HomeMy WebLinkAboutFMC 2024Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10023037 08/13/2024 Jaco #3347 Fastrip #26 2698 Oswell Street Bakersfield 93306 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fsiher 1073967 10278702 03/10/2025 Veeder Root - C33847 07/24/2025 Vaporless Manufacturing LLC #5346 03/14/2025 08/13/2024 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder Root TLS350 336.02 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 Unleaded 1 STP L2 420 Unleaded 1 Annular L3 208 Diesel STP L4 420 Diesel Annular L6 420 Premium Annular L7 208 Unleaded 2 STP L8 420 Unleaded 2 Annular L9 208 Dispenser 1/2 L10 208 Dispenser 3/4 L11 208 Dispenser 5/6 L12 208 Dispenser 7/8 L13 208 Trans Sump N. L14 208 Trans Sump S. L15 208 Premium STP Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V 87 Unleaded T2 FX1V 91 Premium T3 FX1DV Diesel Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. 08/13/2024 PRICE SIG N NOPARKING EXISTING BUILDING G H CATCHBASIN W W SLOPE RETAINING WALL DRAINAGE WAY SLOPE AL6AL4AL2AL8 F V F V F V F12,000 GALLONPREMIUM12,000 GALLONDEISEL12,000 GALLON87-1 UNLEADED12,000 GALLON87-2 UNLEADEDSTPL7STPL1STPL3STPL15L10 34L912L13L1278L1156L14N AUBURN ST. PROPERTY LINE OSWELL ST.DUMPSTERCOLUMN SUPPORTINGRESTAURANT SIGN (2x) STORAGE CONTAINER LEGEND L1 87-1 STP L2 87-1 ANNULAR L3 DSL STP L4 DSL ANNULAR L6 91 ANNULAR L7 87-2 STP L8 87-2 ANNULAR L9 UDC 1 - 2 L10 UDC 3 - 4 L11 UDC 5 - 6 L12 UDC 7 - 8 L13 N TRANS SUMP L14 S TRANS SUMP L15 91 STP 87 GAS 3/2 INCH DBL WALLED PIPE 91 GAS 3/2 INCH DBL WALLED PIPE DIESEL 3/2 INCH DBL WALLED PIPE VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE VAPOR VENT 2 INCH SINGLE WALLED PIPE PRODUCT SPILL CONTAINER VAPOR SPILL CONTAINER ANNULAR EMERGENCY SHUT-OFF OVERFILL ALARM FIRE EXTINGUISHER GAS METER SHUT-OFF WATER METER SHUT-SHUT OFF HEALY CAS EVACUATION MEETING POINT AUTOMATIC TANK GUAGE CIRCUIT BREAKER UST ELECTRICAL PANEL AIR AND WATER HAZ-WASTE DRUM W G A H P V SCALE: SITE MAP C1 VICINITY MAP PROJECT DATA 1"=10'-0" INCHES012 SHEET SIZE 22 X 34 2698 OSWELL ST. BAKERSFIELD, CA 93306 PROJECT OWNER: JACO HILL PO. BOX 82515 BAKERSFIELD, CA 93380 CONTACT: SITE PLOT PLAN FOR: FACILITY ID: 15-021-00300 CERS ID 10023037 FASTRIP #3347 2698 OSWELL ST. BAKERSFIELD, CA 93306 01/10/17 REV.OSWELL ST.HWY 178 APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Jaco #3347 Fastrip #262698 Oswell StreetBakersfield100230373/47/8MPDMPDMPDMPD1/25/6ProductProductProductProductMark Fisher Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10023037 08/13/2024 Jaco #3347 Fastrip #26 2698 Oswell Street Bakersfield 93306 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fsiher 1073967 10278702 03/10/2025 OPW - 1193587 08/04/2025 PEI1200, 1 hour hydrostatic test All Spill Buckets 08/13/2024 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. 87-1 OPW 87-2 OPW 91 OPW Diesel OPW JACO #3347 SYSTEM SETUP Responses Received: 200 FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 AUG 13, 2024 10:04 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNL 1 5743 46.38 0.0 87.4 6257 2 DIESEL 2875 27.74 0.8 87.0 9125 3 PNL 4649 39.47 0.0 88.0 7351 4 UNL 2 6020 48.13 0.7 85.7 5980 I90500 AUG 13, 2024 10:04 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 AUG 13, 2024 10:04 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 AUG 13, 2024 10:04 AM SHIFT TIME 1 : 6:00 AM I50202 AUG 13, 2024 10:04 AM SHIFT TIME 2 : DISABLED I50203 AUG 13, 2024 10:04 AM SHIFT TIME 3 : DISABLED I50204 AUG 13, 2024 10:04 AM SHIFT TIME 4 : DISABLED I54600 AUG 13, 2024 10:04 AM TANK PER TST NEEDED WRN: DISABLED I54900 AUG 13, 2024 10:04 AM TANK ANN TST NEEDED WRN: DISABLED I55300 AUG 13, 2024 10:04 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 AUG 13, 2024 10:04 AM LINE PER TST NEEDED WRN: DISABLED I55900 AUG 13, 2024 10:04 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 AUG 13, 2024 10:04 AM PRINT TC VOLUMES ENABLED I50E00 AUG 13, 2024 10:04 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 AUG 13, 2024 10:04 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 AUG 13, 2024 10:04 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 AUG 13, 2024 10:04 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 AUG 13, 2024 10:04 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 AUG 13, 2024 10:04 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 AUG 13, 2024 10:04 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 AUG 13, 2024 10:04 AM TANK CHART SECURITY DISABLED I5BD00 AUG 13, 2024 10:04 AM CUSTOM ALARM LABELS DISABLED I56000 AUG 13, 2024 10:04 AM MASS/DENSITY DISABLED I88101 AUG 13, 2024 10:04 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 AUG 13, 2024 10:04 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 AUG 13, 2024 10:04 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 AUG 13, 2024 10:04 AM I88105 AUG 13, 2024 10:04 AM I88106 AUG 13, 2024 10:04 AM I52000 AUG 13, 2024 10:04 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE ??? 13, 2024 DISABLED 2 ON DATE ??? 13, 2024 DISABLED 3 ON DATE ??? 13, 2024 DISABLED 4 ON DATE ??? 13, 2024 DISABLED 5 ON DATE ??? 13, 2024 DISABLED 6 ON DATE ??? 13, 2024 DISABLED 7 ON DATE ??? 13, 2024 DISABLED 8 ON DATE ??? 13, 2024 DISABLED I60100 AUG 13, 2024 10:04 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNL 1 ON 2 DIESEL ON 3 PNL ON 4 UNL 2 ON I60200 AUG 13, 2024 10:04 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNL 1 2 DIESEL 3 PNL 4 UNL 2 I60300 AUG 13, 2024 10:04 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNL 1 1 2 DIESEL 2 3 PNL 3 4 UNL 2 4 I60900 AUG 13, 2024 10:04 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNL 1 0.000700 2 DIESEL 0.000450 3 PNL 0.000700 4 UNL 2 0.000700 I60700 AUG 13, 2024 10:04 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNL 1 96.00 2 DIESEL 96.00 3 PNL 96.00 4 UNL 2 96.00 I60A00 AUG 13, 2024 10:04 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL 1 1 PT 12000 2 DIESEL 1 PT 12000 3 PNL 1 PT 12000 4 UNL 2 1 PT 12000 I60400 AUG 13, 2024 10:04 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 1 12000 2 DIESEL 12000 3 PNL 12000 4 UNL 2 12000 I60500 AUG 13, 2024 10:04 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 1 12000 0 0 0 2 DIESEL 12000 0 0 0 3 PNL 12000 0 0 0 4 UNL 2 12000 0 0 0 I60600 AUG 13, 2024 10:04 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 1 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 DIESEL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 PNL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 UNL 2 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 AUG 13, 2024 10:04 AM TANK PRODUCT LABEL METER DATA 1 UNL 1 NO 2 DIESEL NO 3 PNL NO 4 UNL 2 NO I62F00 AUG 13, 2024 10:04 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNL 1 4.0 IN. 2 DIESEL 4.0 IN. 3 PNL 4.0 IN. 4 UNL 2 3.0 IN. I62700 AUG 13, 2024 10:04 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNL 1 2.0 2 DIESEL 2.0 3 PNL 2.0 4 UNL 2 2.0 I64200 AUG 13, 2024 10:04 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNL 1 LOW 2 DIESEL LOW 3 PNL LOW 4 UNL 2 LOW I62400 AUG 13, 2024 10:04 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNL 1 3.0 2 DIESEL 3.0 3 PNL 3.0 4 UNL 2 3.0 I62800 AUG 13, 2024 10:04 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 12000 2 DIESEL 12000 3 PNL 12000 4 UNL 2 12000 I62300 AUG 13, 2024 10:04 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 10800 2 DIESEL 10800 3 PNL 10800 4 UNL 2 10800 I62200 AUG 13, 2024 10:04 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 11400 2 DIESEL 11400 3 PNL 11400 4 UNL 2 11400 I62900 AUG 13, 2024 10:04 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 1200 2 DIESEL 1200 3 PNL 1200 4 UNL 2 1200 I62100 AUG 13, 2024 10:04 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 1200 2 DIESEL 1200 3 PNL 1200 4 UNL 2 1200 I62600 AUG 13, 2024 10:04 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 99 2 DIESEL 99 3 PNL 99 4 UNL 2 99 I62500 AUG 13, 2024 10:04 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 99 2 DIESEL 99 3 PNL 99 4 UNL 2 99 I60800 AUG 13, 2024 10:04 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNL 1 0.00 2 DIESEL 0.00 3 PNL 0.00 4 UNL 2 0.00 I60B00 AUG 13, 2024 10:04 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 AUG 13, 2024 10:04 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNL 1 0.00 2 DIESEL 0.00 3 PNL 0.00 4 UNL 2 0.00 I61200 AUG 13, 2024 10:04 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNL 1 4 NONE 2 DIESEL NONE NONE 3 PNL NONE NONE 4 UNL 2 1 NONE I63600 AUG 13, 2024 10:04 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 1 120 2 DIESEL 120 3 PNL 120 4 UNL 2 120 I62A00 AUG 13, 2024 10:04 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 1 0 2 DIESEL 0 3 PNL 0 4 UNL 2 0 I62C00 AUG 13, 2024 10:04 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNL 1 STANDARD 2 DIESEL STANDARD 3 PNL STANDARD 4 UNL 2 STANDARD I62D00 AUG 13, 2024 10:04 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNL 1 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 2 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 3 PNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 4 UNL 2 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 AUG 13, 2024 10:05 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNL 1 OFF OFF 2 DIESEL OFF OFF 3 PNL OFF OFF 4 UNL 2 OFF OFF I63000 AUG 13, 2024 10:05 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNL 1 OFF 2 DIESEL OFF 3 PNL OFF 4 UNL 2 OFF I63200 AUG 13, 2024 10:05 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNL 1 OFF 2 DIESEL OFF 3 PNL OFF 4 UNL 2 OFF I61000 AUG 13, 2024 10:05 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNL 1 1 2 DIESEL 1 3 PNL 1 4 UNL 2 1 I63A00 AUG 13, 2024 10:05 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNL 1 10.00% 2 DIESEL 10.00% 3 PNL 10.00% 4 UNL 2 10.00% I61100 AUG 13, 2024 10:05 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK JUL 23, 2010 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 AUG 13, 2024 10:05 AM CSLD PROBABLITY OF DETECTION I61400 AUG 13, 2024 10:05 AM CSLD CLIMATE FACTOR I61600 AUG 13, 2024 10:05 AM TANK PRODUCT LABEL CAL UPDATE 1 UNL 1 IMMEDIATE 2 DIESEL IMMEDIATE 3 PNL IMMEDIATE 4 UNL 2 IMMEDIATE I61A00 AUG 13, 2024 10:05 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNL 1 DISABLED 2 DIESEL DISABLED 3 PNL DISABLED 4 UNL 2 DISABLED I61B00 AUG 13, 2024 10:05 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 AUG 13, 2024 10:05 AM CSLD REPORT ONLY I62B00 AUG 13, 2024 10:05 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNL 1 ??? 0, 0 2 DIESEL ??? 0, 0 3 PNL ??? 0, 0 4 UNL 2 ??? 0, 0 I63300 AUG 13, 2024 10:05 AM LEAK TEST REPORT FORMAT: NORMAL I63400 AUG 13, 2024 10:05 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 0 2 DIESEL 0 3 PNL 0 4 UNL 2 0 I63500 AUG 13, 2024 10:05 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 1 2 DIESEL 1 3 PNL 1 4 UNL 2 1 I63900 AUG 13, 2024 10:05 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNL 1 END FACTOR: NONE 2 DIESEL END FACTOR: NONE 3 PNL END FACTOR: NONE 4 UNL 2 END FACTOR: NONE I78000 AUG 13, 2024 10:05 AM I77700 AUG 13, 2024 10:05 AM I77800 AUG 13, 2024 10:05 AM I78C00 AUG 13, 2024 10:05 AM I78300 AUG 13, 2024 10:05 AM I78F00 AUG 13, 2024 10:05 AM I78700 AUG 13, 2024 10:05 AM I70200 AUG 13, 2024 10:05 AM LIQUID LABEL DEVICE LABEL 1 UNL 1 STP 2 UNL 1 ANN 3 DSL STP 4 DSL ANN 5 6 PNL ANN 7 UNL 2 STP 8 UNL 2 ANN 9 DISP 1-2 10 DISP 3-4 11 DISP 5-6 12 DISP 7-8 13 TRANS SUMP NO 14 TRANS SUMP SO 15 PNL STP 16 UNL 1 ANN I70300 AUG 13, 2024 10:05 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL 1 STP TRI-STATE (SINGLE FLOAT) 2 UNL 1 ANN TRI-STATE (SINGLE FLOAT) 3 DSL STP TRI-STATE (SINGLE FLOAT) 4 DSL ANN TRI-STATE (SINGLE FLOAT) 5 TRI-STATE (SINGLE FLOAT) 6 PNL ANN TRI-STATE (SINGLE FLOAT) 7 UNL 2 STP TRI-STATE (SINGLE FLOAT) 8 UNL 2 ANN TRI-STATE (SINGLE FLOAT) 9 DISP 1-2 TRI-STATE (SINGLE FLOAT) 10 DISP 3-4 TRI-STATE (SINGLE FLOAT) 11 DISP 5-6 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT) 13 TRANS SUMP NO TRI-STATE (SINGLE FLOAT) 14 TRANS SUMP SO TRI-STATE (SINGLE FLOAT) 15 PNL STP TRI-STATE (SINGLE FLOAT) 16 UNL 1 ANN TRI-STATE (SINGLE FLOAT) I70400 AUG 13, 2024 10:05 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL 1 STP STP SUMP 2 UNL 1 ANN ANNULAR SPACE 3 DSL STP STP SUMP 4 DSL ANN ANNULAR SPACE 5 OTHER SENSORS 6 PNL ANN ANNULAR SPACE 7 UNL 2 STP STP SUMP 8 UNL 2 ANN ANNULAR SPACE 9 DISP 1-2 DISPENSER PAN 10 DISP 3-4 DISPENSER PAN 11 DISP 5-6 DISPENSER PAN 12 DISP 7-8 DISPENSER PAN 13 TRANS SUMP NO PIPING SUMP 14 TRANS SUMP SO PIPING SUMP 15 PNL STP STP SUMP 16 UNL 1 ANN ANNULAR SPACE I74200 AUG 13, 2024 10:05 AM I74300 AUG 13, 2024 10:05 AM I74400 AUG 13, 2024 10:05 AM I74700 AUG 13, 2024 10:05 AM I74800 AUG 13, 2024 10:05 AM I74900 AUG 13, 2024 10:05 AM I7BC00 AUG 13, 2024 10:05 AM I80200 AUG 13, 2024 10:05 AM I80300 AUG 13, 2024 10:05 AM I80400 AUG 13, 2024 10:05 AM I80700 AUG 13, 2024 10:05 AM RELAY LABEL DEVICE LABEL 1 UNL 1 2 PNL 3 DSL 4 5 OVERFILL ALARM 6 7 8 I80900 AUG 13, 2024 10:05 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL 1 NORMALLY OPEN 2 PNL NORMALLY OPEN 3 DSL NORMALLY CLOSED 4 NORMALLY OPEN 5 OVERFILL ALARM NORMALLY OPEN 6 NORMALLY OPEN 7 NORMALLY OPEN 8 NORMALLY OPEN I80B00 AUG 13, 2024 10:05 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNL 1 1 2 PNL 3 3 DSL NONE 4 NONE 5 OVERFILL ALARM NONE 6 NONE 7 NONE 8 NONE I80A00 AUG 13, 2024 10:05 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNL 1 PUMP CONTROL OUTPUT 2 PNL PUMP CONTROL OUTPUT 3 DSL STANDARD 4 STANDARD 5 OVERFILL ALARM STANDARD 6 STANDARD 7 STANDARD 8 STANDARD I80C00 AUG 13, 2024 10:05 AM I80800 AUG 13, 2024 10:05 AM RELAY SETUP REPORT R 1:UNL 1 TYPE: PUMP CONTROL OUTPUT TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 7:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 7:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PNL TYPE: PUMP CONTROL OUTPUT TANK #: 3 LIQUID SENSOR ALMS L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L15:FUEL ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L15:SENSOR OUT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L15:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DSL TYPE: STANDARD NORMALLY CLOSED TANK #: NONE LIQUID SENSOR ALMS L 3:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L 3:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 5:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM R 6: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 7: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 8: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 AUG 13, 2024 10:06 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 AUG 13, 2024 10:06 AM I72300 AUG 13, 2024 10:06 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 PS 3-4 VAPOR PRESSURE 02 FM 1-2 AIR FLOW METER 03 FM 3-4 AIR FLOW METER 04 FM 5-6 AIR FLOW METER 05 FM 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 AUG 13, 2024 10:06 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 AUG 13, 2024 10:06 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 AUG 13, 2024 10:06 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 VAPOR PROCESSOR TYPE NONE IV4700 AUG 13, 2024 10:06 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 AUG 13, 2024 10:06 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 ACCEPT HIGH ORVR: YES IV4A00 AUG 13, 2024 10:06 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 02 BLEND3 02 02 02 01 02 BLEND3 03 03 03 02 02 BLEND3 04 04 04 02 02 BLEND3 05 05 05 03 02 BLEND3 06 06 06 03 02 BLEND3 07 07 07 04 02 BLEND3 08 08 08 04 02 BLEND3 IV4B00 AUG 13, 2024 10:06 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 03/01 09/01 xx/xx 02 01 02/02 03/02 09/02 xx/xx 03 02 02/03 03/03 09/03 xx/xx 04 02 02/04 03/04 09/04 xx/xx 05 03 02/05 03/05 09/05 xx/xx 06 03 02/06 03/06 09/06 xx/xx 07 04 02/07 03/07 09/07 xx/xx 08 04 02/08 03/08 09/08 xx/xx IV4900 AUG 13, 2024 10:06 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 AUG 13, 2024 10:06 AM ISD VERSION: 01.07 JACO #3347 ALARM HISTORY BEFORE: Responses Received: I10200 AUG 13, 2024 10:07 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39557 39572 2 4 PROBE / G.T. 163015 163161 3 INTERSTITIAL BD 201752 201661 4 INTERSTITIAL BD 201230 201111 5 UNUSED 4944149 4917971 6 UNUSED 4941027 4918119 7 UNUSED 4939812 4914968 8 UNUSED 4938848 4915010 9 STP SENSE BOARD 33158 33188 10 RELAY BOARD 14944 14971 11 RELAY BOARD 14923 14908 12 UNUSED 4940499 4917576 13 UNUSED 4941316 4913368 14 UNUSED 4940436 4916265 15 UNUSED 4937880 4918528 16 UNUSED 4940457 4922546 COMM 1 ELEC DISP INT. 100495 100538 COMM 2 RS232 SERIAL BD 14902 14950 COMM 3 RS232 SERIAL BD 15007 14993 COMM 4 UNUSED 4943055 4916688 COMM 5 UNUSED 4939032 4914615 COMM 6 UNUSED 4939472 4917872 I90200 AUG 13, 2024 10:07 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 AUG 13, 2024 10:07 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 1 STP SUMP UNL 1 STP FUEL ALARM CLEAR 8-12-24 10:42AM L 1 STP SUMP UNL 1 STP FUEL ALARM ALARM 8-12-24 7:30AM L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 8-10-24 7:48PM L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 8-10-24 5:34PM L 3 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L 8 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L 7 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L15 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L14 PIPE TRANS SUMP SO SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L 4 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L13 PIPE TRANS SUMP NO SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 8-06-24 10:51AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 8-06-24 10:50AM L 4 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 8-06-24 10:50AM L 3 STP SUMP DSL STP SENSOR OUT ALARM ALARM 8-06-24 10:50AM L 8 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 8-06-24 10:50AM L15 STP SUMP PNL STP SENSOR OUT ALARM ALARM 8-06-24 10:50AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 8-06-24 10:50AM L14 PIPE TRANS SUMP SO SENSOR OUT ALARM ALARM 8-06-24 10:50AM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM ALARM 8-06-24 10:50AM L 7 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 8-06-24 10:50AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 8-06-24 10:50AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 8-06-24 10:50AM L13 PIPE TRANS SUMP NO SENSOR OUT ALARM ALARM 8-06-24 10:50AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 8-06-24 10:50AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 8-06-24 10:50AM L14 PIPE TRANS SUMP SO FUEL ALARM CLEAR 8-06-24 10:35AM L14 PIPE TRANS SUMP SO FUEL ALARM ALARM 8-06-24 10:35AM L13 PIPE TRANS SUMP NO FUEL ALARM CLEAR 8-06-24 10:33AM L13 PIPE TRANS SUMP NO FUEL ALARM ALARM 8-06-24 10:33AM L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 8-06-24 10:27AM L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 8-06-24 10:27AM L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 8-06-24 10:26AM L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 8-06-24 10:26AM L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 8-06-24 10:24AM L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 8-06-24 10:23AM L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 8-06-24 10:22AM L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 8-06-24 10:22AM L15 STP SUMP PNL STP FUEL ALARM CLEAR 8-06-24 10:20AM L15 STP SUMP PNL STP FUEL ALARM ALARM 8-06-24 10:20AM L 3 STP SUMP DSL STP FUEL ALARM CLEAR 8-06-24 10:19AM L 3 STP SUMP DSL STP FUEL ALARM ALARM 8-06-24 10:19AM L 1 STP SUMP UNL 1 STP FUEL ALARM CLEAR 8-06-24 10:18AM L 1 STP SUMP UNL 1 STP FUEL ALARM ALARM 8-06-24 10:18AM I11200 AUG 13, 2024 10:07 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 7-06-24 2:08PM SYSTEM PRINTER ERROR ALARM 7-06-24 2:08PM SYSTEM PAPER OUT CLEAR 7-06-24 2:08PM SYSTEM PAPER OUT ALARM 7-06-24 2:06PM SYSTEM PRINTER ERROR CLEAR 7-06-24 2:05PM SYSTEM PRINTER ERROR ALARM 7-06-24 2:05PM SYSTEM PRINTER ERROR CLEAR 6-10-24 12:57PM SYSTEM PAPER OUT CLEAR 6-10-24 12:57PM SYSTEM PRINTER ERROR ALARM 6-10-24 12:57PM SYSTEM PAPER OUT ALARM 6-10-24 12:57PM OTHER ISD GROSS PRES WARN CLEAR 5-14-24 12:59PM OTHER ISD GROSS PRES WARN ALARM 5-09-24 10:02AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 4-04-24 10:00AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 4-03-24 10:01AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 4-02-24 10:00AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 3-31-24 10:01AM SYSTEM PRINTER ERROR CLEAR 3-28-24 10:08AM SYSTEM PAPER OUT CLEAR 3-28-24 10:08AM SYSTEM PRINTER ERROR ALARM 3-28-24 10:08AM SYSTEM PAPER OUT ALARM 3-28-24 10:08AM OTHER ISD SENSOR OUT WARN CLEAR 3-11-24 3:15PM OTHER ISD SENSOR OUT WARN ALARM 3-11-24 10:03AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 2-22-24 10:00AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 2-21-24 10:02AM OTHER ISD GROSS PRES WARN CLEAR 2-06-24 10:03AM OTHER ISD GROSS PRES WARN ALARM 2-06-24 10:02AM OTHER ISD GROSS PRES WARN CLEAR 1-30-24 10:09AM OTHER ISD GROSS PRES WARN ALARM 1-30-24 10:03AM OTHER ISD GROSS PRES WARN CLEAR 1-23-24 1:57PM OTHER ISD GROSS PRES WARN ALARM 1-22-24 10:02AM OTHER ISD GROSS PRES WARN CLEAR 1-15-24 1:57PM OTHER ISD GROSS PRES WARN ALARM 1-15-24 10:02AM SYSTEM PRINTER ERROR CLEAR 1-13-24 12:24PM SYSTEM PAPER OUT CLEAR 1-13-24 12:24PM SYSTEM PAPER OUT ALARM 1-13-24 12:24PM SYSTEM PRINTER ERROR ALARM 1-13-24 12:24PM OTHER ISD GROSS PRES WARN CLEAR 12-31-23 10:48AM OTHER ISD GROSS PRES WARN ALARM 12-31-23 10:03AM OTHER ISD GROSS PRES WARN CLEAR 12-24-23 11:07AM OTHER ISD GROSS PRES WARN ALARM 12-24-23 10:02AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 12-22-23 11:23AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 12-21-23 10:02AM OTHER ISD GROSS PRES WARN CLEAR 12-17-23 5:37PM OTHER ISD GROSS PRES WARN ALARM 12-17-23 10:02AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 12-04-23 12:24PM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 12-04-23 12:24PM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 12-04-23 10:02AM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-28-23 10:03AM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 10:43AM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-23-23 10:02AM I20600 AUG 13, 2024 10:07 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 TANK ALARM HISTORY TANK 1 UNL 1 OVERFILL ALARM JUL 6, 2024 11:17 PM MAY 27, 2024 1:05 PM MAR 11, 2024 9:12 AM TANK 2 DIESEL LOW PRODUCT ALARM AUG 13, 2023 4:40 PM DELIVERY NEEDED AUG 13, 2023 4:40 PM TANK 3 PNL OVERFILL ALARM AUG 26, 2023 12:41 PM PROBE OUT JUL 9, 2022 7:49 AM TANK 4 UNL 2 OVERFILL ALARM JUL 23, 2024 11:25 PM JUL 6, 2024 11:24 PM JUN 22, 2024 10:05 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 AUG 13, 2024 10:07 AM I30200 AUG 13, 2024 10:07 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL 1 STP AUG 12, 2024 7:30 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:18 AM FUEL ALARM 2 UNL 1 ANN AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 9:58 AM FUEL ALARM OCT 19, 2023 11:52 AM SENSOR OUT ALARM 3 DSL STP AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:19 AM FUEL ALARM OCT 19, 2023 11:51 AM SENSOR OUT ALARM 4 DSL ANN AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 9:59 AM FUEL ALARM DEC 22, 2023 9:55 AM FUEL ALARM 6 PNL ANN AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:00 AM FUEL ALARM DEC 22, 2023 9:56 AM FUEL ALARM 7 UNL 2 STP AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:17 AM FUEL ALARM OCT 19, 2023 11:51 AM SENSOR OUT ALARM 8 UNL 2 ANN AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 9:57 AM FUEL ALARM OCT 19, 2023 11:52 AM SENSOR OUT ALARM 9 DISP 1-2 AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:26 AM FUEL ALARM OCT 19, 2023 11:51 AM SENSOR OUT ALARM 10 DISP 3-4 AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:23 AM FUEL ALARM OCT 19, 2023 11:51 AM SENSOR OUT ALARM 11 DISP 5-6 AUG 10, 2024 5:34 PM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:27 AM FUEL ALARM 12 DISP 7-8 AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:22 AM FUEL ALARM OCT 19, 2023 11:51 AM SENSOR OUT ALARM 13 TRANS SUMP NO AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:33 AM FUEL ALARM OCT 19, 2023 11:51 AM SENSOR OUT ALARM 14 TRANS SUMP SO AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:35 AM FUEL ALARM DEC 22, 2023 9:53 AM FUEL ALARM 15 PNL STP AUG 6, 2024 10:50 AM SENSOR OUT ALARM AUG 6, 2024 10:20 AM FUEL ALARM OCT 19, 2023 11:52 AM SENSOR OUT ALARM I31600 AUG 13, 2024 10:07 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PS 3-4 2 FM 1-2 3 FM 3-4 4 FM 5-6 5 FM 7-8 I40200 AUG 13, 2024 10:07 AM I40300 AUG 13, 2024 10:07 AM I34200 AUG 13, 2024 10:07 AM I34700 AUG 13, 2024 10:07 AM IV0100 AUG 13, 2024 10:07 AM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-05-14 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-13 10:01:12 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-12 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-11 10:01:11 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-10 10:01:29 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-09 10:02:36 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-04-03 10:01:24 A/L RATIO DEGRADATION FP 7 BLEND3 0.80 24-04-01 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80 24-03-31 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80 24-03-11 10:03:17 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 1:FM 1-2 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-01-24 10:02:54 A/L RATIO DEGRADATION FP 6 BLEND3 0.80 22-09-24 10:01:13 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 193.02 22-09-11 10:02:02 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 143.37 22-08-29 10:01:45 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 29.60 22-06-15 10:02:34 A/L RATIO DEGRADATION FP 7 BLEND3 0.56 22-04-19 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 15-12-16 10:01:58 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 15-12-16 10:01:58 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 15-12-15 10:01:56 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 12-08-18 10:02:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.70 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-08-07 10:01:26 READINESS ISD:PP EVR:PP ISD & EVR READY 24-08-06 10:51:42 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-08-06 10:51:42 ISD STARTUP 24-08-06 10:51:33 ISD SHUTDOWN 24-07-22 10:02:29 READINESS ISD:PP EVR:PP ISD & EVR READY 24-07-21 16:31:47 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-07-21 16:31:47 ISD STARTUP 24-07-21 16:31:01 ISD SHUTDOWN 24-05-26 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 24-05-26 02:44:44 READINESS ISD:PP EVR:NN EVR READINESS PENDING AFTER: Responses Received: I10200 AUG 13, 2024 3:39 PM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39557 39502 2 4 PROBE / G.T. 163015 162872 3 INTERSTITIAL BD 201752 201690 4 INTERSTITIAL BD 201230 200914 5 UNUSED 4944149 4918632 6 UNUSED 4941027 4913553 7 UNUSED 4939812 4919433 8 UNUSED 4938848 4917305 9 STP SENSE BOARD 33158 33166 10 RELAY BOARD 14944 14972 11 RELAY BOARD 14923 14908 12 UNUSED 4940499 4919043 13 UNUSED 4941316 4916957 14 UNUSED 4940436 4912005 15 UNUSED 4937880 4912215 16 UNUSED 4940457 4915039 COMM 1 ELEC DISP INT. 100495 100562 COMM 2 RS232 SERIAL BD 14902 14929 COMM 3 RS232 SERIAL BD 15007 14993 COMM 4 UNUSED 4943055 4916725 COMM 5 UNUSED 4939032 4917020 COMM 6 UNUSED 4939472 4913564 I90200 AUG 13, 2024 3:39 PM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 AUG 13, 2024 3:39 PM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L 8 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L 4 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L 7 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L 3 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L15 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 8-13-24 10:34AM L14 PIPE TRANS SUMP SO SENSOR OUT ALARM CLEAR 8-13-24 10:33AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 8-13-24 10:33AM L13 PIPE TRANS SUMP NO SENSOR OUT ALARM CLEAR 8-13-24 10:33AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 8-13-24 10:33AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 8-13-24 10:33AM L 4 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 8-13-24 10:33AM L 3 STP SUMP DSL STP SENSOR OUT ALARM ALARM 8-13-24 10:33AM L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM ALARM 8-13-24 10:33AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 8-13-24 10:33AM L 8 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 8-13-24 10:33AM L15 STP SUMP PNL STP SENSOR OUT ALARM ALARM 8-13-24 10:33AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 8-13-24 10:33AM L 7 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 8-13-24 10:33AM L14 PIPE TRANS SUMP SO SENSOR OUT ALARM ALARM 8-13-24 10:33AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 8-13-24 10:33AM L13 PIPE TRANS SUMP NO SENSOR OUT ALARM ALARM 8-13-24 10:33AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 8-13-24 10:33AM L 8 ANNULAR UNL 2 ANN FUEL ALARM CLEAR 8-13-24 10:28AM L 8 ANNULAR UNL 2 ANN FUEL ALARM ALARM 8-13-24 10:27AM L 2 ANNULAR UNL 1 ANN FUEL ALARM CLEAR 8-13-24 10:27AM L 2 ANNULAR UNL 1 ANN FUEL ALARM ALARM 8-13-24 10:26AM L 4 ANNULAR DSL ANN FUEL ALARM CLEAR 8-13-24 10:26AM L 4 ANNULAR DSL ANN FUEL ALARM ALARM 8-13-24 10:26AM L 6 ANNULAR PNL ANN FUEL ALARM CLEAR 8-13-24 10:25AM L 6 ANNULAR PNL ANN FUEL ALARM ALARM 8-13-24 10:24AM L13 PIPE TRANS SUMP NO FUEL ALARM CLEAR 8-13-24 10:24AM L13 PIPE TRANS SUMP NO FUEL ALARM ALARM 8-13-24 10:23AM L14 PIPE TRANS SUMP SO FUEL ALARM CLEAR 8-13-24 10:22AM L14 PIPE TRANS SUMP SO FUEL ALARM ALARM 8-13-24 10:22AM L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 8-13-24 10:20AM L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 8-13-24 10:20AM L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 8-13-24 10:19AM L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 8-13-24 10:19AM L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 8-13-24 10:19AM L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 8-13-24 10:18AM L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 8-13-24 10:18AM L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 8-13-24 10:17AM L15 STP SUMP PNL STP FUEL ALARM CLEAR 8-13-24 10:17AM L15 STP SUMP PNL STP FUEL ALARM ALARM 8-13-24 10:17AM I11200 AUG 13, 2024 3:39 PM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 7-06-24 2:08PM SYSTEM PRINTER ERROR ALARM 7-06-24 2:08PM SYSTEM PAPER OUT CLEAR 7-06-24 2:08PM SYSTEM PAPER OUT ALARM 7-06-24 2:06PM SYSTEM PRINTER ERROR CLEAR 7-06-24 2:05PM SYSTEM PRINTER ERROR ALARM 7-06-24 2:05PM SYSTEM PRINTER ERROR CLEAR 6-10-24 12:57PM SYSTEM PAPER OUT CLEAR 6-10-24 12:57PM SYSTEM PRINTER ERROR ALARM 6-10-24 12:57PM SYSTEM PAPER OUT ALARM 6-10-24 12:57PM OTHER ISD GROSS PRES WARN CLEAR 5-14-24 12:59PM OTHER ISD GROSS PRES WARN ALARM 5-09-24 10:02AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 4-04-24 10:00AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 4-03-24 10:01AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 4-02-24 10:00AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 3-31-24 10:01AM SYSTEM PRINTER ERROR CLEAR 3-28-24 10:08AM SYSTEM PAPER OUT CLEAR 3-28-24 10:08AM SYSTEM PRINTER ERROR ALARM 3-28-24 10:08AM SYSTEM PAPER OUT ALARM 3-28-24 10:08AM OTHER ISD SENSOR OUT WARN CLEAR 3-11-24 3:15PM OTHER ISD SENSOR OUT WARN ALARM 3-11-24 10:03AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 2-22-24 10:00AM h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 2-21-24 10:02AM OTHER ISD GROSS PRES WARN CLEAR 2-06-24 10:03AM OTHER ISD GROSS PRES WARN ALARM 2-06-24 10:02AM OTHER ISD GROSS PRES WARN CLEAR 1-30-24 10:09AM OTHER ISD GROSS PRES WARN ALARM 1-30-24 10:03AM OTHER ISD GROSS PRES WARN CLEAR 1-23-24 1:57PM OTHER ISD GROSS PRES WARN ALARM 1-22-24 10:02AM OTHER ISD GROSS PRES WARN CLEAR 1-15-24 1:57PM OTHER ISD GROSS PRES WARN ALARM 1-15-24 10:02AM SYSTEM PRINTER ERROR CLEAR 1-13-24 12:24PM SYSTEM PAPER OUT CLEAR 1-13-24 12:24PM SYSTEM PAPER OUT ALARM 1-13-24 12:24PM SYSTEM PRINTER ERROR ALARM 1-13-24 12:24PM OTHER ISD GROSS PRES WARN CLEAR 12-31-23 10:48AM OTHER ISD GROSS PRES WARN ALARM 12-31-23 10:03AM OTHER ISD GROSS PRES WARN CLEAR 12-24-23 11:07AM OTHER ISD GROSS PRES WARN ALARM 12-24-23 10:02AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 12-22-23 11:23AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 12-21-23 10:02AM OTHER ISD GROSS PRES WARN CLEAR 12-17-23 5:37PM OTHER ISD GROSS PRES WARN ALARM 12-17-23 10:02AM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 12-04-23 12:24PM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 12-04-23 12:24PM h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 12-04-23 10:02AM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-28-23 10:03AM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 10:43AM h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 11-23-23 10:02AM I20600 AUG 13, 2024 3:39 PM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 TANK ALARM HISTORY TANK 1 UNL 1 OVERFILL ALARM JUL 6, 2024 11:17 PM MAY 27, 2024 1:05 PM MAR 11, 2024 9:12 AM TANK 2 DIESEL LOW PRODUCT ALARM AUG 13, 2023 4:40 PM DELIVERY NEEDED AUG 13, 2023 4:40 PM TANK 3 PNL OVERFILL ALARM AUG 26, 2023 12:41 PM PROBE OUT JUL 9, 2022 7:49 AM TANK 4 UNL 2 OVERFILL ALARM JUL 23, 2024 11:25 PM JUL 6, 2024 11:24 PM JUN 22, 2024 10:05 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 AUG 13, 2024 3:39 PM I30200 AUG 13, 2024 3:39 PM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL 1 STP AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:14 AM FUEL ALARM AUG 12, 2024 7:30 AM FUEL ALARM 2 UNL 1 ANN AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:26 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 3 DSL STP AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:16 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 4 DSL ANN AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:26 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 6 PNL ANN AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:24 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 7 UNL 2 STP AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:13 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 8 UNL 2 ANN AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:27 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 9 DISP 1-2 AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:17 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 10 DISP 3-4 AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:18 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 11 DISP 5-6 AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:20 AM FUEL ALARM AUG 10, 2024 5:34 PM FUEL ALARM 12 DISP 7-8 AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:19 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 13 TRANS SUMP NO AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:23 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 14 TRANS SUMP SO AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:22 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM 15 PNL STP AUG 13, 2024 10:33 AM SENSOR OUT ALARM AUG 13, 2024 10:17 AM FUEL ALARM AUG 6, 2024 10:50 AM SENSOR OUT ALARM I31600 AUG 13, 2024 3:39 PM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 PS 3-4 2 FM 1-2 3 FM 3-4 4 FM 5-6 5 FM 7-8 I40200 AUG 13, 2024 3:39 PM I40300 AUG 13, 2024 3:39 PM I34200 AUG 13, 2024 3:39 PM I34700 AUG 13, 2024 3:39 PM IV0100 AUG 13, 2024 3:39 PM FASTRIP 347 2698 OSWELL ST BAKERSFIELD 93306 661-872-8721 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-05-14 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-13 10:01:12 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-12 10:01:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-11 10:01:11 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-10 10:01:29 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-05-09 10:02:36 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79 24-04-03 10:01:24 A/L RATIO DEGRADATION FP 7 BLEND3 0.80 24-04-01 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80 24-03-31 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.80 24-03-11 10:03:17 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 1:FM 1-2 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-01-24 10:02:54 A/L RATIO DEGRADATION FP 6 BLEND3 0.80 22-09-24 10:01:13 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 193.02 22-09-11 10:02:02 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 143.37 22-08-29 10:01:45 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 29.60 22-06-15 10:02:34 A/L RATIO DEGRADATION FP 7 BLEND3 0.56 22-04-19 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 15-12-16 10:01:58 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 15-12-16 10:01:58 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 15-12-15 10:01:56 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 12-08-18 10:02:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.70 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-08-13 10:36:15 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-08-13 10:36:15 ISD STARTUP 24-08-13 10:35:53 ISD SHUTDOWN 24-08-07 10:01:26 READINESS ISD:PP EVR:PP ISD & EVR READY 24-08-06 10:51:42 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-08-06 10:51:42 ISD STARTUP 24-08-06 10:51:33 ISD SHUTDOWN 24-07-22 10:02:29 READINESS ISD:PP EVR:PP ISD & EVR READY 24-07-21 16:31:47 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-07-21 16:31:47 ISD STARTUP