HomeMy WebLinkAbout5573_Bakersfield CA_IS-ELD_Interim ReportExclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 1 of 2
Test Type:
Facility Name: Job #: 5573
Prepared For: PO #:
Site Address:
City: Primary Test Leak Rate: 0.005gph
State and Zip: CA 93309 Secondary Test Leak Rate: NA
Start Date:End Date:
SYSTEM Test MDL TK-1 87 TK-2 89 TK-3 91 TK-4 DSL VR
MDleak ELD Tank:0.005 GPH PASS FAIL PASS Inconclusive
Fill Spill Bucket Hydo:0.1 GPH PASS PASS PASS PASS
Vapor Bucket Hydro:0.1 GPH PASS PASS PASS NA
Certifying Field Technician: Ricardo Gonzalez State Lic. # :
Certification Leak Rate: 0.005gph
Certifying Technician Signature: Date:
Statement Confirmed by: Date: 12/13/2024
This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak
sensitivity listed above by using one or more of the following DPleak®,MDleak®and PHDleak®EPA aproved Methods.
The DPleak®,MDleak®and PHDleak®Methods are the most versatile and comprehensive testing procedures offered to
the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®and PHDleak®Method
can be assured that their facility has passed the Nation's highest standard in preventative leak detection.
I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National
Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is
true and correct to the best of my knowledge.
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
Office use only
04-1695
Fast Break Mobil
4800 White Lane
Bakersfield
5/3/2024 6/19/2024
Fast Break Mobil
ELD Well Proximity Interim Report CONFIDENTIAL
ELD Well Proximity Interim Report
Exclusive Providers for MDleak® MSleak® DPleak® and
PHDleak® Testing Technologies
Page 2 of 2
4800 White Lane Log of Repaired Leak/s
CONFIDENTIAL
TK-1 87 TK-2 89 TK-3 91 TK-4 DSL VR
Tank Volume: 10000 10000 10000 10000 10000 10000 10000 10000
Manufacture: Other Steel Other Steel Other Steel Other Steel
Interstice: Single Wall Single Wall Single Wall Single Wall
Depth To Tank:
Tank Dia:
Depth to Fuel:
Tank Sump Boots Turbine
Tank Sump Penetration Turbine
6
EVR:
Reference #Date Time Status System Component Manufacture
12 5/3/24 8:55 Leak Pretest TK-2 89 Fill bucket
Reference #Date Time Status System Component Manufacture
Log of Unrepaired Leaks
Spill Buckets:
Log of Repaired Leaks
Manufacture
Product Lines:
Vapor Return / Vent:
Flex:
Shear Valve Manufacture:
Containment Boots:
Piping Information
Manufacture:
Manufacture:
UDC/Dispensers Information
Number of Dispensers:
Depth to Ground Water:
Tank Information