Loading...
HomeMy WebLinkAbout5784_Bakersfield CA_LL_Cert_250317 (1)Providers for MDleak® MSleak® DPleak®, MCleak® and PHDleak® Testing Technologies Page 1 of 2 Test Type: Job #: 5784 Facility Name: PO #: Prepared For: Site Address: City: State and Zip: CA 93313 Start Date:End Date: SYSTEM TK-1 87 TK-2 91 TK-3 E85 TK-4 DSL VR Product Primary MDleak:0.005 GPH PASS PASS PASS PASS Product Secondary:0.1 GPH PASS PASS PASS PASS Vent Primary MDleak:0.005 GPH PASS PASS PASS PASS Vent Secondary:0.1 GPH PASS PASS PASS PASS VR Primary MDleak:0.005 GPH PASS PASS NA NA VR Secondary:0.1 GPH PASS PASS NA NA MDleak Tank:0.005 GPH PASS PASS PASS PASS Turbine Sump Fittings:0.005 GPH PASS PASS PASS PASS Fill/Vapor Sump Fittings:0.005 GPH PASS PASS PASS PASS UDC Fittings:0.005 GPH PASS PASS PASS PASS Fill Bucket:0.005 GPH PASS PASS PASS PASS Vapor Bucket:0.005 GPH PASS PASS PASS NA Vent Box Fittings 0.005 GPH PASS PASS PASS PASS Fill Spill Bucket Hydro:0.1 GPH PASS PASS PASS PASS Vapor Bucket Hydro:0.1 GPH PASS PASS PASS NA Bakersfield 3/13/20253/12/2025 Complete Fueling Solutions Facility Certification CONFIDENTIAL California ELD New Construction Test 76 Gas Station 5741 Taft Highway Providers for MDleak® MSleak® DPleak®, MCleak® and PHDleak® Testing Technologies Page 2 of 2 Test Type: Facility Name: Job #: 5784 Prepared For: PO #: Site Address: City: State and Zip: CA 93313 Start Date:End Date: SYSTEM TK-1 87 TK-2 91 TK-3 E85 TK-4 DSL VR 10,000 5,000 10,000 5,000 Modern Modern Modern Modern Dry Dry Dry Dry 64"63"61"64" 8 ft 8 ft 8 ft 8 ft No Fuel No Fuel No Fuel No Fuel Tank Sump Boots Turbine Modern Bravo 6.00 0 0 0 Manufacture EVR: Certifying Field Technician: State Lic. # : 04-1695 Certification Leak Rate: 0.005gph Certifying Technician Signature: Date: Statement Confirmed by: Date: Ricardo Gonzalez Tank Volume in Gallons: UST Manufacture: Type of Interstice: Depth To Top Tank: Tank Diameter: OPW Bravo Smith Smith Unisource Spill Buckets: Gilbarco Office use only 3/17/2025 Depth to Ground Water: Component Manufacture: UDC/Dispensers Information Number of Dispensers: Manufacture: Shear Valve Manufacture: Containment Boots: Piping Information Product Lines: Vapor Return / Vent: Depth of Liquid Within Tank: 3/13/2025 3/12/2025 3/13/2025 Facility Certification CONFIDENTIAL California ELD New Construction Test 5741 Taft Highway Bakersfield 76 Gas Station Complete Fueling Solutions Flex: If you have any questions on the testing please do not hesitate to call. @ 855-255-5325. I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is true and correct to the best of my knowledge. This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak sensitivity listed above by using one or more of the following DPleak®,MDleak®,MCleak and PHDleak®EPA aproved Methods.These Methods are the most versatile and comprehensive testing procedures offered to the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®,MCleak,and PHDleak®Method can be assured that their facility has passed the Nation's highest standard in preventative leak detection. OPW