HomeMy WebLinkAbout5710_Bakersfield CA _Final_CERT_241018Providers for MDleak® MSleak® DPleak®, MCleak® and
PHDleak® Testing Technologies
Page 1 of 2
Test Type: Job #: 5710
Facility Name: PO #:
Prepared For:
Site Address:
City:
State and Zip: CA 93307
Start Date:End Date:
SYSTEM Test MDL TK-1 87 TK-2 91 TK-3 DSL TK-4 E-85 VR
Product Primary MDleak:0.005 GPH PASS PASS PASS PASS
Product Secondary:0.1 GPH PASS PASS PASS PASS
Vent Primary MDleak:0.005 GPH PASS PASS PASS PASS
Vent Secondary:0.1 GPH PASS PASS PASS PASS
VR Primary MDleak:0.005 GPH PASS PASS NA NA
VR Secondary:0.1 GPH PASS PASS PASS PASS
MDleak Tank:0.005 GPH PASS PASS PASS PASS
Turbine Sump Fittings:0.005 GPH PASS PASS PASS PASS
Fill/Vapor Sump Fittings:0.005 GPH PASS PASS PASS PASS
UDC Fittings:0.005 GPH PASS PASS PASS PASS
Vent Box Fittings 0.005 GPH PASS PASS PASS PASS
10/10/2024
Complete Fueling Solutions
Facility Certification CONFIDENTIAL
California ELD New Construction Test
Arco AMPM
1631 Hosking Ave
Bakersfield
10/11/2024
Providers for MDleak® MSleak® DPleak®, MCleak® and
PHDleak® Testing Technologies
Page 2 of 2
Test Type:
Facility Name: Job #: 5710
Prepared For: PO #:
Site Address:
City:
State and Zip: CA 93307
Start Date:End Date:
SYSTEM TK-1 87 TK-2 91 TK-3 DSL TK-4 E-85 VR
20000 10000 12000 10000
Modern Modern Modern Modern
Dry Dry Dry Dry
Tank Sump Boots Turbine
8.00 0 0 0
Manufacture
EVR:
Certifying Field Technician: State Lic. # : 21-1772
Certification Leak Rate: 0.005gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date:
Arco AMPM
Complete Fueling Solutions
Flex:
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National
Workgroup on Leak Detection Evaluations (NWGLDE) organization and that the information contained in this report is
true and correct to the best of my knowledge.
This is a statement to confirm that the components listed above, at the time of testing, have been tested to a leak
sensitivity listed above by using one or more of the following DPleak®, MDleak®, MCleak and PHDleak® EPA aproved
Methods. These Methods are the most versatile and comprehensive testing procedures offered to the petroleum
industry. All petroleum owners and contractors which utilize the DPleak®, MDleak®, MCleak, and PHDleak® Method can
be assured that their facility has passed the Nation's highest standard in preventative leak detection.
Facility Certification CONFIDENTIAL
California ELD New Construction Test
1631 Hosking Ave
Bakersfield
Office use only
10/18/2024
Depth to Ground Water:
Component Manufacture:
UDC/Dispensers Information
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Containment Boots:
Piping Information
Product Lines:
Vapor Return / Vent:
Depth of Liquid Within Tank:
10/11/2024
10/10/2024 10/11/2024
Ben Getz
Spill Buckets:
Tank Volume in Gallons:
UST Manufacture:
Type of Interstice:
Depth To Top Tank:
Tank Diameter: