HomeMy WebLinkAbout2024-12-17 HAZMAT Inspection 5677 Gosford Rd - Buffalo Wild Wings.pdfCurrent Date:12/17/2024 16:05
Occupant:Buffalo Wild Wings 3527 Inspection
Date:
12/17/2024
Occupant Name:Buffalo Wild Wings 3527 Inspection Date:12/17/2024
Street Number:5677 Occupant Code:97751
Street Name:Gosford City:Bakersfield
Street Type:Road Postal Code:93311
Inspector:Pisano , Liseth State:California
Passed:No
Inspection Type:Hazmat Annual
Violations
Violation
Code Description
5307.3.2 Gas detection system.
Where ventilation is not provided in accordance with Section 5307.3.1, a gas detection system shall be
provided in rooms or indoor areas and in below-grade outdoor locations with insulated carbon dioxide
systems. Carbon dioxide sensors shall be provided within 12 inches (305 mm) of the floor in the area where
the gas is expected to accumulate or other approved locations. The system shall be designed as follows:
1.Activates an audible and visible supervisory alarm at a normally attended location upon detection of a
carbon dioxide concentration of 5,000 ppm (9000 mg/m3).
2.Activates an audible and visible alarm within the room or immediate area where the system is installed upon
detection of a carbon dioxide concentration of 30,000 ppm (54 000 mg/m3).
Violation Count:1 Inspection Fee:0.00
Type First Name Last Name Signature Date Signature Graphic
Owner/Rep.Melissa Lamb 12/17/2024
Inspector Liseth Pisano 12/17/2024
Conducted an annual hazardous materials inspection. The following must be corrected within 24 hours.
1. The CO2 monitor must be repaired. It is turned off.
Complete Inspection Report - With Documents
Facility Information
Inspection Information
Signatures
Inspection Notes
Documents
Page 1 of 4
Occupant:Buffalo Wild Wings 3527 Inspection
Date:
12/17/2024
Current Date:12/17/2024 16:05
Inspection Documents
Violation Documents
Location Attributes:Commercial Hood; Fire Alarm; Fire Safety; HMBP; Sprinkler System
Admin Information
Page 2 of 4
Occupant:Buffalo Wild Wings 3527 Inspection
Date:
12/17/2024
Current Date:12/17/2024 16:05
HazMat - HMBP
Administration/Documentation
Question Answer Notes
Did the facility adequately establish and
implement a business plan when
storing/handling a hazardous material at
or above reportable quantities in CERS?
Yes
Did the facility annually review and
electronically certify in CERS that the
business plan is complete and accurate
on or before the required due date?
Yes
Does the facility have a copy of the
business plan readily available with
responsibilities for emergency response
or training for review?
Yes
Did the facility update CERS within 30
days of any one or more of the following
events: 1) A 100 percent or more
increase in the quantity of a previously
disclosed material. 2) Any handling of a
previously undisclosed hazardous
materials at or above reportable
quantities. 3) A change of business
address, business ownership, or business
name. 4) A substantial change in the
handler's operations that requires
modification to any portion of the
business plan.
Yes
Did the facility inform the property
owner in writing that an HMBP is
required for the facility?
Yes
Did the facility provide the property
owner a copy of the HMBP upon
request??
Yes
Did the facility report complete or
accurate information in the Business
Activities Page and/or Business Owner
Operator Identification Page in CERS?
Yes
Did the facility report complete and
accurate hazardous material inventory
information for all hazardous materials
on site at or above reportable quantities
in CERS?
Yes
Did the facility adequately establish an
emergency response plan in CERS?Yes
Did the facility submit a site map with all
the required content in CERS?Yes
Training
Question Answer Notes
Did the facility submit an adequate
training program with safety procedures
in the event of a release or threatened
release of a hazardous material in CERS?
Yes
Page 3 of 4
Occupant:Buffalo Wild Wings 3527 Inspection
Date:
12/17/2024
Current Date:12/17/2024 16:05
Did the facility provide initial and
refresher training to all employees and
maintain records for 3 years?
Yes
Operations/Maintenance
Question Answer Notes
Does the facility have adequate signage
for hazardous materials storage?Yes
Are hazardous materials separated form
incompatibles?Yes
Release/Leaks/Spills
Question Answer Notes
Did the facility fail to report a release or
threatened release of a hazardous
material to the unified program agency
and to Cal OES?
N/A
Page 4 of 4