II'Tanknology
8501 N. MoPac Expressway, Suite 400
Austin, Texas 78759
Phone: (512) 451-6334
Fax: (512) 459-1459
Date Printed and Mailed: 09/08/2004
KERN CTY - ENVIROMENTAL HEALTH
2700 M STREET
SUITE 300
BAKERSFIELD, CA. 93301
Test Date: 08/27/2004
Order Number: 3136161
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
CHEVRON 206561
3360 PANAMA LN.
BAKERSFIELD, CA. 93304
Testing performed:
Leak detector tests
Monitor Certification
Secondary Containment-Spill Container
Sincerely,
-:D~ K~
Dawn Kohlmeyer
Manager, Field Reporting
.--+,
C)
CJ
c-....J
r--
..-
0-
W
cf)
't
t- rÞ DJnknology
CLIENT: CHEVRON U.S.A.
P.O. BOX 2292
145 S. STATE COLLEGE BLVD.
BREA, CA 92822-2292
SAM STEVENSON
(909)765-6536
TANKNOLOGY CERTIFICATE OF TESTING
8900 SHOAL CREEK, BUILDING 200 AUSTIN, TEXAS 78757
TELEPHONE (512) 451-6334 FAX (512) 459-1459
TEST RESULT SUMMARY REPORT
WORK ORDER NUMBER: 3136161
CUSTOMER PO:
SITE: CHEVRON 206561
3360 PANAMA LN.
BAKERSFIELD, CA 93304
PURPOSE: COMPLIANCE
TEST DATE: 08/27104
MANAGER
(661 )396-7047
TEST TYPE: TLD-1
1
2
3
1 SUPREME
2 PLUS
3 UNLEADED
DW FIBERG
DW FIBERG
DW FIBERG
PRESSURE
PRESSURE
PRESSURE
y
y
y
1
2
3
1 FE PETRO
2 RED JACKET
3 FE PETRO
MLD
FX1V
MLD
BJ255 P
10401-8864 P
BJ256 P
For owner detailed report information, visit www.tanknology.com and select On-Line Reports-WRAP, or contact your local Tanknology office.
Tester Name: ALBERT J. QUEIROS
Technician Certification Number:91-1448
t14/j~
Printed 09/08/2004 10:01 SBOWERS
,.
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
~~ 7ånlmology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
TEST DATE:08/27 /04
CLlENT:CHEVRON U. S .A.
WORK ORDER NUMBER3136161
SITE:CHEVRON 206561
Tank 10: 1 1
Product: SUPREME
Capacity in gallons: 11,849
Diameter in inches: 120.00
Length in inches: 245
Material: DW FIBERG
COMMENTS
Tank manifolded: NO
Vent manifolded: YES
Vapor recovery manifolded: YES
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage 1 vapor recovery:
Stage II vapor recovery:
168.5
176.0
45.0
4.0
DUAL
BALANCE
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Bubble
Make: FE PETRO
Ullage Model: MLD
SIN: BJ~55
Open time in sec: 9.00
Holding psi: 28
Resiliency cc: 240 NOT
Test leak rate ml/m: 189.0 TESTED
Metering psi: 10
Calib. leak in gph: 3.00
Results: PASS
COMMENTS
NOT
TESTED
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
2.0
175.0
NOT
TESTED
NOT
TESTED
NOT
TESTED
NOT
TESTED
PRESSURE
FE PETRO
Impact Valves Operational: YES
Printed 09/08/2004 10:01
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
t-~ DJnlmology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
TEST DATE:08/27 /04
CLlENT:CHEVRON U.S.A.
WORK ORDER NUMBER3136161
SITE:CHEVRON 206561
Tank ID: 2 2
Product: PLUS
Capacity in gallons: 11,849
Diameter in inches: 120 . 00
Length in inches: 245
Material: DW FIBERG
COMMENTS
Tank manifolded: NO
Vent manifolded: YES
Vapor recovery manifolded: YES
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: / /
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
172.0
176,0
49.0
4.0
DUAL
BALANCE
Start (in)
End (in)
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
Bubble
Ullage
Make:
Model:
SIN:
Open time in sec:
Holding psi:
Resiliency cc:
Test leak rate ml/m:
Metering psi:
Calib. leak in gph:
Results:
NOT
TESTED
RED JACKET
FX1V
10401-8864
4.00
32
200
189.0
15
3.00
PASS
NOT
TESTED
COMMENTS
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
2.0
175.0
NOT
TESTED
NOT
TESTED
NOT
TESTED
NOT
TESTED
PRESSURE
FE PETRO
Jmpact Valves Operational: YES
Printed 09/08/2004 10:01
INDIVIDUAL TANK INFORMATION AND TEST RESULTS
~~ Dlnlmology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757 (512) 451-6334
TEST DATE: 08127 104
CLlENT:CHEVRON U.S.A.
WORK ORDER NUMBER3136161
SITE:CHEVRON 206561
Tank ID: 3 3
Product: UNLEADED
Capacity in gallons: 11,849
Diameter in inches: 120 . 00
Length in inches: 245
Material: DW FIBERG
COMMENTS
Tank manifolded: NO
Vent manifolded: YES
Vapor recovery manifolded: YES
Overfill protection: YES
Overspill protection: YES
Installed: ATG
CP installed on: 1 1
Bottom to top fill in inches:
Bottom to grade in inches:
Fill pipe length in inches:
Fill pipe diameter in inches:
Stage I vapor recovery:
Stage II vapor recovery:
176.0
182.0
52.0
4.0
DUAL
BALANCE
Start (in)
End (in)
New/passed Failed/replaced New/passed Failed/replaced
L.D. #1 L.D. #1 L.D. #2 L.D. #2
Dipped Water Level:
Dipped Product Level:
Probe Water Level:
Ingress Detected: Water
Test time:
Inclinometer reading:
VacuTect Test Type:
VacuTect Probe Entry Point:
Pressure Set Point:
Tank water level in inches:
Water table depth in inches:
Determined by (method):
Result:
COMMENTS
Bubble
Make: FE PETRO
Ullage Model: MLD
SIN: BJ256
Open time in sec: 8.00
Holding psi: 30
Resiliency cc: 240 NOT
Test leak rate ml/m: 189.0 TESTED
Metering psi: 10
Calib. leak in gph: 3.00
Results: PASS
COMMENTS
NOT
TESTED
Material:
Diameter (in):
Length (ft):
Test psi:
Bleedback cc:
Test time (min):
Start time:
End time:
Final gph:
Result:
Pump type:
Pump make:
COMMENTS
DW FIBERG
2.0
175.0
NOT
TESTED
NOT
TESTED
NOT
TESTED
NOT
TESTED
PRESSURE
FE PETRO
Impact Valves Operational: YES
Printed 09/08/200410:01
MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6. 7, Health and Safety Code; Chapter 16, Division 3 Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. If more than one monitoring system control panel is installed at the facility, a separate
certification or report must be prepared for each monitorinq system control panel by the technician who performs the work. A copy of this form must be provided to the tank
system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A General Information
Facility Name: CHEVRON 206561
Site Address: 3360 PANAMA LN.
City: BAKERSFIELD
Contact Phone No: 396-7047
Date otTesting/Service: 08/27/2004
CA
Zip: 93304
Facility Contact Person: MANAGER
Make/Model of Monitoring System:VEEDEROOTTLS350 Work Order Number: 3136161
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment inspected/serviced
Tank 10: 1-91 Tank ID: 2-89
X In-Tank Gauging Probe. Model: MAG-2 ex In-Tank Gauging Probe. Model: MAG-2
~ 409 IX1 Annular Space or Vault Sensor. 409
X Annular Space or Vault Sensor. Model: Model:
~ 352 -
X Piping Sump/Trench Sensor(s). Model: ..:::. Piping Sump/Trench Sensor(s). Model: 352
:;::: 352 352
X Fill Sump Sensor(s). Model: Fill Sump Sensor(s). Model:
=::
X Mechanical Line Leak Detector. Model: MLD v Mechanical Line Leak Detector. Model: FX1V
= Electronic Line Leak Detector. Model: =
Electronic Line Leak Detector. Model:
X Tank Overfill/High-Level Sensor. Model: MAG-2 X Tank Overfill/High-Level Sensor. Model: MAG-2
= Other (specify equipment type and model in Section E on page 2). Other (specify equipment type and model in Section E on page 2).
-
Tank ID: ;'\-1'\ { TanklD:
X In-Tank Gauging Probe. Model: MAG-2 -
== In-Tank Gauging Probe. Model:
X Annular Space or Vault Sensor. Model: 409 Annular Space or Vault Sensor. Model:
X Piping Sump/Trench Sensor(s). Model: 352 Piping Sump/Trench Sensor(s). Model:
~ Fill Sump Sensor(s). Model: 352 -
X Fill Sump Sensor(s). Model:
::;::: Mechanical Line Leak Detector. Model: MLD -
~ Mechanical Line Leak Detector. Model:
- Electronic Line Leak Detector. Model: =
Electronic Line Leak Detector. Model:
X Tank Overfill/High-Level Sensor. Model: MAG-2 - Tank Overfill/High-Level Sensor. Model:
==
Other (specify equipment type and model in Section E on page 2). - Other (specify equipment type and model in Section E on page 2).
- -
ulspenser IU: 1/2 Dispenser ID: 3/4
Qg Dispenser Containment Sensor(s) Model: 322 Xl Dispenser Containment Sensor(s) Model: 322
ŒJ ShearValve(s). 1] Shear Valve(s)
D Dispenser Containment Float(s) and Chain(s). I Dispenser Containment Float(s) and Chain(s).
Dispenser ID: 5/6 Dispenser ID: 7/8
[K] Dispenser Containment Sensor(s) Model: 322 "Xl Dispenser Containment Sensor(s). Model: 322
~ Shear Valve(s). ~ Shear Valve(s).
n Dispenser Containment Float(s) and Chain(s). I Dispenser Containment Float(s) and Chain(s).
Dispenser ID: Dispenser ID:
o Dispenser Containment Sensor(s) Model: I Dispenser Containment Sensor(s). Model:
~
D Shear Valve(s). ::J Shear Valve(s).
o Dispenser Containment Float(s) and Chain(s). =:J Dispenser Containment Float(s) and Chain(s).
· If the facility contains more tanks or dispensers, copy this form. Include information for every tank and dispenser at the facility.
C. Certification
I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines.
Attached to this certification is information (e.g manufacturers' checklists) necessary to verify that this information is correct.
and a Site Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached
a copy of the (Check all that apply): rJ System set-up ~ Alarm history report
tId//~
Technician Name (print): ALBERT J. QUEIROS
Certification No.: 000-00-2808
Signature:
License. No.:
Testing Company Name: Tanknology
Site Address: 8900 Shoal Creek, Bldg. 200 Austin, TX 78757
Phone No.: (800) 800-4633
Date otTesting/Servicing: 08/27/2004
Monitoring System Certification
Page 1 of 3
Based on CA form dated 03/01
Monitoring System Certification
Site Address: 3360 PANAMA LN.
Date of Testing/Service: 08/27/2004
D. Results of Testing/Servicing
Software Version Installed: 112.02
Complete the following checklist:
I [Xl Yes DNa' Is the audible alarm operational?
o Yes DNa' Is the visual alarm operational?
o Yes DNa' Were all sensors visually inspected, functionally tested, and confirmed operational?
o Yes DNa' Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not
interfere with their proper operation?
o Yes DNa' nN/A If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational?
o Yes DNa' ON/A For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate positive
shut-down? (check all that apply) Œ] SumplTrench Sensors; Œ] Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? Œ] Yes ONo
o Yes DNa' DN/A For tank systems that utilize the monitoring system as the primary tank overfill warning device (Le.: no mechanical
overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill points(s) and operating
properly? If so, at what percent of tank capacity does the alarm trigger? 95 %
DYes' 0Na Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the
manufacturer name and model for all replacement parts in Section E, below.
DYes' 0Na Was liquid found inside any secondary containment systems designed as dry systems? (check all that apply) o Product;
D Water. If yes, describe causes in Section E, below.
o Yes DNa' Was monitoring system set-up reviewed to ensure proper settings? Attach set-up reports, if applicable.
o Yes DNa' Is all monitoring equipment operational per manufacturers' specifications?
. In Section E below, describe how and when these deficiences were or will be corrected.
E. Comments:
Page 2 of 3
Based on CA form dated 03/01
Monitoring System Certification
Site Address: 3360 PANAMA LN.
Date of Testing/Service: 08/27/2004
F. In-Tank Gauging I SIR Equipment
~ Check this box if tank gauging is used only for inventory control.
o Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
ŒJves DNo' Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
ŒJves DNo' Were all tank gauging probes visually inspected for damage and residue buildup?
ŒJves DNo' Was accuracy of system product level readings tested?
ŒJves DNo' Was accuracy of system water level readings tested?
ŒJVes DNo' Were all probes reinstalled properly?
ŒJyes DNo' Were all items on the equipment manufacturers' maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
G. Line leak Detectors (llD) :
D Check this box if LLDs are not installed.
Complete the following checklist:
o Yes DNo' DN/A For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
(Check all that apply) Simulated leak rate: 0 3 g.p.h 0 0.1 g.p.h 00.2 g.p.h
ß]Yes DNo' Were all LLDs confirmed operational and accurate within regulatory requirements?
Œ]Yes DNo' Was the testing apparatus properly calibrated?
o Yes DNO' DN/A For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
DYes DNo' Œ] N/A For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
DYes DNo' 0N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
DYes DNo' 0N/A For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test?
DYes DNo' 0N/A For electronic LLDs, have all accessible wiring connections been visually inspected?
o Yes DNo' Were all items on the equipment manufacturers' maintenance checklist completed?
* In the Section H, below, describe how and when these deficiencies were or will be corrected.
H. Comments:
Page 3 of 3
Based on CA form dated 03/01
SB-989 SECONDARY CONTAINMENT SUMMARY RESULTS
1-" Tanknology
TEST DATE:08/27/2004
BREA
SAM STEVENSON
909-765-6536
CA
92822
WORK ORDER NO.: 3136J.6J.
SITE: CHEVRON 20656J.
3360 PANAMA LN.
BAKERSFIELD CA 93304
CLIENT: CHEVRON U.S.A.
P.O. BOX 2292
J.45 S. STATE COLLEGE BLVD.
Piping Interstital Tests
1
2
3
OPW
OPW
OPW
Pass
Fail
Pass
Tanknology representative: JERRY BELLOLl
Services conducted by: ALBERT J. QUEIROS
~
t1d/!~
:t.DJnImoIogy Test Date: 08/27/2004
Work Order: 3136161
SECONDARY CONTAINMENT TEST RESULTS
SUMP TESTS
Type Tank or Disp Manufacturer Model or Diam./WidthlLength Depth Test Method Start Initial Level Finish Final Pass/
# Material (") (") Time Level Change Time Result Fail
Spill Container 1 OPW Plastic 12" 5 GAL 10:50 8" FROM NONE 11:20 8" FROM Pass
Spill Container 2 OPW Plastic 12" 5 GAL 10:50 8" FROM 7" 11:20 1" FROM Fail
Spill Container 3 OPW Plastic 12" 5 GAL 10:50 8" FROM NONE 11:20 8" FROM Pass
Comments: Sl)SPECT PLUS BUCKET IS NOT TIGHT WHERE PLASTIC FLEX, BOLTS TO BOTTOM PLASTIC DISH.
TEST DATE: 08/27/04
CLlENT:CHEVRON U. S .A.
>ó<·.SITE DIAGRAM
~~ Tånknology
8900 SHOAL CREEK, BUILDING 200
AUSTIN, TEXAS 78757
(512) 451-6334
FAX (512) 459-1459
WORK ORDER NUMBER3136161
SITE: CHEVRON 206561
CCX) VENTS
§ § § ( ~ ~ )
PLU UL SUP
S
~ ~ ~ ( )
CD CD CD ~ ~
E
~S CHEVRON
#206561
Printed 09/08/2004 10:01 SBOWERS
Work Order:
3136161
CHEVRON I.BA CSI-1849
336a PANAMA LANE
BAKERaFIELD CA.93:J04
SS-2CS5IPH-396-7047
AUG 27. 2004 a:02 AM
SYST'Ð'I STATlS JŒPCRT
- - - - - - .- - - - - -
ALL FUNCTIONS MGRI'W.·
----- SENSOR ALARM -----
L 3: 92-£TP alt1P
BTP SlI1P
LIQUID WARN] ~
~OO 27. 20(14 9:54 AM
----- BEM30R AlARM -----::..
L 3:92--aTP BlJ'IP
8TP SlJ"IP
LIQUID ~NING
AUG 27. 2004 B:54 AM
----- SEI'8>R ALARI'I -~--
L 1: 92-ANN~R
MNOl.AA SPAc£
FUEL AI.ARh
AUG 27. 2004 8:56 AM
----- SEHSOR ALARM -----
L 2:92-FILL SlJ1P
PIPltoe SlI1P
HIGH LIQUID ALARM
AUG 27. 2004 a:59.AM
----- SENSOR ALARM -----
L 2:92-FILL BUMP
PIPI NG SlJ'1P
HIGH LIGUID ~
AUC '7. 2004 8:59 AM
----- SEIÐ>R AtAøt ___h
L 2:92-FIll. SlI1P
PIPIMG SlJ1P
HIGH LIGUID AlARM
AUG 21. 2004 a~59 AM
----- OENSOR ALARM -----
L 2: 9:?-P I 11. SUl'1Þ
PIP!r1G SI.t1l'
LIQUID LW!NING
A~ 27. :~004. 9:00 At!
. ----- SENSOR ALARM -----
L 2:92-FILL SUMP
PIP! IG Slt1P
H[GH LIQUID ALARM
. AUG 27. 2004 9: 00 AM
----- SENSOR ALARH -----
L 7:B7-ANNIJLAR
ANNlJ1.AR SPMCE
Fl./EL ALARM
AUG 21. 2004 9:01 AM
----- SENSOR ~ -----
L B:B7-FILL SlI1P
PIPItç 81!1P
HIGH LIQUID ALARM
AUC 27. '2004 9:02 AM
----- SENSOR ALARM ---__
L S:S7-FILL SUHP
PIPING SU1P
LIQUID WARNING
AUG 27. 2004 9:03 AM
----- SE~R ALARM -----
L e:S7-tILL SUMP
PIP I NO St.t1P
HIGH LIQUID ALARM
AUG 27. 2004 9:03 AM
---- IN-TANK ALARM -----
T ] :SUJ>RÐ1E
PROBE OUT
AUG 27. 2004 9:04 AM
--- I "'-TANK ALARM ---__
T I :SlIÞlID'IE
I NVAl. ID FUEL LE:VEt.
AUG 27. 2D04 9:D4 AM
----- SENSOR AlAJi!M
L 4:S9-ANNULAR -----
~NfoUl.AR SP~ÇE
FUEL AlAfìt1
AUG 2_. 2004 9:0B AM
----- SENSOR ALARM -----
L 5:S9-PILL SUMP
PIPlfC BlJ1P
HJGH LIQUID AlARM
AVO 27. 2004 9:10 AM
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757
Work Order:
31.361.61.
~:.
----- SENSOR ALARM -----
'L 5:a9-FtLL S\l'U>
¡. IP n~ BlJ'IP
LIQUI D ~NI NG
AUG 27. 2004 9:10 AM
----- SENSOR AIARI'1 ----
L 5:89-~tLL SUMP
PIPING SLt1P
HIGH LIQUID ~
AUG 27. 2D04 9aD Ar1
..,
IN-TANK ALARM -----
T 3: UNLEADED
PTlOBE OUT
AUQ 27. 2004 9:14 AM
.---- IN-TANK AIARI'1 -----
T 2:PLlS .
DELIVER't NBEDEI>
AUG 27. 2004 9=15 AM
---- IN-TANK ALARM -----
.T 2:PLlJB
1.QI,¡J PRODOOT A1.ARf'I
.Aut·2? 2004 9:15 AM
õ','
---- IN-TANK ALARM -----
T 2¡PUB
I NVAL I D FUEL LEVEl.
AUG 27. 2004 9:&5 AM
..'
~-::_J~-TAÑK ALARM -----
---- IN-TANK ~ ----~
T 3: UNLEADED
, HICH W\TER AI.ARP1
AUG 27. 2004 9:19 AM
---- IN-TANK ALARM -----
T I :SUPRE'fE
HIOH WATER WARNHC
AUG 27. 2004 9~25 AM
IN-TANK ALARM -----
T 3: UNLEADED
HIGH WATER W\RNING
AUG 27. 2004 9:18 AM
---- IN-TANK ALARM -----
T 2:PLlJS
HIGH WATER ALARM
AUG 27. 2G04 9:25 AM
---- IN-TANK ALARM -----
T ~: UNLEADED
HIGH PRODOCT ALAIm
AUG 27. 2004 9:19 AM
---- IN-TANK ALARM -----
T 2:PLtJB
HIGH WATER '*'RNl NG
AUG 27. 2004 9:25 AM
T 1 :SUPRÐ1E
I NllENTORY I NC'REASE
I~E START
AUC 27. 2004 9:04 AM
VOLU'1£ . - HIS I GALS
WATER = 0.00 I MCHES'
TEMP ~ 86.2 DEe F
---- IN-TANI( ALARM -.----
T 1 :SUPRÐ1E
HI GH PRODlXrt ALARM
AUG 21. 2004 9:31 AM
I NCRFAsE END
AUG 27. 2004 9:;?2 ~
VOLlt1E ~ I 0025 GALS
WATER = 8.16 l~HES
TÐ1P .. 86.1 DEe F
l' 3: UNLEADED
I NVENTORV I tcREASE
I NCRFASE START
AUG 27. 2004 9:19 AM
VOLUME .. 9879 GALS
WATER .. 6,15 ItcHES
TÐ1S> = 85 . B DEe F
GROSS INCREASE- 8144
1'0 NET I NCREASE- 7995
1 NCREASE END
AUG 27. 2004 9~39 AM
---- IN-TANK ALARM -----
T 1: SlIPRÐ't1':
tit GH I*'TER AI..A:RI'I
AUG 27. 2Q04 9:25 AM
VOLIJ'IE
WATER
TE11P
.. 10907 GAlS
.. 0.00 INCHES
.. 81.6 DEG F
GROSS INCREASE- 929
TO NET INCREASE- 898
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757
Work Order:
3136161
:S
T 1: SUPREME
INVENT<»lY I~
J NCREAS~ START
AUG 27, 20Q4" 9:26 AM
IJOLlME
WATER
'CEMP
'" 10025 GAtS
.. 8.16 INeMES
.. '18.9 DEG F
I NCREASE END
AUG 21. 2004 9:51 AM
VOLlt1E
,*,TER
TEMP
.. I 0804 GALs
.. 0.00 INCHES
.. 80.~DEG F
GROSs U£Rf"ASEz 779
TC 'NET INCREASE= 755
T 3: Ut4.EAD£D
I NVENTOR'/ INCREASE
I NCREPiS£ START
AUG 27. 2004 9:52 AM
VOLLttE .. 8R51 GALS
WATER z 0 . DO I NCHEB
TEMP Ii 91-.7 ·DEG F
11'CRE'llSE BND
AuG 27, 2004 IC:09 AM
VOLlJ'€ .. 9203 GALS
WATER .. a.DD INCHES
TEMP ... 91.9 DEG F
GROSa t tcRF.ASE~ 352
1C NET I NCRFÞBE- 343
--. " smSOR ALARM ----..
L b:l:r9-BTP SUMP·
ST1' S1.I11'
LIidU1D w.:\RNI NG
AOO 27. 2004 10:23 AM
T 2:PU.e
I MIENTOR'o' [NCR£ASE
1 NCREASE START
AUG 27. 2004 JO:07 AM
VOLU1E .. 7992 GALS
WATER = 0.00 I~HES
TEI'IP .. 93. 1 DEG F
t tCREASE END
AUG 27. 2004 10:23 AM
VOLlI'Œ .. 9506 GAlß
WATER .. 0.00 INCHES
TEMP .. 92.8 DEG F
GROSS INCREASE.. 1544
- TC NET INCREASE~ 1509
----- SENSOR ~LARH -----
L 6:S9-5TP Sl.MP
BTP SLt'IP
LIQUJ II WAJi!N I /loG
AUG 27. 2Q04 ID:23 AM
---- IN-TANK ALARM -----
T 1 :SUPREME
HIGH PRODlCT AlARI'I
AUG 27. 2004 10:34 AM
IN-TANK ALARM -----
T 2:PLlS
HIGH PRODOCT ALARI1
AUG 27. 2004 10:40 AM
---- IN-TANK ALARM -----
T 2:PLlJS
OVERFIlL ALARI'I
AUG 27. 2004 10:40 AM
---- IN-TANK ALARM -----
T 1 :SlWRÐ'IE
OVERF ¡ LL AUlI<M
AUG 27, 2004 10:40 AM
---- I N-TANK ALARM -----
T 3:U~LEAD£D
HIGH PRODUCT ALA~
AUG 27. 20D4 10:40 AM
---- IN-TANK ALARM -----
T 3: UNLEADED
OVERFIU. AUœ1
AUG 27. 2004 10:41 AM
---- IN-TANK ALARM -----
T 2 :PLlB
DELIVERY NEEDED
AUG 27. 2004 JO:44 AM
---- IN-TANK ALARM -----
T 1 :SUPRÐ1E
DELIVERY NEEDED
AUG 27. 2004 20:44 AM
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757
Work Order:
31.361.61.
..'
---- BEteOR AI..MM ----
LIO:DISI>ENSER PAN 1-2
DISÞEHBER PAN
HIGH LIQUID ~
AUG 27. 2004 10:4& AM
---- 1 N-TANK ALARM ----
T 1 :SlJPRÐ1E -
LOW PRODUCT ALAR1
Aoo 2'1. 2004 10:49 AM
. .
IN-TANK ALARM -----
T 2 ~PUB
LW PRODUCT AUØI
Al.C 27. 2004 10:49 AM
IH-TArÐC AlAJ!'! -----
T::): UNLEADED
DELIVER\' NEEDED
Al.C '1:1. 2004 10: 49 AM
T 2:PLlS
1 M1EÞITORY I HCREASE
I NCREABE STAJIT
RUG 2'1. 2004 10:26 AM
VOLlI'IE .. 9536 GALS
~TER . 0.00 I NCHEB
TEMP . 93.7 DEG F
INcRFASE END
AUG: 27. 2094 I 0: 56 AM
VOLlt'IE .. 11706 GAUJ
~TER .~ 0.00 INCHES
T£Mp . 94.2 DEe F
GROSS INCREASE- 2170
TC NET I~" 2115
T I:SUPREME
II'NENTOIi\' J NCREASE
] ~ SfART'
AUG 27. 2004 10:2~ AM
VOLlI"IE F 10144 GALS
WATER ~ 0 .00 INCHES
TEMP .. 79.9 DEG F
I NCREA6E END
AUC 27. 2004 10=56 AM
VOLU1E .. L 1834 GALS
WATER .. 0 . 00 1 NCHES
TEI'IP .. 81. e DEe F
GROSS INCREASE'" 1£.90
TO mrr INCREASE" 1651
T 3:UNU:ADED
J r+JENrORY ¡ NCREASE
1 NCJæASE START
AUG 27. 2004 10:40 AM
VOLlt'IE - 9203 GAlß
~ER .. 0.00 INCHES
TEI1J> = 95.:2 DEO F
I NCREASE END
AUG 21. 2004 10:57 AM
VOLlJ'IE .. n 41 4 GALS
~TER .. O.G[I INCHES
TEMP = 95.2 DEG F
GROSS INCREASE- 22\1
TC NET I tf::REASE" 2156
---- I N-TANIC ALARt1 -----
T 3:UNLEADED
LOI.I PRODUCT ALARI1
AUG 27. 2004 10:57 AM
---- IN-TANK AlARM -----
T 2:PLlJB
PROBE OIIf
AUG 27. 2004 10:51 AM
IN-TANK AU\RH ----
T 2:PLU8
LOLl TB1P ~NI toG
AUG 27. 2004 10:58 AM
----- SENSOR ALARM ----
L 5:S9-FILL SUMP
P¡P¡~ SLt1P
SENSOr;! OUT AiARf'1
AUG 27. 2004 10:59 AM
---- IN-TANK ALARM -----
T 1 :SUPRÐ1E
PROBE OUT
AUG 27. 2004 10:59 AM
---- IN-TANK ALARM -----
T t :SUPR8'1E
INVALID Fua. LEVEl.
AUG 27. 2004 11:00 AM
----- BENSO~ ALARM -----
L 2:92-PILL SUMP
PIPING SlÏ"IP
HIGH LIQUID ~L~RH
AUG 27. 2004 11:00 AM
~
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757
....¡-. I}
Work Order:
3136161
ï:-2~9~~~R8~ -----
PIPING SLttP
BEteOR OUT A1ARI1
Auç 27, 2004 11:00 AM
---- JN~TANK AlARM -----
T ;); UNL£AtIED
PROBE OUT
AUG 27. 2004 11:05 AM
. ----- S£1t3OR AI.ARf1 -----
L 8:S'l-FILL StI1P
PIPIt«; Sll1P
BEtÐOR our A1.ARI1
ROO 27, 2004 11 i 07 fV'I
T 2:PLlS-
INVENTORY 1 ~~
t~ START
AUG 27. 2004 10:57 AM
VOLlI1E
WATER
TÐ1P
.. 707 GAlß
.. 0.00 ItcHES
.. 97.7 DEG F
I NCREASE END
AUG 2'. 2D04 11:16 AM
VOLI.t1£ ... 31:161 GALS
WATER '" 0.00 I fICHES
Ta1P .. 91.0 DEO F
GROSS IICREASE- 3154
TC I'ŒJ' I r«;'REASE- 3096
T 1 ;SUPRÐ1E
J NV£NTORY J flCJŒASE
J I'CRF.AsE START
AUG 27, 2004 10;59 AM
VOLltIE .. 633 GAlß
~ .. Q.Oß ltc~
· <:nr '" 82 .:i DEG ~
I NCR£ASE END
AUG 27. 2Q04 11:16 AM
VOLlJIŒ ~ 2714 GI\LS
~TER ~ 0.00 INCHES
TEMP - 82.9 DEG F
GROœ INCREASE'" 2081
TC NET It£RFABE.. 204'1
CHEVRON USA CSI-1849
3361:1 PANAMA ~NE
BAKERSFIElD CA.93304
SS-20651PH-396-7047
AUG 27. 2004 11:29 AM
B"ISTEM STATIJ3 REPQRT
- - - - - - - - - - - -
ALL FUtcTIOtoS NORtIAL
Tanknology-NDE 8900 Shoal Creek, Building 200 Austin, Texas 78757