ELECTRICAL SER VICES, INC.
ANNUAL CATHODIC PROTECTION SYSTEM SURVEY
CIRCLE DELI
1416 GOLDEN STATE AVENUE
BAKERSFIELD, CALIFORNIA
Prepared For:
Circle Deli
1416 Golden State Avenue ~
Bakersfield, California 93301-2033
Prepared B~!:
Corrosion-Electrical Services, Inc.
14020 Maryton Avenue
Santa Fe Springs, California 90670
August 2002
14020 MARYTON AVENUE, SANTA FE SPRINGS, CALIFORNIA 90670 _PHONE: (562) 921-9522 FAX: (562) 921..6885
CA. LICENSE C-lO 684718
CORROSION-
ELECTRICAL SER VICES, INC.
TABLE OF CONTENTS
INTRODUCTION
BACKGROUND
SURVEY PROCEDURES
SURVEY ANALYSIS
CONCLUSIONS AND RECOMMENDATIONS
TABLES
Potential Survey Data Sheet
· Cathodic Protection System Maintenance Record Sheet
· Rectifier Data Sheet
1
1
1
2
2
14020 MARYTON A VENUE, SANTA FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885
CA. LICENSE C-lO 684718
CORROSION-
ELECTRICAL SER VICES, INC.
INTRODUCTION
This report contains information pertinent to the successful operation of the cathodic
protection system located at B.P. Circle Deli, 1416 Golden State Avenue, Bakersfield,
California, including present and historical data, system specifications, survey
procedures and recommended maintenance program.
BACKGROUND
The impressed current cathodic protection system installed at this facility in 1995
consists of the following items:
Four 3-inch diameter x 60-inch long graphite anodes installed in two 12-inch
diameter x 20-foot deep cathodic protection wells. The wells are backfilled with
petroleum coke breeze and vented to the surface via PVC piping. A traffic-rated
road-box is placed over each anode well. The anodes are connected to the rectifier
by a header cable.
· One Good-All rectifier rated at 50 volts and 12 Amperes (DC).
· Miscellaneous electrical fittings and cathode header cable.
SURVEY PROCEDURES
The following procedures were followed during the annual survey:
· The rectifier was inspected and the operating voltage and amperage were noted.
Structure-to-soil potentials were measured with a digital voltmeter connected
between the structure and a saturated copper-copper sulfate reference electrode in
contact with the earth. Test point locations are listed on the attached data sheets.
During the above procedure the tap settings on the rectifier were adjusted as
needed to ensure that sufficient protective current is being applied to the
underground metallic structures at this facility.
14020 MARYTON AVENUE, SANTA FE SPRINGS, CALIFORNL4 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885
CA. LICENSE C-lO 684718 1
CORROSION-
ELECTRICAL SER VICES, INC.
SURVEY ANALYSIS
Structure to soil potential measurements for each test point are above National
Association of Corrosion Engineers (NACE) design criteria of 850 millivolts (mV) with
cathodic protection applied. Rectifier output (DC volts and amperes) and potential
measurement data for each test location are shown on the enclosed data sheets.
CONCLUSIONS AND RECOMMENDATIONS
Based upon our visual inspection and the data obtained during the survey, Corrosion-
Electrical Services, Inc., concludes the following:
· The cathodic protection system is operating as de'signed and the underground tanks
and associated piping are receiving adequate protective currenL
Corrosion-Electrical Services, Inc., recommends that the rectifier data (volts and
amps) be recorded weekly on the attached Rectifier Data Sheet and mailed or faxed
to Corrosion-Electrical Services, Inc., on a quarterly basis. If any significant changes
are observed in the volts and/or amperes on the rectifier, Corrosion-Electrical
Services, Inc., should be notified immediately.
Along with the above Corrosion-Electrical Services, Inc., recommends, that in order
to protect your investment, an annual survey be performed by a qualified
individual. We will forward a letter approximately one year from this date
requesting your authorization to perform this service on your behalf.
14020 MARYTON AVENUE, SANTA FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885
CA. LICENSE C-lO 684718 2
.CORROSION-
.. ELECTRICAL SERVICES, INC.
This annual survey was conducted in accordance with the procedures described in the
National Association of Corrosion Engineers (NACE) Standard Recommended Practice
RP0285-95, Corrosion Control of Underground Storage Tank Systems by Cathodic Protection
and American Petroleum Institute (APo Recommended Practice 1632, Cathodic
Protection of Underground Petroleum Storage Tanks and Piping Systems.
Thank you for the opportunity to assist you in this phase of your cathodic mitigation
program. If you have any questions please contact us at your convenience.
Respectfully,
CORROSION-ELECTRICAL SERVICES, INC.
Latricia J. Brewis
President
14020 MARYTON AVENUE, SANT~4 FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885
CA. LICENSE C-lO 684718 3
CORROSION-
, , ELECTRICAL SERVICES, INC.
CLIENT: CIRCLE DELI
TEST DATE:
SYSTEM LOCATION:
8-28-02
SERVICE STATION NO:
CES NO: S2199
1416 GOLDEN STATE AVENUE. BAKERSFIELD. CALIFORNIA
ENGINEER: TECHICIAN: S. BREWIS
RECTIFIER DATA
MANUFACTURER: GOOD-ALL SERIAL NO.: 95UT2286
RATING: 50 VOLTS: 12 AMPERES: VAC: 120
OU'I~UT: 12 VOLTS: 1 AMPERES: MONITOR CHECK:
SETTING: B - 2
HOURMETER 62152.8 HRS LAST READING: 29893.0 HRS DATE: 12-6-98
CHANGE IN READING: 32259.8 HRS ACTUAL 32616 HRS DAYS OFF: 14
FIELD TEST DATA
STRUCTURE-TO-SOIL
TEST LOCATION POTENTIAL 0VIV)
I (on) I (off)
FUEL TANK #1 - SUPER UNLEADED -1047 -464
FUEL TANK #2 - REGULAR UNLEADED -1048 -493
FUEL TANK #3 -
FUEL TANK #4 -
FUEL TANK #5 -
FUEL TANK #6 -
VENTS - -1003 -476
DISPENSER - #1 & 2 -1057 -374
DISPENSER ' #3 & 4 -1051 -475
DISPENSER - #5 & 6 -1054 -475
DISPENSER -
DISPENSER -
DISPENSER -
WATER LINES -
GAS CO. ~ -
ELECTRICAL CONDUIT -
CuCuSO4 REFERENCE LOCATION @: NORTH EAST CORNER BY CARD ROOM
REMARKS: (FIELD) ANNUAL SURVEY. SYSTEM IS OPERATING AS DESIGNED. ALL POTENTIALS ARE
ABOVE THE NACE CRITERIA OF -850 MILLIVOLTS.
14020 MARYTON AVENUE, SANT/I [CE SPRINGS, CALIFORNL4 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885
CA. LICENSE C'10 684718
CORROSION-
ELECTRICAL SERVICES, INC.
CATHODIC PROTECTION SYSTEM MAINTENANCE RECORD SHEET
LOCATION OF RECTfFIER UNIT: STORAGE AREA
TYPE OF RECTIFIER: AIR COOLED WALL MOUNTED
TYPE OF ANODES: GRAPHITE
RECTIFIER MANUFACTURED BY:
RECTIFIER AC INPUT: 120
RECTIFIER DC OLrrPUT: 50
DATE SYSTEM TURNED ON: IULY 11, 1995
QUANTITY 4_ SIZE:
GOOD-ALL SERIAL #95UT2286
3 X 60 LONG
VOLTS 1 PHASE
VOLTS 12 AMPERES
60 CYCLE
RECI'IFIER READINGS
RECTIFIER SEITING DC OUTIq3T
BY DATE REMARKS
COARSE FINE VOLT AMPS
A 3 4.0 .4 LB 7-11-95 START UP SURVEY
B 3 17.6 1.8 BS 12-27-95 FOLLOW UP SURVEY
B 2 12 1 MH 12-6-98 ANNUAL SURVEY
B 2 12 1 SB 8-28-02 ANNUAL SURVEY
14020 MARYTON AVENUE, SANTA FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885
CA. LICENSE C-lO 684718
£ORROSION-
ELECTRICAL SER VICES, INC.
RECTIFIER QUARTERLY RECORDING SHEET
RECORD WEEKLY
OWNER CIRCLE DELI LOCATION
JOB # S2199
1416 GOLDEN STATE AVE., BAKERSFIELD, CA.
UNIT D.C. OUTPUT
DATE TIME REMARKS BY
NO. VOLTS AMPS
1 12 1 8-28-02 ANNUAL SURVEY SB
UNIT NO.
UNIT NO.
UNIT LOCATION: STORAGE AREA
UNIT LOCATION:
NORMAL RANGE:
UNIT NO. 1 VOLTS 9 - 15 AMPS
UNIT NO. VOLTS AMPS
.5 - 4.0
NOTE: IF UNIT STABILIZES OUTSIDE NORMAL, NOTIFY YOUR ENGINEER !!!
MAIL TO CORROSION-ELECTRICAL SERVICES, INC. QUARTERLY
14020 MARYTON AF'ENUE, SANTA FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885
CA. LICENSE C-lO 684718