HomeMy WebLinkAboutEMC 2025Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10022566 01-15-2025
Mt Vernon & Columbus ARCO
2698 Mt Vernon Ave Bakersfield, Ca 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
1073967
8492093 03/23/2025
Veeder Root C26937 03/15/2025
01-15-2025 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VEEDER ROOT TLS-350 336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 794380-208 87 STP
L2 794390-409 87 ANNULAR
L3 794380-208 91 STP
L4 794390-409 91 ANNULAR
L5 794380-208 DISPENSER 1/2
L6 794380-208 DISPENSER 3/4
L7 794380-208 DISPENSER 5/6
L8 794380-208 DISPENSER 7/8
L9 794380-208 87 FILL
L10 794380-208 91 FILL
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 UNLEADED
T2 FX1V 91 PREMIUM
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Performed EMC due to dispenser replacement.
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
Arco Ampm Setup and alarm history.
Setup.
Responses Received:
200
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
JAN 15, 2025 3:31 PM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED R 8770 53.30 ‐0.2 66.6 10933
2 PREMIUM 2360 30.38 0.0 73.9 9489
I90500
JAN 15, 2025 3:31 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336‐100‐C
CREATED ‐ 21.02.13.11.53
S‐MODULE# 330160‐004‐a
SYSTEM FEATURES:
PERIODIC IN‐TANK TESTS
ANNUAL IN‐TANK TESTS
ISD/APM
I50500
JAN 15, 2025 3:31 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JAN 15, 2025 3:31 PM
SHIFT TIME 1 : 6:00 AM
I50202
JAN 15, 2025 3:31 PM
SHIFT TIME 2 : DISABLED
I50203
JAN 15, 2025 3:31 PM
SHIFT TIME 3 : DISABLED
I50204
JAN 15, 2025 3:31 PM
SHIFT TIME 4 : DISABLED
I54600
JAN 15, 2025 3:31 PM
TANK PER TST NEEDED WRN: DISABLED
I54900
JAN 15, 2025 3:31 PM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JAN 15, 2025 3:31 PM
LINE RE‐ENABLE METHOD
PASS LINE TEST
I55600
JAN 15, 2025 3:31 PM
LINE PER TST NEEDED WRN: DISABLED
I55900
JAN 15, 2025 3:31 PM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JAN 15, 2025 3:31 PM
PRINT TC VOLUMES
ENABLED
I50E00
JAN 15, 2025 3:31 PM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JAN 15, 2025 3:31 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JAN 15, 2025 3:31 PM
H‐PROTOCOL DATA FORMAT
HEIGHT
I51A01
JAN 15, 2025 3:31 PM
DAYLIGHT SAVING TIME
ENABLED OFF
I51B00
JAN 15, 2025 3:31 PM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JAN 15, 2025 3:31 PM
RE‐DIRECT LOCAL PRINTOUT
DISABLED
I50400
JAN 15, 2025 3:31 PM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JAN 15, 2025 3:31 PM
TANK CHART SECURITY
DISABLED
I5BD00
JAN 15, 2025 3:31 PM
CUSTOM ALARM LABELS
DISABLED
I56000
JAN 15, 2025 3:31 PM
MASS/DENSITY
DISABLED
I88101
JAN 15, 2025 3:31 PM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS‐232 SECURITY
CODE : DISABLED
I88102
JAN 15, 2025 3:31 PM
PORT SETTINGS:
COMM BOARD : 2 (S‐SAT )
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS‐232 SECURITY
CODE : DISABLED
DTR NORMAL STATE: HIGH
I88103
JAN 15, 2025 3:31 PM
PORT SETTINGS:
COMM BOARD : 3 (RS‐232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS‐232 SECURITY
CODE : DISABLED
I88104
JAN 15, 2025 3:31 PM
I88105
JAN 15, 2025 3:31 PM
I88106
JAN 15, 2025 3:31 PM
I52000
JAN 15, 2025 3:31 PM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE ??? 15, 2025 DISABLED
2 ON DATE ??? 15, 2025 DISABLED
3 ON DATE ??? 15, 2025 DISABLED
4 ON DATE ??? 15, 2025 DISABLED
5 ON DATE ??? 15, 2025 DISABLED
6 ON DATE ??? 15, 2025 DISABLED
7 ON DATE ??? 15, 2025 DISABLED
8 ON DATE ??? 15, 2025 DISABLED
I60100
JAN 15, 2025 3:31 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED R ON
2 PREMIUM ON
3 OFF
4 OFF
I60200
JAN 15, 2025 3:31 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED R
2 PREMIUM
3
4
I60300
JAN 15, 2025 3:31 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED R 1
2 PREMIUM 3
3 3
4 4
I60900
JAN 15, 2025 3:31 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED R 0.000700
2 PREMIUM 0.000700
3 0.000000
4 0.000000
I60700
JAN 15, 2025 3:31 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED R 117.50
2 PREMIUM 117.50
3 0.00
4 0.00
I60A00
JAN 15, 2025 3:31 PM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED R
20 PTS 19703 2 PREMIUM 20 PTS 11849 3
1 PT 0 4 1 PT
0
I60400
JAN 15, 2025 3:31 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 19703
2 PREMIUM 11849
3 0
4 0
I60500
JAN 15, 2025 3:31 PM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 19703 16062 9961 3824
2 PREMIUM 11849 9717 5992 2243
3 0 0 0 0
4 0 0 0 0
I60600
JAN 15, 2025 3:31 PM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 19703 19389 18791 18010
17091 16062 14923 13739
12507 11269 9961 8678
7409 6170 4977 3824
2780 1878 1049 400
2 PREMIUM 11849 11676 11334 10963
10334 9717 9027 8307
7554 6795 5992 5204
4426 3652 2941 2243
1616 1079 594 221
3 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JAN 15, 2025 3:31 PM
TANK PRODUCT LABEL METER DATA
1 UNLEADED R NO
2 PREMIUM NO
3 NO
4 NO
I62F00
JAN 15, 2025 3:31 PM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED R 4.0 IN.
2 PREMIUM 4.0 IN.
I62700
JAN 15, 2025 3:31 PM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED R 2.0
2 PREMIUM 2.0
I64200
JAN 15, 2025 3:31 PM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED R LOW
2 PREMIUM LOW
I62400
JAN 15, 2025 3:31 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED R 3.0
2 PREMIUM 3.0
I62800
JAN 15, 2025 3:31 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 19703
2 PREMIUM 11849
3 0
4 0
I62300
JAN 15, 2025 3:31 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 17733
2 PREMIUM 10664
3 0
4 0
I62200
JAN 15, 2025 3:31 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 18718
2 PREMIUM 11257
3 0
4 0
I62900
JAN 15, 2025 3:31 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 2955
2 PREMIUM 1777
3 0
4 0
I62100
JAN 15, 2025 3:31 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 1000
2 PREMIUM 500
3 0
4 0
I62600
JAN 15, 2025 3:31 PM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 99
2 PREMIUM 99
3 99
4 99
I62500
JAN 15, 2025 3:31 PM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 99
2 PREMIUM 99
3 99
4 99
I60800
JAN 15, 2025 3:31 PM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED R 1.00
2 PREMIUM 0.00
3 0.00
4 0.00
I60B00
JAN 15, 2025 3:31 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JAN 15, 2025 3:31 PM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED R 0.00
2 PREMIUM 0.00
3 0.00
4 0.00
I61200
JAN 15, 2025 3:31 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED R NONE NONE
2 PREMIUM NONE NONE
3 NONE NONE
4 NONE NONE
I63600
JAN 15, 2025 3:31 PM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 5713
2 PREMIUM 3436
3 0
4 0
I62A00
JAN 15, 2025 3:31 PM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 5713
2 PREMIUM 3436
3 0
4 0
I62C00
JAN 15, 2025 3:31 PM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED R STANDARD
2 PREMIUM STANDARD
3 STANDARD
4 STANDARD
I62D00
JAN 15, 2025 3:31 PM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED R GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JAN 15, 2025 3:31 PM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED R OFF OFF
2 PREMIUM OFF OFF
3 OFF OFF
4 OFF OFF
I63000
JAN 15, 2025 3:31 PM
IN‐TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED R OFF
2 PREMIUM OFF
3 OFF
4 OFF
I63200
JAN 15, 2025 3:31 PM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED R OFF
2 PREMIUM OFF
3 OFF
4 OFF
I61000
JAN 15, 2025 3:31 PM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED R 5
2 PREMIUM 2
3 1
4 1
I63A00
JAN 15, 2025 3:32 PM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED R 10.00%
2 PREMIUM 10.00%
3 10.00%
4 10.00%
I61100
JAN 15, 2025 3:32 PM
LEAK TEST METHOD
‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐
TEST ON DATE : ALL TANK
FEB 13, 2021
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
JAN 15, 2025 3:32 PM
CSLD PROBABLITY OF DETECTION
I61400
JAN 15, 2025 3:32 PM
CSLD CLIMATE FACTOR
I61600
JAN 15, 2025 3:32 PM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED R IMMEDIATE
2 PREMIUM IMMEDIATE
3 IMMEDIATE
4 IMMEDIATE
I61A00
JAN 15, 2025 3:32 PM
IN‐TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED R DISABLED
2 PREMIUM DISABLED
3 DISABLED
4 DISABLED
I61B00
JAN 15, 2025 3:32 PM
IN‐TANK LEAK GROSS TEST AUTO‐CONFIRM
I61C00
JAN 15, 2025 3:32 PM
CSLD REPORT ONLY
I62B00
JAN 15, 2025 3:32 PM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED R ??? 0, 0
2 PREMIUM ??? 0, 0
3 ??? 0, 0
4 ??? 0, 0
I63300
JAN 15, 2025 3:32 PM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JAN 15, 2025 3:32 PM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 0
2 PREMIUM 0
3 0
4 0
I63500
JAN 15, 2025 3:32 PM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 1
2 PREMIUM 1
3 1
4 1
I63900
JAN 15, 2025 3:32 PM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED R
END FACTOR: NONE
2 PREMIUM
END FACTOR: NONE
3
END FACTOR: NONE
4
END FACTOR: NONE
I78000
JAN 15, 2025 3:32 PM
I77700
JAN 15, 2025 3:32 PM
I77800
JAN 15, 2025 3:32 PM
I78C00
JAN 15, 2025 3:32 PM
I78300
JAN 15, 2025 3:32 PM
I78F00
JAN 15, 2025 3:32 PM
I78700
JAN 15, 2025 3:32 PM
I70200
JAN 15, 2025 3:32 PM
LIQUID LABEL
DEVICE LABEL
1 87 STP
2 87 ANN
3 91 STP
4 91 ANN
5 DISP 1‐2
6 DISP 3‐4
7 DISP 5‐6
8 DISP 7‐8
9 87 FILL
10 91 FILL
11
12
13
14
15
16
I70300
JAN 15, 2025 3:32 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87 STP TRI‐STATE (SINGLE FLOAT)
2 87 ANN TRI‐STATE (SINGLE FLOAT)
3 91 STP TRI‐STATE (SINGLE FLOAT)
4 91 ANN TRI‐STATE (SINGLE FLOAT)
5 DISP 1‐2 TRI‐STATE (SINGLE FLOAT)
6 DISP 3‐4 TRI‐STATE (SINGLE FLOAT)
7 DISP 5‐6 TRI‐STATE (SINGLE FLOAT)
8 DISP 7‐8 TRI‐STATE (SINGLE FLOAT)
9 87 FILL TRI‐STATE (SINGLE FLOAT)
10 91 FILL TRI‐STATE (SINGLE FLOAT)
11 TRI‐STATE (SINGLE FLOAT)
12 TRI‐STATE (SINGLE FLOAT)
13 TRI‐STATE (SINGLE FLOAT)
14 TRI‐STATE (SINGLE FLOAT)
15 TRI‐STATE (SINGLE FLOAT)
16 TRI‐STATE (SINGLE FLOAT)
I70400
JAN 15, 2025 3:32 PM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 87 STP STP SUMP
2 87 ANN ANNULAR SPACE
3 91 STP STP SUMP
4 91 ANN ANNULAR SPACE
5 DISP 1‐2 DISPENSER PAN
6 DISP 3‐4 DISPENSER PAN
7 DISP 5‐6 DISPENSER PAN
8 DISP 7‐8 DISPENSER PAN
9 87 FILL PIPING SUMP
10 91 FILL PIPING SUMP
11 OTHER SENSORS
12 OTHER SENSORS
13 OTHER SENSORS
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
JAN 15, 2025 3:32 PM
I74300
JAN 15, 2025 3:32 PM
I74400
JAN 15, 2025 3:32 PM
I74700
JAN 15, 2025 3:32 PM
I74800
JAN 15, 2025 3:32 PM
I74900
JAN 15, 2025 3:32 PM
I7BC00
JAN 15, 2025 3:32 PM
I80200
JAN 15, 2025 3:32 PM
I80300
JAN 15, 2025 3:32 PM
I80400
JAN 15, 2025 3:32 PM
I80700
JAN 15, 2025 3:32 PM
RELAY LABEL
DEVICE LABEL
1 87 STP
2 91 STP
3
4 OVERFILL
I80900
JAN 15, 2025 3:32 PM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 87 STP NORMALLY CLOSED
2 91 STP NORMALLY CLOSED
3 NORMALLY OPEN
4 OVERFILL NORMALLY OPEN
I80B00
JAN 15, 2025 3:32 PM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 87 STP 1
2 91 STP 2
3 NONE
4 OVERFILL NONE
I80A00
JAN 15, 2025 3:32 PM
RELAY TYPE
RELAY DESIGNATION TYPE
1 87 STP STANDARD
2 91 STP STANDARD
3 STANDARD
4 OVERFILL STANDARD
I80C00
JAN 15, 2025 3:32 PM
I80800
JAN 15, 2025 3:32 PM
RELAY SETUP REPORT
R 1:87 STP
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 1:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 1:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 2:91 STP
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 3:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 3:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 3:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
‐ NO ALARM ASSIGNMENTS ‐
R 4:OVERFILL
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN‐TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
I79000
JAN 15, 2025 3:32 PM
EDIM:1 VR:330273‐002‐C TD:97.11.13.15.52
I79100
JAN 15, 2025 3:32 PM
I72300
JAN 15, 2025 3:32 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 1‐2 PS VAPOR PRESSURE
02 1‐2 AFM AIR FLOW METER
03 3‐4 AFM AIR FLOW METER
04 5‐6 AFM AIR FLOW METER
05 UNKNOWN
06 7‐8 AFM AIR FLOW METER
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JAN 15, 2025 3:32 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
JAN 15, 2025 3:32 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
NOZZLE A/L RANGE
A/L RATIO: 0.95 ‐ 1.15
IV4000
JAN 15, 2025 3:32 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
VAPOR PROCESSOR TYPE
NONE
IV4700
JAN 15, 2025 3:32 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JAN 15, 2025 3:32 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
ACCEPT HIGH ORVR: YES
IV4A00
JAN 15, 2025 3:32 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 00 01 01 01 BLEND3
02 01 02 01 01 BLEND3
03 02 03 02 01 BLEND3
04 03 04 02 01 BLEND3
05 04 05 03 01 BLEND3
06 05 06 03 01 BLEND3
07 06 07 04 01 BLEND3
08 07 08 04 01 BLEND3
IV4B00
JAN 15, 2025 3:32 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
00 01 00/01 01/01 09/01 xx/xx
01 01 00/02 01/02 09/02 xx/xx
02 02 00/03 01/03 09/03 xx/xx
03 02 00/04 01/04 09/04 xx/xx
04 03 00/05 01/05 09/05 xx/xx
05 03 00/06 01/06 09/06 xx/xx
06 04 00/07 01/07 09/07 xx/xx
07 04 00/08 01/08 09/08 xx/xx
IV4900
JAN 15, 2025 3:33 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JAN 15, 2025 3:33 PM
ISD VERSION: 01.06
Alarm History
Responses Received:
I10200
JAN 15, 2025 3:34 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 UNUSED 9664766 9647619
2 UNUSED 9635214 9618362
3 UNUSED 9637789 9615784
4 UNUSED 9641376 9613009
5 4 PROBE / G.T. 164016 163950
6 INTERSTITIAL BD 202132 202070
7 8SMARTSENSOR BD 39464 39444
8 INTERSTITIAL BD 202155 202185
9 UNUSED 9648581 9626037
10 RELAY BOARD 15014 15007
11 UNUSED 9643146 9626500
12 UNUSED 9638767 9617489
13 UNUSED 9640461 9625399
14 UNUSED 9642045 9618767
15 UNUSED 9637975 9609668
16 UNUSED 9634630 9616278
COMM 1 ELEC DISP INT. 101398 101365
COMM 2 SERIAL SAT BD 484622 484639
COMM 3 RS232 SERIAL BD 15058 15051
COMM 4 UNUSED 9645632 9625531
COMM 5 UNUSED 9645104 9622557
COMM 6 UNUSED 9641011 9616168
I90200
JAN 15, 2025 3:34 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336‐100‐C
CREATED ‐ 21.02.13.11.53
S‐MODULE# 330160‐004‐a
SYSTEM FEATURES:
PERIODIC IN‐TANK TESTS
ANNUAL IN‐TANK TESTS
ISD/APM
I11100
JAN 15, 2025 3:34 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 5 DISP PAN DISP 1‐2 SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L 6 DISP PAN DISP 3‐4 SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L 8 DISP PAN DISP 7‐8 SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L 7 DISP PAN DISP 5‐6 SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L10 PIPE 91 FILL SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L 9 PIPE 87 FILL SENSOR OUT ALARM CLEAR 1‐15‐25 3:25PM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L 8 DISP PAN DISP 7‐8 SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L 7 DISP PAN DISP 5‐6 SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L 1 STP SUMP 87 STP SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L 6 DISP PAN DISP 3‐4 SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L10 PIPE 91 FILL SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L 5 DISP PAN DISP 1‐2 SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L 9 PIPE 87 FILL SENSOR OUT ALARM ALARM 1‐15‐25 3:24PM
L 5 DISP PAN DISP 1‐2 FUEL ALARM CLEAR 1‐15‐25 3:24PM
L 5 DISP PAN DISP 1‐2 FUEL ALARM ALARM 1‐15‐25 3:24PM
L 4 ANNULAR 91 ANN FUEL ALARM CLEAR 1‐15‐25 3:24PM
L 4 ANNULAR 91 ANN FUEL ALARM ALARM 1‐15‐25 3:24PM
L 6 DISP PAN DISP 3‐4 FUEL ALARM CLEAR 1‐15‐25 3:23PM
L 6 DISP PAN DISP 3‐4 FUEL ALARM ALARM 1‐15‐25 3:23PM
L 3 STP SUMP 91 STP FUEL ALARM CLEAR 1‐15‐25 3:23PM
L 3 STP SUMP 91 STP FUEL ALARM ALARM 1‐15‐25 3:23PM
L 7 DISP PAN DISP 5‐6 FUEL ALARM CLEAR 1‐15‐25 3:23PM
L 7 DISP PAN DISP 5‐6 FUEL ALARM ALARM 1‐15‐25 3:23PM
L10 PIPE 91 FILL FUEL ALARM CLEAR 1‐15‐25 3:22PM
L10 PIPE 91 FILL FUEL ALARM ALARM 1‐15‐25 3:22PM
L 2 ANNULAR 87 ANN FUEL ALARM CLEAR 1‐15‐25 3:22PM
L 2 ANNULAR 87 ANN FUEL ALARM ALARM 1‐15‐25 3:22PM
L 9 PIPE 87 FILL FUEL ALARM CLEAR 1‐15‐25 3:22PM
L 9 PIPE 87 FILL FUEL ALARM ALARM 1‐15‐25 3:22PM
L 1 STP SUMP 87 STP FUEL ALARM CLEAR 1‐15‐25 3:22PM
L 1 STP SUMP 87 STP FUEL ALARM ALARM 1‐15‐25 3:22PM
L 8 DISP PAN DISP 7‐8 FUEL ALARM CLEAR 1‐15‐25 3:22PM
L 8 DISP PAN DISP 7‐8 FUEL ALARM ALARM 1‐15‐25 3:22PM
OTHER MISSING RELAY SETUP CLEAR 1‐15‐25 3:09PM
OTHER MISS VAPOR FLOW MTR CLEAR 1‐15‐25 3:06PM
OTHER MISSING HOSE SETUP CLEAR 1‐15‐25 3:06PM
OTHER MISS VAPOR FLOW MTR ALARM 1‐15‐25 2:56PM
OTHER MISSING HOSE SETUP ALARM 1‐15‐25 2:56PM
OTHER MISSING HOSE SETUP CLEAR 1‐15‐25 2:13PM
s 5 OTHER COMMUNICATION ALARM CLEAR 1‐15‐25 12:03PM
s 5 OTHER COMMUNICATION ALARM ALARM 1‐14‐25 5:40PM
s 5 OTHER COMMUNICATION ALARM CLEAR 1‐14‐25 4:59PM
OTHER MISS VAPOR PRES SEN CLEAR 1‐14‐25 4:52PM
I11200
JAN 15, 2025 3:34 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
NON‐PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
OTHER ISD SETUP WARN CLEAR 1‐15‐25 3:19PM
OTHER ISD SENSOR OUT WARN CLEAR 1‐15‐25 3:14PM
OTHER ISD SENSOR OUT WARN ALARM 1‐15‐25 12:00AM
OTHER ISD SETUP WARN ALARM 1‐15‐25 12:00AM
I20600
JAN 15, 2025 3:34 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
TANK ALARM HISTORY
TANK 1 UNLEADED R
TANK 2 PREMIUM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JAN 15, 2025 3:34 PM
I30200
JAN 15, 2025 3:34 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 STP
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:22 PM FUEL ALARM
2 87 ANN
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:22 PM FUEL ALARM
3 91 STP
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:23 PM FUEL ALARM
4 91 ANN
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:24 PM FUEL ALARM
5 DISP 1‐2
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:24 PM FUEL ALARM
6 DISP 3‐4
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:23 PM FUEL ALARM
7 DISP 5‐6
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:23 PM FUEL ALARM
8 DISP 7‐8
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:22 PM FUEL ALARM
9 87 FILL
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:22 PM FUEL ALARM
10 91 FILL
JAN 15, 2025 3:24 PM SENSOR OUT ALARM
JAN 15, 2025 3:22 PM FUEL ALARM
I31600
JAN 15, 2025 3:34 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 1‐2 PS
2 1‐2 AFM
3 3‐4 AFM
JAN 14, 2025 4:46 PM COMMUNICATION ALARM
4 5‐6 AFM
JAN 14, 2025 4:46 PM COMMUNICATION ALARM
6 7‐8 AFM
I40200
JAN 15, 2025 3:34 PM
I40300
JAN 15, 2025 3:34 PM
I34200
JAN 15, 2025 3:34 PM
I34700
JAN 15, 2025 3:34 PM
IV0100
JAN 15, 2025 3:34 PM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFID CA 93306
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :NOTEST
EVR VAPOR CONTAINMENT :NOTEST
ISD MONITOR UP‐TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
25‐01‐15 00:00:09 SENSOR OUT SELFTEST s 5
25‐01‐15 00:00:09 SETUP SELFTEST
MISSING HOSE(S)
25‐01‐15 00:00:09 SETUP SELFTEST
MISSING SHUTDOWN RELAY(S)
25‐01‐14 10:01:52 SENSOR OUT SELFTEST s 5
25‐01‐14 10:01:52 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.63
25‐01‐13 10:03:30 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.68
25‐01‐06 10:02:30 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.89
24‐12‐30 10:01:53 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.75
24‐12‐23 10:02:01 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.90
24‐12‐22 10:02:08 A/L RATIO DEGRADATION FP 8 BLEND3 0.77
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
24‐10‐25 10:04:01 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
23‐09‐11 10:03:19 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
19‐09‐22 10:02:52 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
19‐07‐23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
19‐07‐23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
18‐08‐11 10:03:51 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 1.97
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
25‐01‐15 15:25:36 READINESS ISD:PF EVR:NNN CHECK ISD SENSORS
25‐01‐15 15:25:36 ISD STARTUP
25‐01‐15 15:25:30 ISD SHUTDOWN
25‐01‐15 15:19:43 ISD SELFTEST TEST MANUALLY CLEARED
25‐01‐15 15:14:22 SENSOR OUT TEST MANUALLY CLEARED
25‐01‐15 00:00:09 READINESS ISD:FN EVR:NNN CHECK SETUP CONFIGURATION
25‐01‐14 16:02:00 TIME CHANGE DETECTED AT: 25‐01‐14 08:01:09
25‐01‐14 15:44:50 SENSOR OUT TEST MANUALLY CLEARED
25‐01‐06 10:47:58 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24‐12‐30 10:02:40 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED