BAKERSFIELD FIRE DEPARTMENT
OFFICE OF ENVIRONMENTAL SERVICES
INSPECTOR STEVE UNDERWOOD
900 TRUXTUN AVE., STE. 210
BAKERSFIELD, CA. 93301
Test Date: 09/26/2007
Order Number: 3155161
Dear Regulator,
Date Printed and Mailed: 10/09/2007
Enclosed are the results of recent testing performed at the following facility:
7-ELEVEN #26599, MKT 2133
6529 EAST BRUNDAGE LANE
BAKERSFIELD, CA. 93307
Testing performed:
Dynamic Pressure Source
EVR-Stage I Pressure Integrity Drop Tube
Liquid Removal tests
Stage II pressure decay tests
Sincerely,
~ c>~ ~~~
Post•It'"routing request pad 76gq
Dawn Kohlmeyer ROUTING - ~~~
Manager, Field Reporting Please REQUEST
READ To
HANDLE r -'~ l 1 ~e ' e`er
^ APPROVE 'W''-\\ ^• - ~-f'L.
and ~.iQ~
^ FORWARD
^ RETURN ~ ~~ ^~
KEEP OR DISCARD ~~ C
^ REVIEW WITH ME t ~~
t Gars I'I ~/~-(2~
Date ~ t 2D
- From ~'
SAN JOAQUIN VALLEY AIR POLLUTION CONTROL DISTRICT
TP-201.4 Dynamic Back Pressure
Source Information FACILITY PARAMETERS
GDF Name and Address District Inspector Phase II System Type
7-ELEVEN #26599, MKT 2133 ABSENT Phase II System Type
6529 EAST BRUNDAGE LANE Device Type Used Balance
MANOMETER Assist
BAKERSFIELD,CA 93307 Hirt
Phase I System Type Hasstech
Permit # S-2138-1-6 EVR Healy
E.O G-70-52 2 Point Other
Coaxial Manifolded? YO or N
Date of Last Calibration: 02/12/2007 Type of Test: Wet / Dry Leak Check: Pass / Fail
Dynamic Back Pressure, Inches H ~J
Nozzle Grade Result
40 CFH 60 CFH 80 CFH
1 E.W.4015 ALL .05 .24 .42 PASS
2 E.W. 4015 ALL .09 .25 .55 PASS
3 E.W. 4015 ALL .09 .27 .41 PASS
4 E.W. 4015 ALL .08 .27 .46 PASS
Test Conducted By: Test Company: Date of Test:
TIMOTHY COULTER Tanknology 09/26/2007
Signature: Confirmation # Tester Certification #
~'~~
07-8811
T-6037
San. Joaquin Valley Unified Air Pollution Control District
;, ~ Pressure Decay Test TP201.3
Confirmtion. No.
Permit No:
Site Name:
Address:
07-8811
S-2138-1-6
7-ELEVEN #26599, MKT 2133
6529 EAST BRUNDAGE LANE
BAKERSFIELD
Phone: 661366-4788
Phase I System? EVR / 2 / Coaxial
Phase II System? BALANCE / ASSIST /OTHER
Total Number of Nozzles: 4
Nozzles for Tank # 1: 4
Nozzles for Tank # 2: 4
Balance "Nozzle End" hoses must be drained prior to test.
Testing Company
Name: TANKNOLOGY
Address: 41785 Enterprise Circle S Suite D
Temecula Cp 92590
Phone: (951)676-4060
Tanks Manifolded? Yes
Work Order: 3155161
Nozzles for Tank # 3: 4
Nozzles for Tank # 4:
Number of hoses over 100m1:
0
Tank Information 1 2 3 4 All
1. Product Grade 87-MAIN 87-SYPHON 91
2. Actual Tank Capacity, gallons 9989 10000 10000 0 29989
3. Gasoline Volume, gallons 7946 7926 3856 0 19728
4. Ullage, (V) gallons (line #2 minus line #3) 2043 2074 6144 0 10261
5. Start Time 0958 1030 1030
6. Initial Test Pressure, inches H2O 2.00 2.00 2.00
7. Pressure after 1 minute, inches H2O 1.95 1.98 1.98
8. Pressure after 2 minutes, inches H2O 1.90 1.95 1.95
9. Pressure after 3 minutes, inches H2O 1.85 1.93 1.93
10. Pressure after 4 minutes, inches H2O 1.90 1.90
11. Pressure after 5 minutes, inches H2O 1.87 1.87
12. Allowable Final Pressure (See table 1A or 16) 1.86 1.86 1.86
13. Pass /Fail PASS
Nitrogen introducing point. Phase I vapor coupler or Phase II vapor riser: Phase I / Phase I
Record Vapor Coupler Integrity Test Assembly pressure after 1 minute: 2.10
What type of pressure device used : Incline Manometer ~ Mechanical ~ Digital -must do drift tes
7-31-07 Enter Calibration date for pressure device (90 days ).
.07 Enter initial tank ullage pressure (Vent if over 0.5 in, w.c. )
3 Enter flowmeter rate, F (Must be 1 to 5 CFM ).
~= V
3:49 Enter Calculate ullage fill time, t2.
3:17 Enter actual fill-time. [1522] F
.00 Enter ending value of drift test (Must be 0.01 in. w.c. or less ).
Tester: TIMOTHY COULTER
.~-.6~
Signature:
Tester ID: T-6037
Test Date: 09/26/2007
San Joaquin Valley Air Pollution Control District
TP 201.1 C/D Drop Tube Tests Report Form
Permit Number: S-2138-1-6
Site Name: 7-ELEVEN #26599, MKT 2133
Address 6529 EAST BRUNDAGE LANE
City BAKERSFIELD Zip93307
•E
Test Company:
Technician:
Test Certification:
Calibration Date of Pressure Device
•1
TANKNOLOGY. INC.
TIMOTHY COULTER
07/31 /2007
Drop Tube Drain Valve and Overfill Prevention Device Pressure Integrity Test
^ Strai ht Dro Tube ^X Overfill Prevention Device
Drop Tube Drain Valve Pressure Test
Flow Rate 80 ml/min Drop Tube Overfill Prevention Device Tes
Flow Rate 200 ml/min "Corrected" Overfill Device Leak Test Result
Time to reach 2 Drain Valve Final Time to reach 2 Overfill Leak Final Overfill Minus Equals
in. H2O at SOmI Leak Rate' Pressure in. H~ at 200m1 Rate' Pressure Device Leak
Rate Drain Valve
Leak Rate Corrected Leak rate
for Overfill Device
Tank: Grade: ml/min in H~ ml/min in H2O ml/min ml/min ml/min
1 87-M 6 SEC 0.00 2.05 122 SEC 0.00 2.05 0.00 0.00 0.00 PASS
2 87-5 7 SEC 0.00 2.05 136 SEC 0.00 2.05 0.00 0.00 0.00 PASS
3 91 5 SEC 0.00 2.05 146 SEC 0.00 2.05 0.00 0.00 0.00 PASS
Signature of Technician:
Test Date: 09/26/2007
Work order: 3155161
y
LIQUID REMOVAL TEST
TP CARB 201.6
Testing Results
Facility Name: 7-ELEVEN #26599, MKT 2133
Facility Address: 6529 EAST BRUNDAGE LANE,
Test Date: 09/26/2007
Test Unit S#:
System Type: BALANCE
Page 1
Work Order: 3155161
Disp # Grade GPM Wall Fuel Gallons Post Fuel
in hose Liquid
Removal Pass/
Fail
Retention
1 ALL 0.000 0.000 0.000 0.000 0.000 P
2 ALL 0.000 0.000 0.000 0.000 0.000 P
3 ALL 0.000 0.000 0.000 0.000 0.000 P
4 ALL 0.000 0.000 0.000 0.000 0.000 P
Technician: Timothy Coulter
Signature:
~~~.-
TANKNOLOGY
41785 Enterprise Circle S Suite D
Temecula CA 92590
(951)676-4060
~~
s~ ,
TEST DATE: 09/26/07
CLIENT:7-ELEVEN, INC.
SITE DIAGRAM
- 7an
8501 N MOPAC EXPRESSWAY, SUITE 400
AUSTIN, TEXAS 78759
(512)451-6334
FAX (512) 459-1459
WORK ORDER NUMBER3155161
SITE:7-ELEVEN#26599, MKT 2133
L8
L2 L4
4 3
STP ~ O OF I REG
1
L7 L5
P/S ~ O O I REG/
~ SLV
L3 L6
2 ~ STP ~ O O I PREM
1
L1
DROPTUBE FLAPPER VALVES
N
E AIR/
H2O
58
rn~
~~
i~
1
1~
1
~~ VENTS
Printed 10/09/2007 08:28 ACRAMER