HomeMy WebLinkAbout2024-10-02 HMBP 1523 Panama Ln STE 101 Wings Stop.pdfCurrent Date:04/04/2025 12:19
Occupant:Wingstop Inspection
Date:
10/02/2024
Occupant Name:Wingstop Inspection Date:10/02/2024
Street Number:1523 Occupant Code:113903
Street Name:Panama City:Bakersfield
Street Type:Lane Postal Code:93307
Inspector:Pisano , Liseth State:California Occupant Suite:E-101
Passed:No
Inspection Type:Hazmat Annual
Violations
Violation Code Description
HSC 6.95 25507 Failure to adequately establish and implement a business
plan when storing/handling a hazardous material at or
above reportable quantities.
HSC 6.95 25508.2 Failure to annually review and electronically certify that the
business plan is complete and accurate on or before the
required due date.
HSC 6.95 25505(c)Failure to have a business plan readily available to personnel
of the business or the unified program facility with
responsibilities for emergency response or training.
HSC 6.95 25508.1(a)-(f)"Failure to electronically update business plan within 30 days
of any one of the following events:
1) A 100 percent or more increase in the quantity of a
previously disclosed material.
2) Any handling of a previously undisclosed hazardous
materials at or above reportable quantities.
3) A change of business address, business ownership, or
business name.
4) A substantial change in the handler's operations that
requires modification to any portion of the business plan."
HSC 6.95 25505.1 Failure to notify property owner in writing that the business
is subject to the Hazardous Materials Business Plan and has
complied with its provisions.
HSC 6.95 25505.1 Failure to provide a copy of the business plan to the owner
or the owner's agent within five working days after
receiving a request for a copy from the owner or the
owner's agent.
19 CCR 1 5030.3(a)(1); HSC 6.95 25508(a)(1), 25508(a)(3)Failure to electronically submit the Business Activities Page
and/or Business Owner Operator Identification Page, or
failure to report complete or accurate information on these
forms.
HSC 6.95 25506, 25505(a)(1), 25508(a)(1), 25508(a)(3)Failure to electronically submit complete and accurate
hazardous material inventory information for all hazardous
materials on site at or above reportable quantities.
19 CCR 1 5040.1, 5040.2; HSC 6.95 25507.1(a), 25508(a)(1)Failure to electronically submit the emergency response
plan and procedures when not meeting the agricultural
Complete Inspection Report - With Documents
Facility Information
Inspection Information
Page 1 of 10
Occupant:Wingstop Inspection
Date:
10/02/2024
Current Date:04/04/2025 12:19
handler exemption requirements.
HSC 6.95 25505(a)(2), 25508(a)(1), 25508(a)(3)Failure to electronically submit a site map with all required
content.
19 CCR 1 5030.10(a); HSC 6.95 25505(a)(4), 25508(a)(1),
25508(a)(3)
Failure to establish and/or electronically submit an adequate
training program in safety procedures in the event of a
release or threatened release of a hazardous material.
*Verify agricultural handler exemption HSC 25507.1
19 CCR 1 5030.10(b); HSC 6.95 25505(a)(4)Failure to provide initial and annual training to all employees
in safety procedures in the event of a release or threatened
release of a hazardous material or failure to document and
maintain training records for a minimum of three years.
4006.1.1 Maintenance and style.
Signs and markings required by Section 4006.1 shall not be
obscured or removed; shall be in English as a primary
language or in symbols allowed by this code; shall be
durable; and the size, color and lettering shall be approved.
Violation Count:13 Inspection Fee:0.00
Type First Name Last Name Signature Date Signature Graphic
Owner/Rep.Daisy Cervantes 10/02/2024
Inspector Liseth Pisano 10/02/2024
Business must report in the California environmental reporting system, also known as CERS.
Inspection Documents
Violation Documents
Location Attributes:Commercial Hood; Fire Safety; Sprinkler System
Signatures
Inspection Notes
Documents
Admin Information
Page 2 of 10
Occupant:Wingstop Inspection
Date:
10/02/2024
Current Date:04/04/2025 12:19
Fire Safety Inspection
Exterior
Question Answer Notes
Address visible from street?Yes
Hazardous or dead vegetation or
combustible material on property No
Fire lanes painted and maintained Yes
OS&Y in good condition and secured
unobstructed Yes
FDC are accessible Yes
Audible alarm for sprinkler system in
good condition Yes
Knoxbox present, keys secured and
correct keys Yes
Private fire hydrants maintained and
tested Na
3ft Clearence maintained around fire
hydrants Yes
Interior
Question Answer Notes
Fire Extinguishers must be maintained,
tested and inspected Yes
Exit signs fully illuminated in normal and
emergency mode Yes
Exit doors operable from inside without
special knowledge or a key Yes
Exit isles, hallways and stairs clean of
obstructions Yes
Circuit breakers properly labeled Yes
Electrical outlets and junction boxes
properly covered Yes
Extension cords not being used in lieu of
permanent wiring.Yes
No items stored 24" non-sprinklered or
18" sprinklered ceilings.Yes
No visible penetrations in ceiling tile or
holes in drywall Yes
Fire Alarm
Question Answer Notes
Fire alarm system tested and maintained Yes
Fire Sprinkler
Question Answer Notes
Fire sprinkler system serviced and
maintained Yes
Commercial Hood
Page 3 of 10
Occupant:Wingstop Inspection
Date:
10/02/2024
Current Date:04/04/2025 12:19
Question Answer Notes
Kitchen hood extinguishing system
serviced within the last 6 months Yes
Kitchen hood has been properly cleaned
and serviced Yes
K class fire extinguisher is present and
serviced Yes
Hazmat
Question Answer Notes
Facility has reported into CERs No
CERs has been updated or certified for
current year No
Carbon monoxide detector present and
working Yes
Page 4 of 10
Occupant:Wingstop Inspection
Date:
10/02/2024
Current Date:04/04/2025 12:19
UST DW Inspection Annual
UST Inspection
Question Answer Notes
Facility ID#
EPA ID #
Facility has valid permit to operate?
UST operating permit application for
facility and tank information submitted.
A complete and accurate response plan
has been submitted, approved and
maintained
Owner/Operator has not made false
statment or representation of required
documents.
Failure to submit the Designated
Operator ID form within 30 days of
installing a UST system or within 30 days
of change.
Failure to have a properly qualified
service technician test leak detection
equipment as required every 12 months,
sensors, lineleak detectors, ATG
Failure to conduct secondary
containment testing or meet one of the
following requirements: Within 6 months
of install and every 36 months thereafter.
Failure to submit secondary containment
testing results on the secondary
containment test form to the CUPA
within 30 days after the test.
Failure to notify CUPA within 48 hours
prior to testing.
Leak detection equipment has an audible
and visual alarm as required
Failure to continuously monitor the
interstitial space of double-walled tank
with an audible and visual alarm system
The UST system shuts down the pump or
stops the flow when a leak is detected
Failure of the double wall pressurized
piping to be continuously monitored with
a system that activates an audible and
visual alarm or stops the flow at the
dispenser when a leak is detected
Failure of leak detection equipment to
be installed, calibrated, operated and/or
maintained in accordance with
manufacturers instructions
Page 5 of 10
Occupant:Wingstop Inspection
Date:
10/02/2024
Current Date:04/04/2025 12:19
Failure of UST system to be designed and
constructed with a monitoring system
capable of detecting the entry of
hazardous substance into the secondary
containment
Failure of leak detection equipment to
be installed, maintained and located such
that equipment is capable of detecting a
leak at the earliest possible oppertunity
Leak detection equipment disabled or
tampered with in a manner that would
prevent the monitoring system from
detecting and/or alerting the
owner/operator of a leak
Failure of a UST system installed on or
after July 1, 2003 and before July 1,
2004, to be designed and constructed
with a monitoring system capable of
detecting the entry of hazardous
substance stored in the primary
containment into t he secondary
containment and capable of detecting
water intrusion into the secondary
Failure to properly affix tag/sticker on
each monitoring equipment being
certified or replaced
Failure to maintain the interstitial space
such that a breach in the primary or
secondary containment is detected
before the liquid or vapor phase of the
hazardous substance stored in the UST
tank is released into the environment
Failure of UST system installed on or
after July 1, 2004, to be designed and
constructed with a monitoring system
capable of detecting the entry of the
liquid or vapor phase of the hazardous
substance stored in the primary
containment into the secondary and
capable of detecting water intrusion into
the secondary containment
Failure to install a line leak detector
Failure of line leak detector monitoring
single wall pressurized piping to meet
the requirements
Failure of the functional line leak
detector to have the capability of
detecting a release of 3.0gph, restrict or
shut off the flow of product through the
piping when a leak is detected
Failure to keep water and debris out of
secondary containment
failure to maintain secondary
containment piping to allow liquid to
flow into the sump in the event of a leak
Page 6 of 10
Occupant:Wingstop Inspection
Date:
10/02/2024
Current Date:04/04/2025 12:19
Failure to maintain secondary
containment
Spill bucket is installed and has functional
drain valve
Failure to operate UST system to prevent
unauthorized releases including spills
and/or overfills
Overfill prevention system has not been
overridden and meets the overfill
requirments
Failure to submit and maintain current
certification of financial responsibility or
other mechanism of financial assurance
Failure to maintain on-site, or off-site at a
readily available location if approved by
the UPA, copies of the Designated
Underground Storage Tank Operator
Visual Inspection Report and all
attachments for 36 months
Failure to comply with one of more of
the following Designated Operator
inspection requirements
DO employee training is current for at
least one employee on site and a training
logbook is kept
Failure to maintain monitoring records
for 36 months and for the release
detection equipment for 60 months
Failure to maintain records of repairs,
linings, and upgrades on site, or off site if
approved by the UPA
Failure to submit and have current UST
monitoring plan readily accessible at the
facility
Failure to maintain written agreement
between UST Owner and Operator
Failure to record any unauthorized
releases from the primary containment
Failure to comply with any of the
applicable requirements of the permit
issued for the operation of the UST
system
Failure to demonstrate to the UPA that
the equipment and methods used to
monitor the UST system are certified by
an independent third-party as complying
with the standards set forth
Red tag has been removed, defaced,
altered, or otherwise tampered with so
that the information on the tag is not
legible
Page 7 of 10
Occupant:Wingstop Inspection
Date:
10/02/2024
Current Date:04/04/2025 12:19
Owner/operator deposited or allowed
for the deposite of petroleum or a
hazardous substance into a UST that has
a red tag affixed to the fill pipe
Results of Inspection:
Commercial Hood
Question Answer Notes
Kitchen hood extinguishing system
serviced within the last 6 months
Kitchen hood has been properly cleaned
and serviced
K class fire extinguisher is present and
serviced
Hazmat
Question Answer Notes
Facility has reported into CERs
Carbon monoxide detector present and
working
CERs has been updated or certified for
current year
Page 8 of 10
Occupant:Wingstop Inspection
Date:
10/02/2024
Current Date:04/04/2025 12:19
HazMat - HMBP
Administration/Documentation
Question Answer Notes
Did the facility adequately establish and
implement a business plan when
storing/handling a hazardous material at
or above reportable quantities in CERS?
No
Did the facility annually review and
electronically certify in CERS that the
business plan is complete and accurate
on or before the required due date?
No
Does the facility have a copy of the
business plan readily available with
responsibilities for emergency response
or training for review?
No
Did the facility update CERS within 30
days of any one or more of the following
events: 1) A 100 percent or more
increase in the quantity of a previously
disclosed material. 2) Any handling of a
previously undisclosed hazardous
materials at or above reportable
quantities. 3) A change of business
address, business ownership, or business
name. 4) A substantial change in the
handler's operations that requires
modification to any portion of the
business plan.
No
Did the facility inform the property
owner in writing that an HMBP is
required for the facility?
No
Did the facility provide the property
owner a copy of the HMBP upon
request??
No
Did the facility report complete or
accurate information in the Business
Activities Page and/or Business Owner
Operator Identification Page in CERS?
No
Did the facility report complete and
accurate hazardous material inventory
information for all hazardous materials
on site at or above reportable quantities
in CERS?
No
Did the facility adequately establish an
emergency response plan in CERS?No
Did the facility submit a site map with all
the required content in CERS?No
Training
Question Answer Notes
Did the facility submit an adequate
training program with safety procedures
in the event of a release or threatened
release of a hazardous material in CERS?
No
Page 9 of 10
Occupant:Wingstop Inspection
Date:
10/02/2024
Current Date:04/04/2025 12:19
Did the facility provide initial and
refresher training to all employees and
maintain records for 3 years?
No
Operations/Maintenance
Question Answer Notes
Does the facility have adequate signage
for hazardous materials storage?No
Are hazardous materials separated form
incompatibles?Yes
Release/Leaks/Spills
Question Answer Notes
Did the facility fail to report a release or
threatened release of a hazardous
material to the unified program agency
and to Cal OES?
N/A
Page 10 of 10