Date Printed and Mailed: 07/28/2004
BAKERSFIELD FIRE DEPARTMENT
OFFICE OF ENVIRONMENTAL SERVICES
INSPECTOR STEVE UNDERWOOD
900 TRUXTUN AVE., STE. 210
BAKERSFIELD, CA. 93301
Test Date: 07/13/2004
Order Number: 3135565
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
ULTRAMAR 074
3225 BUÇK OWENS BLVD.
HWY . 99/HwY 58
BAKERSFIELD, CA. 93301
Testing performed:
Leak detector tests
Line tests
Monitor Certification
Sincerely,
:D~.K~
, Dawn Kohlmeyer
Manager, Field Reporting
~>~
~ ~ .
.~
,
. .
~., Dlnlcnology
PURPOSE: COMPLIANCE
TEST DATE: 07/13/04
CLIENT: VALERO
685 WEST THIRD ST
HANFORD, CA 93230
Sandy Huff
(559)583-3298
TANKNOLOGY CERTIFICATE OF TESTING
8900 SHOAL CREEK, BUILDING 200 AUSTIN, TEXAS 78757
TELEPHONE (512) 451-6334 FAX (512) 459-1459
TEST RESULT SUMMARY REPORT
WORK ORDER NUMBER: 3135565
CUSTOMER PO:
SITE: ULTRAMAR 074
3225 BUCK OWENS BLVD.
HWY 99/HWY 58
BAKERSFIELD, CA 93301
Manager
(661 )324-9481
TEST TYPE: TLD-1
87
89
20k
20k
3 UNLEADED
4 PLUS
6 DIESEL
7 DIESEL
DW FIBERG
DW FIBERG
DW FIBERG
DW FIBERG
PRESSURE P 0.006
PRESSURE P 0.006
PRESSURE P P P P 0.003 0.003 0.003 0.009
PRESSURE P P 0.003 0.014
y
y
y
y
87
89
20k
20k
3 RED JACKET
4 RED JACKET
6 RED JACKET
7 RED JACKET
FX2V
FX1V
FX2-DV
FX2-DV
110211102 P
111796 P
21199 9638 P
4120 4744 P
87 3 RED JACKET
For owner detailed report information, visit www.tanknology.com and select On-Line Reports-WRAP, or contact your local Tanknology office.
Tester Name: WILLIAM ROGERS
ø//S-'¡-/
Technician Certification Number: 1647
Printed 07/27/2004 15:32 KOHLMEYER
¡.
~
... ';: ..
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
~.DJnImoIogy
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757(512) 451-6334
TEST DATE: 07/13/04
CLIENT: VALERO
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
Tank ID: 87 3
Product: UNLEADED
Capacity in gallons: 14, 139
Diameter in inches: 95.00
Length in inches: 337
Material: . DW STEEL
COMMENTS
Tank manifolded: NO
Vent manifolded: YES
Vapor recovery manifolded: YES
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
140.5
146.0
44.5
4.0
DUAL
ASSIST
Start (in)
End (in)
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
, VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
Bubble
NOT
TESTED
Make: RED JACKET RED JACKET
Ullage Model: FX1-DV FX2V
SIN: 10304 8268 110211102
Open time in sec: 4.00
Holding psi: 12
Resiliency cc: 150 NOT
Test leak rate mllm: 189.0 TESTED
Metering psi: 40
Calib. leak in gph: 3.00 3.00
Results: PASS PASS
COMMENTS
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
2.0
30.0
50
o
40
15:03
15:43
0.006
PASS
PRESSURE
RED JACKET
NOT
TESTED
NOT
TESTED
NOT
TESTED
Impact Valves Operational: YES
Printed 07/27/2004 15:32
i'
~
-=- ': .
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
~~ DlnImoIogy
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757. (512) 451-6334
TEST DATE: 07 /13/04
CLIENT: VALERO
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
Tank ID: 89 4
Product: PLUS
Capacity in gallons: 10,139
Diameter in inches: 95.00
Length in inches: 337
Material: DW STEEL
COMMENTS
Tank manifolded: NO
Vent manifolded: YES
Vapor recovery manifolded: YES
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
138.5
145.0
42.5
4.0
DUAL
ASSIST
Start (in)
End (in)
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
Bubble
NOT
TESTED
Ullage
Make:
Model:
SIN:
Open time in see:
Holding psi:
Resiliency cc:
Test leak rate mllm:
Metering psi:
Calib. leak in gph:
Results:
NOT
TESTED
RED JACKET
FX1V
111796 5324
2.00
14
100
189.0
40
3.00
PASS
COMMENTS
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
2.0
30.0
50
o
40
15:03
15:43
0.006
PASS
PRESSURE
RED JACKET
NOT
TESTED
NOT
TESTED
NOT
TESTED
Impact Valves Operational: YES
Printed 07/27/2004 15:32
TEST DATE: 07/13/04
CLIENT: VALERO
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
-~ Dlnlmology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
Tank ID: 2 Ok 6
Product: DIESEL
Capacity in gallons: 20 I 068
Diameter in inches: 129 . 00
Length in inches: 358
Material: DW STEEL
Tank manifolded: NO
Vent manifolded: NO
Vapor recovery manifolded: NO
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
193.0
201. 0
64.0
4.0
NONE
NONE
COMMENTS
Lines b, C, d and a & b form tank #7 are all stilite lines.
Start (in)
End (in)
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Water Level:
Dipped Product Level:
. Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
Bubble
Ullage
Make:
Model:
SIN:
Open time in sec:
Holding psi:
Resiliency cc:
Test leak rate ml/m:
Metering psi:
Calib. leak in gph:
Results:
RED JACKET
FX2-DV
21199 9638
NOT
TESTED
6.00
14
450
189.0
42
3.00
PASS
NOT
TESTED
COMMENTS
COMMENTS
Material: DW FIBERG DW FIBERG DW FIBERG DW FIBERG
Diameter (in): 3.0 3.0 3.0 3.0
Length (ft): 220.0 20.0 20.0 20.0
Test psi: 50 SO SO SO
Bleedback cc: 0 0 0 0
Test time (min): SO 40 30 30
Start time: 09:36 12:33 11:46 11:06
End time: 10:26 13:13 12:16 11:36
Final gph: 0.003 0.003 0.003 0.009
Result: PASS PASS PASS PASS
Pump type: PRESSURE PRESSURE PRESSURE PRESSURE
Pump make: RED JACKET RED JACKET RED JACKET RED JACKET
COMMENTS Impact Valves Operational: YES
Printed 07/27/2004 15:32
;;: ~I
~ .
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
-fÞDJnknoIogy
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757.(512) 451-6334
TEST DATE: 07 /13/04
CLIENT: VALERO
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
Tank ID: 20k 7
Product: DIESEL
Capacity in gallons: 20, 000
Diameter in inches: 129 .00
Length in inches: 357
Material: DW STEEL
Tank manifolded: NO
Vent manifolded: NO
Vapor recovery manifolded: NO
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
193.0
201. 0
64.0
4.0
NONE
NONE
COMMENTS
this tank does not exist. it is put in only to be able to show all of the satellite lines for the diesel tank.
Start (in)
End (in)
New/passed Failed/replaced New/passed· Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
Bubble
Make:
Model:
SIN:
Open time in sec:
Holding psi:
Resiliency cc:
Test leak rate ml/m:
Metering psi:
Calib. leak in gph:
Results:
NOT
TESTED
Ullage
RED JACKET
FX2~DV
4120 4744
4.00
14
480
189.0
44
3.00
PASS
NOT
TESTED
COMMENTS
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
"" COMMENTS
DW FIBERG
3.0
20.0
DW FIBERG
3.0
20.0
50
o
50
09:36
10:26
0.003
PASS
PRESSURE
RED JACKET
Impact Valves Operational: YES
NOT
TESTED
50
o
30
10:32
11:02
0.014
PASS
o
NOT 0
TEST~ß:OO
00:00
0.000
PRESSURE
RED JACKET
Printed 07/27/2004 15:32
. '
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6. 7, Health and Safety Code; Chapter 16, Division 3 Title 23, California Code of Regulations
. . This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility, a separate
certification or reDort must be DreDared for each monitorina svstem control Danel by the technician who performs the work. A copy of this form must be provided to the tank
system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: UL TRAMAR 074
Site Address: 3225 BiJCK OWENS BLVD.
HWY 99/HWY 58
City: BAKERSFIELD
Contact Phone No: 324-9481
Date of Testing/Service: 07113/2004
CA
Zip: 93301
Facility Contact Person: Manager
MakelModel of Monitoring System: GILBARCO EMC Work Order Number: 3135565
B. Inventory of Equipment TestedlCertified
Check the appropriate boxes to indicate specific equipment inspected/serviced
Tank ID: 87 Tank ID: 89 .
X In-Tank Gauging Probe. Model: 730 X In-Tank Gauging Probe. Model: 730
X Annular Space or Vault Sensor. Model: 420 XI Annular Space or Vault Sensor. Model: 420
X Piping SumpffrenchSensor(s). Model: 208 Yl Piping SumpfTrench Sensor(s). Model: 208
= -
Fill Sump Sensor(s). Model:
= Fill Sump Sensor(s). Model:
X Mechanical Line Leak Detector. Model: FX1DV 'II. Mechanical Line Leak Detector. Model: FXW
= Electronic Line Leak Detector. Model: ;.;.;.
Electronic Line Leak Detector. Model:
= =
Tank Overfill/High-Level Sensor. Model: Tank Overfill/High-Level Sensor. Model:
=
Other (specify equipment type and model in Section E on page 2). - Other (specify equipment type and model in Section E on page 2).
Tank ID: UIt:::>t:L Tank ID:
X In-Tank Gauging Probe. Model: 730 - Model:
In-Tank Gauging Probe.
~ Annular Space or Vault Sensor. Model: 420 Annular Space or Vault Sensor.
~ Model:
~ Piping Sumpffrench Sensor(s). Model: 208 Piping Sumpffrench Sensor(s). Model:
Fill Sump Sensor(s). Model:
= Fill Sump Sensor(s), Model:
X Mechanical Line Leak Detector. Model: FX2DV (2) - Mechanical Line Leak Detector. Model:
= Electronic Line Leak Detector. Model: -
= Electronic Line Leak Detector. Model:
Tank Overfill/High-Level Sensor. Model:
= Tank Overfill/High-Level Sensor. Model:
X Other (specify equipment type and model in Section E on page 2). D Other (specify equipment type and model in Section E on page 2).
- IDlspenser ID: 1/2 Dispenser ID: 3/4
D Dispenser Containment Sensor(s) Model: n Dispenser Containment Sensor(s) Model:
[K] Shear Valve(s). ŒJ Shear Valve(s)
D Dispenser Containment Float(s) and Chain(s). n Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 5/6 Dispenser ID: 7/8
D Dispenser Containment Sensor(s) Model: n Dispenser Containment Sensor(s). Model:
ŒJ Shear Valve(s). ~ Shear Valve(s).
n Dispenser Containment Float(s) and Chain(s). o Dispenser Containment Float(s) and Chain(s).
Dispenser ID: DSL 1 Dispenser ID: DSL2
D Dispenser Containment Sensor(s) Model: o Dispenser Containment Sensor(s). Model:
ŒJ Shear Valve(s). :R]Shear Valve(s).
D Dispenser Containment Float(s) and Chain(s). =:J Dispenser Containment Float(s) and Chain(s).
* If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines.
Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): 0 System set-up ŒJ Alarm history report
Signature:
License. No.:
Phone No.: (800) 800-4633
Date otTesting/Servicing: 07/13/2004
Þ//~I-/
Technician Name (print): WILLIAM ROGERS
Certification No.: 8520
Testing Company Name: Tanknology
Site Address: 8900 Shoal Creek, Bldg. 200 Austin, TX 78757
Monitorin2 System Certification
Page 1 of 3
Based on CA form dated 03/01
Monitoring System Certification
I'
I
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
Date of Testing/Service: 07/13/2004
D. Results of Testing/Servicing
Software Version Installed: 7.03
Complete the following checklist:
rxl Yes DNo' Is the audible alarm operational?
~ Yes DNo' Is the visual alarm operational?
~ Yes DNo' Were all sensors visually inspected, functionally tested, and confirmed operational?
~ Yes DNo' Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not
interfere with their proper operation?
n Yes DNo' IIXlNtA If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
DYes ~NO' DNtA For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive
shut-down? (check all that apply) 0 SumplTrench Sensors; 0 Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? DYes n No
~ Yes ONO' ONtA For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e.: no mechanical
overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill points{s) and operating
properly? If so, at what percent of tank capacity does the alarm trigger? 90 %
~ Yes' ONO Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E, below.
DYes' ~NO Was liquid found inside any secondary containment systems designed as dry systems? (check all that apply) o Product;
o Water. If yes, describe causes in Section E, below.
~ Yes ONO' Was monitoring system set-up reviewed to ensure proper settings? Attach set-up reports, if applicable.
~ Yes ONO' Is all monitoring equipment operational per manufacturers' specifications?
. In Section E below, describe how and when these deficiences were or will be corrected.
E. Comments:
THERE WAS AN ADDITIONAL SUMP CALLED A FILTER SUMP- SENSOR (208)
REPLACED 1 FX1 DV LEAK DETECTOR IN THE 87 LINE.
Page 2 of 3
Based on CA form dated 03/01
· '
Monitoring System Certification
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
Date of Testing/Service: 07/13/2004
F. In-Tank Gauging I SIR Equipment
o Check this box if tank gauging is used only for inventory control.
D Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
ŒJves DNo· Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
ŒJves DNo· Were all tank gauging probes visually inspected for damage and residue buildup?
ŒJves DNo· Was accuracy of system product level readings tested?
ŒJves DNo· Was accuracy of system water level readings tested?
0ves DNo· Were all probes reinstalled properly?
ŒJves DNo· Were all items on the equipment manufacturers' maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line leak Detectors (llD) :
D Check this box if LLDs are not installed.
Complete the following checklist:
Œ]ves DNo· DN/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
(Check all that apply) Simulated leak rate: ~ 3 g.p.h 0 0.1 g.p.h 00.2 g.p.h
/Xl Yes DNo· Were all LLDs confirmed operational and accurate within regulatory requirements?
Œ]ves DNo· Was the testing apparatus properly calibrated?
o Yes DNO· DN/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
DYes DNo· [! N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
DYes ONO· Œ]N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
DYes ONO· 0N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test?
DYes ONO· 0N/A For electronic LLDs, have all accessible wiring connections been visually inspected?
o Yes ONO· Were all items on the equipment manufacturers' maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Page 3 of 3
Based on CA form dated 03/01
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6. 7, Health and Safety Code; Chapter 16, Division 3 Title 23, California Code of Regulations
· .This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility, a separate
certification or reDar! must be prepared for each monitorina svstem control panel by the technician who performs the work. A copy of this form must be provided to the tank
system owner/operator. The owner/operator must submit a copy of this form to the local agency regulatingUST systems within 30 days of test date,
A. General Information
Facility Name: UL TRAMAR 074
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
City: BAKERSFIELD
Contact Phone No: 324-9481
Date of Testing/Service: 07/13/2004
CA
Zip: 93301
Facility Contact Person: Manager
MakelModel of Monitoring System: Work Order Number: 3135565
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced
Tank ID: Tank ID:
In-Tank Gauging Probe, Model: n In-Tank Gauging Probe. Model:
= Model: 1 Annular Space or Vault Sensor.
Annular Space or Vault Sensor. Model:
= Piping SumplTrench Sensor(s). Model: - .
Piping SumplTrench Sensor(s). Model:
= -
Fill Sump Sensor(s). Model:
= Fill Sump Sensor(s). Model:
= Mechanical Line Leak Detector. Model: Mechanical Line Leak Detector. Model:
= Model: ;;;;;;
Electronic Line Leak Detector. Electronic Line Leak Detector. Model:
= Model: =
Tank OverfilVHigh-Level Sensor. Tank OverfilVHigh-Level Sensor. Model:
= Other (specify equipment type and model in Section E on page 2). Other (specify equipment type and model in Section E on page 2).
'--
TanklD: Tank ID:
- In-Tank Gauging Probe. Model: r- In-Tank Gauging Probe. Model:
= Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
= Piping SumplTrench Sensor(s). Model: Piping SumplTrench Sensor(s). Model:
= Fill Sump Sensor(s). Model: r-
= Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: - Mechanical Line Leak Detector. MOdel:
= Electronic Line Leak Detector. Model: =
= Electronic Line Leak Detector. Model:
Tank Overfill/High-Level Sensor. Model: - Tank Overfill/High-Level Sensor. Model:
=
Other (specify equipment type and model in Section E on page 2). - Other (specify equipment type and model in Section E on page 2).
- -
IDlspenser IU: DSL3 DispenserlD: DSL 4
o Dispenser Containment Sensor(s) Model: I Dispenser Containment Sensor(s) Model:
ŒJ Shear Valve(s). XJ Shear Valve(s)
o Dispenser Containment Float(s) and Chain(s), h Dispenser Containment Float(s) and Chain(s).
Dispenser ID: DSL5 Dispenser ID:
o Dispenser Containment Sensor(s) Model: h Dispenser Containment Sensor(s). Model:
[K] Shear Valve(s). tJ Shear Valve(s).
In Dispenser Containment Float(s) and Chain(s). h Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
o Dispenser Containment Sensor(s) Model: h Dispenser Containment Sensor(s). Model:
'--'
D Shear Valve(s). D Shear Valve(s).
D Dispenser Containment Float(s) and Chain(s). D Dispenser Containment Float(s) and Chain(s).
* If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines.
Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): D System set-up D Alarm history report
Signature:
License. No.:
Phone No.: (800) 800-4633
Date of Testing/Servicing: 07/13/2004
µ//S'1-/
Technician Name (print): WILLIAM ROGERS
Certification No.:
Testing Company Name: Tanknology
Site Address: 8900 Shoal Creek, Bldg. 200 Austin, TX 78757
Monitoring System Certification
Page 1 of3
Based on CA form dated 03/01
SITE DIAGRAM
1- ~ DJnIcnology
8900 SHOAL CREEK. BUILDING 200
AUSTIN. TEXAS 78757
(512) 451-6334
FAX (512) 459-1459
TEST DATE: 07/13/04
CLIENT: VALERO
WORK ORDER NUMBER3135565
SITE: ULTRAMAR 074
o sump ~ ~
~ ~ ~ ~ ð
~ ..~
C-STORE
8 ~ ~ 0
ENT :E
CD
0 VENTS :J
()
0 18~ ~~
Ultra mar #51-4
@ UL
3225 Buck Owens Blvd. 16~~
Bakersfield, CA
CD
CAR WAS
DSL
Printed 07/27/200415:32 KOHLMEYER
W òrk Ordèr:
¡
¡
!
I'
I
I
I
!
¡
I
I
I
I
I
I
l
I
3135565
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757
· ,
;1""\(,'\' (0"
\. /\ <-'/,,:
Wórk ûrdèr:
3135565
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757
, ;. i: _
-~ ~ \ ,~,//
ë .¡'\ \\ ~. '7
:",y
.., 'Tanlcnology
8900 Shoal Creek Blvd, Building 200
Austin, Texas 78757
Phone: (512) 451-6334
Fax: (512) 459-1459
Date Printed and Mailed: 07/28/2004
KERN CTY - ENVIROMENTAL HEALTH
2700 M STREET
SU ITE 300
BAKERSFIELD, CA. 93301
Test Date: 07/13/2004
Order Number: 3135565
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
UL TRAMAR 074
3225 BUCK OWENS BLVD.
HWY 99/HWY 58
BAKERSFIELD, CA. 93301
Testing performed:
Leak detector tests
Line tests
Monitor Certification
Sincerèly,
:b~K~
Dawn Kohlmeyer
Manager, Field Reporting
J~ DJnknology
PURPOSE: COMPLIANCE
TEST DATE: 07/13/04
CLIENT: VALERO
685 WEST THIRD ST
HANFORD, CA 93230
Sandy Huff
(559)583-3298
TANKNOLOGY CERTIFICATE OF TESTING
8900 SHOAL CREEK, BUILDING 200 AUSTIN, TEXAS 78757
TELEPHONE (512) 451-6334 FAX (512) 459-1459
TEST RESULT SUMMARY REPORT WORK ORDER NUMBER: 3135565
CUSTOMER PO:
SITE: ULTRAMAR 074
3225 BUCK OWENS BLVD.
HWY 99/HWY 58
BAKERSFIELD, CA 93301
Manager
(661 )324-9481
htness Tests Results
87
89
20k
20k
UNLEADED
PLUS
DIESEL
DIESEL
14,139 95.00 DW STEEL
10,139 95.00 DW STEEL
20,068 129.0 DW STEEL
20,000 129.0 DW STEEL
*Where regulations require, for VacuTect external water level may be depth of dry well or water is assumed at lowest point that can be confirmed dry.
Product Pi e Ti htness Test Results
87 3 DW FIBERG PRESSURE P 0.006 TLD-1 Y
89 4 DW FIBERG PRESSURE P 0.006 TLD-1 Y
20k 6 DW FIBERG PRESSURE P P P P 0.003 0.003 0.003 0.009 TLD-1 Y
20k 7 DW FIBERG PRESSURE P P 0.003 0.014 TLD-1 Y
87
89
20k
20k
3 RED JACKE T
4 RED JACKET
6 RED JACKET
7 RED JACKET
FX2V
FX1V
FX2-DV
FX2 -DV
110211102 P
111796 P
21199 9638 P
4120 4744 P
87
3
FX1-DV
10304 8268 P
For owner detailed report information, visit www.tanknology.com and select On-Line Reports-WRAP, or contact your local Tanknology office:
Tester Name: WILLIAM ROGERS Technician Certification Number: 1647
Tester Signature: ~ I' Date Signed: r .....-'~-oJ
I declare under penalty of perjury that I am . censed tank tester in the State of California and that the information contained i~IS report
is true and correct to the best of my knowledge,
.. .
-wÞ'DJnknology
PURPOSE: COMPLIANCE
TEST DATE: 07/13/04
CLIENT: VALERO
685 WEST THIRD ST
HANFORD, CA 93230
Sandy Huff
(559)583-3298
TANKNOLOGY CERTIFICATE OF TESTING
8900 SHOAL CREEK, BUILDING 200 AUSTIN, TEXAS 78757
TELEPHONE (512) 451-6334 FAX (512) 459-1459
TEST RESULT SUMMARY REPORT
WORK ORDER NUMBER: 3135565
CUSTOMER PO:
SITE: UL TRAMAR 074
3225 BUCK OWENS BLVD.
HWY 99/HWY 58
BAKERSFIELD, CA 93301
Manager
(661 )324-9481
TEST TYPE: TLD-1
87
89
20k
20k
3 UNLEADED
4 PLUS
6 DIESEL
7 D7ESEL
DW FIBERG
DW FIBERG
DW FIBERG
DW F:IBERG
PRESSURE P 0.006
PRESSURE P 0.006
PRESSURE P P P P 0.003 0.003 0.003 0.009
PRESSURE P P 0.003 0.014
y
y
y
y
87
89
20k
20k
3 RED JACKET FX2V
4 RED JACKET FX1V
6 RED JACKET FX2-DV
7 RED JACKET FX2-DV
110211102 P
111796 P
21199 9638 P
4120 4744 P
87
3 RED JACKET
FX1-DV
10304 8268 P
For owner detailed report information, visit www.tanknology.com and select On-Line Reports-WRAP, or contact your local Tanknology office.
Tester Name: WILLIAM ROGERS
ø//S''¡-/
Technician Certification Number: 1647
Printed 07/28/2004 07:50 SBOWERS
., ,
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
t-~ DJnknology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78751 (512) 451-6334
TEST DATE: 07 /13/04
CLI ENT: VALERO
WORK ORDER NUMBER3'l35565
SITE:ULTRAMAR 074
Tank 10: 87 3
Product: UNLEADED
Capacity in gallons: 14,139
Diameter in inches: 95. 00
Length in inches: 337
Material: DW STEEL
COMMENTS
Tank manifolded: NO
Vent manifolded: YES
Vapor recovery manifolded: YES
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
140.5
146.0
44.5
4.0
DUAL
ASSIST
Start (i n)
End (in)
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
Bubble
Make: RED JACKET RED JACKET
Ullage Model: FX1-DV FX2V
SIN: 1030t 8~68 110~1110~
Open time in sec: 4.00
Holding psi: 12
Resiliency cc: 150 NOT
'Test leak ratð mllm: 1ô9.0 TESTED
Meterìng psi: 40
Calib. leak in gph: 3.00 3.00
Results: PASS PASS
COMMENTS
NOT
TESTED
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Tes\time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
2.0
30.0
50
o
40
15:03
15:43
0.006
PASS
PRESSURE
RED JACKET
NOT
TESTED
NOT
TESTED
NOT
TESTED
Impact Valves Operational: YES
Printed 07/28/2004 07:50
~:' .
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
~., Tånknology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
TEST DATE:07/13/04
CLlENT:VALERO
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
Tank ID: 89 4
Product: PLUS
Capacity in gallons: 10,139
Diameter in inches: 95.00
Length in inches: 337
Material: DW STEEL
COMMENTS
Tank manifolded: NO
Vent manifolded: YES
Vapor recovery manifolded: YES
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
138.5
145.0
42.5
4.0
DUAL
ASSIST
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
Bubble
NOT
TESTED
Ullage
Make:
Model:
SIN:
Open time in see:
Holding psi:
Resiliency cc:
Test leak rate mUm:
Metering psi:
Calib. leak in gph:
Results:
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
RED JACKET
FX1V
111796 5324
2.00
14
100
18ir.c
40
3.00
PASS
NOT
TESTED
COMMENTS
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
2.0
30.0
50
o
40
15:03
15:43
0.006
PASS
PRESSURE
RED .JACKET
NOT
TESTED
NOT
TESTED
NOT
TESTED
Impact Valves Operational: YES
Printed 07/28/2004 07:50
..'; -1
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
~~ Dlnlmology
8900 SHOAL CREEK, BUILDING 200
AUS-TIN, TEXAS 78757 (512) 451-6334
TEST DATE: 07 /13/04
CLlENT:VALERO
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
Tank ID: 20k 6
Product: DIESEL
Capacity in gallons: 20, 068
Diameter in inches: 129 .00
Length in inches: 358
Material: DW STEEL
Tank manifolded: NO
Vent manifolded: NO
Vapor recovery manifolded: NO
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
COMMENTS
Lines b, c, d and a & b form tank #7 are all stilite lines.
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
193.0
201. 0
64.0
4.0
NONE
NONE
Start (in)
End (in)
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
Bubble
Ullag.e
Make:
Model:
SIN:
Opentime in see:
Holding psi:
Resiliency cc:
rest lèak rate ml/m:
Metering psi:
Calib. leak in gph:
Results:
NOT
TESTED
COMMENTS
COMMENTS
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
RED JACKET
FX2-DV
21199 9638
6.00
14
4~0
189.0
42
3.00
PASS
NOT
TESTED
Material: DW FIBERG DW FIBERG DW FIBERG DW FIBERG
Diameter (in): 3.0 3.0 3.0 3.0
Length (ft): 220.0 20.0 20.0 20.0
Test psi: 50 50 50 50
Bleedback cc: 0 0 0 0
Test time (min): 50 40 30 30
Start time: 09:36 12:33 11:46 11:06
End time: 10:26 13:13 12:16 11:36
Final gph: 0.003 0.003 0.003 0.009
Result: PASS PASS PASS PASS
Pump type: PRESSURE PRESSURE PRESSURE PRESSURE
Pump make: RED JACKET RED JACKET RED JACKET RED JACKET
COMMENTS Impact Valves Operational: YES
Printed 07/28/2004 07:50
-,; .
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
~~ DJnknology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
TEST DATE: 07 /13/04
CLlENT:VALERO
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
Tank 10: 20k 7
Product: DIESEL
Capacity in gallons: 20,000
Diameter in inches: 129.00
Length in inches: 357
Material: DW STEEL
Tank manifolded: NO
Vent manifolded: NO
Vapor recovery manifolded: NO
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches;
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
193.0
201. 0
64.0
4.0
NONE
NONE
COMMENTS
this tank does not exist. it is put in only to be able to show all of the satel~ite lines for the diesel tank.
Start (in)
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTectTestType:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
End (in)
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Bubble
Make:
Model:
SIN:
Open time in see:
Holding psi:
Resiliency cc:
Test leak rate m!/m:
Metering psi:
Calib. leak in gph:
Results:
NOT
TESTED
Material:
Diameter (in):
Length (ft):
Test psi.:
Bleedback cc:
Test time (miny:
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
Ullage
RED JACKET
PX2-DV
n~o 47U
4.00
14
480
189.0
44
3.00
PASS
NOT
TESTED
COMMENTS
DW FIBERG
3.0
20.0
DW FIBERG
3.0
20.0
SO
o
SO
09:36
10:26
0.003
PASS
PRESSURE
RED JACKET
Impact Valves Operational: YES
NOT
TESTED
SO
o
30
10:32
11:02
0.014
PASS
o
NOT 0
TES~2>:OO
00:00
0.000
PRESSURE
RED JACKET
Printed 07/28/2004 07:50
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6. 7, Hea/th and Safety Code; Chapter 16, Division 3 Tit/e 23, California Code of Regu/ations
. This fonn must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility, a separate
certification or reoort must be prepared for each monitorina system control panel by the technician who perfonns the work, A copy of this fonn must be provided to the tank
system owner/operator. The owner/operator must submit a copy of this fonn to the local agency regulating UST systems within 30 days of test date,
A. General Information
Facility Name: UL TRAMAR 074
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
City: BAKERSFIELD
Contact Phone No: 324-9481
Date of resting/Service: 07/13/2004
CA
Zip: 93301
Facility Contact Person: Manager
Make/Model of Monitoring System:GILBARCO EMC Work Order Number: 3135565
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced
Tank ID: 87 Tank ID: 89
X In-Tank Gauging Probe. Model: 730 xl In-Tank Gauging Probe, Model: 730
X Annular Space or Vault Sensor. Model: 420 XI Annular Space or Vault Sensor. Model: 420
X Piping SumplTrench Sensor(s). Model: 208 o Piping SumplTrench Sensor(s). Model: 208
= Fill Sump Sensor(s). Model: -
= Fill Sump Sensor(s). Model:
~ Mechanical Line leak Detector. Model: FX1DV v Mechanical Line leak Detector. Model: FX1V
=
= Electronic Line leak Detector, Model: Electronic line leak Detector. Model:
= Tank OverfilUHigh-level Sensor. Model: =
Tank OverfilUHigh-level Sensor. Model:
= Other (specify equipment type and model in Section E on page 2). Other (specify equipment type and model in Section E on page 2).
-
Tank ID: LJII:::"iI::L Tank ID:
:&J In-Tank Gauging Probe, Model: 730 - In-Tank Gauging Probe. Model:
X Annular Space or Vault Sensor. Model: 420 Annular Space or Vault Sensor. Model:
)( Piping SumplTrench Sensor(s). Model: 208 Piping SumpITrench 5ensor(s). Model:
== Fill Sump Sensor(s). Model: - Model:
= Fill Sump Sensor(s).
X Mechanical Line Leak Detector. Model: FX2DV (2) - Mechanical Line leak Detector. Model:
= Electronic Line leak Detector. Model: =
= Electronic Line leak Detector. Model:
Tank Overfilì/High-Level Sensor. Model: -
X Tank OverfilUHigh-Level Sensor. Model:
Other (specify equipment type and model in Section E on page 2). - Other (specify equipment type and model in Section E on page 2).
- -
¡Ulspenser IU: 1/2 Dispenser ID: 3/4
D Dispenser Containment Sensor(s) Model: -, Dispenser Containment Sensor(s) Model:
ŒJ Shear Valve(s). XJ ShearValve(s)
D Dispenser Containment Float(s) and Chain(s), =, Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 5/6 Dispenser ID: 7/8
o Dispenser Containment Sensor(s) Model: t Dispenser Containment Sensor(s). Model:
o Shear Valve(s). '!J ShearValve(s).
'1 Dispenser Containment Float(s) and Chain(s). --, Dispenser Containment Float(s) and Chain(s).
Dispenser ID: DSL 1 Dispenser lD: DSL2
D Dispenser Containment Sensor(s) Model: r Dispenser Containment Sensor(s). Model:
-'
ŒJ ShearValve(s). :Kl Shear Valve(s).
o Dispenser Containment Float(s) and Chain(s). tJ Dispenser Containment Float(s) and Chain(s).
. If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines.
Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): 0 System set-up [8] Alarm history report
Technician Name (print): WILLIAM ROGERS
Certification No.: 8520
Testing Company Name: Tanknology
Site Address: 8900 Shoal Creek, Bldg. 200 Austin, TX 78757
ß/#'S'1-/
Signature:
License. No.:
Phone No.: (800) 800-4633
Date otTesting/Servicing: 07/13/2004
Monitoring System Certification
Page 1 of 3
Based on CA form dated 03/01
Monitoring System Certification
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
Date of Testing/Service: 07/13/2004
D. Results of Testing/Servicing
Software Version Installed: 7.03
Complete the following checklist:
!Xl Yes nNo' Is the audible alarm operational?
o Yes DNo' Is the visual alarm operational?
o Yes nNO' Were all sensors visually inspected, functionally tested, and confirmed operational?
o Yes DNo' Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not
interfere with their proper operation?
n Yes nNo' JxlN/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
DYes [8]No' DN/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive
shut-down? (check all that apply) D Sumprrrench Sensors; D Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? DYes DNo
o Yes DNo' DN/A For tank systems that utilize the monitoring system as the primary tank overfill waming device (I.e.: no mechanical
overfill prevention valve is installed), is the overfill waming alarm visible and audible at the tank fill points(s) and operating
properly? If so, at what percent of tank capacity does the alarm trigger? 90 %
o Yes' DNO Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E, below.
DYes' 0No Was liquid found inside any secondary containment systems designed as dry systems? (check all that apply) D Product;
o Water. If yes, describe causes in Section E, below.
o Yes DNo' Was monitoring system set-up reviewed to ensure proper settings? Attach set-up reports, if applicable.
o Yes DNo' Is all monitoring equipment operational per manufacturers' specifications?
. In Section E below, describe how and when these deficiences were or will. be corrected.
E. Comments:
THERE WAS AN ADDITIONAL SUMP CALLED A FILTER SUMp·· SENSOR (208)
REPLACED 1 FX1DV LEAK DETECTOR IN THE 87 LINE.
Page 2 of 3
Based on CA form dated 03/01
~,. "
Monitoring System Certification
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
Date of Testing/Service: 07/13/2004
F. In-Tank Gauging I SIR Equipment
o Check this box if tank gauging is used only for inventory control.
o Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
0ves ONO' Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
0ves ONO' Were all tank gauging probes visually inspected for damage and residue buildup?
0ves ONO' Was accuracy of system product level readings tested?
0ves ONO' Was accuracy of system water level readings tested?
ŒJves ONO' Were all probes reinstalled properly?
0ves ONO' Were all items on the equipment manufacturers' maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line leak Detectors (llD) :
D Check this box if LLDs are not installed.
Complete the following checklist:
I!]ves ONO' ONtA For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
(Check all that apply) Simulated leak rate: [8] 3 g.p.h 0 0.1 g.p.h 00.2 g.p.h
10ves ONo' Were all LLDs confirmed operational and accurate within regulatory requirements?
,Œ]ves ONO' Was the testing apparatus properly calibrated?
0ves ONO' ONtA For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
Dves ONO' 0N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
DVes ONo' 0NtA For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
Dves ONo' 0NtA For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test?
Dves ONO' I!]N/A For electronic LLDs, have all accessible wiring connections been visually inspected?
0. Yes DNo' Were all items on the equipment manufacturers' maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Page 3 of 3
Based on CA form dated 03/01
..;;; .
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3 Title 23, California Code of Regulations
. This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility, a separate
certification or reDort must be DreDared for each monitorino system control Danel by the technician who performs the work. A copy of this form must be provided to the tank
system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: UL TRAMAR 074
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
City: BAKERSFIELD
Contact Phone No: 324-9481
Date otTesting/Service: 07/13/2004
CA
Zip: 93301
Facility Contact Person: Manager
Make/Model of Monitoring System: Work Order Number: 3135565
B. Inventory of Equipment TestedlCertified
Check the appropriate boxes to indicate specific equipment inspected/serviced
Tank ID: Tank ID:
In-Tank Gauging Probe. Model: n In-Tank Gauging Probe. Model:
=
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
= Piping Sumpffrench Sensor(s). Model: -
Piping Sumpffrench Sensor(s). Model:
= Fill Sump Sensor(s). Model: =
Fill Sump Sensor(s). Model:
= Mechanical Line Leak Detector. Model: =
Mechanical Line Leak Detector. Model:
= Electronic Line Leak Detector. Model: ¡;;;;;
Electronic Line Leak Detector. Model:
= Tank OverfilVHigh-Level Sensor. ¡=
Model: Tank OverfilVHigh-Level Sensor. Model:
= Other (specify equipment type and model in Section E on page 2). Other (specify equipment type and model in Section E on page 2).
'--
Tank ID: Tank ID:
- In-Tank Gauging Probe. Model: ,...-
= In-Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
= Piping Sumpffrench Sensor(s). Model:
Piping SumpfTrench Sensor(s). Model:
= Fill Sump Sensor(s). Model: -
= Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: ,..... Mechanical Line Leak Detector. Model:
= Electronic Line Leak Detector. Model: ,...-
¡;;;;; Electronic Line Leak Detector. Model:
Tank Overfill/High-Level Sensor. Model: ,.....
= I Tank Overfill/High-Level Sensor. Model:
Other (specify equipment type and model in Section E on page 2). ,..... Other (specify equipment type and model in Section E on page 2).
- '--
ulspenser IU: DSL3 Dispenser ID: DSL 4
o Dispenser Containment Sensor(s) Model: ,...- Dispenser Containment Sensor(s) Model:
:Eí ShearValve(s). "X Shear Valve(s)
D Dispenser Containment Float(s) and Chain(s). := Dispenser Containment Float(s) and Chain(s).
Dispenser lD: DSL5 Dispenser ID:
D Dispenser Containment Sensor(s) Model: n Dispenser Containment Sensor(s). Model:
~ Shear Valve(s). tJ ShearValve(s).
n Dispenser Containment Float(s) and Chain(s). D Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
D Dispenser Containment Sensor(s) Model: D Dispenser Containment Sensor(s). Model:
D Shear Valve(s). o Shear Valve(s).
D Dispenser Containment Float(s) and Chain(s). o Dispenser Containment Float(s) and Chain(s).
* If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines.
Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): 0 System set-up 0 Alarm history report
Technician Name (print): WILLIAM ROGERS
Certification No.:
Testing Company Name: Tanknology
Site Address: 8900 Shoal Creek, Bldg. 200 Austin, TX 78757
µ//5'I-/
Signature:
License. No.:
Phone No.: (800) 800-4633
Date of Testing/Servicing: 07/13/2004
Monitoring System Certification
Page 1 of 3
Based on CA form dated 03/01
.-
TEST DATE: 07/13/04
CLIENT: VALERO
SITE DIAGRAM
t-~ DJnknoIogy
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757
(512) 451-6334
FAX (512) 459-1459
WORK ORDER NUMBER3135565
SITE: ULTRAMAR 074
'. "'"
Osump ~ ~
¢ ~ ~ ~ ð
~ ~
C-STOt"{E
OJ
~ ~ c:
8 0
^
0
ENT :E
()
0 VENTS ::J
en
0) 18~ ~~
Ultramar #51-4
@ UL
3225 Buck Owens Blvd. 16tt~
Bakersfield, CA
ø
CAR WAS
DSL
Printed 07/28/2004 07:50 SBOWERS
. -
.
Work Order:
3135565
SENSOR ALARt1 ..
L 5:DIE8EL St,MP
STP SUMP
FUEL ALARM
JUt 13. 2004 B:?8 AM
u___ SENSOR ALARt'1 -----
L 6:DIE9EL ANUL
ANNULAR SPACE
fUEL ALARM
JUL 13. 2004 8:30 AM
SENSOR ALARM -----
L 7:ftLTER SIJM¡:'
PIPING SUMP
fUEL ALARM
JUL 13. 20IJ4 8:33 AM
.--- IN-TANK ALARM -----
T 1 :DIE8EL Z
HI ':;H PRODUCT ALAR,!,1
JUL 13. 2004 8:37 ~1
BEACON 3074
3225 BOCK OWENS
BAKERSFIELD.CA 93308
661 324-9481
JUL 13. 2004 8:37 AM
~(STEH STATUS REPORT
- - - - - - - - - - - -
l' 1 ¡HICH PRùDUC1' ALARM
---- tN-TANK ALA~1 -----
T 1 :DIESEL :2
OVEFlf I LL ALARM
JUL 13. 2004 8:37 AM
'/~ ~ .<,'-'
'\ r ,",-
: .
\. >.
ALARM _u__
/\¥ /.
IN-TANK AI.AFiM
T 1 :DIES£t. :2
HIGH PRODUCT ALARM
JUL 13. 2004 8:37 AM
.--- I N-TANK ALARM -__u
T 1 :DIESEL :2
DEl I VERY NEEDED
JUL 13. 2004 8:38 AM
---- IN-TANK ALARM -----
T 1 :tm:aEl 2
LO~J PRODUCT ALARM
JUL 13. 2004 8:38 At1
---- IN-TANK ALARM -----
T 1 :DIESEl.. 2
HIGH WATER AL.ARM
JUL 13. 2004 8:48 AM
---- IN-1'AN1< ALARM u___
T 1 :IH
HIGH RN1 NO
JUt 13. 004 8:48 AM
t..
STP
PUEL ALARr1
JUL 13. 2004 2:15 N1
SENSOR ALARM -~---
t.. a:UNL ANUL
ANNULAR SPACE
FUEL ALARM
JUt. 13. 2004 2:16 PH
----- SENSOR ALARM -----
L I: FLUB 8l11P
SIP SUMP
FUEL AL.ARM
JUL 13. 2004 2:17 PM
- ---- SENSOR ALARM
L 4:F'I.UB ANUL
ANNULAR SPACE
PUEl ALARM
~1UL l~,. 200.: 2: 17 Pi~~
---- IN-TANK ALARM -----
T 3: UNLEADED
PROBE Ot!i
JUt 13. 2004 2;18 PM
---- IN-TAN1< ALARM -----
T 3:UNLEADED
INVALID FUEL LEVEL
JUt 13. 2004 2:18 PH
---- tN-TANK ALARM -----
T 4:PLUB
PROBE OUT
Jut 13. 2004 2:19 PH
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757
o
.
. iW . t i-
Work Order:
31.35565
_~'"~hA«=~_'"W""",/,w¡;__m
¡N-TA~~ ALARM -----
T :3: UNLEAí.¡EI)
HIGH ~IATER ALARM
Jut 13. 200~ 2:19 PM
---- !N-TANK ALARM -----
í ',3: UNLEADED
HIGH WATER WARNIJ'll(;
JUL 13. 2004 2:19 PM
---- IN-TANK ALARM -----
T :3: UNLEADED
HIGH PRODUCT ALARM
JUL 13. 2004 2:20 PM
---- IN-TANK ALARM -----
r :]: UNLEADED
OVERFILL ALARM
JUL 13. 2004 2:21 PM
---- IN-TANK ALARM -----
T 3:UNtEADED
DELIVERY NEEDED
JUL 13. 2004 2:22 PM
---- IN-TANX ALARM --___
T :]: UNLEADED
LOW PRODUCT ALARM
JUL 13. 2004 2:22 PM
. "/ ~ / ,,' , 1_>
---- IN-TAt« ALARM -----
T 4 : PLUS
HIGH PRODUC'T
JUt 13. 2004 PM
@
---- IN-TANK ALARM ---
T 4 :PLtB
OVERFILL ALARM
JUL 13. 2004 2:25 PM
---- iN-TANK ALARM -----
T 4 : PLUS
HIGH WATER ALARM
JUL 1.3. ¡¡¡004 2:~m PM
---- IN-TANK ALARM -----
T :3: Uf'U.£ADED
HWH PRODUCT ALARM
JUL 13. 2004 2:25 PM
---- IN-TANX ALARM -----
T 4:PllJB
HIGH WATER WARNING
Jut 13. 2004 2:33 PM
---- IN-TAt« ALARM -----
T 4:PUJB
MAX PRODUCT ALARM
JUt 13. 2004 2:25 PM
---- IN-TANK ALARM -----
T 3:UNLEADED
MAX PRODOCT ALARM
JUL 13. 2004 2:26 PM
---- IN-TANK ALARM -----
T 4 :PLtJ9
LOW PRODOCT ALARM
JUL 13. 2004 2:27 PM
---- IN-TANK ALARM -----
i 4:PLlIS
DELIVER\' NEEDED
JUL 13. 2004 2:27 PM
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757
0~~
e
., Tanlcnology
., Î
..'
e
8900 Shoal Creek Blvd, Building 200
Austin, Texas 78757
Phone: (512) 451-6334
Fax: (512) 459-1459
Date Printed and Mailed: 07/28/2004
BAKERSFIELD FIRE DEPARTMENT
OFFICE OF ENVIRONMENTAL SERVICES
INSPECTOR STEVE UNDERWOOD
900 TRUXTUN AVE., STE. 210
BAKERSFIELD, CA. 93301
Test Date: 07/13/2004
Order Number: 3135565
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
UL TRAMAR 074
3225 BUCK OWENS BLVD.
HWY 99/HWY 58
BAKERSFIELD, CA. 93301
Testing performed:
Leak detector tests
Line tests
Monitor Certification
Sincerely,
J)~K~
Dawn Kohlmeyer
Manager, Field Reporting
~Jt~ n.nknology
PURPOSE: COMPLIANCE
TEST DATE: 07/13/04
CLIENT: VALERO
685 WEST THIRD ST
HANFORD, CA 93230
Sandy Huff
(559)583-3298
NKNOLOGY CERTIFICATE OF TESTI.
8900 SHOAL CREEK, BUILDING 200 AUSTIN, TEXAS 7 7
TELEPHONE (512) 451-6334 FAX (512) 459-1459
TEST RESULT SUMMARY REPORT WORK ORDER NUMBER: 3135565
CUSTOMER PO:
SITE: ULTRAMAR 074
3225 BUCK OWENS BLVD.
HWY 99/HWY 58
BAKERSFIELD, CA 93301
Manager
(661 )324-9481
htness Tests Results
87
89
20k
20k
UNLEADED
PLUS
DIESEL
DIESEL
14,139 95.00 DW STEEL
10,139 95.00 DW STEEL
20,068 129.0 DW STEEL
20,000 129.0 DW STEEL
·Where regulations require, for VacuTect external water level may b~ depth of dry well or water is assumed at lowest point that can be confirmed dry.
Product Pi e Ti htness Test Results
87 3 DW FIBERG PRESSURE P 0.006 TLD-1 Y
89 4 DW FIBERG PRESSURE P 0.006 TLD-1 Y
20k 6 DW FIBERG PRESSURE P P P P 0.003 0.003 0.003 0.009 TLD:"'l Y
20k 7 DW FIBERG PRESSURE P P 0.003 0.014 TLD-1 Y
87
89
20k
20k
3 RED JACKET FX2V
4 RED JACKET FX1V
6 RED JACKET FX2-DV
7 RED JACKET FX2-DV
110211102 P
111796 P
21199 9638 P
4120 4744 P
87
3
FX1-DV
10304 8268 P
For owner detailed report information, visit www,tanknology.com and select On-Line Reports-WRAP, or contact your local Tanknology office.
Tester Name: WILLIAM ROGERS
Teo",'O" Cert'fio"'o, N"m'e""47 ~
Date Signed: ~ t.( -6
icensed tank tester in the State of California and that the information contained in this report
edge. .
Tester Signature:
I declare under penalty of e 'ury at I
is true and correct to the best of my kno
f \'
¡
1-~ Dlnlmology
Sandy Huff
(559)583-3298
TANKNOLOGY CERTIFICATE OF TESTING
8900 SHOAL CREEK, BUILDING 200 AUSTIN, TEXAS 78757-
TELEPHONE (512) 451-6334 FAX (512) 459-1459
TEST RESULT SUMMARY REPORT
WORK ORDER NUMBER: 3135565
CUSTOMER PO:
SITE: UL TRAMAR 074
3225 BUCK OWENS BLVD.
HWY 99/HWY 58
BAKERSFIELD, CA 93301
Manager
{661 )324-9481
PURPOSE: COMPLIANCE
TEST DATE: 07/13/04
CLIENT: VALERO
685 WEST THIRD ST
HANFORD, CA 93230
TEST TYPE: TLD-1
UNLEADED
PLUS
DIESEL
DIESEL
PRESSURE
PRESSURE
PRESSURE P
PRESSURE
P
P
P
P
P
0.003 0.003 0.009
0.003 0.014
y
y
87
89
20k
20k
3 RED JACKET
4 RED JACKET
6 RED JACKET
7 RED JACKET
FX2V
FX1V
FX2-DV
FX2-DV
110211102 P
111796 P
21199 9638 P
4120 47'44 P
87
3 RED JACKET
FX1-DV
10304 8268 P
For owner detailed report information, visit www.tanknology.com and select On-Line Reports-WRAP, or contact your local Tanknology office.
Tester Name: WILLIAM ROGERS
Technician Certification Number: 1647
þ//S'¡"/
Printed 07/28/2004 07:26 SBOWERS
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
r~ Dlnknology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
TEST DATE: 07 /13/04
CLlENT:VALERO
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
TanklD: 87 3
Product: UNLEADED
Capacity in gallons: 14, 139
Diameter in inches: 95.00
Length in inches: 337
Material: DW STEEL
COMMENTS
jì¡.¡¡II~iQ:gfi,1111Q:~1iWJi&iÆ;;;\h¡¡j~'0
Tank manifolded: NO Bottom to top fill in inches:
Vent manifolded: YES Bottom to grade in inches:
Vapor recovery manifolded: YES Fill pipe length in inches:
Overfill protection: YES Fill pipe diameter in inches:
Overspill protection: YES Stage I vapor recovery:
Installed: ATG Stage II vapor recovery:
CP installed on: / /
140.5
146.0
44.5
4.0
DUAL
ASSIST
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Bubble
Make: RED JACKET RED JACKET
Ullage Model: FX1-DV FX2V
SIN: 10304 8268 110211102
Open time in see: 4.00
Holding psi: 12
Resiliency cc: 150 NOT
Test leak rate ml/m: 189.0 TESTED
Metering psi: 40
Calib. leak in gph: 3.00 3.00
Results: PASS PASS
COMMENTS
NOT
TESTED
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
2.0
30.0
50
o
40
15:03
15:43
0.006
PASS
PRESSURE
RED JACKET
NOT
TESTED
NOT
TESTED
NOT
TESTED
Impact Valves. Operational: YES
Printed 07/28/2004 07:26
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
-., Tånknology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
TEST DATE: 07 /13/04
CLlENT:VALERO
WORK ORDER NUMBER3BS565
SITE:ULTRAMAR 074
TanklD: 89 4
Product: PLUS
Capacity in gallons: 10,139
Diameter in inches: 95. 00
Length in inches: 337
Material: DW STEEL
COMMENTS
Tank manifolded: NO
Vent manifolded: YES
Vapor recovery manifolded: YES
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
138.5
145.0
42.5
4.0
DUAL
ASSIST
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTectTestType:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
Bubble
Make:
Model:
SIN:
Open time in sec:
Holding psi:
Resiliency cc:
Test leak rate ml/m:
Metering psi:
Calib. leak in gph:
Results:
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
RED JACKET
FX1V
111796 5324
2.00
14
100
189.0
40
3.00
PASS
NOT
TESTED
Ullage
NOT
TESTED
COMMENTS
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
2.0
30.0
50
o
40
15:03
15:43
0.006
PASS
PRESSURE
RED JACKET
NOT
TESTED
NOT
TESTED
NOT
TESTED
Impact Valves Operational: YES
Printed 07/28/2004 07:26
, i'
TEST DATE: 07 /13/04
CLlENT:VALERO
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
t-~ DJnImoIogy
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
Tank 10: 20k 6
Product: DIESEL
Capacity in gallons: 20, 068
Diameter in inches: 129.00
Length in inches: 358
Material: DW STEEL
Tank manifolded: NO
Vent manifolded: NO
Vapor recovery manifolded: NO
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
193.0
201. 0
64.0
4.0
NONE
NONE
COMMENTS
Lines b, c, d and a & b form tank #7 are all stilite lines.
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Bubble
Ullage
Make:
Model:
SIN:
Open time in sec:
Holding psi:
Resiliency cc:
est leak rate ml/m:
Metering psi:
Calib. leak in gph:
Results:
RED JACKET
FX2-DV
NOT
TESTED
21199 9638
6.00
14
450
189.0
42
3.00
PASS
NOT
TESTED
COMMENTS
COMMENTS
Material: DW FIBERG DW FIBERG DW FIBERG DW FIBERG
Diameter (in): 3.0 3.0 3.0 3.0
Length (ft): 220.0 20.0 20.0 20.0
Test psi: 50 50 50 50
Bleedback cc: 0 0 0 0
Test time (min): 50 40 30 30
Start time: 09:36 12:33 11:46 11:06
End time: 10:26 13:13 12:16 11:36
Final gph: 0.003 0.003 0.003 0.009
Result: PASS PASS PASS PASS
Pump type: PRESSURE PRESSURE PRESSURE PRESSURE
Pump make: RED JACKET RED JACKET RED JACKET RED JACKET
COMMENTS Impact Valves Operational: YES
Printed 07/28/2004 07:26
..
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
t-. DJnknoIogy
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
TEST DATE: 07 /13/04
CLlENT:VALERO
Tank 10: 20k 7
Product: DIESEL
Capacity in gallons: 20,000
Diameter in inches: 129.00
Length in inches: 357
Material: DW STEEL
WORK ORDER NUMBER3135565
SITE:ULTRAMAR 074
bi;iI(tmfi~W:8MAjJi ~fi!;;
Tank manifolded: NO
Vent manifolded: NO
Vapor recovery manifolded: NO
Overfill protection: YES
Overspíll protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
193.0
201. 0
64.0
4.0
NONE
NONE
COMMENTS
this tank does not exist. it is put in only to be able to show all of the satellite lines for the diesel tank.
åík~~IT'ªRgm. "lWlriill···
;1"".A!;!ä "+h.,,§g., . .,.:
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
Bubble
Ullage
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Make:
Model:
SIN:
Open time in see:
Holding psi:
Resiliency cc:
Test leak rate ml/m:
Metering psi:
Calib. leak in gph:
Results:
COMMENTS
RED JACKET
FX2-DV
4120 .744
4.00
14
480
1.89.0
44
3.00
PASS
NOT
TESTED
NOT
TESTED
Material:
Diameter (in):
Length (ft}:
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
3.0
20.0
o
NOT 0
TESTM>:OO
00:00
0.000
PRESSURE
RED JACKET
DW FIBERG
3.0
20.0
50
o
50
09:36
10:26
0.003
PASS
PRESSURE
RED JACKET
Impact Valves Operational: YES
50
o
30
10:32
11:02
0.014
PASS
NOT
TESTED
Printed 07/28/2004 07:26
I .'; \
. . i ..
t" ,
" 07/'8/2004 04:20 PM
e
e
T.nknolo4~ 9088784081
1/2
TANKNOlOGV-SO. CALIFORNIA
PH. (909) 308-1210
27576 COMMERCE CTR. DR. STE:. 1G9
TEMECUIA, CA 92590
3416
15-2'¡4~J
pm
61'--- 0 (& L(
. WellsFargoBank.NA
Calirornia
www.WeB.rð,gO-con,
. .' , ' NOT NEGOrrABLE
111003" ~ bill I. L 2 2000 21. 1':0 12 bO 2502 bill
FACILITY ()LfrLA ~/t'YL .!t:. Ü7¿~
ADDRESS .~ 2-7-5 r"&OLk,., Ol.l)8t,) ')
PERMIT TO OPERA IE # V l-llZi
OPERATORS NAME._l
OWNERS NAME
:--¡UMßER OF TANKS TO BE TESTED
TANK # VOLUME
A ~
,.,~ L b (:)(;r(;
~ 7c) <:"::'(.1'6
IS PIPING GOING TO BE TESTED X'
CONTENTS
(1~; ((¿l:'~L')
ß1s.(' M/()")
:"Píf:~~,
--
T ANI< TESTfNG COMPANY . ,'-Ì\1-J WÙ1.-ù h. ~, 4....rL,
MAILfNG ADDRESS Lrc? f) c; r;0fBUJ (¿'C;f,: Lj fLkl,C;: ~}~c;r if ··Ttj42Ú..JL,
~~.-. ,
NAME & PHONE NUMBER OF CONTACT PERSON I )-;,µ (_.1\:-µ1· ft(.lLk{,: ?J7~
TEST METHOD '-IlJ ) _.' ,
NAME OF TESTER l0uÁ/ rløáOL--";
CERTIFlCATION # 03 .-. ll.t,4·-1
DATE & TIME TEST IS TO BE CONDUCTED 711~ I 61-' ~) (~~CC I{-n·~
~
DATE
/'/ .
S~E,'
APPROVED BY
jC'
MONITE~ç:J~~§o!l£~ t~~~Jc~t!~TION
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3 Title 2;'.mia Code of Regulations
"
This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility, a separate
certification or reDQrt must be prepared for each monitorino. system control panel by the technician who performs the work. A copy of this form must be provided to the tank
system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: UL TRAMAR 074
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
City: BAKERSFIELD
Contact Phone No: 324-9481
Date of Testing/Service: 07/13/2004
CA
Zip: 93301
Facility Contact Person: Manager
Make/Model of Monitoring System:GILBARCO EMC Work Order Number: 3135565
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced
Tank ID: 87 Tank ID: 89
X In-Tank Gauging Probe. Model: 730 xl In-Tank Gauging Probe. Model: 730
::;:;: 420 rxr Annular Space or Vault Sensor.
X Annular Space or Vault Sensor. Model: Model: 420
X Piping SumpfTrench Sensor(s). Model: 208 rvl Piping SumpfTrench Sensor(s). Model: 208
= -
Fill Sump Sensor(s). Model:
= Fill Sump Sensor(s), Model:
~ Mechanical Line Leak Detector. Model: FX1DV y Mechanical Line Leak Detector. Model: FX1V
= Electronic Line Leak Detector. Model: -
= = Electronic Line Leak Detector. Model:
Tank OverfilVHigh-Level Sensor. Model: Tank OverfilVHigh-Level Sensor. Model:
= Other (specify equipment type and model in Section E on page 2). Other (specify equipment type and model in Section E on page 2).
-
Tank ID: JIESEL Tank ID:
X In-Tank Gauging Probe. Model: 730 ...-
In-Tank Gauging Probe. Model:
== Annular Space or Vault Sensor. Model: 420 Annular Space or Vault Sensor,
X Model:
~ Piping SumpfTrench Sensor(s).. Model: 208 Piping SumplTrench Sensor(s), Model:
:= Fill Sump Sensor(s). Model:
~ Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: FX2DV (2) - Mechanical Line Leak Detector. Model:
:= Electronic Line Leak Detector, Model: =
Þ= Electronic Line Leak Detector. Model:
Tank OverfilVHigh-Level Sensor. Model: =
~ Tank Overfill/High-Level Sensor. Model:
Other (specify equipment type and model in Section E on page 2), - Other (specify equipment type and model in Section E on page 2),
'-- -
ulspenser IU: 1/2 Dispenser ID: 3/4
D Dispenser Containment Sensor(s) Model: r-- Dispenser Containment Sensor(s) Model:
[K] Shear Valve(s). 'X Shear Valve(s)
o Dispenser Containment Float(s) and Chain(s). :== Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 5/6 Dispenser ID: 7/8
D Dispenser Containment Sensor(s) Model: ì Dispenser Containment Sensor(s). Model:
[8] ShearValve(s). ~ Shear Valve(s).
n Dispenser Containment Float(s) and Chain(s). -, Dispenser Containment Float(s) and Chain(s).
Dispenser ID: DSL 1 Dispenser ID: DSL2
D Dispenser Containment Sensor(s) Model: o Dispenser Containment Sensor(s). Model:
[K] Shear Valve(s). o Shear Valve(s).
D Dispenser Containment Float(s) and Chain(s). D Dispenser Containment Float(s) and Chain(s).
· If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines.
Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): 0 System set-up ~ Alarm history report
Technician Name (print): WILLIAM ROGERS
Certification No.: 8520
Testing Company Name: Tanknology
Site Address: 8900 Shoal Creek, Bldg. 200 Austin, TX 78757
p//5'~/
Signature:
License. No.:
Phone No.: (800) 800-4633
Date of Testing/Servicing: 07/13/2004
Monitoring System Certification
Page 1 of 3
Based on CA form dated 03/01
, ,
,
.
ï;;
,eitoring System Certification
-
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
Date of Testing/Service: 07/13/2004
D. Results of Testing/Servicing
Software Version Installed: 7.03
Complete the following checklist:
IX1 Yes nNo· Is the audible alarm operational?
o Yes rJ No . Is the visual alarm operational?
o Yes [J No . Were all sensors visually inspected, functionally tested, and confirmed operational?
o Yes ONO' Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not
interfere with their proper operation?
DYes ONO· [XlN/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
DYes 0NO· ON/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive
shut-down? (check all that apply) D SumpfTrench Sensors; D Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? DYes DNo
o Yes ONo· DN/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e.: no mechanical
overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill pOints(s) and operating
properly? If so, at what percent of tank capacity does the alarm trigger? 90 %
o Yes· ONO Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E, below.
DYes' Œ]No Was liquid found inside any secondary containment systems designed as dry systems? (check all that apply) D Product;
o Water. If yes, describe causes in Section E, below.
o Yes DNo· Was monitoring system set-up reviewed to ensure proper settings? Attach set-up reports, if applicable.
Œ] Yes DNo· Is all monitoring equipment operational per manufacturers' specifications?
* In Section E below, describe how and when these deficiences were or will be corrected.
E. Comments:
THERE WAS AN ADDITIONAL SUMP CALLED A FILTER SUMP- SENSOR (208)
REPLACED 1 FX1DV LEAK DETECTOR IN THE 87 LINE.
Page 2 of 3
Based on CA form dated 03/01
,.
.A'
,it
nnlitoring System Certification
e
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
Date otTesting/Service: 07/13/2004
F. In-Tank Gauging I SIR Equipment
o Check this box if tank gauging is used only for inventory control.
o Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
0ves DNo' Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
0Ves DNo' Were all tank gauging probes visually inspected for damage and residue buildup?
o Yes DNo' Was accuracy of system product level readings tested?
0ves DNo' Was accuracy of system water level readings tested?
0Ves DNo' Were all probes reinstalled properfy?
o Yes DNo' Were all items on the equipment manufacturers' maintenance checklist completed?
. In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors (LLD) :
D Check this box if LLDs are not installed.
Complete the following checklist:
0ves DNo' DN/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
(Check all that apply) Simulated leak rate: 0 3 g.p.h 0 0.1 g.p.h 00.2 g.p.h
10ves DNo' Were all LLDs confirmed operational and accurate within regulatory requirements?
1M Ves DNo' Was the testing apparatus properly calibrated?
Œ]ves DNo' DN/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
DVes DNo' 0N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
DVes DNo' 0N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
DVes DNo' 0N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test?
DVes DNo' 0N/A For electronic LLDs, have all accessible wiring connections been visually inspected?
0ves DNo' Were all items on the equipment manufacturers' maintenance checklist completed?
· In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Page 3 of 3
Based on CA form dated 03/01
MONITE~Ç?J~~§!I£~ tf~~Jc~~~~TION
Authority Cited: Chapter 6.7, Health and Safety Code; Chapter 16, Division 3 Title 23~¡.mia Code of Regulations
This fOI1T1 must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility, a separate
certification or repOrt must be orepared for each monitorinQ svstem control panel by the technician who perfOI1T1S the work. A copy of this fOI1T1 must be provided to the tank
system owner/operator. The owner/operator must submit a copy of this fOI1T1 to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: ULTRAMAR 074
Site Address: 3225 BUCK OWENS BLVD.
HWY 99/HWY 58
City: BAKERSFIELD
Contact Phone No: 324-9481
Date of Testing/Service: 07/13/2004
CA
Zip: 93301
Facility Contact Person: Manager
Make/Model of Monitoring System: Work Order Number: 3135565
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced
Tank ID: Tank 10:
= In-Tank Gauging Probe. Model: In-Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: ~ Annular Space or Vault Sensor. Model:
=
Piping SumplTrench Sensor(s}. Model: Piping SumpfTrench Sensor(s). Model:
= Fill Sump Sensor(s). Model: r-
:= Fill Sump Sensor(s). Model:
= Mechanical Line Leak Detector. Model:
= ¡;;;;; Mechanical Line Leak Detector. Model:
Electronic Line Leak Detector. Model: Electronic Line Leak Detector. Model:
= Tank OverfilVHigh-Level Sensor. Model: r=
= Tank OverfilVHigh-Level Sensor. Model:
Other (specify equipment type and model in Section E on page 2). "- Other (specify equipment type and model in Section E on page 2),
TanklD: Tank ID:
In-Tank Gauging Probe. Model: r-
= In-Tank Gauging Probe. Model:
Annular Space or Vault Sensor. Model: Annular Space or Vault Sensor. Model:
i= Piping SumpfTrench Sensor(s). Model: Piping SumpfTrench Sensor(s).
Model:
:= Fill Sump Sensor(s). Model: r-
Þ= Fill Sump Sensor(s). Model:
Mechanical Line Leak Detector. Model: r- Mechanical Line Leak Detector. Model:
:= Electronic Line Leak Detector. Model: r-
:= Electronic Line Leak Detector. Model:
Tank OverfilVHigh-Level Sensor. Model: r-
:= Tank Overfill/High-Level Sensor. Model:
Other (specify equipment type and model in Section E on page 2). r- Other (specify equipment type and model in Section E on page 2).
-- '-
u¡spenser IU: DSL3 Dispenser ID: DSL 4
o Dispenser Containment Sensor(s) Model: r-- Dispenser Containment Sensor(s) Model:
ø Shear Valve(s). 'X Shear Valve(s)
D Dispenser Containment Float(s) and Chain(s). ~ Dispenser Containment Float(s) and Chain(s).
Dispenser lD: DSL5 Dispenser ID:
o Dispenser Containment Sensor(s) Model: n Dispenser Containment Sensor(s). Model:
[8J Shear Valve(s). D ShearValve(s).
n Dispenser Containment Float(s) and Chain(s). o Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
o Dispenser Containment Sensor(s) Model: n Dispenser Containment Sensor(s). Model:
.........
D Shear Valve(s). D ShearValve(s).
o Dispenser Containment Float(s) and Chain(s). D Dispenser Containment Float(s) and Chain(s).
. If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines.
Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): 0 System set-up DAlarm history report
Technician Name (print): WILLIAM ROGERS
Certification No.:
Testing Company Name: Tanknology
Site Address: 8900 Shoal Creek, Bldg. 200 Austin, TX 78757
/A//5'I-/
Signature:
License. No.:
Phone No.: (800) 800-4633
Date otTesting/Servicing: 07/13/2004
Monitoring System Certification
Page 1 of 3
Based on CA form dated 03/01
e
e
"i'
..
SITE DIAGRAM
~~ Dlnknology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757
(512) 451-6334
FAX (512) 459-1459
TEST DATE: 07/13/04
CLIENT: VALERO
WORK ORDER NUMBER3135565
SITE: ULTRAMAR 074
o sump ~ ~
~ ~ ~ ~ ð
~ ~
C-STORE
OJ
~. ~ c:
8 0
"
0
ENT ::E
CD
0 VENTS :J
en
0) ~#~ ~~
@ Ultramar #51-4 UL
3225 Buck Owens Blvd. lô~~
Bakersfield, CA
CD
CAR WASH
DSL
Printed 07/28/2004 07:26 SBOWERS
Work· Order:
31.35565
'~M~~,__U~
- - SEN~:;OR "LARf"
L "1: F lLTER :3Uf'1P
P! P J J'¡'~ .'3U1'1F'
f L.iEL t\I,AE:'!
JUt. 13, 2004 8:33 AM
n__ IN-TRNJ< HLAPr'l _u__
T I: [II LSEL2
HIGH PRODUCT ALARr"1
JUt. 13. 2004 8:37 AM
BEACON 3014
322", 81).::1< (YvlENS
BI\J<ERSF!ELD.CR 93308
661 32>1-9481
,JUL 1:J. 2004 8:37 {\f'1
SYßTE~1 ¡nATUS REPORT
____._'A
- - - -
1; 1 ~ tl, 1C-H ',~"R<JIiLJCT f,\~_HPf1
e
ALARM
ALARM
8:37 Al'1
e
ALARM
2:15 Pt'1
AlÁRM--~--
ALARM
8: 38 f\l'1
'h_ IN-THNK ALARM --_h
:DIESEL '2
IVERI( NEEDED
13. 2004 8:38 AM
T 1
lOW
JUt.
A~1
SENSOR ALARI'1
l J:UNL ANIJL
ANNuLAR 8PA\:'E
FUEL ALARM
JUL 13. 2004 2: 16 Pt"1
SENSOR ALARM
L 1 :PLUS SUMP
STP SUt'1P
FUEL ALARt1
JUL 13. 2004 2:17 PM
- SENSOR ALARM
L <I : PLUS ANUL
ANNULAR S¡>ACE
FUEL ALARM
JUt. 13. 2004 2:17 PM
---- IN-TAMK ALARM -----
T :J:UNLEADED
PRQBE OUT
JUL 13. 2004 2:18 PM
---- IN-TANK ALARM
T :3: UNLEf\DED
INVALID FUEL LEVEL
JUt 13. 2004 2:18 PM
ALAR~1
2: ¡ Pt1
:. _h !ti-TAN}; ALARM
í 1 :OIESEl 2
Ii I CiH lJATER ALflRH
JUL 13. 2004 8:48 AM
---- IN-TANK ALARM -----
T 1 :DIESEL 2
HI (;H ~JHTER WHRN t NCi
JUL I:], 2004 8:48 ~1
~M
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757
o
::. ~ b
. . W òrK Order:
j
31.35565
"W~'~"~",",'-"""""''''''_''''''''n^''''~__
f'M
-- -- [N - TI,H/( ALhR!1 - _u_
"T '): UNLEADED
HIGH WATER WARNING
Jut 13. 2004 2:19 PM
n__ iN-TnNK ALnPJ1 ----
T :3:UNLEADED
HIGH PRODU'::'T f~LARM
,Jut 13. 2004 2: 20 PM
1 N-TANK ALAF:i
T J:UNLEhDED
OVERF I LL ALARt'1
JUL 13. 2004 2:21 PM
---- !N-TANK ALARM -----
T : UNLEADED
I'vERY NEEDED
13. 2004 2:22 PM
ALARM -----
ALARt1
2:22 Pf"l
e
e
@
>"tARl! n_ - -
FM
---- IN-TANK ALARM
T 4 : PLUS
OVERFILL ALARM
Jut 13. 2004 2:25 PM
---- IN-TANK ALARM -----
T 4 : PLUS
HIGH WATER ALARM
JUL 13. 2004 2:33 PtJ
l!i-TIINK ALARI'1 ---.,-
T 3: UNL&ìDED
HIGH PRODUCT ALARM
Jut 13. 2004 2:25 PM
---- IN-TANK ALARM -----
T 4:PLUB
H \i.:;H WATER WARN I NG
Jut 13. 2004 2:33 PM
---- IN-TAl'll: ALARM
T 4 :PUJS
["Ifi>< PRODUCT ALARM
JUL 13. 2004 2:25 YM
..--- IN-TANK ALARM -----
T :J:UNLEADED
MAX PROD~:T ALAkfl
JUL 13. 2004 2:26 PM
"--- IN-TANK ALARM
T 4:PLUS
PRODlM'.:T
13, 2004 PM
:27 FM
Tanknology-NDE &900 Shoal Creek, Building 200 Austin, Texas 78757
,v
~¡\,..-.
e
e
) ; ~k V\LERO
7~ ENERGY CORPORATION
Post Office Box 696000· San Antonio, Texas 78269-6000
April 27, 2004
City of Bakersfield
Office of Emergency Services
1715 Chester Ave., Ste 300
Bakersfield, CA 93301
Dear Sirs:
Re: Financial Responsibility - Fiscal Year 2003 - UST Facilities
Enclosed are the documents for Valero Energy Corporation demonstrating financial
assurance for Underground Storage Tank (UST) facilities owned by specific subsidiaries
of Valero. These documents, listed below, have been updated to include Valero Energy
Corporation's financial data for fiscal year 2003. Please forward to the appropriate
personnel within your agency.
·
~etter from CFO specifying the successful completion of the financial test of self-
msurance
Guarantee by Valero Energy Corporation on behalf of the specific Valero
subsidiary(s) owning the USTs.
An addendum (list) that specifies the locations and tanks at each facility covered by
these financial assurance mechanisms.
·
·
Should you have any questions, please contact me at (210) 592-4235 or e-mail:
i ohn. wi llrodt@valero.com.
:\ trul~ yours,
J~~t~
Retail Compliance
JW/ss
Enclosures
V8159.p65
1
4/26/2004
FACILITY ID #
.'
.-;!
.,
T:\CONSTRUC\O&EADMIN\REPORT -1 \01 CACTNY.RPT
Valero Energy Corporation Fiscal Year 2003 Financial Assurance - Retail UST
STATE COUNTY
00719
00719
00719
PRODUCT
D
p
U
CAPACITY
20068
10140
14130
KERN
CA
CITY
BAKERSFIELD
ADDRESS
3225 BUCK OWENS BLVD
ZONE
352
STATUS
o
STORE #
3074
i
!
e
-
,
1.
e
.-
.
~k V\LERO
71f ENERGY CORPORATION
April 19, 2004
Certified Mail - Return Receipt Requested
State of California
State Water Resources Control Board
Division of Clean Water Programs
P. O. Box 944212
Sacramento, California 94244-2120
Attn: Scott Bacon
RE: UST Financial Responsibility - Fiscal Year 2003
Dear Mr. Bacon:
e
Michael S. Ciskowski
Executive Vice President
and Chief Financial Officer
I am the Chief Financial Officer of Valero Energy Corporation (Valero) located at P. O. Box 500,
San Antonio, Texas 78292-0500. This letter is in support of the use of the financial test of self-
insurance and guarantee to demonstrate financial responsibility for taking corrective action and/or
compensating third parties for bodily injury and property damage caused by sudden accidental
releases and/or non-sudden accidental releases in the amount of at least $1,000,000 per occurrence
and $2,000,000 annual aggregate arising from operating underground storage tanks.
Underground storage tanks at the following facilities are assured by this financial test or a financial
test under an authorized State program by this guarantor (see attached addendum).
A financial test and guarantee are also used by this guarantor to demonstrate evidence of financial
responsibility in the following amounts under other EP A regulations or state programs authorized
by EPA under 40 CFR parts 271 and 145:
EP A Regulation
Closure (§§ 264.143 and 265.143) ......................
Post-Closure Care (§§ 264.145 and 265.145)......
Liability Coverage (§§ 264.147 and 265.147).....
Corrective Action (§ 264.1 01 (b)) ........................
Plugging and Abandomnent (§ 144.63)...............
Authorized State Programs
Closure . .... ............................ ....... ............... ......
Post-C]osure Care .............................................
Liabi]ity Coverage ............................................
Corrective Action .............................................
Plugging and Abandonment .............................
Tota] .... ......... .................... ......... .......
$ 7,440,302
$ 12,025,805
$ 10,000,000
$ 25,356,397
$ 979,940
$ 547,583
$ 312,489
$ 1,000,000
N/A
N/A
$ 57,662,5]6
One Valero Place· San Antonio, Texas 78212
Post Office Box 500· San Antonio, Texas 78292-0500· Telephone (210) 370-2146 · Facsimile (210) 370-2497
Mike.Ciskowski @valero.com
¡'
UST Financial Responsibility e
April 19, 2004
Page 2 of3
e
Valero has not received an adverse opmIOn, a disclaimer of opinion, or a "going concern"
qualification from an independent auditor on its financial statements for the latest completed fiscal
year.
1.
2.
3.
4.
5.
6.
7.
ALTERNATIVE II
Amount of annual UST aggregate coverage being assured by a test, and/or
guarantee................................................................................................................... .
Amount of corrective action, closure and post-closure care costs, liability coverage,
and plugging and abandonment costs covered by a financial test, and/or guarantee.
Sum of lines 1 and 2...................................................................................................
Total tangibles assets .................. ......................................... ........ ........ ........ ..............
Total liabilities (if any of the amount reported on line 3 is included in total
liabilities, you may deduct that amount from this line and add that amount to line
6)................................................................................................................................
Tangible net worth (subtract line 5 rrom line 4) ........................................................
Total assets in the U.S. (required only ifless than 90 percent of assets are located in
the U.S.) ...... .......... ............ ........... .............. ..... ............ .............. ......... ........... ....... ......
8.
Is line 6 at least $10 million? .....................................................................................
9.
Is line 6 at least 6 times line 3? ..................................................................................
10.
Are at least 90 percent of assets located in the U.S.? (If "No," complete line 1] .)....
11.
Is line 7 at least 6 times line 3? ..................................................................................
Fill in either Lines 12-15 or Lines 16-18:
12.
Current assets.............................................................................................................
13.
Current liabilities ............. ........ ....... ........... ....... ....... ................ ............ ............... .......
14.
Net working capital (subtract line 13 from 12) ..........................................................
15.
Is line 14 at least 6 times line 3? ................................................................................
16.
ClUTent bond rating of most recent bond issue..........................................................
17.
Name of rating service ................................................................................. ..............
18.
Date of maturity of bond.......... ..... .......................................... ...... .................. ...........
19.
Have financial statements for the latest fiscal year been filed with the SEC, the
Energy lnfonnation Administration, or the Rural Electrification Administration? ...
$2,000,000
$57,662,516
$59,662,516
$12,942,300,000
$9,929,000,000
$3,013,300,000
$13,459,500,000
Yes
Yes
No
Yes
No
Yes
N/A
N/A
N/A
N/A
BBB
Standard & Poor's
4-1·2014
Yes
UST Financial Responsibility _
April 19, 2004 ..
Page 3 of3
e
I hereby certify that the wording of this letter is identical to the wording specified in 40 CFR part
280.95 (d) as such regulations were constituted on the date shown immediately below.
'-
~~.~~
Michael S. Ciskowski
Executive Vice President and
Chief Financial Officer
tf, (9 r 0 ~
Date
e
e
Guarantee
Guarantee made this April 19, 2004 by Valero Energy Corporation, a business entity
organized under the laws of the State of Delaware, herein referred to as guarantor, to the California
State Water Resources Control Board (SWRCB) and to any and al1 third parties, and obligees, on
behalf of Ultramar Inc. (UI), Valero Refining Co. - CA (VRC), Valero Refining & Marketing of
CA (VRMC) and Valero Marketing & Supply Co. (VMSC) of P.O. Box 696000, San Antonio,
Texas 78269-6000.
Recitals
(1) Guarantor meets or exceeds the financial test criteria of 40 CFR 280.95 (b) or (c) and (d)
and agrees to comply with the requirements for guarantors as specified in 40 CFR 280.96(b).
(2) VI, VRC, VRMC and VMSC own or operate the fol1owing underground storage tank(s)
covered by this guarantee:
See addendum to this guarantee.
This guarantee satisfies 40 CFR part 280, subpart H requirements for assuring funding for taking
corrective action and for compensating third parties for bodily injury and property damage caused
by either sudden accidental releases or non-sudden accidental releases or accidental releases,
arising rrom operating the above-identified underground storage tank(s) in the amount of
$1,000,000 per occurrence and $2,000,000 annual aggregate.
(3) On behalf of our subsidiary, guarantor guarantees to SWRCB and to any and all third
parties that:
In the event that VI, VRC, VRMC and VMSC fail to provide alternative coverage within
60 days after receipt of a notice of cancel1ation of this guarantee and the Director of the SWRCB
has determined or suspects that a release has occurred at an underground storage tank covered by
this guarantee, the guarantor, upon instructions from the Director, shall fund a standby trust fund in
accordance with the provisions of 40 CFR 280.108, in an amount not to exceed the coverage limits
specified above.
In the event that the Director determines that VI, VRC, VRMC and VMSC have failed to
perfonn corrective action for releases arising out of the operation of the above-identified tank(s) in
accordance with 40 CFR part 280, subpart F, the guarantor upon written instructions rrom the
Director shaH fund a standby trust in accordance with the provisions of 40 CFR 280.108, in an
amount not to exceed the coverage limits specified above.
If VI, VRC, VRMC and VMSC fail to satisfy a judgment or award based on a
determination of liability for bodily injury or property damage to third parties caused by sudden
and/or non-sudden accidental reJeases arising rrom the operation of the above-identified tank(s), or
fails to pay an amount agreed to in settlement of a claim arising rrom or al1eged to arise from such
injury or damage, the guarantor, upon WTitten instructions from the Director, shall fund a standby
trust in accordance with the provisions of 40 CFR 280.108 to satisfy such judgment(s), award(s), or
settlement agreement(s) up to the limits of coverage specified above.
(4) Guarantor agrees that if, at the end of any fiscal year before cancel1ation of this guarantee,
the guarantor fails to meet the financial test criteria of 40 CFR 280.95 (b) or (c) and (d), guarantor
shall send within 120 days of such failure, by certified mail, notice to VI, VRC, VRMC and
VMSC. The guarantee wi11 terminate 120 days from the date of receipt of the notice by UI, VRC,
VRMC and VMSC, as evidenced by the return receipt.
- 1 -
e
e
(5) Guarantor agrees to notify UI, VRC, VRMC and VMSC by certified mail of a voluntary or
involuntary proceeding under Title 11 (Bankruptcy), U.s. Code naming guarantor as debtor, within
10 days after commencement of the proceeding.
(6) Guarantor agrees to remain bound under this guarantee notwithstanding any modification
or alteration of any obligation of VI, VRC, VRMC and VMSC pursuant to 40 CFR part 280.
(7) Guarantor agrees to remain bound under this guarantee for so long as VI, VRC, VRMC
and VMSC must comply with the applicable financial responsibility requirements of 40 CFR part
280, subpart H for the above-identified tank(s), except that guarantor may cancel this guarantee by
sending notice by certified mail to UI, VRC, VRMC and VMSC, such cancellation to become
effective no earlier than 120 days after receipt of such notice by UI, VRC, VRMC and VMSC, as
evidenced by the return receipt.
(8) The guarantor's obligation does not apply to any of the following:
(a) Any obligation of VI, VRC, VRMC and VMSC under a workers' compensation,
disability benefits, or unemployment compensation law or other similar law;
(b) Bodily injury to an employee of UI, VRC, VRMC and VMSC arising from, and in the
course of, employment by UI, VRC, VRMC and VMSC;
(c) Bodily injury or property damage arising from the ownership, maintenance, use, or
entrustment to others of any aircraft, motor vehicle, or watercraft;
(d) Property damage to any property owned, rented, loaded to, in the care, custody, or
control of, or occupied by VI, VRC, VRMC and VMSC that is not the direct result of a release
from a petroleum underground storage tank;
(e) Bodily damage or property damage for which VI, VRC, VRMC and VMSC are
obligated to pay damages by reason of the assumption of liability in a contract or agreement other
than a contract or agreement entered into to meet the requirements of 40 CFR 280.93.
(9) Guarantor expressly waives notice of acceptance of this guarantee by SWRCB, by any or
all third parties, or by UI, VRC, VRMC and VMSC.
I hereby certify that the wording of this guarantee is identical to the wording specified in 40 CFR
280.96(c) as such regulations were constituted on the effective date shown immediately below.
Effective date: .1/--/9 -tJ ~
Valero Energy Corporation
...
¡At)~ 1. (;).fr)- '
Michael S. Ciskowski
Executive Vice President and
Chief Financial Officer
Signature of witness or notary: ~ ø~
- 2 -
e
e
-.
, -;
State of California
State of Water Resources Control Board
Division of Clean Water Programs
P.O. Box 944212
Sacramento, CA 94244-2120
Onstructions on reverse side)
CERTIFICATION OF FINANCIAL RESPONSIBiliTY
FOR UNDERGROUND STORAGE TANKS CONT AJNING PETROLEUM
A.
CCR:
I am required to demonstrate Financia1 Responsibility in the Required amounts as specified in Section 2807, Chapter 18, Div. 3, Title 23,
o
o or
I miBion dollars per occurrence
AND
o
~
I miBion dollars annua1 aggregate
or
2 mi1lion dol1ars annua1 aggregate
500,000 dollars per occurrence
B. Valero Energy Corporation hereby certifies that it is in compliance with the requirements of Section 2807,
(Name of Tank Owner or Operator)
Article 3, Chapter 18, Division 3, Title 23, Califomia Code of Regulations.
The mechanisms used to demonstrate financial responsibility as required by Section 2807 are as follows:
State UST Fund
State UST Cleanup Fund
P.O. Box 944212
Sacramento, CA
94244-2120
NJA
$995,000 per Continuous
occurrence and
annual aggregate
Yes
Yes
Chief Financial
Officer Letter
Valero Energy Corporation
P.O. Box 500
San Antono, TX
78292-0500
NJA
$1,000,000 per Annual
occurence and
$2,000,000
annual aggregate
Yes
Yes
Guarantee
Valero Energy Corporation
P.O. Box 500
San Antono, TX
78292-0500
N/A
$1,000,000 per Annual
occurence and
$2,000,000
annual aggregate
Yes
Yes
Note: If you are using the State Fund as any part of your demonstration of financial responsibility, your execution and submission of
this certification also certifies that you are in compliance with all conditions for participation in the Fund.
D. Facility Name
See attached list.
Facility Address
Facility Name
Facility Address
Facility Name
Facility Address
E. Signature of Tank Owner or Operator
~ J, cJ~~'
Slgnture of Witness or Notary
Date
Name and Title of Tank Owner or Operator
Michael S. Ciskowski - Executive Vice President and Chief
Financial Officer
Name of Witness or Notary
If/i1!D'f
Date
~ /t1 /()¥
CFR (Revised 04/95)
FILE: Orlglnal- Local Agency
Copie5 - FacilitylSite(5)