November 12, 2004
Certified Mail - Return Receipt Requested
('
E-Certified
91 7108 2133 3930 8586 133~
City of Bakersfield
Fire Department
2101 "H" Street
Bakersfield, CA 93301
Re: SB98 Test Results
3221 "H" Street, Bakersfield Geo Par: SA-098
CLLC: BKFDCA14
To Whom It May Concern:
Enclosed are the S8989 Test results for the above-referenced location.
Feel free to call if you have any questions.
Very Truly Yours,
TAIT ENVIRONMENTAL SYSTEMS
~~
ALAN THROCKMORTON
Compliance Manager
AT:clb
: \tes\pacbell\sb989\letters\bkfdca 14
cc: Andy Taylor
Linda Porter (Post At Site)
CA Lie #588098 . AZ Lie #095984 . NV Lie #0049666
1863 North Neville Street. Orange, California 92865 . 714.560.8222 . 714.685.0006 Fax
3283 Luyung Drive· Rancho Cordova, California 95742 . 916.858.1090 . 916.858.1011 Fax
www.SB989.com
¡ ,
SWRCB, January 2002
Page_of_
Secondary Containment Testing Report Form
This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the
appropriate pages of this form to report results for all components tested. The completed form, written test procedures, and
printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: SBC I Date of Testing: 11/9/04
Facility Address: 3221 "H" STREET BAKERSFIELD, CA
Facility Contact: I Phone:
Date Local Agency Was Notified of Testing : 48 HOURS PRIOR - AT LEAST
Name of Local Agency Inspector (ifpresent during testing): NONE
Company Name: T AIT ENVIRONMENTAL SYSTEMS
Technician Conducting Test: ROBERT ALLEN
Credentials: ~ CSLB Licensed Contractor SWRCB Licensed Tank Tester
License Type: A B ASB C-10 HAZ I License Number: 588098
Manufacturer Trainine
Manufacturer Component( s) Date Training Expires
SUPPLIED UPON REQUEST
2. TESTING CONTRACTOR INFORMATION
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not Repairs Component Pass Fail Not Repairs
Tested Made Tested Made
ANNULAR ~ 0
FILL SUMP ~ 0
PIPING SUMP ~ 0
SUPPLY SECONDARY ~ 0
RETURN SECONDARY ~ 0
VENT SECONDARY ~ 0
0
-J
If hydrostatic testing was performed, describe what was done with the water after completion of tests:
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge, the facts stated in this document are accurate and in full compliance with legal requirements
~
~
Date:
11/9/04
Technician's Signature:
,
).\ .
SWRCB, January 2002
Page_of_
Test Method Developed By:
4. TANK ANNULAR TESTING
o Tank Manufacturer t81 Industry Standard
Other (Specify)
o Pressure t81 Vacuum
Professional Engineer
Test Method Used:
Hydrostatic
Other (Specify)
Test Equipment Used: 4" GLYCERIN FILLED DIAL GAUGE
Equipment Resolution:
nk# 1 Tank # Tank # Tank #
Is Tank Exempt From Testing?' DYes o No Yes o No Yes No Yes No
Tank Capacity: 6,000
Tank Material: STEEL / GLASS
Tank Manufacturer: MODERN
Product Stored: DIESEL
Wait time between applying
pressure/vacuum/water and I HOUR
starting test:
Test Start Time: 10:00
Initial Reading (R1): -7
Test End Time: 11 :00
Final Reading (RF): -7
Test Duration: 1 HOUR
Change in Reading (RF-R¡): 0
Pass/Fail Threshold or Criteria: 0
Test Result: t81 Pass o Fail o Pass o Fail o Pass o Fai o Pass o Fail
Was sensor removed for testing? t81 Yes No NA Yes No NA Yes No NA Yes No NA
Was sensor properly replaced and t81 Yes No NA Yes No NA Yes No NA Yes No NA
verified functional after testing?
Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests)
, Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary
containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt !Tom periodic containment
testing. {California Code of Regulations, Title 23, Section 2637(a)(6)}
j . ~
SWRCB, January 2002
Page_of_
Test Method Developed By:
5. SECONDARY PIPE TESTING
o Piping Manufacturer 12] Industry Standard
Other (Specify)
12] Pressure Vacuum
Professional Engineer
Test Method Used:
Hydrostatic
Other (Specify)
Test Equipment Used: 4" GLYCERIN FILLED DIAL GAUGE
Equipment Resolution:
Piping Material:
Piping Manufacturer:
Piping Diameter:
Length of Piping Run:
Product Stored:
Method and location of
i in -run isolation:
Wait time between applying
pressure/vacuum/water and
starting test:
Test Start Time:
Initial Reading (R¡):
Test End Time:
Final Reading (RF):
Test Duration:
Change in Reading (RF-R¡):
Pass/Fail Threshold or
Criteria:
Test Result:
Piping Run #
SUPPLY
PLASTIC
WESTERN
Piping Run #
RETURN
PLASTIC
WESTERN
Piping Run #
VENT
FIBERGLASS
SMITH
Piping Run #
314"
I"
3"
30'
DIESEL
30'
DIESEL
25'
DIESEL
15 MINUTES 15 MINUTES 15 MINUTES
9:05 9:05 I I: I 5
5 PSI 5 PSI 5 PSI
10:05 10:05 12: 15
5 PSI 5 PSI 5 PSI
I HOUR I HOUR I HOUR
0 0 0
0 0 0
12] Pass o Fail 12] Pass o Fail 12] Pass o Fail o Pass o Fail
Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests)
:¡.-
SWRCB, January 2002
Page_of_
6. PIPING SUMP TESTING
Test Method Developed By: Sump Manufacturer ~ Industry Standard o Professional Engineer
Other (Specify)
Test Method Used: Pressure Vacuum ~ Hydrostatic
Other (Specify)
Test Equipment Used: TEMPSONIC TEST UNIT Equipment Resolution:
Sump # Sump # Sump # Sump #
Sump Diameter: 31"
Sump Depth: 49"
Sump Material: FIBERGLASS
Height from Tank Top to Top of 16"
Highest Piping Penetration:
Height from Tank Top to Lowest 12"
Electrical Penetration:
Condition of sump prior to testing: GOOD
Portion of Sump Tested' ABOVE PIPING
Does turbine shut down when
sump sensor detects liquid (both Yes No ~NA Yes No NA Yes No NA Yes No NA
product and water)?-
Turbine shutdown response time N/A
Is system programmed for fail-safe Yes No ~NA Yes No NA Yes No NA Yes No NA
shutdown?-
Was fail-safe verified to be Yes No ~NA Yes No NA Yes No NA Yes No NA
operational?-
Wait time between applying
pressure/vacuum/water and starting 15 MINUTES
test:
Test Start Time: 10:10 / 10:25
Initial Reading (R,): 0 / 0
Test End Time: 10:25 / 10:40
Final Reading (RF): .0005 / .0005
Test Duration: 15 MINUTES
Change in Reading (RF-R1): .0005 / .0005
Pass/Fail Threshold or Criteria: .0020 / .0020
Test Result: ~ Pass o Fail o Pass o Fail o Pass o Fail o Pass o Fail
Was sensor removed for testing? ~Yes No NA DYes No NA Yes No NA Yes No NA
Was sensor properly replaced and ~Yes No NA DYes No NA Yes No NA Yes No NA
verified functional after testing?
Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests)
, Ifthe entire depth of the sump is not tested, specify how much was tested. If the answer to ªºy of the questions indicated with an
asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG-160)
:~'."
SWRCB, January 2002
Page_of_
8. FILL RISER CONTAINMENT SUMP TESTING
Facility is Not Equipped With Fill Riser Containment Sumps
Fill Riser Containment Sumps are Present, but were Not Tested
Test Method Developed By: Sump Manufacturer ¡g¡ Industry Standard D Professional Engineer
Other (Specify)
Test Method Used: Pressure Vacuum ¡g¡ Hydrostatic
Other (Specify)
Test Equipment Used: TEMPSONIC TEST UNIT Equipment Resolution:
Fill Sump # Fill Sump # Fill Sump # Fill Sump #
Sump Diameter: 31"
Sump Depth: 49"
Height from Tank Top to Top of
Highest Piping Penetration: NA
Height from Tank Top to Lowest
Electrical Penetration: 12"
Condition of sump prior to
testing: GOOD
Portion of Sump Tested ABOVE COLLAR
Sump Material: FIBERGLASS
Wait time between applying
pressure/vacuum/water and 15 MINUTES
starting test:
Test Start Time: 9:02 / 9:17
Initial Reading (R,): 0 / 0
Test End Time: 9:17 / 9:32
Final Reading (RF): 0 / 0
Test Duration: 15 MINUTES
Change in Reading (RF-R¡): 0 / 0
Pass/Fail Threshold or Criteria: .0020 / .0020
Test Result: ¡g¡ Pass D Fail D Pass o Fail D Pass o Fail D Pass o Fai.1
Is there a sensor in the sump? t8J Yes No DYes No DYes No DYes No
Does the sensor alarm when
either product or water is ¡g¡ Yes No NA DYes No NA DYes No NA DYes No NA
detected?
Was sensor removed for testing? t8:1Yes No NA DYes No NA DYes No NA DYes No NA
Was sensor properly replaced and t8:I Yes No NA DYes No NA DYes No NA DYes No NA
verified functional after testing?
Comments - (include information on repairs made prior to testing, and recommendedfollow-up for failed tests)