HomeMy WebLinkAboutMITIGATION 8/2002¢O~ZtO$~ON- ELECTRICAL SER VICES, INC. ANNUAL CATHODIC PROTECTION SYSTEM SURVEY CIRCLE DELI 1416 GOLDEN STATE AVENUE BAKERSFIELD, CALIFORNIA Prepared For: Circle Deli 1416 Golden State Avenue ~ Bakersfield, California 93301-2033 Prepared B~!: Corrosion-Electrical Services, Inc. 14020 Maryton Avenue Santa Fe Springs, California 90670 August 2002 14020 MARYTON AVENUE, SANTA FE SPRINGS, CALIFORNIA 90670 _PHONE: (562) 921-9522 FAX: (562) 921..6885 CA. LICENSE C-lO 684718 CORROSION- ELECTRICAL SER VICES, INC. TABLE OF CONTENTS INTRODUCTION BACKGROUND SURVEY PROCEDURES SURVEY ANALYSIS CONCLUSIONS AND RECOMMENDATIONS TABLES Potential Survey Data Sheet · Cathodic Protection System Maintenance Record Sheet · Rectifier Data Sheet 1 1 1 2 2 14020 MARYTON A VENUE, SANTA FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885 CA. LICENSE C-lO 684718 CORROSION- ELECTRICAL SER VICES, INC. INTRODUCTION This report contains information pertinent to the successful operation of the cathodic protection system located at B.P. Circle Deli, 1416 Golden State Avenue, Bakersfield, California, including present and historical data, system specifications, survey procedures and recommended maintenance program. BACKGROUND The impressed current cathodic protection system installed at this facility in 1995 consists of the following items: Four 3-inch diameter x 60-inch long graphite anodes installed in two 12-inch diameter x 20-foot deep cathodic protection wells. The wells are backfilled with petroleum coke breeze and vented to the surface via PVC piping. A traffic-rated road-box is placed over each anode well. The anodes are connected to the rectifier by a header cable. · One Good-All rectifier rated at 50 volts and 12 Amperes (DC). · Miscellaneous electrical fittings and cathode header cable. SURVEY PROCEDURES The following procedures were followed during the annual survey: · The rectifier was inspected and the operating voltage and amperage were noted. Structure-to-soil potentials were measured with a digital voltmeter connected between the structure and a saturated copper-copper sulfate reference electrode in contact with the earth. Test point locations are listed on the attached data sheets. During the above procedure the tap settings on the rectifier were adjusted as needed to ensure that sufficient protective current is being applied to the underground metallic structures at this facility. 14020 MARYTON AVENUE, SANTA FE SPRINGS, CALIFORNL4 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885 CA. LICENSE C-lO 684718 1 CORROSION- ELECTRICAL SER VICES, INC. SURVEY ANALYSIS Structure to soil potential measurements for each test point are above National Association of Corrosion Engineers (NACE) design criteria of 850 millivolts (mV) with cathodic protection applied. Rectifier output (DC volts and amperes) and potential measurement data for each test location are shown on the enclosed data sheets. CONCLUSIONS AND RECOMMENDATIONS Based upon our visual inspection and the data obtained during the survey, Corrosion- Electrical Services, Inc., concludes the following: · The cathodic protection system is operating as de'signed and the underground tanks and associated piping are receiving adequate protective currenL Corrosion-Electrical Services, Inc., recommends that the rectifier data (volts and amps) be recorded weekly on the attached Rectifier Data Sheet and mailed or faxed to Corrosion-Electrical Services, Inc., on a quarterly basis. If any significant changes are observed in the volts and/or amperes on the rectifier, Corrosion-Electrical Services, Inc., should be notified immediately. Along with the above Corrosion-Electrical Services, Inc., recommends, that in order to protect your investment, an annual survey be performed by a qualified individual. We will forward a letter approximately one year from this date requesting your authorization to perform this service on your behalf. 14020 MARYTON AVENUE, SANTA FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885 CA. LICENSE C-lO 684718 2 .CORROSION- .. ELECTRICAL SERVICES, INC. This annual survey was conducted in accordance with the procedures described in the National Association of Corrosion Engineers (NACE) Standard Recommended Practice RP0285-95, Corrosion Control of Underground Storage Tank Systems by Cathodic Protection and American Petroleum Institute (APo Recommended Practice 1632, Cathodic Protection of Underground Petroleum Storage Tanks and Piping Systems. Thank you for the opportunity to assist you in this phase of your cathodic mitigation program. If you have any questions please contact us at your convenience. Respectfully, CORROSION-ELECTRICAL SERVICES, INC. Latricia J. Brewis President 14020 MARYTON AVENUE, SANT~4 FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885 CA. LICENSE C-lO 684718 3 CORROSION- , , ELECTRICAL SERVICES, INC. CLIENT: CIRCLE DELI TEST DATE: SYSTEM LOCATION: 8-28-02 SERVICE STATION NO: CES NO: S2199 1416 GOLDEN STATE AVENUE. BAKERSFIELD. CALIFORNIA ENGINEER: TECHICIAN: S. BREWIS RECTIFIER DATA MANUFACTURER: GOOD-ALL SERIAL NO.: 95UT2286 RATING: 50 VOLTS: 12 AMPERES: VAC: 120 OU'I~UT: 12 VOLTS: 1 AMPERES: MONITOR CHECK: SETTING: B - 2 HOURMETER 62152.8 HRS LAST READING: 29893.0 HRS DATE: 12-6-98 CHANGE IN READING: 32259.8 HRS ACTUAL 32616 HRS DAYS OFF: 14 FIELD TEST DATA STRUCTURE-TO-SOIL TEST LOCATION POTENTIAL 0VIV) I (on) I (off) FUEL TANK #1 - SUPER UNLEADED -1047 -464 FUEL TANK #2 - REGULAR UNLEADED -1048 -493 FUEL TANK #3 - FUEL TANK #4 - FUEL TANK #5 - FUEL TANK #6 - VENTS - -1003 -476 DISPENSER - #1 & 2 -1057 -374 DISPENSER ' #3 & 4 -1051 -475 DISPENSER - #5 & 6 -1054 -475 DISPENSER - DISPENSER - DISPENSER - WATER LINES - GAS CO. ~ - ELECTRICAL CONDUIT - CuCuSO4 REFERENCE LOCATION @: NORTH EAST CORNER BY CARD ROOM REMARKS: (FIELD) ANNUAL SURVEY. SYSTEM IS OPERATING AS DESIGNED. ALL POTENTIALS ARE ABOVE THE NACE CRITERIA OF -850 MILLIVOLTS. 14020 MARYTON AVENUE, SANT/I [CE SPRINGS, CALIFORNL4 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885 CA. LICENSE C'10 684718 CORROSION- ELECTRICAL SERVICES, INC. CATHODIC PROTECTION SYSTEM MAINTENANCE RECORD SHEET LOCATION OF RECTfFIER UNIT: STORAGE AREA TYPE OF RECTIFIER: AIR COOLED WALL MOUNTED TYPE OF ANODES: GRAPHITE RECTIFIER MANUFACTURED BY: RECTIFIER AC INPUT: 120 RECTIFIER DC OLrrPUT: 50 DATE SYSTEM TURNED ON: IULY 11, 1995 QUANTITY 4_ SIZE: GOOD-ALL SERIAL #95UT2286 3 X 60 LONG VOLTS 1 PHASE VOLTS 12 AMPERES 60 CYCLE RECI'IFIER READINGS RECTIFIER SEITING DC OUTIq3T BY DATE REMARKS COARSE FINE VOLT AMPS A 3 4.0 .4 LB 7-11-95 START UP SURVEY B 3 17.6 1.8 BS 12-27-95 FOLLOW UP SURVEY B 2 12 1 MH 12-6-98 ANNUAL SURVEY B 2 12 1 SB 8-28-02 ANNUAL SURVEY 14020 MARYTON AVENUE, SANTA FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885 CA. LICENSE C-lO 684718 £ORROSION- ELECTRICAL SER VICES, INC. RECTIFIER QUARTERLY RECORDING SHEET RECORD WEEKLY OWNER CIRCLE DELI LOCATION JOB # S2199 1416 GOLDEN STATE AVE., BAKERSFIELD, CA. UNIT D.C. OUTPUT DATE TIME REMARKS BY NO. VOLTS AMPS 1 12 1 8-28-02 ANNUAL SURVEY SB UNIT NO. UNIT NO. UNIT LOCATION: STORAGE AREA UNIT LOCATION: NORMAL RANGE: UNIT NO. 1 VOLTS 9 - 15 AMPS UNIT NO. VOLTS AMPS .5 - 4.0 NOTE: IF UNIT STABILIZES OUTSIDE NORMAL, NOTIFY YOUR ENGINEER !!! MAIL TO CORROSION-ELECTRICAL SERVICES, INC. QUARTERLY 14020 MARYTON AF'ENUE, SANTA FE SPRINGS, CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885 CA. LICENSE C-lO 684718