Violations
Violation Code Description
901.6 Inspection, testing and maintenance.
Fire protection and life safety systems shall
be maintained in an operative condition at
all times, and shall be replaced or repaired
where defective. Nonrequired fire
protection and life safety systems and
equipment shall be inspected, tested and
maintained or removed in accordance with
Section 901.8. All fire alarm systems, fire
detection systems, automatic sprinkler or
extinguishing systems, communication
systems, and all other equipment, material
or systems required by these regulations
shall be maintained in an operable condition
at all times in accordance with this code and
California Code of Regulations, Title 19,
Division 1. Upon disruption or diminishment
of the fire protective qualities of such
equipment, material or systems, immediate
action shall be instituted to affect a
reestablishment of such equipment, material
or systems to their original normal and
operational condition. [California Code of
Regulations, Title 19, Division 1, §1.14]
Maintenance. Every fire alarm system or
device, sprinkler system, fire extinguisher,
fire hose, fire-resistive assembly or any other
fire safety assembly, device, material or
equipment installed and retained in service
in any building or structure subject to
California Code of Regulations, Title 19,
Division 1 regulations shall be maintained in
an operable condition at all times in
accordance with California Code of
Regulations, Title 19, Division 1 regulations
and with their intended use. [California Code
of Regulations, Title 19, Division 1, §3.24]
Maintenance of Equipment. All fire alarm
systems, fire detection systems, automatic
sprinkler or extinguishing systems,
communication systems, and all other
equipment, material or systems required by
California Code of Regulations, Title 19,
Division 1 shall be maintained in an operable
condition at all times. Upon disruption or
diminishment of the fire protective qualities
of such equipment, material or systems,
immediate action shall be instituted to
affect a reestablishment of such equipment
material or systems to their original normal
and operational condition. [California Code
of Regulations Title 19 Division 1 §904(a)]Current Date:02/04/2025 12:58
of Regulations, Title 19, Division 1, §904(a)]Required Inspection, Testing and
Maintenance Frequencies.
(a) All automatic fire extinguishing systems,
including systems installed as an alternate to
other building requirements, shall be
inspected, tested and maintained in
accordance with the following frequencies.
Local authorities may require more frequent
inspection, testing and maintenance and
additional procedures.
[California Code of Regulations, Title 19,
Division 1, §904(a)(1)] Required Inspection,
Testing and Maintenance Frequencies.
(1) Water-based fire protection systems shall
be inspected, tested and maintained in
accordance with the frequencies required by
NFPA 25 (2011 edition) including Annexes A,
B, C, D, E, F and G as amended by the State
of California. (Published as NFPA 25, 2013
California Edition.)
[California Code of Regulations, Title 19,
Division 1, §904(b)] Required Inspection,
Testing and Maintenance Frequencies.
(b) When proof of the installation date of
standpipe systems or automatic fire
sprinkler systems cannot be furnished, such
systems shall receive initial testing and
maintenance by July 1, 1985.
[California Code of Regulations, Title 19,
Division 1, §904.2(a)] Testing and
Maintenance Requirements.
(a) All testing and maintenance on automatic
fire extinguishing systems in accordance
with Health & Safety Code Section 13195
shall be performed by those licensed in
accordance with Health and Safety Code
Section 13196.5.
Exceptions:
(1) The State Fire Marshal may waive, in
writing, licensing of fire departments which
conduct fire sprinkler and standpipe system
testing and maintenance.
(2) Service on fire alarm systems and
industrial systems as specified in Health and
Safety Code Sections 13196.5(b) and (c) may
be conducted without a license.
(3) Testing and maintenance on automatic
fire extinguishing systems exempted in
writing by the State Fire Marshal, when the
building owner or occupant has the staff and
equipment to conduct testing and
maintenance.
[California Code of Regulations, Title 19,
Division 1, §904.2(b)] Testing and
Maintenance Requirements.
(b) Any testing and maintenance of
automatic fire extinguishing systems shall be
performed in accordance with these
i t
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Current Date:02/04/2025 12:58
requirements.Exceptions:
(1) The State Fire Marshal may waive, in
writing, the requirement that testing and
maintenance be performed in accordance
with these requirements when a licensee can
demonstrate that a system cannot
functionally be tested and maintained in
accordance with the California Code of
Regulations, Title 19, Division 1, Chapter 5.
(2) If at any time a licensee encounters a
specialized or modified system which cannot
be tested and maintained in accordance with
California Code of Regulations, Title 19,
Division 1, Chapter 5, the licensee shall
contact the State Fire Marshal and test and
maintain the system as directed.
(A) The intent of this section is to cover
automatic fire extinguishing systems as
originally designed, installed and approved
by the Authority Having Jurisdiction. It is
not, however, intended to require that such
systems be upgraded to current adopted
standards.
[California Code of Regulations, Title 19,
Division 1, §904.2(h)] Testing and
Maintenance Requirements.
(h) At the time of testing and maintenance,
building management shall be consulted to
avoid unnecessary disturbance of normal
building operation.
[California Code of Regulations, Title 19,
Division 1, §904.2(i)] Testing and
Maintenance Requirements.
(i) The licensee shall contact the local fire
authority having jurisdiction prior to testing
and maintenance of a system when required
by the local fire authority having jurisdiction
to do so.
1008.1 Means of egress illumination.
Illumination shall be provided in the means
of egress in accordance with Section 1008.2.
Under emergency power, means of egress
illumination shall comply with Section
1008.3.
603.2.2 Open electrical terminations.
Open junction boxes and open-wiring splices
shall be prohibited. Approved covers shall be
provided for all switch and electrical outlet
boxes.
703.1 Maintaining protection.
Materials and firestop systems used to
protect membrane and through
penetrations in fire-resistance-rated
construction and construction installed to
resist the passage of smoke shall be
maintained. The materials and firestop
systems shall be securely attached to or
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Current Date:02/04/2025 12:58
y ybonded to the construction being
penetrated with no openings visible through
or into the cavity of the construction. Where
the system design number is known, the
system shall be inspected to the listing
criteria and manufacturer’s installation
instructions.
907.8 Inspection, testing and maintenance.
The maintenance and testing schedules and
procedures for fire alarm and fire detection
systems shall be in accordance with Sections
907.8.1 through 907.8.4 and NFPA 72.
Records of inspection, testing and
maintenance shall be maintained.
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Violation Count:5 Inspection Fee:0.00
Type
First
Name
Last
Name
Signature
Date Signature Graphic
Inspect
or
Liseth Pisano 02/04/2025
Owner/
Rep.
Angel Rodrig
uez
02/04/2025
Conducted a High Rise and Hazardous Materials Inspections. The following must be corrected
within 30 days.
1. The fire alarm is in trouble. The fire alarm must be brought back to normal.
2. The fire extinguisher in the security room is pass due for service. It was last serviced in May
2023. Service the fire extinguisher on the 8th floor, room 872).
3. Close junction box in the first floor electrical room.
4. Exit signs must be fully illuminated in the normal and back up modes. Repair the exit sign in
the lobby of the first floor. The exit signs on the ninth floor must all be repaired.
5. Replace all missing outlet covers on the vacant first floor area and in the staff restroom of
the fifth floor.
6. Replace ceiling tiles on the fourth floor. Several ceiling tiles have holes.
7. Reminder: Report CERS on or before 2/19/2025.
Current Date:02/04/2025 12:58
Signatures
Inspection Notes
Documents
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Inspection Documents
Current Date:02/04/2025 12:58
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Current Date:02/04/2025 12:58
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Current Date:02/04/2025 12:58
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Violation Documents
Current Date:02/04/2025 12:58
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Current Date:02/04/2025 12:58
Fire Safety Inspection
Exterior
Question Answer Notes
Address visible from street?Yes
Hazardous or dead vegetation
or combustible material on
property
Yes
Fire lanes painted and
maintained Yes
OS&Y in good condition and
secured unobstructed Na
FDC are accessible Yes
Audible alarm for sprinkler
system in good condition Yes
Knoxbox present, keys secured
and correct keys Yes
Private fire hydrants
maintained and tested Yes
3ft Clearence maintained
around fire hydrants Yes
Interior
Question Answer Notes
Fire Extinguishers must be
maintained, tested and
inspected
No
Exit signs fully illuminated in
normal and emergency mode No
Exit doors operable from
inside without special
knowledge or a key
Yes
Exit isles, hallways and stairs
clean of obstructions Yes
Circuit breakers properly
labeled Yes
Electrical outlets and junction
boxes properly covered No
Extension cords not being
used in lieu of permanent
wiring.
Yes
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Current Date:02/04/2025 12:58
No items stored 24" non-
sprinklered or 18" sprinklered
ceilings.
Yes
No visible penetrations in
ceiling tile or holes in drywall No
Fire Alarm
Question Answer Notes
Fire alarm system tested and
maintained No The fire alarm is in trouble.
Fire Sprinkler
Question Answer Notes
Fire sprinkler system serviced
and maintained Yes
Commercial Hood
Question Answer Notes
Kitchen hood extinguishing
system serviced within the last
6 months
N/A
Kitchen hood has been
properly cleaned and serviced N/A
K class fire extinguisher is
present and serviced N/A
Hazmat
Question Answer Notes
Facility has reported into CERs Yes
CERs has been updated or
certified for current year Yes
Carbon monoxide detector
present and working N/A
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Current Date:02/04/2025 12:58
HazMat - HMBP
Administration/Documentation
Question Answer Notes
Did the facility adequately
establish and implement a
business plan when
storing/handling a hazardous
material at or above
reportable quantities in CERS?
Yes
Did the facility annually review
and electronically certify in
CERS that the business plan is
complete and accurate on or
before the required due date?
Yes
Does the facility have a copy of
the business plan readily
available with responsibilities
for emergency response or
training for review?
Yes
Did the facility update CERS
within 30 days of any one or
more of the following events:
1) A 100 percent or more
increase in the quantity of a
previously disclosed material.
2) Any handling of a previously
undisclosed hazardous
materials at or above
reportable quantities. 3) A
change of business address,
business ownership, or
business name. 4) A
substantial change in the
handler's operations that
requires modification to any
portion of the business plan.
Yes
Did the facility inform the
property owner in writing that
an HMBP is required for the
facility?
Yes
Did the facility provide the
property owner a copy of the
HMBP upon request??
Yes
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Current Date:02/04/2025 12:58
Did the facility report
complete or accurate
information in the Business
Activities Page and/or
Business Owner Operator
Identification Page in CERS?
Yes
Did the facility report
complete and accurate
hazardous material inventory
information for all hazardous
materials on site at or above
reportable quantities in CERS?
Yes
Did the facility adequately
establish an emergency
response plan in CERS?
Yes
Did the facility submit a site
map with all the required
content in CERS?
Yes
Training
Question Answer Notes
Did the facility submit an
adequate training program
with safety procedures in the
event of a release or
threatened release of a
hazardous material in CERS?
Yes
Did the facility provide initial
and refresher training to all
employees and maintain
records for 3 years?
Yes
Operations/Maintenance
Question Answer Notes
Does the facility have
adequate signage for
hazardous materials storage?
Yes
Are hazardous materials
separated form incompatibles?Yes
Release/Leaks/Spills
Question Answer Notes
Did the facility fail to report a
release or threatened release
of a hazardous material to the
unified program agency and to
Cal OES?
N/A
Occupant:TRUXTUN TOWER
ASSOC
Inspection
Date:
02/04/2025
Current Date:02/04/2025 12:58