Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ☐ Installation ☐ Repair ☒ 12 Month
1. FACILITY INFORMATION
CERS ID
10022950
Certification Date
8/30/2024
Facility Name
Ming ARCO AM/PM
Facility Address
4203 Ming Ave.
City
Bakersfield
ZIP Code
93309
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification
Advanced Compliance
Phone
661-706-4321
Mailing Address
4007 Brae Burn Dr Bakersfield Ca. 93306
Service Technician Performing Test
Bruce W. Hinsley
Contractor/Tank Tester License Number
971259
ICC Number
8032698
ICC Expiration Date
6/26/2025
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
Veeder-Root 4/21/2026
Redjacket LLD 1/4/2026
VMI 1/4/2026
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is
attached; and all information contained herein is accurate.
Service Technician Signature Date
8/30/2024
Total # of Pages
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Veeder-Root
Model of Monitoring System
Control Panel
TLS-350
Software Version Installed
336.01
Attach the post-certification reports if the monitoring system is capable of generating either;
X Monitoring System Set-up X Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? X ☐
Secondary containment systems are free of damage, debris, or liquid? X ☐
Are the audible and visual alarms operational? X ☐
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on
floats; and 2) tested for functionality and confirmed operational? X ☐ ☐
Are all sensors installed to detect a release at the earliest opportunity in the secondary
containment? X ☐ ☐
The monitoring system set-up was reviewed, and proper settings confirmed? X ☐ ☐
Was the monitoring control panel’s backup battery visually inspected, functionally tested,
and confirmed operational? X ☐ ☐
Does the flow of fuel stop at the dispenser if a release is detected in the under-dispenser
containment? X ☐ ☐
Does the turbine automatically shut down if the piping secondary containment monitoring
system fails to operate or is electrically disconnected? X ☐ ☐
Does the turbine automatically shut down if the piping secondary containment monitoring
system detects a release? Which sensors initiate positive shut down? (Check all that apply)
X Sump X UDC
X ☐ ☐
If monitoring system alarms are relayed to a remote monitoring center, is all communication
equipment operational? ☐ ☐ X
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming.
Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
L-1 794390-409 87 T1 Tank Annular X ☐
L-2 794380-208 87 T1 STP Sump X ☐
L-3 794380-208 87 T1 Fill Sump X ☐
L-4 794390-409 87 T2 Tank Annular X ☐
L-5 794380-208 87 T2 STP Sump X ☐
L-6 794380-208 87 T2 Fill Sump X ☐
L-7 794390-409 87 T3 Tank Annular X ☐
L-8 794380-208 87 T3 STP Sump X ☐
L-9 794380-208 87 T3 Fill Sump X ☐
L-10 794390-409 91 Tank Annular X ☐
L-11 794380-208 91 Fill Sump X ☐
L-12 794380-208 91 STP Sump X ☐
L-13 794380-208 UDC 1-2 X ☐
L-14 794380-208 UDC 3-4 X ☐
L-15 794380-208 UDC 5-6 X ☐
L-16 794380-208 UDC 7-8 X ☐
L-17 794380-208 UDC 9-10 X ☐
L-18 794380-208 UDC 11-12 X ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
7. LINE LEAK DETECTOR TESTING
☐ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
X 3 GPH ☐ 0.1 GPH ☐ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? X ☐ ☐
For emergency generator tank systems, does the LLD create an audible and visual alarm
when a leak is detected? ☐ ☐ X
For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is
detected? ☐ ☐ X
For electronic LLDs, does the turbine automatically shut off when a release is detected? X ☐ ☐
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring
system is disabled or disconnected? X ☐ ☐
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring
system malfunctions or fails a tightness test? X ☐ ☐
For electronic LLDs, have all accessible wiring connections been visually inspected for
kinks and breaks? X ☐ ☐
Were all items on the equipment manufacturer’s maintenance checklist completed? X ☐ ☐
Were all LLDs confirmed operational within regulatory requirements? X ☐ ☐
LLD ID LLD Model Lines Monitored Pass Fail
87 PLLD 87 X ☐
91 PLLD 91 X ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
8. IN-TANK GAUGING TESTING
X Check this box if tank gauging is used only for inventory control.
☐ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination;
and 2) tested for ground faults? ☐ ☐ ☐
Were all in-tank gauging probes visually inspected for damage and residue buildup to
ensure that floats move freely, functionally tested, and confirmed operational? ☐ ☐ ☐
Was accuracy of system’s product level readings tested? ☐ ☐ ☐
Was accuracy of system’s water level readings tested? ☐ ☐ ☐
Were all probes reinstalled properly? ☐ ☐ ☐
Were all items on the equipment manufacturer’s maintenance checklist completed? ☐ ☐ ☐
Probe ID Probe Model Tanks Monitored Pass Fail
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
☐ ☐
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
Tank #2 & #3 spill containers fail testing due to leaking drain valves.
Ver. 1.5 – 08.20.14
Shear Valve Operation Test
CERS ID: 10022950 Test Company: Advanced Compliance
Site Name: Ming ARCO AM/PM Technician: Bruce W. Hinsley
Site Address: 4203 Ming Ave. Certification Number Expiration Date
City: Bakersfield Zip: 93309 ICC (SERVICE TECH): 8032698 6/25/2025
Date/Time of Test: 8/2/30024 09:00
Product
Grade
Dispenser
Number
1.Shear Valve
Type
(Product or
Vapor)
2. Is the
shear valve
properly
anchored?
3. Is the shear valve
within ½ in of dispenser
island?
4. Is the lever arm
free moving?
5. Does the lever
arm close poppet
valve?
6. Can you Dispense
with shear valve in
closed position?
Pass / Fail
87 1-2 P Y Y Y Y No Pass
91 1-2 P Y Y Y Y No Pass
87 3-3 P Y Y Y Y No Pass
91 3-4 P Y Y Y Y No Pass
87 5-6 P Y Y Y Y No Pass
91 5-6 P Y Y Y Y No Pass
87 7-8 P Y Y Y Y No Pass
91 7-8 P Y Y Y Y No Pass
87 9-10 P Y Y Y Y No Pass
91 9-10 P Y Y Y Y No Pass
87 11-12 P Y Y Y Y No Pass
91 11-12 P Y Y Y Y No Pass
.
Signature of Technician: ___________________________ Date: 8/30/2024
Advanced Compliance
4007 Brae Burn Drive
Bakersfield, Ca. 93306
661-706-4321 Fax# 661-589-9329
VAPORLESS MANUFACTURING, INC.
LDT-890 Leak Detector Test Record
Contractor: Advanced Compliance Customer: ARCO AMPM
Date: 8/30/2024 Location: 4302 Ming Ave. Bakersfield, Ca.
Product: 87 UL Technician: Bruce W. Hinsley
Submersible Pump Identification
Manufacturer: Redjacket Model No.:
Serial No.: Notes:
Leak Detector Identification
Manufacturer: Veeder-Root Description: PLLD
Diaphragm-type: Piston-type:
Tamper-proof seal installed: Other Style Leak Detector: Electronic
Notes:
Leak Detector in Submersible Pump Test at Dispenser
Operating Pump Pressure (psi): 27 (para. 15)
Gallons per hour rate: 3.0 (para. 22)
Line pressure with pump shut off (psi): 20 (para. 23)
Bleed-back Test with pump off (ml): 100 (para. 26)
Step-through time to full flow (secs): N/A (para. 30)
Leak detector stays in leak search position (Yes/No): N/A (para. 42)
Leak Detector Test
Pass / Fail Notes:
Pass
*Complete thermal expansion test before failing leak detector
Advanced Compliance
4007 Brae Burn Drive
Bakersfield, Ca. 93306
661-706-4321 Fax# 661-589-9329
VAPORLESS MANUFACTURING, INC.
LDT-890 Leak Detector Test Record
Contractor: Advanced Compliance Customer: ARCO AMPM
Date: 8/30/2024 Location: 4302 Ming Ave. Bakersfield, Ca.
Product: 91 UL Technician: Bruce W. Hinsley
Submersible Pump Identification
Manufacturer: Redjacket Model No.:
Serial No.: Notes:
Leak Detector Identification
Manufacturer: Veeder-Root Description: PLLD
Diaphragm-type: Piston-type:
Tamper-proof seal installed: Other Style Leak Detector: Electronic
Notes:
Leak Detector in Submersible Pump Test at Dispenser
Operating Pump Pressure (psi): 28 (para. 15)
Gallons per hour rate: 3.0 (para. 22)
Line pressure with pump shut off (psi): 21 (para. 23)
Bleed-back Test with pump off (ml): 95 (para. 26)
Step-through time to full flow (secs): N/A (para. 30)
Leak detector stays in leak search position (Yes/No): N/A (para. 42)
Leak Detector Test
Pass / Fail Notes:
Pass
*Complete thermal expansion test before failing leak detector
CERS = California Environmental Reporting System, ID = Identification, UST = Underground storage tank, ICC = International Code Council
UNDERGROUND STORAGE TANK
SPILL CONTAINER TESTING REPORT FORM (Page 1 of 1)
Type of Action Installation Test Repair Test 12 Month Test
I. FACILITY INFORMATION
CERS ID
10022950
Date of Spill Container Test
8/30/2024
Business Name (Same as Facility Name or DBA-Doing Business As.)
Ming ARCO AM/PM
Business Site Address
4203 Ming Ave.
City
Bakersfield
ZIP Code
93309
II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION
Name of UST Service Technician Performing the Test (Print as shown on the ICC Certification.)
Bruce W. Hinsley
Phone #
(661) 706 - 4321 Ext.
Contractor/Tank Tester License #
971259
ICC Certification #
8032698
ICC Certification Expiration Date
6/25/2025
Spill Container Testing Training and Certifications (List applicable certifications.)
III. SPILL CONTAINER TESTING INFORMATION
Test Method Used:
Manufacturer Guidelines: (Specify)
Industry Code or Engineering Standard: (Specify) Industry Standard
Engineered Method: (Specify)
Attach the testing procedures and all documentation required to determine the results. # of Attached Pages
Tank ID: (By tank number, stored product, etc.) T1 87 T2 87 T3 87 T4 91
Spill Container Manufacturer: OPW OPW OPW OPW
Method of Cathodic Protection
Non-Metallic Non-Metallic Non-Metallic Non-Metallic
Isolation Isolation Isolation Isolation
Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.)
Inside Diameter of Spill Container: (Inches) 15" 15" 15" 15"
Depth of Spill Container: (Inches) 20" 20" 20" 20'
Does the spill container have a 5 gallon capacity? Yes No Yes No Yes No Yes No
Method to Keep Spill Container Empty
Drain Valve Drain Valve Drain Valve Drain Valve
Onsite Pump Onsite Pump Onsite Pump Onsite Pump
Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.) Other
(Specify in section V.)
IV. SUMMARY OF TESTING RESULTS
Spill Container Test Results Pass Fail Pass Fail Pass Fail Pass Fail
V. COMMENTS
All items marked “Fail” above must be explained in this section. Any additional comments may also be provided here.
Tank #2 & #3 spill containers fail testing due to leaking drain valves.
VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS TESTING
I hereby certify that the spill containers were tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section
2637.1 and all the information contained herein is accurate.
UST Service Technician Signature
If the facility has more components than this form accommodates, additional copies of this page may be attached.