HomeMy WebLinkAboutOPI 2024CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council, OPE = Overfill Prevention Equipment
Page 1 of 2
TYPE OF ACTION Installation Repair 36 Month
1. FACILITY INFORMATION
CERS ID Inspection Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Inspection Phone
Mailing Address
Service Technician Performing Inspection
Contractor/Tank Tester License Number
ICC Number Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. INSPECTION PROCEDURES INFORMATION
Inspection Procedures Used Components Inspected
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING INSPECTION
I hereby certify that the OPE was inspected in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.2; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date Total # of Pages
Additional copies of this page may be attached.
Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s)
Page 2 of 2
6. OVERFILL PREVENTION EQUIPMENT DETAILS
Tank ID (one OPE per column)
Are both vent and tank riser piping
secondarily contained?
Yes
No
Yes
No
Yes
No
Yes
No
OPE Model
What is the OPE response when
activated?
(Check all that apply.)
Shut off
Flow
Restricts
Flow
Audible
Alarm
Visual
Alarm
Shut off
Flow
Restricts
Flow
Audible
Alarm
Visual
Alarm
Shut off
Flow
Restricts
Flow
Audible
Alarm
Visual
Alarm
Shut off
Flow
Restricts
Flow
Audible
Alarm
Visual
Alarm
Are flow restrictors installed on vent piping
that may interfere with the OPE operation?
Yes*
No
Yes*
No
Yes*
No
Yes*
No
At what level in the tank is the OPE set to
activate? (Inches from bottom of tank)
What is the percent capacity of the tank at
which the OPE activates?
Is the OPE in proper operating condition to
respond when the stored substance
reaches the designated regulatory level?
Yes
No
Yes*
No
Yes*
No
Yes*
No
7. SUMMARY OF TESTING RESULTS
OPE Inspection Results Pass
Fail
Pass
Fail
Pass
Fail
Pass
Fail
1
8. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
* Mark here if:
Flow restrictors interfere with overfill prevention and equipment repairs required.
90
9684
44
54 1/2
79 1/2
10 1/2
9126
94
T1 87MCK 2708605
90
9684
94
41
51 3/4
10 3/4
79 1/4
9105
T2 89CK 2708605
90
9684
94
41
51 3/4
10 3/4
79 1/4
9105
T3 91CK 2708605
<
I10100
OCT 25, 2024 11:37 AM
CIRCLE K 2708605
5600 AUBURN ST
BAKERSFIELD CA,93306
661-871-7979
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
>
<
I20100
OCT 25, 2024 11:37 AM
CIRCLE K 2708605
5600 AUBURN ST
BAKERSFIELD CA,93306
661-871-7979
IN-TANK INVENTORY
TANK PRODUCT VOLUME TC VOLUME ULLAGE HEIGHT
WATER TEMP
1 UNL Premium 4386 4308 5298 41.18
0.00 85.44
2 UNL Plus NoBlend 4023 3936 5661 38.58
0.00 90.80
3 UNL Regular 6906 6800 2778 59.49
0.00 81.90
>
<
I51700
OCT 25, 2024 11:37 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
>
<
I60100
OCT 25, 2024 11:37 AM
1
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNL Premium ON
2 UNL Plus NoBlend ON
3 UNL Regular ON
4 87 UNLEADED OFF
>
<
I60200
OCT 25, 2024 11:37 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNL Premium
2 UNL Plus NoBlend
3 UNL Regular
4 87 UNLEADED
>
<
I60300
OCT 25, 2024 11:37 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNL Premium C
2 UNL Plus NoBlend B
3 UNL Regular A
4 87 UNLEADED 4
>
<
I60400
OCT 25, 2024 11:38 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL Premium 9684
2 UNL Plus NoBlend 9684
3 UNL Regular 9684
4 87 UNLEADED 9684
>
<
I60700
OCT 25, 2024 11:38 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
2
1 UNL Premium 90.00
2 UNL Plus NoBlend 90.00
3 UNL Regular 90.00
4 87 UNLEADED 90.00
>
<
I60900
OCT 25, 2024 11:38 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNL Premium 0.000700
2 UNL Plus NoBlend 0.000700
3 UNL Regular 0.000700
4 87 UNLEADED 0.000070
>
<
I61200
OCT 25, 2024 11:38 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE
MANIFOLDED TANKS
1 UNL Premium NONE NONE
2 UNL Plus NoBlend NONE NONE
3 UNL Regular NONE NONE
4 87 UNLEADED NONE NONE
>
<
I62200
OCT 25, 2024 11:38 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL Premium 9200
2 UNL Plus NoBlend 9200
3 UNL Regular 9200
4 87 UNLEADED 9325
>
<
I62300
OCT 25, 2024 11:38 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL Premium 8716
2 UNL Plus NoBlend 8716
3 UNL Regular 8716
3
4 87 UNLEADED 8834
>
<
I62400
OCT 25, 2024 11:38 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNL Premium 1.0
2 UNL Plus NoBlend 1.0
3 UNL Regular 1.0
>
<
I62800
OCT 25, 2024 11:38 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL Premium 9684
2 UNL Plus NoBlend 9684
3 UNL Regular 9684
4 87 UNLEADED 9816
>
<
I62900
OCT 25, 2024 11:38 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL Premium 982
2 UNL Plus NoBlend 982
3 UNL Regular 982
4 87 UNLEADED 982
>
<
I70300
OCT 25, 2024 11:38 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87 ANNULAR TRI-STATE (SINGLE FLOAT)
2 87 TURBINE TRI-STATE (SINGLE FLOAT)
3 89 ANNULAR TRI-STATE (SINGLE FLOAT)
4 89 TURBINE TRI-STATE (SINGLE FLOAT)
5 91 ANNULAR TRI-STATE (SINGLE FLOAT)
6 91 TURBINE TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
4
>
<
I20600
OCT 25, 2024 11:38 AM
CIRCLE K 2708605
5600 AUBURN ST
BAKERSFIELD CA,93306
661-871-7979
TANK ALARM HISTORY
TANK 1 UNL Premium
PROBE OUT JUL 18, 2022 3:03 PM
HIGH WATER WARNING NOV 21, 2023 12:40 PM
TANK 2 UNL Plus NoBlend
PROBE OUT JUL 18, 2022 3:03 PM
TANK 3 UNL Regular
LOW PRODUCT ALARM MAR 25, 2024 11:41 AM
AUG 28, 2023 4:54 PM
INVALID FUEL LEVEL MAR 25, 2024 11:41 AM
PROBE OUT JUL 18, 2022 3:03 PM
DELIVERY NEEDED SEP 10, 2024 4:49 PM
MAR 24, 2024 7:37 PM
DEC 19, 2023 7:51 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
5
TANK 13
TANK 14
TANK 15
TANK 16
>
<
I30200
OCT 25, 2024 11:41 AM
CIRCLE K 2708605
5600 AUBURN ST
BAKERSFIELD CA,93306
661-871-7979
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 ANNULAR
OCT 25, 2024 8:55 AM FUEL ALARM
OCT 25, 2024 8:55 AM FUEL ALARM
OCT 11, 2023 6:23 AM FUEL ALARM
2 87 TURBINE
OCT 25, 2024 8:52 AM FUEL ALARM
OCT 25, 2024 8:52 AM FUEL ALARM
OCT 25, 2024 8:50 AM FUEL ALARM
3 89 ANNULAR
OCT 25, 2024 9:00 AM FUEL ALARM
OCT 10, 2023 10:31 AM FUEL ALARM
OCT 10, 2023 10:26 AM FUEL ALARM
4 89 TURBINE
OCT 25, 2024 8:52 AM FUEL ALARM
OCT 10, 2023 10:09 AM FUEL ALARM
OCT 13, 2022 10:10 AM FUEL ALARM
5 91 ANNULAR
OCT 25, 2024 9:02 AM FUEL ALARM
OCT 25, 2024 9:02 AM FUEL ALARM
OCT 10, 2023 10:37 AM FUEL ALARM
6 91 TURBINE
OCT 25, 2024 8:53 AM FUEL ALARM
OCT 10, 2023 10:08 AM FUEL ALARM
OCT 13, 2022 10:09 AM FUEL ALARM
>
<
I10100
OCT 25, 2024 11:41 AM
6
CIRCLE K 2708605
5600 AUBURN ST
BAKERSFIELD CA,93306
661-871-7979
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
>
<
I90200
OCT 25, 2024 11:41 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
>
7