HomeMy WebLinkAboutSURVEY REP. 10/18/2004 (COPY)
::í
.F'-LYJRROSION-
. \'0/-, ELECTRICAL SERVICES! INC.
October 18, 2004
Delimart
9628 Rosedale Highway
Bakersfield, California 93312
Attention:
Diana Meyer
Please find enclosed a copy of your annual cathodic protection survey report for 2004.
The cathodic protection system is operating as designed. If you have any questions
please contact us at your convenience at (562) 921-9522.
Respectfully,
Corrosion-Electrical Services, Inc.
ù-()
Latricia J. Brewis
President
1-1020 Jf4RYTON AVENUE, SANTA FE SPRINGS. CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885
CA. LICENSE C-IO 68./718
AJ,èORROSION-
ELECTRICAL· SERVICES, INC.
9-24-04
CES NO:
SERVICE STATION NO:
S2022
CLIENT: DELIMART
TEST DATE:
SYSTEM LOCATION:
9628 ROSEDALE HIGHWAY. BAKERSFIELD. CALIFORNIA
ENGINEER:
TECHICIAN:
1. BREWIS
RECTIFIER DATA
MANUFACTURER: GOOD-ALL SERIAL NO.: 9161123
RATING: 80 VOLTS: 20 AMPERES: VAC: 120
OUTPUT: 18 VOLTS: 4.5 . AMPERES: MONITOR CHECK:
SETTING: A-5
HOURMETER N/A HRS LAST READING: HRS DATE:
CHANGE IN READING: HRS ACTUAL HRS DAYS OFF:
FIELD TEST DATA
STRUCTURE-TO-SOIL
TEST LOCATION POTENTIAL (MY)
I (on) I (off)
FUELTANK#l- PLUS UNLEADED -941 -523
FUEL TANK #2 - SUPER UNLEADED -935 -523
FUEL TANK #3 - DIESEL -939 -523
FUEL TANK #4 -
FUEL TANK #5 -
FUEL TANK #6 -
VENTS - -865 -523
DISPENSER - 1-2 -873 -523
DISPENSER - 3-4 -874 -523
DISPENSER - 5-6 -867 -523
DISPENSER - 7-8 -858 -523
DISPENSER -
DISPENSER -
WATER LINES -
GAS CO. METER -
ELECI'RlCAL CONDUIT -
CuCuS04 REFERENCE LOCATION @: CP TEST BOX
REMARKS: (FIELD) ANNUAL SURVEY. SYSTEM IS OPERATING AS DESIGNED. ALL POTENTIALS ARE
ABOVE THE NACE CRITERIA OF -850 MILLIVOLTS.
].1020 ltfARYTON AVEjVUE, SANTA FE SPRINGS, CALlFORNL4 90670 PHONE: (562) 921-9522 FAX: (562) 921-6S.U
C4. LICENSE C-10 68./718