Loading...
HomeMy WebLinkAbout2024-09-30 Inspection Report 1601 Panama Ln STE D-105 Happy Dragon.pdfCurrent Date:09/30/2024 16:51 Occupant:Happy Dragon Inspection Date: 09/30/2024 Occupant Name:Happy Dragon Inspection Date:09/30/2024 Street Number:1601 Occupant Code:119780 Street Name:Panama City:Bakersfield Street Type:Lane Postal Code:93307 Inspector:Pisano , Liseth State:California Occupant Suite:D-105 Passed:No Inspection Type:Hazmat Annual Violations Violation Code Description 903.4.2 Alarms. One exterior approved audible device, located on the exterior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler waterflow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Visible alarm notification appliances shall not be required except when required by Section 907. Complete Inspection Report - With Documents Facility Information Inspection Information Page 1 of 8 Occupant:Happy Dragon Inspection Date: 09/30/2024 Current Date:09/30/2024 16:51 901.6 Inspection, testing and maintenance. Fire protection and life safety systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection and life safety systems and equipment shall be inspected, tested and maintained or removed in accordance with Section 901.8. All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems required by these regulations shall be maintained in an operable condition at all times in accordance with this code and California Code of Regulations, Title 19, Division 1. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment, material or systems to their original normal and operational condition. [California Code of Regulations, Title 19, Division 1, §1.14] Maintenance. Every fire alarm system or device, sprinkler system, fire extinguisher, fire hose, fire-resistive assembly or any other fire safety assembly, device, material or equipment installed and retained in service in any building or structure subject to California Code of Regulations, Title 19, Division 1 regulations shall be maintained in an operable condition at all times in accordance with California Code of Regulations, Title 19, Division 1 regulations and with their intended use. [California Code of Regulations, Title 19, Division 1, §3.24] Maintenance of Equipment. All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems required by California Code of Regulations, Title 19, Division 1 shall be maintained in an operable condition at all times. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment material or systems to their original normal and operational condition. [California Code of Regulations, Title 19, Division 1, §904(a)] Required Inspection, Testing and Maintenance Frequencies. (a) All automatic fire extinguishing systems, including systems installed as an alternate to other building requirements, shall be inspected, tested and maintained in accordance with the following frequencies. Local authorities may require more frequent inspection, testing and maintenance and additional procedures. [California Code of Regulations, Title 19, Division 1, §904(a)(1)] Required Inspection, Testing and Maintenance Frequencies. (1) Water-based fire protection systems shall be inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition) including Annexes A, B, C, D, E, F and G as amended by the State of California. (Published as NFPA 25, 2013 California Edition.) [California Code of Regulations, Title 19, Division 1, §904(b)] Required Inspection, Testing and Maintenance Frequencies. (b) When proof of the installation date of standpipe systems or automatic fire sprinkler systems cannot be furnished, such systems shall receive initial testing and maintenance by July 1, 1985. [California Code of Regulations, Title 19, Division 1, §904.2(a)] Testing and Maintenance Requirements. (a) All testing and maintenance on automatic fire extinguishing systems in accordance with Health & Safety Code Section 13195 shall be performed by those licensed in accordance with Health and Safety Code Section 13196.5. Exceptions: (1) The State Fire Marshal may waive, in writing, licensing of fire departments which conduct fire sprinkler and standpipe system testing and maintenance. (2) Service on fire alarm systems and industrial systems as specified in Health and Safety Code Sections 13196.5(b) and (c) may be conducted without a license. (3) Testing and maintenance on automatic fire extinguishing systems exempted in writing by the State Fire Marshal, when the building owner or occupant has the staff and equipment to conduct testing and maintenance. [California Code of Regulations, Title 19, Division 1, §904.2(b)] Testing and Maintenance Requirements. (b) Any testing and maintenance of automatic fire extinguishing systems shall be performed in accordance with these requirements. Exceptions: (1) The State Fire Marshal may waive, in writing, the requirement that testing and maintenance be performed in accordance with these requirements when a licensee can demonstrate that a system cannot functionally be tested and maintained in accordance with the California Code of Regulations, Title 19, Division 1, Chapter 5. (2) If at any time a licensee encounters a specialized or modified system which cannot be tested and maintained in accordance with California Code of Regulations, Title 19, Division 1, Chapter 5, the licensee shall contact the State Fire Marshal and test and maintain the system as directed. (A) The intent of this section is to cover automatic fire extinguishing systems as originally designed, installed and approved by the Authority Having Jurisdiction. It is not, however, intended to require that such systems be upgraded to current adopted standards. [California Code of Regulations, Title 19, Division 1, §904.2(h)] Testing and Maintenance Requirements. (h) At the time of testing and maintenance, building management shall be consulted to avoid unnecessary disturbance of normal building operation. Page 2 of 8 Occupant:Happy Dragon Inspection Date: 09/30/2024 Current Date:09/30/2024 16:51 disturbance of normal building operation. [California Code of Regulations, Title 19, Division 1, §904.2(i)] Testing and Maintenance Requirements. (i) The licensee shall contact the local fire authority having jurisdiction prior to testing and maintenance of a system when required by the local fire authority having jurisdiction to do so. 904.5.1 System test. Systems shall be inspected and tested for proper operation at six-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. Extinguishing system units shall be weighed and the required amount of agent verified. Stored pressure-type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals indicated by the manufacturer. 606.3.3.1 Inspection. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code official. Inspections shall be completed by qualified individuals. Violation Count:4 Inspection Fee:0.00 Type First Name Last Name Signature Date Signature Graphic Owner/Rep.Alicia Contreras 09/30/2024 Inspector Liseth Pisano 09/30/2024 Conducted a fire, safety inspection, commercial hood inspection, and a hazardous materials inspection. The following must be corrected. 1. Replace the missing escutcheons in the lobby, kitchen, and employee restroom. 2. Secure CO2 tanks with a chain to prevent them from falling and leaking. 3. Replace vent cover in the storage room. 4. Commercial hood must be cleaned as soon as possible. No cleaning date on the commercial hood. 5. Commercial hood pull station is past due for service. It was last serviced in March of 2024. It is past due as of September 2024. The violations must be corrected on or before September 30, 2024. Let me know as soon as the violations have been corrected to reinspect. The facility no longer has reportable quantities of CO2 on site. The facility only has 90 pounds of CO2. Facility is still responsible for any billing for the hazardous materials for pre previous quantities. Inspection Documents Violation Documents Signatures Inspection Notes Documents Admin Information Page 3 of 8 Occupant:Happy Dragon Inspection Date: 09/30/2024 Current Date:09/30/2024 16:51 Location Attributes:Commercial Hood; Fire Safety; HMBP Page 4 of 8 Occupant:Happy Dragon Inspection Date: 09/30/2024 Current Date:09/30/2024 16:51 Fire Safety Inspection Exterior Question Answer Notes Address visible from street?Yes Hazardous or dead vegetation or combustible material on property No Fire lanes painted and maintained Yes OS&Y in good condition and secured unobstructed Yes FDC are accessible Yes Audible alarm for sprinkler system in good condition No Knoxbox present, keys secured and correct keys Yes Private fire hydrants maintained and tested Na 3ft Clearence maintained around fire hydrants Yes Interior Question Answer Notes Fire Extinguishers must be maintained, tested and inspected Yes Exit signs fully illuminated in normal and emergency mode Yes Exit doors operable from inside without special knowledge or a key Yes Exit isles, hallways and stairs clean of obstructions Yes Circuit breakers properly labeled Yes Electrical outlets and junction boxes properly covered Yes Extension cords not being used in lieu of permanent wiring.Yes No items stored 24" non-sprinklered or 18" sprinklered ceilings.Yes No visible penetrations in ceiling tile or holes in drywall Yes Fire Alarm Question Answer Notes Fire alarm system tested and maintained Yes Fire Alarm General Fire Sprinkler Question Answer Notes Fire sprinkler system serviced and maintained No Page 5 of 8 Occupant:Happy Dragon Inspection Date: 09/30/2024 Current Date:09/30/2024 16:51 Fire Sprinkler General Commercial Hood Question Answer Notes Kitchen hood extinguishing system serviced within the last 6 months No Kitchen hood has been properly cleaned and serviced No K class fire extinguisher is present and serviced Yes Hazmat Question Answer Notes Facility has reported into CERs N/A CERs has been updated or certified for current year N/A Carbon monoxide detector present and working N/A Page 6 of 8 Occupant:Happy Dragon Inspection Date: 09/30/2024 Current Date:09/30/2024 16:51 Commercial Hood Reinspection Exterior Question Answer Notes Address visible from street? Hazardous or dead vegetation or combustible material on property Fire lanes painted and maintained OS&Y in good condition and secured unobstructed FDC are accessible Audible alarm for sprinkler system in good condition Knoxbox present, keys secured and correct keys Private fire hydrants maintained and tested 3ft Clearence maintained around fire hydrants Interior Question Answer Notes Fire Extinguishers must be maintained, tested and inspected Exit signs fully illuminated in normal and emergency mode Exit doors operable from inside without special knowledge or a key Exit isles, hallways and stairs clean of obstructions Circuit breakers properly labeled Electrical outlets and junction boxes properly covered Extension cords not being used in lieu of permanent wiring. No items stored 24" non-sprinklered or 18" sprinklered ceilings. No visible penetrations in ceiling tile or holes in drywall Fire Alarm Question Answer Notes Fire alarm system tested and maintained Fire Alarm General Fire Sprinkler Question Answer Notes Fire sprinkler system serviced and maintained Page 7 of 8 Occupant:Happy Dragon Inspection Date: 09/30/2024 Current Date:09/30/2024 16:51 Fire Sprinkler General Commercial Hood Question Answer Notes Kitchen hood extinguishing system serviced within the last 6 months Kitchen hood has been properly cleaned and serviced K class fire extinguisher is present and serviced Hazmat Question Answer Notes Facility has reported into CERs Carbon monoxide detector present and working CERs has been updated or certified for current year Page 8 of 8