HomeMy WebLinkAbout2025-03-31 HMBP 1534 19th St Tina Marie's.pdfCurrent Date:03/31/2025 13:02
Occupant:TINA MARIE'S (PREVIOUSLY
CHEFS CHOICE)
Inspection
Date:
03/31/2025
Occupant Name:TINA MARIE'S (PREVIOUSLY CHEFS
CHOICE)
Inspection Date:03/31/2025
Street Number:1534 Occupant Code:116783
Street Name:19th City:Bakersfield
Street Type:Street Postal Code:93301
Inspector:Pisano , Liseth State:California
Passed:No
Inspection Type:Hazmat Annual
Violations
Violation Code Description
1008.1 Means of egress illumination.
Illumination shall be provided in the means of egress in
accordance with Section 1008.2. Under emergency power,
means of egress illumination shall comply with Section
1008.3.
5307.3.2 Gas detection system.
Where ventilation is not provided in accordance with Section
5307.3.1, a gas detection system shall be provided in rooms
or indoor areas and in below-grade outdoor locations with
insulated carbon dioxide systems. Carbon dioxide sensors
shall be provided within 12 inches (305 mm) of the floor in
the area where the gas is expected to accumulate or other
approved locations. The system shall be designed as
follows:
1.Activates an audible and visible supervisory alarm at a
normally attended location upon detection of a carbon
dioxide concentration of 5,000 ppm (9000 mg/m3).
2.Activates an audible and visible alarm within the room or
immediate area where the system is installed upon
detection of a carbon dioxide concentration of 30,000 ppm
(54 000 mg/m3).
703.1 Maintaining protection.
Materials and firestop systems used to protect membrane
and through penetrations in fire-resistance-rated
construction and construction installed to resist the
passage of smoke shall be maintained. The materials and
firestop systems shall be securely attached to or bonded to
the construction being penetrated with no openings visible
through or into the cavity of the construction. Where the
system design number is known, the system shall be
inspected to the listing criteria and manufacturer’s
installation instructions.
Violation Count:3 Inspection Fee:0.00
Complete Inspection Report - With Documents
Facility Information
Inspection Information
Signatures
Page 1 of 4
Occupant:TINA MARIE'S (PREVIOUSLY
CHEFS CHOICE)
Inspection
Date:
03/31/2025
Current Date:03/31/2025 13:02
Type First Name Last Name Signature Date Signature Graphic
Owner/Rep.Taylor Barber 03/31/2025
Inspector Liseth Pisano 03/31/2025
Conducted a hazardous materials and fire safety inspection. The following must be
corrected within 30 days.
1. Repair the horn strobe for the commercial hood. Device must be properly installed.
2. The CO2 monitor is in error. The CO2 must be normal.
3. Replace the missing ceiling tile in the back hallway CO2 area.
4. Repair the emergency exit signs in the back hallway CO2 area.
5. Replace missing door on the breaker panel in the back hallway CO2 area.
Inspection Documents
Violation Documents
Location Attributes:Commercial Hood; HMBP
Inspection Notes
Documents
Admin Information
Page 2 of 4
Occupant:TINA MARIE'S (PREVIOUSLY
CHEFS CHOICE)
Inspection
Date:
03/31/2025
Current Date:03/31/2025 13:02
Fire Safety Inspection
Exterior
Question Answer Notes
Address visible from street?Yes
Hazardous or dead vegetation or
combustible material on property Yes
Fire lanes painted and maintained Yes
OS&Y in good condition and secured
unobstructed Na
FDC are accessible NA
Audible alarm for sprinkler system in
good condition Na
Knoxbox present, keys secured and
correct keys Na
Private fire hydrants maintained and
tested Yes
3ft Clearence maintained around fire
hydrants Yes
Interior
Question Answer Notes
Fire Extinguishers must be maintained,
tested and inspected Yes
Exit signs fully illuminated in normal and
emergency mode No
Exit doors operable from inside without
special knowledge or a key Yes
Exit isles, hallways and stairs clean of
obstructions Yes
Circuit breakers properly labeled Yes
Electrical outlets and junction boxes
properly covered Yes
Extension cords not being used in lieu of
permanent wiring.Yes
No items stored 24" non-sprinklered or
18" sprinklered ceilings.Yes
No visible penetrations in ceiling tile or
holes in drywall No
Fire Alarm
Question Answer Notes
Fire alarm system tested and maintained N/A
Fire Sprinkler
Question Answer Notes
Fire sprinkler system serviced and
maintained N/A
Commercial Hood
Page 3 of 4
Occupant:TINA MARIE'S (PREVIOUSLY
CHEFS CHOICE)
Inspection
Date:
03/31/2025
Current Date:03/31/2025 13:02
Question Answer Notes
Kitchen hood extinguishing system
serviced within the last 6 months Yes
Kitchen hood has been properly cleaned
and serviced Yes
K class fire extinguisher is present and
serviced Yes
Hazmat
Question Answer Notes
Facility has reported into CERs Yes
CERs has been updated or certified for
current year Yes
Carbon monoxide detector present and
working No