Loading...
HomeMy WebLinkAbout5556WP_Bakersfield CA_CERT 7-18-2024Exclusive Providers for MDleak® MSleak® DPleak® and PHDleak® Testing Technologies Page 1 of 2 Test Type: Facility Name: Job #: 5556 Prepared For: PO #: Site Address: City: Primary Test Leak Rate: State and Zip: CA 93304 Secondary Test Leak Rate: Start Date:End Date: SYSTEM Test MDL TK-1-87 TK-2-91 Product Primary:0.005 GPH PASS PASS MDleak ELD Tank:0.005 GPH PASS PASS Turbine Sump:0.005 GPH PASS PASS Fill/Vapor Sump:0.005 GPH PASS PASS UDC's:0.005 GPH PASS PASS Fill Bucket Primary:0.005 GPH PASS PASS Vapor Bucket Primary:0.005 GPH PASS PASS Fill Spill Bucket Hydo:0.1 GPH PASS PASS Vapor Bucket Hydro:0.1 GPH PASS PASS Certifying Field Technician: Ricardo Gonzalez State Lic. # : Certification Leak Rate: Certifying Technician Signature: Date: Statement Confirmed by: Date: Eagle Fuel Facility Certification CONFIDENTIAL California ELD Well Proximity Test W/Fuel Eagle Fuel 3401 S. Chester Ave Bakersfield 6/21/2024 8/1/2024 04-1695 7/18/2024 7/18/2024 This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak sensitivity listed above by using one or more of the following DPleak®,MDleak®and PHDleak®EPA aproved Methods. The DPleak®,MDleak®and PHDleak®Methods are the most versatile and comprehensive testing procedures offered to the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®and PHDleak®Method can be assured that their facility has passed the Nation's highest standard in preventative leak detection. I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is true and correct to the best of my knowledge. If you have any questions on the testing please do not hesitate to call. @ 855-255-5325. Office use only Exclusive Providers for MDleak® MSleak® DPleak® and PHDleak® Testing Technologies Page 2 of 2 3401 S. Chester Ave Log of Repaired Leak/s CONFIDENTIAL TK-1-87 TK-2-91 Tank Volume: 10000 10000 Manufacture: Other Steel Other Steel Interstice: Single Wall Single Wall Depth To Tank: 42"41' Tank Dia: 8 ft 8 ft Depth to Fuel: 120"114" Tank Sump Boots Turbine Unknown Unknown Red Jacket 4 Gilbarco OPW Unknown APT Smith Unknown OPW EVR: Healy Reference #Date Time Status System Component Manufacture 20 6/21/24 11:08 Repaired TK-1-87 STP Sump Leak detector tubing repaired. 29 6/21/24 12:30 Repaired TK-2-91 Fill bucket New swivel installed in fill bucket Reference #Date Time Status System Component Manufacture Tank Information Manufacture: UDC/Dispensers Information Number of Dispensers: Depth to Ground Water: Product Lines: Vapor Return / Vent: Flex: Shear Valve Manufacture: Containment Boots: Piping Information Manufacture: Manufacture Log of Unrepaired Leaks Spill Buckets: Log of Repaired Leaks