HomeMy WebLinkAbout2025-02-20 Cabaret Inspection 1207 19th St The Mint Bar.pdfCurrent Date:02/20/2025 11:50
Occupant:The Mint Bar Inspection
Date:
02/20/2025
Occupant Name:The Mint Bar Inspection Date:02/20/2025
Street Number:1207
Street Name:19th City:Bakersfield
Street Type:Street Postal Code:93301
Inspector:Pisano , Liseth State:CA
Passed:No
Inspection Type:Cabaret license inspection
Violations
Violation Code Description
603.2.2 Open electrical terminations.
Open junction boxes and open-wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.6 Extension cords.
Extension cords shall not be a substitute for permanent
wiring and shall be listed and labeled in accordance with UL
817. Extension cords shall not be affixed to structures,
extended through walls, ceilings or floors, or under doors
or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords
shall be used only with portable appliances. Extension cords
marked for indoor use shall not be used outdoors.
HSC 25515 Failure to report to CERs and submit a business plan,
inventory and site map.
HSC 25505 Failure to complete and electronically submit initially,
annually or triennially, a business plan when storing/handling
a hazardous material at or above reportable quantities.
5307.3.2 Gas detection system.
Where ventilation is not provided in accordance with Section
5307.3.1, a gas detection system shall be provided in rooms
or indoor areas and in below-grade outdoor locations with
insulated carbon dioxide systems. Carbon dioxide sensors
shall be provided within 12 inches (305 mm) of the floor in
the area where the gas is expected to accumulate or other
approved locations. The system shall be designed as
follows:
1.Activates an audible and visible supervisory alarm at a
normally attended location upon detection of a carbon
dioxide concentration of 5,000 ppm (9000 mg/m3).
2.Activates an audible and visible alarm within the room or
immediate area where the system is installed upon
detection of a carbon dioxide concentration of 30,000 ppm
(54 000 mg/m3).
Violation Count:5 Inspection Fee:0.00
Complete Inspection Report - With Documents
Facility Information
Inspection Information
Page 1 of 4
Occupant:The Mint Bar Inspection
Date:
02/20/2025
Current Date:02/20/2025 11:50
Type First Name Last Name Signature Date Signature Graphic
Owner/Rep.Walter Walston 02/20/2025
Inspector Liseth Pisano 02/20/2025
Conducted a Cabaret Inspection. The following must be corrected within 30 days.
1. Close open electrical in the restroom ceiling.
2. Reminder to service all fire extinguishers on or before 2/29/2025.
3. Remove the green extension cord behind the bar. Extension cords are not allowed.
4. The facility has a bulk CO2 tank. The CO2 tank must be reported in the California
Environmental Reporting System (CERS).
5. Install a CO2 or carbon dioxide detector near the soda dispenser.
Inspection Documents
Violation Documents
Signatures
Inspection Notes
Documents
Page 2 of 4
Occupant:The Mint Bar Inspection
Date:
02/20/2025
Current Date:02/20/2025 11:50
Fire Safety Inspection
Exterior
Question Answer Notes
Address visible from street?Yes
Hazardous or dead vegetation or
combustible material on property Yes
Fire lanes painted and maintained Yes
OS&Y in good condition and secured
unobstructed Na
FDC are accessible NA
Audible alarm for sprinkler system in
good condition Na
Knoxbox present, keys secured and
correct keys Na
Private fire hydrants maintained and
tested Yes
3ft Clearence maintained around fire
hydrants Yes
Interior
Question Answer Notes
Fire Extinguishers must be maintained,
tested and inspected Yes
Exit signs fully illuminated in normal and
emergency mode Yes
Exit doors operable from inside without
special knowledge or a key Yes
Exit isles, hallways and stairs clean of
obstructions Yes
Circuit breakers properly labeled Yes
Electrical outlets and junction boxes
properly covered No
Extension cords not being used in lieu of
permanent wiring.No
No items stored 24" non-sprinklered or
18" sprinklered ceilings.Yes
No visible penetrations in ceiling tile or
holes in drywall Yes
Fire Alarm
Question Answer Notes
Fire alarm system tested and maintained N/A
Fire Sprinkler
Question Answer Notes
Fire sprinkler system serviced and
maintained N/A
Commercial Hood
Page 3 of 4
Occupant:The Mint Bar Inspection
Date:
02/20/2025
Current Date:02/20/2025 11:50
Question Answer Notes
Kitchen hood extinguishing system
serviced within the last 6 months N/A
Kitchen hood has been properly cleaned
and serviced N/A
K class fire extinguisher is present and
serviced N/A
Hazmat
Question Answer Notes
Facility has reported into CERs No
CERs has been updated or certified for
current year No
Carbon monoxide detector present and
working No
Page 4 of 4