HomeMy WebLinkAboutSURVEY REP. 10/18/2004 (COPY) ::í .F'-LYJRROSION- . \'0/-, ELECTRICAL SERVICES! INC. October 18, 2004 Delimart 9628 Rosedale Highway Bakersfield, California 93312 Attention: Diana Meyer Please find enclosed a copy of your annual cathodic protection survey report for 2004. The cathodic protection system is operating as designed. If you have any questions please contact us at your convenience at (562) 921-9522. Respectfully, Corrosion-Electrical Services, Inc. ù-() Latricia J. Brewis President 1-1020 Jf4RYTON AVENUE, SANTA FE SPRINGS. CALIFORNIA 90670 PHONE: (562) 921-9522 FAX: (562) 921-6885 CA. LICENSE C-IO 68./718 AJ,èORROSION- ELECTRICAL· SERVICES, INC. 9-24-04 CES NO: SERVICE STATION NO: S2022 CLIENT: DELIMART TEST DATE: SYSTEM LOCATION: 9628 ROSEDALE HIGHWAY. BAKERSFIELD. CALIFORNIA ENGINEER: TECHICIAN: 1. BREWIS RECTIFIER DATA MANUFACTURER: GOOD-ALL SERIAL NO.: 9161123 RATING: 80 VOLTS: 20 AMPERES: VAC: 120 OUTPUT: 18 VOLTS: 4.5 . AMPERES: MONITOR CHECK: SETTING: A-5 HOURMETER N/A HRS LAST READING: HRS DATE: CHANGE IN READING: HRS ACTUAL HRS DAYS OFF: FIELD TEST DATA STRUCTURE-TO-SOIL TEST LOCATION POTENTIAL (MY) I (on) I (off) FUELTANK#l- PLUS UNLEADED -941 -523 FUEL TANK #2 - SUPER UNLEADED -935 -523 FUEL TANK #3 - DIESEL -939 -523 FUEL TANK #4 - FUEL TANK #5 - FUEL TANK #6 - VENTS - -865 -523 DISPENSER - 1-2 -873 -523 DISPENSER - 3-4 -874 -523 DISPENSER - 5-6 -867 -523 DISPENSER - 7-8 -858 -523 DISPENSER - DISPENSER - WATER LINES - GAS CO. METER - ELECI'RlCAL CONDUIT - CuCuS04 REFERENCE LOCATION @: CP TEST BOX REMARKS: (FIELD) ANNUAL SURVEY. SYSTEM IS OPERATING AS DESIGNED. ALL POTENTIALS ARE ABOVE THE NACE CRITERIA OF -850 MILLIVOLTS. ].1020 ltfARYTON AVEjVUE, SANTA FE SPRINGS, CALlFORNL4 90670 PHONE: (562) 921-9522 FAX: (562) 921-6S.U C4. LICENSE C-10 68./718