOAT)
9 DISP 1-2 TRI-STATE (SINGLE FLOAT)
10 DISP 3-4 TRI-STATE (SINGLE FLOAT)
11 DISP 5-6 TRI-STATE (SINGLE FLOAT)
12 DISP 7-8 TRI-STATE (SINGLE FLOAT)
13 TRANS SUMP NO TRI-STATE (SINGLE FLOAT)
14 TRANS SUMP SO TRI-STATE (SINGLE FLOAT)
15 PNL STP TRI-STATE (SINGLE FLOAT)
16 UNL 1 ANN TRI-STATE (SINGLE FLOAT)
I70400
AUG 13, 2024 10:05 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL 1 STP STP SUMP
2 UNL 1 ANN ANNULAR SPACE
3 DSL STP STP SUMP
4 DSL ANN ANNULAR SPACE
5 OTHER SENSORS
6 PNL ANN ANNULAR SPACE
7 UNL 2 STP STP SUMP
8 UNL 2 ANN ANNULAR SPACE
9 DISP 1-2 DISPENSER PAN
10 DISP 3-4 DISPENSER PAN
11 DISP 5-6 DISPENSER PAN
12 DISP 7-8 DISPENSER PAN
13 TRANS SUMP NO PIPING SUMP
14 TRANS SUMP SO PIPING SUMP
15 PNL STP STP SUMP
16 UNL 1 ANN ANNULAR SPACE
I74200
AUG 13, 2024 10:05 AM
I74300
AUG 13, 2024 10:05 AM
I74400
AUG 13, 2024 10:05 AM
I74700
AUG 13, 2024 10:05 AM
I74800
AUG 13, 2024 10:05 AM
I74900
AUG 13, 2024 10:05 AM
I7BC00
AUG 13, 2024 10:05 AM
I80200
AUG 13, 2024 10:05 AM
I80300
AUG 13, 2024 10:05 AM
I80400
AUG 13, 2024 10:05 AM
I80700
AUG 13, 2024 10:05 AM
RELAY LABEL
DEVICE LABEL
1 UNL 1
2 PNL
3 DSL
4
5 OVERFILL ALARM
6
7
8
I80900
AUG 13, 2024 10:05 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNL 1 NORMALLY OPEN
2 PNL NORMALLY OPEN
3 DSL NORMALLY CLOSED
4 NORMALLY OPEN
5 OVERFILL ALARM NORMALLY OPEN
6 NORMALLY OPEN
7 NORMALLY OPEN
8 NORMALLY OPEN
I80B00
AUG 13, 2024 10:05 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNL 1 1
2 PNL 3
3 DSL NONE
4 NONE
5 OVERFILL ALARM NONE
6 NONE
7 NONE
8 NONE
I80A00
AUG 13, 2024 10:05 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNL 1 PUMP CONTROL OUTPUT
2 PNL PUMP CONTROL OUTPUT
3 DSL STANDARD
4 STANDARD
5 OVERFILL ALARM STANDARD
6 STANDARD
7 STANDARD
8 STANDARD
I80C00
AUG 13, 2024 10:05 AM
I80800
AUG 13, 2024 10:05 AM
RELAY SETUP REPORT
R 1:UNL 1
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 1:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 1:SHORT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:PNL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 3
LIQUID SENSOR ALMS
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L15:FUEL ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L15:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DSL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: NONE
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 3:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 3:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 5:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 6:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 7:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 8:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
AUG 13, 2024 10:06 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
AUG 13, 2024 10:06 AM
I72300
AUG 13, 2024 10:06 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 PS 3-4 VAPOR PRESSURE
02 FM 1-2 AIR FLOW METER
03 FM 3-4 AIR FLOW METER
04 FM 5-6 AIR FLOW METER
05 FM 7-8 AIR FLOW METER
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
AUG 13, 2024 10:06 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
AUG 13, 2024 10:06 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
AUG 13, 2024 10:06 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
VAPOR PROCESSOR TYPE
NONE
IV4700
AUG 13, 2024 10:06 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
AUG 13, 2024 10:06 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
ACCEPT HIGH ORVR: YES
IV4A00
AUG 13, 2024 10:06 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
IV4B00
AUG 13, 2024 10:06 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
IV4900
AUG 13, 2024 10:06 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
AUG 13, 2024 10:06 AM
ISD VERSION: 01.07
JACO #3347 ALARM HISTORY
BEFORE:
Responses Received:
I10200
AUG 13, 2024 10:07 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39557 39572
2 4 PROBE / G.T. 163015 163161
3 INTERSTITIAL BD 201752 201661
4 INTERSTITIAL BD 201230 201111
5 UNUSED 4944149 4917971
6 UNUSED 4941027 4918119
7 UNUSED 4939812 4914968
8 UNUSED 4938848 4915010
9 STP SENSE BOARD 33158 33188
10 RELAY BOARD 14944 14971
11 RELAY BOARD 14923 14908
12 UNUSED 4940499 4917576
13 UNUSED 4941316 4913368
14 UNUSED 4940436 4916265
15 UNUSED 4937880 4918528
16 UNUSED 4940457 4922546
COMM 1 ELEC DISP INT. 100495 100538
COMM 2 RS232 SERIAL BD 14902 14950
COMM 3 RS232 SERIAL BD 15007 14993
COMM 4 UNUSED 4943055 4916688
COMM 5 UNUSED 4939032 4914615
COMM 6 UNUSED 4939472 4917872
I90200
AUG 13, 2024 10:07 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 13, 2024 10:07 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 1 STP SUMP UNL 1 STP FUEL ALARM CLEAR 8-12-24 10:42AM
L 1 STP SUMP UNL 1 STP FUEL ALARM ALARM 8-12-24 7:30AM
L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 8-10-24 7:48PM
L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 8-10-24 5:34PM
L 3 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L 8 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L 7 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L15 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L14 PIPE TRANS SUMP SO SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L 4 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L13 PIPE TRANS SUMP NO SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 8-06-24 10:51AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L 4 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L 3 STP SUMP DSL STP SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L 8 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L15 STP SUMP PNL STP SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L14 PIPE TRANS SUMP SO SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L 7 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L13 PIPE TRANS SUMP NO SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 8-06-24 10:50AM
L14 PIPE TRANS SUMP SO FUEL ALARM CLEAR 8-06-24 10:35AM
L14 PIPE TRANS SUMP SO FUEL ALARM ALARM 8-06-24 10:35AM
L13 PIPE TRANS SUMP NO FUEL ALARM CLEAR 8-06-24 10:33AM
L13 PIPE TRANS SUMP NO FUEL ALARM ALARM 8-06-24 10:33AM
L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 8-06-24 10:27AM
L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 8-06-24 10:27AM
L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 8-06-24 10:26AM
L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 8-06-24 10:26AM
L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 8-06-24 10:24AM
L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 8-06-24 10:23AM
L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 8-06-24 10:22AM
L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 8-06-24 10:22AM
L15 STP SUMP PNL STP FUEL ALARM CLEAR 8-06-24 10:20AM
L15 STP SUMP PNL STP FUEL ALARM ALARM 8-06-24 10:20AM
L 3 STP SUMP DSL STP FUEL ALARM CLEAR 8-06-24 10:19AM
L 3 STP SUMP DSL STP FUEL ALARM ALARM 8-06-24 10:19AM
L 1 STP SUMP UNL 1 STP FUEL ALARM CLEAR 8-06-24 10:18AM
L 1 STP SUMP UNL 1 STP FUEL ALARM ALARM 8-06-24 10:18AM
I11200
AUG 13, 2024 10:07 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 7-06-24 2:08PM
SYSTEM PRINTER ERROR ALARM 7-06-24 2:08PM
SYSTEM PAPER OUT CLEAR 7-06-24 2:08PM
SYSTEM PAPER OUT ALARM 7-06-24 2:06PM
SYSTEM PRINTER ERROR CLEAR 7-06-24 2:05PM
SYSTEM PRINTER ERROR ALARM 7-06-24 2:05PM
SYSTEM PRINTER ERROR CLEAR 6-10-24 12:57PM
SYSTEM PAPER OUT CLEAR 6-10-24 12:57PM
SYSTEM PRINTER ERROR ALARM 6-10-24 12:57PM
SYSTEM PAPER OUT ALARM 6-10-24 12:57PM
OTHER ISD GROSS PRES WARN CLEAR 5-14-24 12:59PM
OTHER ISD GROSS PRES WARN ALARM 5-09-24 10:02AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 4-04-24 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 4-03-24 10:01AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 4-02-24 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 3-31-24 10:01AM
SYSTEM PRINTER ERROR CLEAR 3-28-24 10:08AM
SYSTEM PAPER OUT CLEAR 3-28-24 10:08AM
SYSTEM PRINTER ERROR ALARM 3-28-24 10:08AM
SYSTEM PAPER OUT ALARM 3-28-24 10:08AM
OTHER ISD SENSOR OUT WARN CLEAR 3-11-24 3:15PM
OTHER ISD SENSOR OUT WARN ALARM 3-11-24 10:03AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 2-22-24 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 2-21-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 2-06-24 10:03AM
OTHER ISD GROSS PRES WARN ALARM 2-06-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 1-30-24 10:09AM
OTHER ISD GROSS PRES WARN ALARM 1-30-24 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 1-23-24 1:57PM
OTHER ISD GROSS PRES WARN ALARM 1-22-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 1-15-24 1:57PM
OTHER ISD GROSS PRES WARN ALARM 1-15-24 10:02AM
SYSTEM PRINTER ERROR CLEAR 1-13-24 12:24PM
SYSTEM PAPER OUT CLEAR 1-13-24 12:24PM
SYSTEM PAPER OUT ALARM 1-13-24 12:24PM
SYSTEM PRINTER ERROR ALARM 1-13-24 12:24PM
OTHER ISD GROSS PRES WARN CLEAR 12-31-23 10:48AM
OTHER ISD GROSS PRES WARN ALARM 12-31-23 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 12-24-23 11:07AM
OTHER ISD GROSS PRES WARN ALARM 12-24-23 10:02AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 12-22-23 11:23AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 12-21-23 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 12-17-23 5:37PM
OTHER ISD GROSS PRES WARN ALARM 12-17-23 10:02AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 12-04-23 12:24PM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 12-04-23 12:24PM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 12-04-23 10:02AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-28-23 10:03AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 10:43AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-23-23 10:02AM
I20600
AUG 13, 2024 10:07 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
TANK ALARM HISTORY
TANK 1 UNL 1
OVERFILL ALARM JUL 6, 2024 11:17 PM
MAY 27, 2024 1:05 PM
MAR 11, 2024 9:12 AM
TANK 2 DIESEL
LOW PRODUCT ALARM AUG 13, 2023 4:40 PM
DELIVERY NEEDED AUG 13, 2023 4:40 PM
TANK 3 PNL
OVERFILL ALARM AUG 26, 2023 12:41 PM
PROBE OUT JUL 9, 2022 7:49 AM
TANK 4 UNL 2
OVERFILL ALARM JUL 23, 2024 11:25 PM
JUL 6, 2024 11:24 PM
JUN 22, 2024 10:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
AUG 13, 2024 10:07 AM
I30200
AUG 13, 2024 10:07 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL 1 STP
AUG 12, 2024 7:30 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:18 AM FUEL ALARM
2 UNL 1 ANN
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 9:58 AM FUEL ALARM
OCT 19, 2023 11:52 AM SENSOR OUT ALARM
3 DSL STP
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:19 AM FUEL ALARM
OCT 19, 2023 11:51 AM SENSOR OUT ALARM
4 DSL ANN
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 9:59 AM FUEL ALARM
DEC 22, 2023 9:55 AM FUEL ALARM
6 PNL ANN
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:00 AM FUEL ALARM
DEC 22, 2023 9:56 AM FUEL ALARM
7 UNL 2 STP
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:17 AM FUEL ALARM
OCT 19, 2023 11:51 AM SENSOR OUT ALARM
8 UNL 2 ANN
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 9:57 AM FUEL ALARM
OCT 19, 2023 11:52 AM SENSOR OUT ALARM
9 DISP 1-2
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:26 AM FUEL ALARM
OCT 19, 2023 11:51 AM SENSOR OUT ALARM
10 DISP 3-4
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:23 AM FUEL ALARM
OCT 19, 2023 11:51 AM SENSOR OUT ALARM
11 DISP 5-6
AUG 10, 2024 5:34 PM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:27 AM FUEL ALARM
12 DISP 7-8
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:22 AM FUEL ALARM
OCT 19, 2023 11:51 AM SENSOR OUT ALARM
13 TRANS SUMP NO
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:33 AM FUEL ALARM
OCT 19, 2023 11:51 AM SENSOR OUT ALARM
14 TRANS SUMP SO
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:35 AM FUEL ALARM
DEC 22, 2023 9:53 AM FUEL ALARM
15 PNL STP
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
AUG 6, 2024 10:20 AM FUEL ALARM
OCT 19, 2023 11:52 AM SENSOR OUT ALARM
I31600
AUG 13, 2024 10:07 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 3-4
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
I40200
AUG 13, 2024 10:07 AM
I40300
AUG 13, 2024 10:07 AM
I34200
AUG 13, 2024 10:07 AM
I34700
AUG 13, 2024 10:07 AM
IV0100
AUG 13, 2024 10:07 AM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-05-14 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-13 10:01:12 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-12 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-11 10:01:11 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-10 10:01:29 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-09 10:02:36 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-04-03 10:01:24 A/L RATIO DEGRADATION FP 7 BLEND3 0.80
24-04-01 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80
24-03-31 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80
24-03-11 10:03:17 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 1:FM 1-2
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-01-24 10:02:54 A/L RATIO DEGRADATION FP 6 BLEND3 0.80
22-09-24 10:01:13 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 193.02
22-09-11 10:02:02 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 143.37
22-08-29 10:01:45 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 29.60
22-06-15 10:02:34 A/L RATIO DEGRADATION FP 7 BLEND3 0.56
22-04-19 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
15-12-16 10:01:58 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
15-12-16 10:01:58 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
15-12-15 10:01:56 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
12-08-18 10:02:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.70
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-08-07 10:01:26 READINESS ISD:PP EVR:PP ISD & EVR READY
24-08-06 10:51:42 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-08-06 10:51:42 ISD STARTUP
24-08-06 10:51:33 ISD SHUTDOWN
24-07-22 10:02:29 READINESS ISD:PP EVR:PP ISD & EVR READY
24-07-21 16:31:47 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-07-21 16:31:47 ISD STARTUP
24-07-21 16:31:01 ISD SHUTDOWN
24-05-26 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY
24-05-26 02:44:44 READINESS ISD:PP EVR:NN EVR READINESS PENDING
AFTER:
Responses Received:
I10200
AUG 13, 2024 3:39 PM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39557 39502
2 4 PROBE / G.T. 163015 162872
3 INTERSTITIAL BD 201752 201690
4 INTERSTITIAL BD 201230 200914
5 UNUSED 4944149 4918632
6 UNUSED 4941027 4913553
7 UNUSED 4939812 4919433
8 UNUSED 4938848 4917305
9 STP SENSE BOARD 33158 33166
10 RELAY BOARD 14944 14972
11 RELAY BOARD 14923 14908
12 UNUSED 4940499 4919043
13 UNUSED 4941316 4916957
14 UNUSED 4940436 4912005
15 UNUSED 4937880 4912215
16 UNUSED 4940457 4915039
COMM 1 ELEC DISP INT. 100495 100562
COMM 2 RS232 SERIAL BD 14902 14929
COMM 3 RS232 SERIAL BD 15007 14993
COMM 4 UNUSED 4943055 4916725
COMM 5 UNUSED 4939032 4917020
COMM 6 UNUSED 4939472 4913564
I90200
AUG 13, 2024 3:39 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 13, 2024 3:39 PM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L 8 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L 4 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L 7 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L 3 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L15 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 8-13-24 10:34AM
L14 PIPE TRANS SUMP SO SENSOR OUT ALARM CLEAR 8-13-24 10:33AM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 8-13-24 10:33AM
L13 PIPE TRANS SUMP NO SENSOR OUT ALARM CLEAR 8-13-24 10:33AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L 4 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L 3 STP SUMP DSL STP SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L 8 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L15 STP SUMP PNL STP SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L 7 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L14 PIPE TRANS SUMP SO SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L13 PIPE TRANS SUMP NO SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 8-13-24 10:33AM
L 8 ANNULAR UNL 2 ANN FUEL ALARM CLEAR 8-13-24 10:28AM
L 8 ANNULAR UNL 2 ANN FUEL ALARM ALARM 8-13-24 10:27AM
L 2 ANNULAR UNL 1 ANN FUEL ALARM CLEAR 8-13-24 10:27AM
L 2 ANNULAR UNL 1 ANN FUEL ALARM ALARM 8-13-24 10:26AM
L 4 ANNULAR DSL ANN FUEL ALARM CLEAR 8-13-24 10:26AM
L 4 ANNULAR DSL ANN FUEL ALARM ALARM 8-13-24 10:26AM
L 6 ANNULAR PNL ANN FUEL ALARM CLEAR 8-13-24 10:25AM
L 6 ANNULAR PNL ANN FUEL ALARM ALARM 8-13-24 10:24AM
L13 PIPE TRANS SUMP NO FUEL ALARM CLEAR 8-13-24 10:24AM
L13 PIPE TRANS SUMP NO FUEL ALARM ALARM 8-13-24 10:23AM
L14 PIPE TRANS SUMP SO FUEL ALARM CLEAR 8-13-24 10:22AM
L14 PIPE TRANS SUMP SO FUEL ALARM ALARM 8-13-24 10:22AM
L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 8-13-24 10:20AM
L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 8-13-24 10:20AM
L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 8-13-24 10:19AM
L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 8-13-24 10:19AM
L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 8-13-24 10:19AM
L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 8-13-24 10:18AM
L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 8-13-24 10:18AM
L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 8-13-24 10:17AM
L15 STP SUMP PNL STP FUEL ALARM CLEAR 8-13-24 10:17AM
L15 STP SUMP PNL STP FUEL ALARM ALARM 8-13-24 10:17AM
I11200
AUG 13, 2024 3:39 PM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 7-06-24 2:08PM
SYSTEM PRINTER ERROR ALARM 7-06-24 2:08PM
SYSTEM PAPER OUT CLEAR 7-06-24 2:08PM
SYSTEM PAPER OUT ALARM 7-06-24 2:06PM
SYSTEM PRINTER ERROR CLEAR 7-06-24 2:05PM
SYSTEM PRINTER ERROR ALARM 7-06-24 2:05PM
SYSTEM PRINTER ERROR CLEAR 6-10-24 12:57PM
SYSTEM PAPER OUT CLEAR 6-10-24 12:57PM
SYSTEM PRINTER ERROR ALARM 6-10-24 12:57PM
SYSTEM PAPER OUT ALARM 6-10-24 12:57PM
OTHER ISD GROSS PRES WARN CLEAR 5-14-24 12:59PM
OTHER ISD GROSS PRES WARN ALARM 5-09-24 10:02AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 4-04-24 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 4-03-24 10:01AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 4-02-24 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 3-31-24 10:01AM
SYSTEM PRINTER ERROR CLEAR 3-28-24 10:08AM
SYSTEM PAPER OUT CLEAR 3-28-24 10:08AM
SYSTEM PRINTER ERROR ALARM 3-28-24 10:08AM
SYSTEM PAPER OUT ALARM 3-28-24 10:08AM
OTHER ISD SENSOR OUT WARN CLEAR 3-11-24 3:15PM
OTHER ISD SENSOR OUT WARN ALARM 3-11-24 10:03AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 2-22-24 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 2-21-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 2-06-24 10:03AM
OTHER ISD GROSS PRES WARN ALARM 2-06-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 1-30-24 10:09AM
OTHER ISD GROSS PRES WARN ALARM 1-30-24 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 1-23-24 1:57PM
OTHER ISD GROSS PRES WARN ALARM 1-22-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 1-15-24 1:57PM
OTHER ISD GROSS PRES WARN ALARM 1-15-24 10:02AM
SYSTEM PRINTER ERROR CLEAR 1-13-24 12:24PM
SYSTEM PAPER OUT CLEAR 1-13-24 12:24PM
SYSTEM PAPER OUT ALARM 1-13-24 12:24PM
SYSTEM PRINTER ERROR ALARM 1-13-24 12:24PM
OTHER ISD GROSS PRES WARN CLEAR 12-31-23 10:48AM
OTHER ISD GROSS PRES WARN ALARM 12-31-23 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 12-24-23 11:07AM
OTHER ISD GROSS PRES WARN ALARM 12-24-23 10:02AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 12-22-23 11:23AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 12-21-23 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 12-17-23 5:37PM
OTHER ISD GROSS PRES WARN ALARM 12-17-23 10:02AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 12-04-23 12:24PM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 12-04-23 12:24PM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 12-04-23 10:02AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-28-23 10:03AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 10:43AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-23-23 10:02AM
I20600
AUG 13, 2024 3:39 PM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
TANK ALARM HISTORY
TANK 1 UNL 1
OVERFILL ALARM JUL 6, 2024 11:17 PM
MAY 27, 2024 1:05 PM
MAR 11, 2024 9:12 AM
TANK 2 DIESEL
LOW PRODUCT ALARM AUG 13, 2023 4:40 PM
DELIVERY NEEDED AUG 13, 2023 4:40 PM
TANK 3 PNL
OVERFILL ALARM AUG 26, 2023 12:41 PM
PROBE OUT JUL 9, 2022 7:49 AM
TANK 4 UNL 2
OVERFILL ALARM JUL 23, 2024 11:25 PM
JUL 6, 2024 11:24 PM
JUN 22, 2024 10:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
AUG 13, 2024 3:39 PM
I30200
AUG 13, 2024 3:39 PM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL 1 STP
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:14 AM FUEL ALARM
AUG 12, 2024 7:30 AM FUEL ALARM
2 UNL 1 ANN
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:26 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
3 DSL STP
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:16 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
4 DSL ANN
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:26 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
6 PNL ANN
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:24 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
7 UNL 2 STP
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:13 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
8 UNL 2 ANN
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:27 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
9 DISP 1-2
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:17 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
10 DISP 3-4
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:18 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
11 DISP 5-6
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:20 AM FUEL ALARM
AUG 10, 2024 5:34 PM FUEL ALARM
12 DISP 7-8
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:19 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
13 TRANS SUMP NO
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:23 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
14 TRANS SUMP SO
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:22 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
15 PNL STP
AUG 13, 2024 10:33 AM SENSOR OUT ALARM
AUG 13, 2024 10:17 AM FUEL ALARM
AUG 6, 2024 10:50 AM SENSOR OUT ALARM
I31600
AUG 13, 2024 3:39 PM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 3-4
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
I40200
AUG 13, 2024 3:39 PM
I40300
AUG 13, 2024 3:39 PM
I34200
AUG 13, 2024 3:39 PM
I34700
AUG 13, 2024 3:39 PM
IV0100
AUG 13, 2024 3:39 PM
FASTRIP 347
2698 OSWELL ST
BAKERSFIELD 93306
661-872-8721
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-05-14 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-13 10:01:12 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-12 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-11 10:01:11 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-10 10:01:29 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-05-09 10:02:36 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
24-04-03 10:01:24 A/L RATIO DEGRADATION FP 7 BLEND3 0.80
24-04-01 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80
24-03-31 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80
24-03-11 10:03:17 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 1:FM 1-2
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-01-24 10:02:54 A/L RATIO DEGRADATION FP 6 BLEND3 0.80
22-09-24 10:01:13 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 193.02
22-09-11 10:02:02 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 143.37
22-08-29 10:01:45 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 29.60
22-06-15 10:02:34 A/L RATIO DEGRADATION FP 7 BLEND3 0.56
22-04-19 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
15-12-16 10:01:58 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
15-12-16 10:01:58 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
15-12-15 10:01:56 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
12-08-18 10:02:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.70
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-08-13 10:36:15 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-08-13 10:36:15 ISD STARTUP
24-08-13 10:35:53 ISD SHUTDOWN
24-08-07 10:01:26 READINESS ISD:PP EVR:PP ISD & EVR READY
24-08-06 10:51:42 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-08-06 10:51:42 ISD STARTUP
24-08-06 10:51:33 ISD SHUTDOWN
24-07-22 10:02:29 READINESS ISD:PP EVR:PP ISD & EVR READY
24-07-21 16:31:47 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-07-21 16:31:47 ISD STARTUP