MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: - Chapter 6.7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be
prepared for each monitoring system control panel by the technician who performs the work. A copy of this form must be provided to
the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems
within 30 days of test date.
A. General Information
Facility Name: Costco Wholesale
Site Address: 3800 Rosedale Hwy.
Facility Contact Person: Sheri Poulpon
Make/Model of Monitoring System: Veeder-Root TLS-350
Bldg. No: 688
City: Bakersfield Zip: 93308
Contact Phone No.: 661-636-0822
Date of Testing/Servicing: 9/1/2004
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced
~ank ID: 87A Tank ID: 87B
o In-Tank Gauging Probe. Model: 847390-109 J In-Tank Gauging Probe Model: 847390-109
o Annular Space or Vault Sensor Model: 794380-301 .¡ Annular Space or Vault Sensor. Model: 794380-301
o Piping Sump / Trench Sensor(s). Model: 794380-352 o Piping Sump / Trench Sensor(s) Model: 794380-352
o Fill Sump Sensor(s). Model: 794380-352 J Fill Sump Sensor(s). Model: 794380-352
o Mechanical Line Leak Detector Model: LLD-99 J Mechanical Line Leak Detector Model: FX2V
o Electronic Line Leak Detector Model: Electronic Line Leak Detector Model:
o Tank Overfill / High-Level Sensor Model: 847390-109 J Tank Overfil1 / High-Level Sensor Model: 847390-109
o Other (speciJy equipment type and model in Section E on Page 2). o Other (specifY equipment type and model in Section E on Page 2).
trank ID: 91 Tank ID: N/A
o In-Tank Gauging Probe. Model: 847390-109 In-Tank Gauging Probe Model:
o Annular Space or Vault Sensor Model: 794380-301 Annular Space or Vault Sensor. Model:
I[ J] Piping Sump / Trench Sensor(s). Model: 794380-352 Piping Sump / Trench Sensor(s) Model:
o Fill Sump Sensor(s). Model: 794380-352 Fill Sump Sensor(s). Model:
o Mechanical Line Leak Detector Model: FX2V o Mechanical Line Leak Detector Model:
o Electronic Line Leak Detector Model: Electronic Line Leak Detector Model:
I~ Tank Overfill / High-Level Sensor Model: 847390-109 Tank Overfill / High-Level Sensor Model:
l Other (speciJy equipment type and model in Section E on Page 2). o Other (specifY equipment type and model in Section E on Page 2).
Dispenser ID: 1/2 Dispenser ID: 3/4
o Dispenser Containment Sensor(s). Model: 794380-208 o Dispenser Containment Sensor(s). Model: 794380-208
o Shear Valve(s). o Shear Valve(s).
o Dispenser Containment Float(s) and Chain(s). o Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 5/6 Dispenser ID: 7/8
o Dispenser Containment Sensor(s). Model: 794380-208 o Dispenser Containment Sensor(s). Model: 794380-208
o Shear Valve(s). o Shear Valve(s).
o Dispenser Containment Float(s) and Chain(s). o Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 9/10 Dispenser ID: 11/12
o Dispenser Containment Sensor(s). Model: 794380-208' o Dispenser Containment Sensor(s). Model: 794380-208
o Shear Valve(s). ., o Shear Valve(s).
o Dispenser Containment Float(s) and Chain(s). o Dispenser Containment Float( s) and Chain( s).
. .
If the faclhty contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification I certify that the equipment identified in this document was inspected/serviced in c íI~nce with the
manufacturers' guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to v a this
information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capabl of ge çh
reports, I have also attached a copy of the report; (check all that apply): 0 System Setup . History Report
Technician Name(print): Bill Karras Signature:
Certification No: 006-05-0734 License. No
Testing Company Name: W.S.K. & Sons Phone No:
Testing Company Addre~ 34455 Sunlight Dr. ,Yucaipa CA. 92399 Date ofTestingiServicing:
Monitoring System Certification
814289
(909) 906-3023
9/1/2004
Page 1 of3
EM
D. Results of Testing/Servicing
Software Version Installed:
322.00
Com lete the followin
.j Yes No*
.j Yes No*
.j Yes No*
.j Yes No*
No
90%
E. Comments:
Agency:
Ralph Huey
Director of Prevention Services
Suite#300
1715 Chester Ave.
Bakersfield, CA. 93301
Page 2 of3
F ; In-Tank Gauging I SIR Equipment:
o Check this box if tank gauging is used only for inventory control
o Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
ound faults?
G. Line Leak Detectors (LLD):
o Check this box ifLLDs are not installed
No*
.¡ N/ A
No*
.¡ N/ A
No*
.¡ N/ A
No*
.¡ N/A
Yes No* Were all items on the e ui ment manufacturer's maintenance checklist com leted?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
For electronic LLDs, does the turbine automaticall shut off if the LLD detects a leak?
For electronic LLDs, does the turbine automaticall
or disconnected?
For electronic LLDs, does the turbine automaticall
malfunctions or fails a test?
For electronic LLDs, have all accessible wirin connections been visuall ins ected?
ortion of the monitoring s stem is disabled
ortion of the monitorin s stem
H. Comments:
Page 3 of3
Department of Environmental Health
Hazardous Mateñals Management Division
. LEAK DETECTOR TEST FORM
DATE q -D i --04 -
FACILITY # lo~\
FACIUTY-NAME-
. .
COSTC.ù W~DLE..s4:L£ -tl- (P71ð
5"600 ~D~cE. DtCJLt£ .J....(wï
1)f.lK~tl..SFÚ=Lb CJt\. 9330'6
)
ÅDDRESS
- .
lEAK DETECTOR TEST RESULTS:-
ALL LEAK DETECTORS ARE TESTED IN-UNE. INDICATE TYPE OF LEAK DETECTOR WITH SERIAL NUMBER (XLD,
XLP, LO-;2000, ETC.).
MAKElMODEL SERIAL # lEAK. RATE PASS OR CHECK VALVE METERING PSI
TESTED (GPH) FAIL PSI
LD#1 L.LO - ~q 02.01"3"? I L - -~.D 'P-&\ S <; - 1 S 3"2-
NEW
LD#2 b~2 V (",SÎD "?>.o ~AS5 i~ 3":?
NEW
lD#3 F¥:2-. V 430'1> '3-0 'V~s.s \'8' '33
NEw
lD#4
NEW
SIGNATURE OF CERTIAED TECHNICIAN
PRINTED NAME OF CERTIAED TECHNICIAN
TESTING COMPANY NAME & TELEPHONE #
~
LJ { LL , PI IV' It; A/:2...f2.
W "3 ~ ¿ 50"-'..s ::¡: Iv d..
'R'S SPEC/RCATlONS.
. LEAK DETECTORS ARE TES.TED IN ACCORDANCE WITH THE MANU¡='
CERTIAED TESTER'S ID#
ODCt>- os .. 0"1
cr -01 ~{)
.3e:.2,"?>
." IF INITIAL LEAK DETECTOR FAILS, ALL REPLACEMENTS SHALL BE TESTED.
SWRCB, January 2002
Page_of_
Secondary Containment Testing Report Form
This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the
appropriate pages of this form to report results for all components tested. The completed form, written test procedures, and
printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
Facility Name: Costco Wholesale #688 I Date ofTesting:9-1-04
Facility Address: 3800 Rosedale Hwy
Facility Contact: Sherry Poulpon I Phone: 661-636-0822
Date Local Agency Was Notified of Testing : 8-17-04
Name of Local Agency Inspector (ifpresent during testing):
1. FACILITY INFORMATION
2. TESTING CONTRACTOR INFORMATION
Company Name: W.S.K. & Sons Inc.
Technician Conducting Test: Bill Karras
Credentials: X CSLB Licensed Contractor D SWRCB Licensed Tank Tester
License Type:General-A I License Number:814289
, "'Jt.... "!If,. ,;.....~~:. ':- '" . >, ~,~ , '0. ,,<7 >:r. ,,'~:"'..;II:,1'!':-" '-:'l"'~ '~,,_"-''OI'''''''-<;"~ ~_""'_~"V ;1\,. t ~"" f'-;'., ~",-._"":::,,"'.o.;;r.-_r,,..¡j. "M;...,"'.,,,,,,,-..,,,~-;:;.:~
Manufacturer Trainine
Manufacturer Component(s) Date Training Expires
Phil- Tite Spill Buckets 10-31-2004
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not Repairs Component Pass Fail Not Repairs
Tested Made Tested Made
Unleaded 87 A Spill Bucket X 0 0 0 0 0 0 0
Unleaded 87 B Spill Bucket X 0 0 0 0 0 0 0
Premium Spill Bucket X 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
a was done with the water after completion of tests:
CERTlFICA
To the best of my knowledJ
ICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
in tllis document are accurate and in full compliance witl, legal requirements
Technician's Signature:
Date: C}..() { - c L(
SWRCB, January 2002
Page_of_
9. SPILUOVERFILL CONTAINMENT BOXES
Facility is Not E ui With S illIOverfill Containment Boxes 0
SpiWOverfill Containment Boxes are Present, but were Not Tested 0
Test Method Developed By: 0 Spill Bucket Manufacturer X Industry Standard
o Other (SpecifY)
Test Method Used: 0 Pressure 0 Vacuum
X Other (SpecifY) Fuel
o Professional Engineer
Hydrostatic
Test Equipment Used: Pressure
Equipment Resolution:
r<:.~; 'c,>;:,: :¿~',~~~;: ~~š" ..,.;:&:-'" -~h:;'::.~~1,¡;"7~?:; à
Bucket Diameter:
Bucket Depth:
Wait time between applying
pressure/vacuum/water and
startin test:
Test Start Time:
Initial Reading (Ra:
Test End Time:
Final Reading (RF):
Test Duration:
Change in Reading (R¡.-R¡):
Pass/Fail Threshold or
Criteria:
Test Result:
11"
12.5"
Spill Box #87B Spill Box #Prem
11" 11"
13" 12
IS Min. IS Min.
9:00 P.M. 9:00 P.M.
9" 9"
10:00 P.M. 10:00 P.M.
9" 9"
1 Hr. I Hr.
0 0
Pass/Gross Pass/Gross
X Pass o Fail X Pass o Fail
Spill Box #
Spill Box # 87 A
15 Min.
9:00 P.M.
9"
10:00 P.M.
9"
1 Hr.
o
Pass! Gross
X Pass 0 Fail
o Pass 0 Fail
Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests)
;YSTEI"! SETUP
- - - -
------
iEP 1, 2004 10: 08 PI"!
,YSTEM UNITS
U.S.
3YSTEM LANGUAGE
ENGLISH
3YSTEM DATE/TIME FORMAT
10N DD YYYY HH:MM:SS xM
~ostco Wholesale 688
3800 Rosedale Hwy
Bakersfjeld, CA
3HIFT TIME 1 DISABLED
3HIFT TIME 2 DISABLED
3HIFT TIME 3 : DISABLED
3HIFT TIME 4 : DISABLED
3HIFT BIR PRINTOUTS
DISABLED
DAILY BIR PRINTOUTS
DISABLED
TICKETED DELIVERY
DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
DISABLED
LINE RE-ENABLE METHOD
PASS LINE TEST
LINE PER TST NEEDED WRN
DISABLED
LINE ANN TST NEEDED WRN
DISABLED
PRINT TC VOLUMES
ENABLED
TEMP COMPENSATION
VALUE (DEG F}: 60.0
STICK HEIGHT OFFSET
DISABLED
H-PROTOCOL DATA FORMAT
HE IGHT
DAYLIGHT SAVING TIME
DISABLED
RE-DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
S
SYSTEM SECURITY
CODE : 000000
COMMUNICATIONS SETUP
------ -
-----
PORT SETTINGS:
COMM BOARD : 1 (EDIM
RS-232 SECURITY
CODE : DISABLED
COMM BOARD 2 (RS-232}
BAUD RATE 9600
PARITY ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
COMM BOARD 3 (FXMOD}
BAUD RATE 2400
PARITY ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
DIAL TYPE : TONE
ANSWER ON : 1 RING
MODEM SETUP STRING :
DIAL TONE INTERVAL: 32
AUTO TRANSMIT SETTINGS:
AUTO LEAK ALARM LIMIT
DISABLED
AUTO HIGH WATER LIMIT
DISABLED
AUTO OVERFILL LIMIT
DISABLED
AUTO LOW PRODUCT
DISABLED
AUTO THEFT LIMIT
DISABLED
AUTO DELIVERY START
DISABLED
AUTO DELIVERY END
DISABLED
AUTO EXTERNAL INPUT ON
DISABLED
AUTO EXTERNAL INPUT OFF
DISABLED
AUTO SENSOR FUEL ALARM
DISABLED
AUTO SENSOR WATER ALARM
DISABLED
AUTO SENSOR OUT ALARM
DISABLED
RECEIVER SETUP:
D 1: RYDER FCS
18668201467
RCVR TYPE: FACSIMILE
PORT NO: 3
RETRY NO: 30
RETRY DELAY: 3
CONFIRMATION REPORT: ON
~ 1f={r;g8
~f<.~-ttßlcI
AUTO DIAL TIME SETUP:
D 1: RYDER FCS
DIAL MONTHLY
WEEK 4 WED
DIAL TIME: 4:00 PM
RECEIVER REPORTS:
PRIORITY HISTORY
RS-232 END OF MESSAGE
DISABLED
AUTO DIAL ALARM SETUP
------ -
-----
D 1: RYDER FCS
IN-TANK ALARMS
ALL:LEAJ< ALARM
ALL:HIGH WATER ALARM
ALL:SUDDEN LOSS ALARM
ALL:PROBE OUT
ALL:HIGH WATER WARNING
ALL:MAX PRODUCT ALARM
ALL:GROSS TEST FAIL
ALL:LOW TEMP WARNING
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
ALL:WATER ALARM
ALL:HIGH LIQUID ALARM
ALL:LOW LIQUID ALARM
ALL:LIQUID WARNING
COMM SIDE DIM ALM
ALL:DISABLED DIM ALARM
ALL:COMMUNICATION ALARM
CD
c::
IN-TANK SETUP
------
T~ 1 :Unl¡:;'aded
PRODUCT CODE
THERMAL COEFF
TANK DIAMETER
TANK PROFILE
FULL VOL
89.6 INCH VOL
59.8 INCH VOL
29.9 INCH VOL
METER DATA
FLOAT SIZE:
WATER WARNING :
HIGH WATER LIMIT:
MAX OR LABEL VOL:
OVERF I LL LI M IT
HIGH PRODUCT
DEL I VERY LI M IT
LOW PRODUCT :
LEAK ALARM LI M IT :
SUDDEN LOSS LIMIT:
TANK TILT
PROBE OFFSET
MANIFOLDED TANKS
Tit: NÇ>NE
LEAK MIN PERIODIC:
LEAK MIN ANNUAL
1
: .000700
11 9 . 50
4 PTS
19951
16216
10017
3781
NO
4.0 IN.
2.0
3.0
19951
90%
17956
95%
18953
25%
4987
2500
8
25
0.00
0.00
80%
1 5960
80%
15960
PERIODIC TEST TYPE
STANDARD
~NNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
~ROSS TEST FAIL
ALARM DISABLED
~NN TEST AVERAGING: OFF
jER TEST AVERAGING: OFF
rANK TEST NOTIFY: OFF
rNK TST SIPHON BREAK:OFF
)ELIVERY DELAY : 2 MIN
)UMP THRESHOLD : 10.00%
T 2:Unleaded
PRODUCT CODE
THERMAL COEFF
TANK DIAI"ETER
TANK PROFILE
FULL VOL
89.6 INCH VOL
59.8 INCH VOL
29.9 INCH VOL
METER DATA
FLOAT SIZE:
WATER WARNING .
HIGH WATER LIMIT:
MAX OR LABEL VOL:.
OVERF I LL LI M IT
HIGH PRODUCT
DELI VERY LI M I T
LOW PRODUCT .
LEAK ALARM LIMIT:
SUDDEN LOSS LIMIT:
TANK TILT
PROBE OFFSET
MANIFOLDED TANKS
TJt: NONE
LEAK MIN PERIODIC:
LEAK MIN ANNUAL
1ÄS~ 7f ~~
(]AføzsttGl/ð
1
: .000700
11 9. 50
4 PTS
19951
16216
10017
3781
NO
T 3:Pr·øniwfl
PRODUCT CODE
THER¡'\AL COEFF
TANK DIAMETER
TANK PROFILE
FULL VOL
89.6 INCH VOL
59.8 INCH VOL
29.9 INCH VOL
METER DATA
2
: .000700
11 9 . 50
4 PTS
1 9951
16216
10017
3781
NO
4.0 IN.
2.0
3.0
19951
90%
17956
95%
18953
25%
4987
2500
8
25
0.00
0.00
FLOAT SIZE: 4.0 IN.
WATER WARNING : 2.0
HIGH WATER LIMIT: 3.0
MAX OR LABEL VOL: 19951
OVERFILL LIMIT 90%
17956
HIGH PRODUCT 95%
18953
DELIVERY LIMIT 25%
4987
LOW PRODUCT : 2500
LEAK ALARM LIMIT: 8
SUDDEN LOSS LI M IT : 25
TANK TILT 0.00
PROBE OFFSET 0.00
MANIFOLDED TANKS
Tit: NONE
80%
15960
LEAK MIN PERIODIC:
80%
1 5960
80%
15960
LEAK MIN ANNUAL
80%
15960
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAG I NG : OFF
PER TEST AVERAGING: OFF
TANK TEST NOT I FY : OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 2 MIN
PUMP THRESHOLD : 10.00%
PERIODIC TEST TYPE
STANDARD
ANNUAL TEST FAIL
ALARM DISABLED
PERIODIC TEST FAIL
ALARM DISABLED
GROSS TEST FAIL
ALARM DISABLED
ANN TEST AVERAGING: OFF
PER TEST AVERAGING: OFF
TANK TEST NOT I FY : OFF
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY : 2 MIN
PUMP THRESHOLD : 10.00%
~
LEAK TE3T 1"1ETHOD
- - - - - - - - - - - -
~ TEST ON DATE : ALL TANK
JAN 1. 1996
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
LEAK TEST REPORT FORMAT
NORMAL
LIQUID SENSOR SETUP
- - - - - - - - - -
L I:UNLEAD A ANNULAR
TRI-STATE <SINGLE FLOAT}
CATEGORY : ANNULAR SPACE
L 2:UNLEAD A FILL
DUAL FLT. DISCRIMINATING
CATEGORY : PIPING SUMP
L 3: UNLEAD A STP
DUAL FLT. DISCRIMINATING
CATEGORY : STP SUMP
L 4:UNLEAD B ANNULAR
TRI-STATE <SINGLE FLOAT>
CATEGORY : ANNULAR SPACE
L 5:UNLEAD B FILL
DUAL FLT. DISCRIMINATING
CATEGORY : PIPING SUMP
L 6:UNLEAD B STP
DUAL FLT. DISCRIMINATING
CATEGORY : STP SUMP
L 7:PREMIUM ANNULAR
TRI-STATE {SINGLE FLOAT>
CATEGORY : ANNULAR SPACE
L 8:PREMIUM FILL
DUAL FLT. DISCRIMINATING
CATEGORY : PIPING SUMP
L 9:PREMIUM STP
DUAL FLT. DISCRIMINATING
CATEGORY : STP SUMP
LI0:DISP PAN 1.2
TRI-STATE <SINGLE FLOAT>
CATEGORY : DISPENSER PAN
LII:DISP PAN 3.4
TRI-STATE {SiNGLE FLOAT>
CATEGORY : DISPENSER PAN
Ll2 :DISP PAN 5..6
TRI-STATE <SINGLE FLOAT)
CATEGORY : DISPENSER PAN
LI3:DISP PAN 7.8
TRI-STATE <SINGLE FLOAT)
CATEGORY : DISPENSER PAN
LI4:DISP PAN 9.10
TRI-STATE <SINGLE FLOAT)
CATEGORY : DISPENSER PAN
Ll 5 : D I SP PAN 1.1. 1 2
TRI-STATE (SINGLE FLOAT>
CATEGORY : DISPENSER PAN
OUTPUT RELAY SETUP
- - - - - - - - - -
R 1:0VERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
IN-TANK ALARMS
ALL:HIGH WATER ALARM
ALL:OVERFILL ALARM
ALL:LOW PRODUCT ALARM
ALL:SUDDEN LOSS ALARM
ALL:HIGH PRODUCT ALARM
ALL:HIGH WATER WARNING
ALL:DELIVERY NEEDED
ALL:MAX PRODUCT ALARM
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL :SHORT ALAR!"!
ALL:WATER ALARM
L 2:HIGH LIQUID ALARM
L 3:HIGH LIQUID ALARM
L 5:HIGH LIQUID ALARM
L 6:HIGH LIQUID ALARM
L 8:HIGH LIQUID ALARM
L 9:HIGH LIQUID ALARM
L 1 :LOW LIQUID ALARt"1
L 4:LOW LIQUID ALARM
L 7:LOW LIQUID ALARM
ALL:LIGUID WARNING
~t.Rg¡
~Glr.
R 2: MEI''1BERSH I P
TYPE:
STANDARD
NORMALLY OPEN
IN-TANK ALARMS
ALL:LEAK ALARM
ALL:HIGH WATER ALARM
ALL:OVERFILL ALARM
ALL:LOW PRODUCT ALARM
ALL:SUDDEN LOSS ALARM
ALL:PROBE OUT
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
ALL:WATER ALARM
L 2:HIGH LIQUID ALARM
L 3:HIGH LIQUID ALARM
L 5:HIGH LIQUID ALARM
L 6:HIGH LIQUID ALARM
L 8:HIGH LIQUID ALARM
L 9:HIGH LIQUID ALARM
L l:LOW LIQUID ALARM
L 4:LOW LIQUID ALARM
L 5:LOW LIQUID ALARM
L 7:LOW LIQUID ALARM
ALL:LIQUID WARNING
R 5:UNLEAD SHUTDOWN
TYPE:
STANDARD
NORMALLY CLOSED
IN-TANK ALARMS
T l:HIGH WATER ALARM
LIQUID SENSOR ALMS
L 1: FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 6:FUEL ALARM
LlO:FUEL ALARM
Ll1 :FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
LI4:FUEL ALARM
LI5:FUEL ALARM
L l:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
LI0:SENSOR OUT ALARM
Lll:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L 1 :SHORT ALAR!"1
L 2:SHORT ALARM
L 3:SHORT ALARM
L 6: SHORT ALARM
LI0:SHORT ALARM
Ll1:SHORT ALARM
LI2:SHORT ALARM
L13:SHORT ALARM
Ll4 : SHORT ALARM
L15:SHORT ALARM
L 2:HIGH LIQUID ALARM
L 3:HIGH LIQUID ALARM
L 6:HIGH LIQUID ALARM
~
R 6:UNLEADED B SHUTDOWN
TYPE:
STANDARD
NORMALLY' CLOSED
IN-TANK ALARMS
T 2:HIGH WATER ALARM
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
LI0:FUEL ALARM
L11 : FUEL ALARM
L12:FUEL ALARM
L1 3 : FUEL ALARM
LI4:FUEL ALARM
L15:FUEL ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
LI0:SENSOR OUT ALARM
Ll1:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13 : SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
LI0:SHORT ALARM
L11 :SHORT ALARM
L1 2 : SHORT ALARM
LI3:SHORT ALARM
LI4:SHORT ALARM
L15:SHORT ALARM
L 3:HIGH LIQUID ALARM
L 5:HIGH LIQUID ALARM
L 6:HIGH LIQUID ALARM
R 7:PREMIUM
TYPE:
STANDARD
NORMALLY CLOSED
IN-TANK ALARMS
T 3:HIGH WATER ALARM
LIQUID SENSOR ALMS
L 7: FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
LI0:FUEL ALARM
L11 : FUEL ALARM
L12:FUEL ALARM
LI3:FUEL ALARM
L14:FUEL ALARM
L15:FUEL ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9 : SENSOR OUT ALAR!"!
LI0:SENSOR OUT ALARM
Lll :SENSOR OUT ALARr"
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9: SHORT ALARI1
L1 0 : SHORT ALARM
L11 :SHORT ALARM
L1 2 :SHORT ALARM
L13:SHORT ALARM
L14 : SHORT ALARM
L15:SHORT ALARM
L 8:HIGH LIQUID ALARM
L 9:HIGH LIQUID ALARM
e~v~
~AE"LO
Costco Wholesale 688
3800 Rosedale Hwy
Bakersfield, CA
SEP 1, 2004 10:09 PM
SERVICE REPORT
NONE
IN-TANK DIAGNOSTIC
- - - - - - - - -
RECONCILIATION SETUP
PROBE DIAGNOSTICS
T 1: PROBE TYPE MAGI
SERIAL NUMBER 609830
ID CHAN = OxCOOO
GRADIENT = 349.4000
NUM SAMPLES = 20
COO 1316.9 COl 19672.9
C02 19673.0 C03 19673.0
C04 19673.0 C05 19673.0
C06 19672.9 C07 19673.0
C08 19673.0 C09 19673.0
C10 19673.0 C11 45583.6
C12 9838.3 C13 10264.5
C14 10559.2 C15 10853.1
C16 10860.3 C17 10767.1
C18 45583.9
SAMPLES READ =36684112
SAMPLES USED =36677723
- - - - - - - - - -
EDIM 1:
AUTOMATIC DAILY CLOSING
TIME: 2:00 AM
AUTO SHIFT #1 CLOSING
TI ME: DISABLED
AUTO SHIFT #2 CLOSING
TIME: DISABLED
AUTO SHIFT #3 CLOSING
TI ME: DISABLED
AUTO SHIFT #4 CLOSING
TIME: DISABLED
PERIODIC RECONCILIATION
MODE: MONTHLY
ALARM: DISABLED
TEMP COMPENSATION
STANDARD
METER CALIBRATION
OFFSET: 0.000%
BUS SLOT FUEL METER TANK
IN-TANK DIAGNOSTIC
---- ---
PROBE DIAGNOSTICS
T 2: PROBE TYPE MAGI
SERIAL NUMBER 609832
ID CHAN = OxCOOO
GRADIENT = 349.2000
NUM SAMPLES =
20
- - - - - - - - - - - -
COl 20567.1
C03 20567.1
C0520567.0
C07 20567.0
C09 20567. 1
Cll 45410.1
C13 9834.5
C1510391.8
C 17 10539. 1
TANK MAP EMPTY
COO 1361.2
C02 20567. 1
C04 20567.0
C06 20567.0
C08 20567.3
CI0 20567.0
C12 9689.6
C14 10115.8
C16 10616.0
C18 45410.4
SAMPLES READ =36682611
SAMPLES USED =36678570
SOFTWARE REVISION LEVEL
VERSION 322.00
SOFTWARE# 346322-100-A
CREATED - 01.10.16.09.48
S-MODULE# 330160-100-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
BIR
r0
IN-TANK DIAGNOSTIC
- - - - - - - - -
PROBE DIAGNOSTICS
;T 3: PROBE TYPE MAGI
SERIAL NUMBER 602053
ID CHAN = OxCOOO
GRADIENT = 349.2500
NUM SAMPLES = 20
COO 1365.0 COl 19009.0
C02 19009.0 C03 19009.0
C04 19009.0 C05 19009.0
C06 19009.1 C07 19009.0
C08 19009.0 C09 19009.0
CI0 19009.0 Cl1 44165.1
C12 9410.5 C13 9672.0
C14 9925.0 C15 10090.8
C16 10498.2 C17 10677.5
C18 44165.9
SAMPLES READ =36682510
SAMPLES USED =36679951
IN-TANK LEA/<: DIAGNOSTIC
- - - - - - - - - - - -
PROBE DIAGNOSTICS
T 1: PROBE T'lF'E MAG 1
SERIAL NUMBER 609830
GRADIENT = 349.4000
NUM SAMPLES = 36576
COO 1 316 . 8 C01 1 8831 . 1
C0218831.1 C0318831.1
C0418831.1 C0518831.1
C06 20975.4 C07 20975.4
C08 20975.4 C09 20975.4
C10 20975.4 Cl1 45584.2
C12 9565.4 C13 10146.3
C14 10409.0 C15 10534.6
C16 10554.2 C17 10496.3
C18 45585.0
IN-TANK LEAK DIAGNOSTIC
- - - - - -
------
PROBE DIAGNOSTICS
T 2: PROBE TYPE MAGI
SERIAL NUMBER 609832
GRADIENT = 349.2000
NUM SAMPLES = 7207
COO 1361.5 COl 20605.6
C02 20605.7 C03 20605.7
C04 20605.7 C05 20605.7
C0621157.2 C0721157.3
C08 21157.2 C09 21157.2
CI021157.2 Cl1 45411.5
C12 9256.7 C13 9535.1
C14 9908.2 C15 10091.4
C16 10350.7 C17 10286.5
C18 45410.9
IN-TANK LEAK DIAGNOSTIC
- - - - - - - - - - - -
PROBE DIAGNOSTICS
T 3: PROBE TYPE MAGI
SERIAL NUMBER 602053
GRADIENT = 349.2500
NUM SAMPLES = 3949
COO 1365.2 Col 19013.7
C02 19013.7 C03 19013.7
C04 19013.7 C05 19013.7
C06 22017.3 C07 22017.3
C08 22017.3 C0922017.3
CI0 22017.3 Cl1 44165.7
C12 9211.0 C13 9780.8
C14 10176.6 C15 10266.1
C16 10599.4 C17 10773.2
C18 44166.3
ACCU_CHART DIAGNOSTICS
- - - - - - -" - - - - -
T I:Unleaded
ACCU
T 2:Unleaded
ACCU
DISABLED
DISABLED
T 3:Premium
ACCU
T 4:
ACCU
DISABLED
DISABLED
LIQUID DIAGNOSTIC
- - - - - - - - - -
L l:UNLEAD A ANNULAR
SAMPLES = 5
LOW REFl= 185
HIGH REFl= 1106
VALUE 1 = 98839
L 2:UNLEAD A FILL
SAMPLES =
LOW REFI=
HIGH REFl =
VALUE 1 =
5
185
1105
147776
L 3:UNLEAD A STP
, SAMPLES=
LOW REFl=
HIGH REFl=
VALUE 1 =
5
186
1105
147641
L 4:UNLEAD B ANNULAR
SAMPLES = 5
LOW REFl= 185
HIGH REFl= 1105
VALUE 1 = 98645
~~=lrræ<6
CÞ:tk~ElJD
L 5:UNLEAD B FILL
SAMPLES =
LOW REF1=
HIGH REF 1 =
VALUE 1 =
5
185
1105
148488
L 6:UNLEAD B STP
SAMPLES =
LOW REFl=
HIGH REFl=
VALUE 1 =
5
186
1106
146994
L 7:PREMIUM ANNULAR
SAMPLES = 5
LOW REFl= 185
HIGH REFl= 1105
VALUE 1 = 98822
L 8:PREMIUM FILL
SAMPLES =
LOW REFl=
HIGH REF 1 =
VALUE 1 =
L 9:PREMIUM STP
SAMPLES =
LOW REFl=
HIGH REFl=
VALUE 1 =
LlO:DISP PAN
SAMPLES =
LOW REF1=
HIGH REFl=
VALUE 1 =
5
186
1106
148202
5
185
1105
148006
1.2
5
186
1104
101850
Lll:DISP PAN 3,4
SAMPLES=
LOW REFl=
HIGH REF 1 =
VALUE 1 =
L12 :DISP PAN
SAI"IPLES=
LOW REFl=
HIGH REFl=
VALUE 1 =
L13:DISP PAN
SAMPLES =
LOW REFl=
HIGH REFl=
VALUE 1 =
L14 :DISP PAN
SAMPLES =
LOW REFl=
HIGH REFl=
VALUEt=
5
185
1105
101310
5,6
5
185
1103
101850
7,8
5
185
1104
101368
9,10
5
186
1103
100779
@
-::
L15:DISP PAN
SAMPLES=
LOW REFI=
HIGH REF! =
VALUE 1 =
II ,12
5
185
1102
102146
Lt6:
SAMPLES= 5
LOW REF1= 186
HIGH REFl= 1102
VALUE 1 =999999680
GROUNDTEI"IP D I AGNOST I C
- - - - - - - - - -
9 1:
SAMPLES = 50
LOW REF1= 186
HIGH REF1= 1104
VALUE 1 =999997056
9 2:
SAMPLES = 50
LOW REF1= 185
HIGH REF1= 1102
VALUE 1 =999997056
9 3:
SAMPLES = 50
LOW REF1= 186
HIGH REF1= 1106
VALUE 1 =999997056
9 4:
SAMPLES = 50
LOW REF1= 186
HIGH REF1= 1104
VALUE 1 =999997056
ALARM HISTORY REPORT
----- SYSTEM ALARM -----
PAPER OUT
SEP 1, 2004 8:44 PM
PRINTER ERROR
SEP 1, 2004 8:44 PM
BATTERV IS OFF
JAN 1, 1996 8:00 AM
C~~9g
~fì~ïf)
ALARI"I HIBTORV REPORT
---- IN-TANK ALARM
T l:Unleaded
SETUP DATA WARNING
SEP 1, 2004 9:28 PM
OVERFILL ALARM
APR 26, 2004 9:26 AM
APR 26, 2004 9:10 AM
MAR 14, 2004 9:58 AM
LOW PRODUCT ALARM
AUG 2, 2004 8:08 PM
APR 29. 2004 2:03 PM
AUG 26. 2003 10:52 PM
HIGH PRODUCT ALARM
SEP 1. 2004 9:28 PM
AUG 26. 2003 10:52 PM
AUG 26. 2003 10:50 PM
INVALID FUEL LEVEL
APR 29, 2004 4:37 PM
AUG 26. 2003 10:53 PM
AUG 26. 2003 10:50 PM
PROBE OUT
APR 26. 2004 3:33 PM
AUG 26. 2003 11:02 PM
AUG 26, 2003 10:42 PM
ALARM HIST(;·R"¡' REPORT
---- IN-TANK ALARM
T 2:Unleaded
HIGH WATER ALARM
AUG 26. 2003 10:43 PM
OVERFILL ALARM
JUN 28. 2004 7:25 AM
MAV 26. 2004 7:22 AM
APR 26. 2004 9:11 AM
LOW PRODUCT ALARM
AUG 2. 2004 8:14 PM
JUN 25. 2004 11:56 AM
JUN 25, 2004 10:05 AM
HIGH PRODUCT ALARM
SEP 1, 2004 9:50 PM
APR 26. 2004 9:13 AM
AUG 26, 2003 10:55 PM
INVALID FUEL LEVEL
APR 29. 2004 4:31 PM
AUG 26, 2003 10:43 PM
PROBE OUT
JUN 25. 2004 11:56 AM
JUN 25, 2004 11:41 AM
JUN 25. 2004 10:21 AM
HIGH WATER WARNING
AUG 26, 2003 10:43 PM
DELIVERV NEEDED
AUG 2. 2004 4:50 PM
AUG 1. 2004 5:00 PM
MAV 10. 2004 6:29 PM
LOW TEMP WARNING
AUG 26.2003 11:04 PM
DELIVERV NEEDED
AUG 2. 2004 4:39 PM
AUG 1. 2004 4:52 PM
JUN 25. 2004 11:56 AM
LOW TEMP WARNING
JUN 25, 2004 11:53 AM
AUG 26. 2003 11:06 PM
Costeo Wholesale 688
3800 Rosedale Hw~
Bakersfield. CA
SEP 1. 2004 10:09 PM
LEAK TEST REPORT
T t:Unleaded
PROBE SERIAL NUM 609830
~ ~ ~ M ¥ END ~ * M M M
NO TEST DATA AVAILABLE
* * * * * END * * * * *
@
ALAR!"! HI E;'WRV REPORT
, ---- í ¡'·j-TANK ALARM -----
T 3:Premium
HIGH WATER ALARM
AUG 26. 2003 10:59 PM
AUG 26. 2003 10:42 PM
OVERFILL ALARM
NOV 29. 2003 11:27 AM
OCT 13. 2003 3:39 PM
SEP 8. 2003 1:20 PM
LOW PRODUCT ALARM
AUG 26. 2003 10:54 PM
AUG 26. 2003 10:39 PM
HIGH PRODUCT ALARM
SEP 1. 2004 9:53 PM
AUG 26. 2003 10:53 PM
INVALID FUEL LEVEL
AUG 26. 2003 10:43 PM
PROBE OUT
SEP 17. 2003 9:17 AM
SEP 17. 2003 8:58 AM
SEP 17. 2003 8:28 AM
HIGH WATER WARNING
AUG 26. 2003 10:59 PM
AUG 26. 2003 10:42 PM
DELIVERY NEEDED
MAR 14. 2004 9:04 AM
AUG 26. 2003 10:54 PM
AUG 26. 2003 10:38 PM
LOW TEMP WARNING
SEP 17. 2003 9:13 AM
AUG 26.2003 11:08 PM
ALARM HiSTOR\' REPORT
----- SENSOR ALARM -----
L I:UNLEAD A ANNULAR
ANNULAR SPACE
FUEL ALARM
SEP 1. 2004 8:27 PM
FUEL ALARM
AUG 26. 2003 9:58 PM
FUEL ALARM
JUL 26. 2003 11:10 AM
ALARM HISTORY REPORT
----- SENSOR ALARM
L 2:UNLEAD A FILL
PIPING SUMP
HIGH LIQUID ALARM
SEP 1. 2004 8:27 PM
HIGH LIQUID ALARM
AUG 26.2003 11:26 PM
HIGH LIQUID ALARM
AUG 26. 2003 10:32 PM
~4rltEð
~áD
ALAR!" HI :=;TC'F:V REPORT
----- E;HJßOF: ALARM
L 6:UNLEAD B STP
STP SUMP
HIGH LIQUID ALARM
SEP 1. 2004·- 8: 47 PM
HIGH LIQUID ALARM
SEP 1. 2004 8:44 PM
HIGH LIQUID ALARM
AUG 26. 2003 9:56 PM
ALARM HISTORY REPORT
----- SENSOR ALARM
L 3:UNLEAD A STP
STP SUMP
HIGH LIQUID ALARM
SEP 1. 2004 8:50 PM
HIGH LIQUID ALARM
MAY 14. 2004 3:30 AM
LIQUID \¡JARNI NG
MAY 14. 2004 3:29 AM
ALARM HISTORV REPORT
----- SENSOR ALARM -----
L 7:PREMIUM ANNULAR
ANNULAR SPACE
FUEL ALARM
SEP 1. 2004 8:26 PM
FUEL ALARM
AUG 26. 2003 10:00 PM
ALARM HISTORY REPORT
----- SENSOR ALARM -----
L 4:UNLEAD B ANNULAR
ANNULAR SPACE
FUEL ALARM
SEP 1. 2004 8:27 PM
FUEL ALARM
AUG 26. 2003 9:59 PM
ALARM HISTORY REPORT
----- SENSOR ALARM
L 8:PREMIUM FILL
PIPING SUMP
HIGH LIQUID ALARM
SEP 1. 2004 8:25 PM
HIGH LIQUID ALARM
AUG 26. 2003 10:20 PM
ALARM HISTORY REPORT
----- SENSOR ALARM
L 5:UNLEAD B FILL
PIPING SUMP
HIGH LIQUID ALARM
SEP 1. 2004 8:26 PM
HIGH LIQUID ALARM
AUG 26. 2003 10:06 PM
FUEL ALARM
JUL 18. 2003 4:56 PM
ALARM HI 8TOF:Y REPORT
----- SENSOR ALARM
L 9:PREMIUI"I STP
STP SUMP
HIGH LIQUID ALARM
SEP 1. 2004 8:28 PM
FUEL ALARM
JUL 8. 2004 9:26 AM
FUEL ALARM
JUL 3. 2004 12:40 AM
(j)
ALARM HISTOR'l REf'ORT
----- SENSOR ALARM
LI0:DISP PAN 1.2
DISPENSER PAN
FUEL ALARM
SEP 1. 2004 9:43 PM
FUEL ALAR!"!
AUG 26. 2003 10:22 PM
ALARM HISTOR\'" REPORT
----- SENSOR ALARM
Ll1:DISP PAN 3.4
DISPENSER PAN
FUEL ALARM
SEP 1. 2004 9:41 PM
FUEL ALARM
AUG 26. 2P03 10:21 PM
ALARM HISTOR'/ REPORT
----- SENSOR ALARM
L12:DISP PAN 5.6
DISPENSER PAN
FUEL ALARM
SEP 1. 2004 9:46 PM
FUEL ALARM
AUG 26. 2003 10:23 PM
ALARM HISTORY REPORT
----- SENSOR ALARM
LI3:DISP PAN 7.8
DISPENSER PAN
FUEL ALARM
SEP 1. 2004 9:49 PM
FUEL ALARM
AUG 26. 2003 10:23 PM
ALARM HISTORV REPORT
----- SENSOR ALARM
L14:DISP PAN 9.10
DISPENSER PAN
FUEL ALARM
SEP 1. 2004 9:56 PM
FUEL ALARM
AUG 26. 2003 10:25 PM
FUEL ALARM
JUL 26. 2003 11:31 AM
ALAR!"1 HI STOR\¡ REPORT
----- SENSOR ALARM
LI5:DISP PAN 11.12
DISPENSER PAN
FUEL ALARM
SEP 1. 2004 9:52 PM
FUEL ALARM
MAR 23. 2004 11:33 AM
FUEL ALARM
MAR 23. 2004 11:04 AM
ALARM HI STORY FŒPORT
----- SENSOR ALARM
L16:
OTHER SENSORS
Costeo Wholesale 688
3800 Rosedal~ Hwy
Bakersfield. CA
SEP 1. 2004 10:10 PM
LEAK TEST REPORT
T 2:Unleaded
PROBE SERIAL NUM 609832
NO TEST DATA AVAILABLE
* * * ~ ~ END * ~ * ~ *
LAST METER EVENT
------
- - - -
SEP 1. 2004
FP:37 M: 1
END EVENT
9:03:32 PM
= T U
9 GALS
SEP 1. 2004 9:07:28 PM
FP 37
START EVENT
SEP 1. 2004 9:08:14 PM
FP 33
START EVENT
SEP 1. 2004 9:08:53 PM
FP:37 M:O = T U
END EVENT
8 GALS
SEP 1. 2004 9:10:20 PM
FP:33 1"1:0 = T U
END EVENT 13 GALS
~q¡=-lÆ<g
~ßoJ~.a'L<\-tì (;[-0
Casteo Wholesale 688
3800 R05~dale Hwy
Bakersfield. CA
SEP 1. 2004 10:10 PM
LAST POWER OUTAGE REPORT
T 1: Unl eaded
PROBE SERIAL NUM 609830
POWER REMOVED
JAN 1. 1970 12:00 AM
VOLU!"IE
WATER VOL
TEMP
o GALS
o GALS
0.0 DEG F
POWER RESTORED
JUL 18. 2003 4:07 PM
VOLUME
WATER VOL
TEMP
12438 GALS
o GALS
91 .4 DEG F
GROSS VOLUME CHANGE
12438 GALS
T 2:Unleaded
PROBE SERIAL NUM 609832
POWER REMOVED
JAN 1. 1970 12:00 AM
VOLUME
WATER VOL
TEMP
o GALS
o GALS
0.0 DEG F
POWER RESTORED
JUL 18. 2003 4:07 PM
VOLUME
WATER VOL
TEMp·
12344 GALS
o GALS
91.4 DEG F
GROSS VOLUME CHANGE
12344 GALS
T 3:Premium
PROBE SERIAL NUM 602053
POWER REMOVED
JAN 1. 1970 12:00 AM
VOLUME
WATER VOL
TEMP
o GALS
o GALS
0.0 DEG F
POWER RESTORED
JUL 18. 2003 4:07 PM
VOLUME
WATER VOL
TEMP
11021 GALS
o GALS
85.9 DEG F
GROSS VOLUI"!E CHANGE
11021 GALS
\~
ARCHI\/E DIAGNOSTIC
------
JUL 18, 2003 3:50:00 PM
VERSION 322.00
SOFTWARE~ 346322-100-A
CREATED - 01.10.16.09.48
S-MODULE~ 330160-100-a
Costeo Wholesale 688
3800 Rosedale Hw~
Bakersfield. CA
SEP 1. 2004 10:10 PM
LEAK TEST REPORT
T 3:Premium
PROBE SERIAL NUM 602053
NO TEST DATA AVAILABLE
BUS SLOT FUEL "'JETER TANK
------ -
-----
TANK f"IAP EMPTY
Costeo Wholesale 688
3800 Rosedale Hw~
Bakel' sf i e I d. CA
SEP 1. 2004 10:11 PM
LAST POWER OUTAGE REPORT
T l:Unleaded
PROBE SERIAL NUM 609830
POWER REMOVED
JAN 1. 1970 12:00 AM
VOLUME
WATER VOL '"
TEMP
o GALS
o GALS
0.0 DEG F
POWER RESTORED
JUL 18. 2003 4:07 PM
VOLUME
WATER VOL '"
TEMP
12438 GALS
o GALS
91 .4 DEG F
GROSS VOLUME CHANGE
12438 GALS
T 2:Unleaded
PROBE SERIAL NUM 609832
POWER REMOVED
JAN 1. 1970 12:00 AM
VOLUME '"
WATER VOL
TEMP
o GALS
o GALS
0.0 DEG F
POWER RESTORED
JUL 18. 2003 4:07 PM
VOLUME
WATER VOL
TEMP
12344 GALS
'" 0 GALS
= 91.4 DEG F
GROSS VOLUME CHANGE
12344 GALS
T 3:Premium
PROBE SERIAL NUM 602053
POWER REMOVED
JAN 1. 1970 12:00 AM
VOLUME
WATER VOL '"
TEMP
o GALS
o GALS
0.0 DEG F
POWER RESTORED
JUL 18. 2003 4:07 PM
VOLUME
WATER VOL
TEMP
11 021 GALS
o GALS
85.9 DEG F
GROSS VOLlJI"IE CHANGE
11021 GALS
~ 4ttæ8'
~~
@)
'-...
-
ø UNL ~ì ~ RNNI..lLI'l\fl.
® u,1\11- ~"l. 8 F'"ILL...
@> U I\H.. l2> ê 1\ s-ry
@) !..\NL. ßì Î? A f\) N v..L.v.\ L
® U~L 'b'l t?> FIL...(....
~l..t~t... ~1 B S'1" Ç>
éJ) p)'t£ \'Y\ 'v- M 4l\JN......U\h-
® 1> &:lE:' 1M \ u..VV' ¡::- ) L<...
(j) f R.. e.1V\ "'..... vVì. 'S\Ç>
@ \)(~? I,¡.. "2.-
® D ¡sf> ~""''Í
@ Di'::>p "'S.....L.e
@ Ì)\ '?e )+'6
® p \S f' c¡ l' 10
@ D\~(' \ +-¡~
4! 6::.<6 ~
C D.sTQO ~~ðLe.. SALE
3 'tScc o.,o:::£D ~ Ly¿- +-l \.J,:)'i
t':>¡4-\(£lQS~I¡;LÞ <;t'Oo. \ ,'3~D"!;
~Lfí
P~'"tA
I
~ -~:------
o
,a... I - n
~ I U ~
¡---~--~--~ -----------
. ,. I ..
I . ¢:I I
I . I . ¡'
~ r-----~ .--- -----------
~. . @: ~
- \
u~· _
~ I n
~. I i U
~----~--~--- -----------.
I ' I
I ""¢:1 .
¿ ~------~--~ ------------
¡:;,: \ ~
~ ,I ~
~------~~~~ ----------~-
'-.. _-,---1' -I _
I -¢:I
~--~---~-~~ ~~----------
I,.
)
I
í.