DATE: January, 2006
We herewith enclose a copy of an automatic fire -sprinkler system check report for
the following facility:
F®untain Plaza
600 C®ffee R®acl
Bakersfield, CA
to the party checked below:
Owner: 600 Coffee Road Partners
C/o L & S Realty Group
4419 Van Nuys Boulevard, #203
Sherman Oaks, CA 91403
Fire Dept:
Thank You
RLH Fire Protection
File: 7256
cc:
Bakersfield City Fire Department
Fire Prevention Division
900 Truxtun Avenue, Suite 210
Bakersfield, CA 93301
[n3 [1_.~ f ~l [~j [i «cy l'- ~i' ~~ ~ c~ c~ f~ ii c~~ ~n~
310 30th Street Bakersfield, CA 93301 Voice 661.322.9344 Fax 661.322.6816 License# 777717
J~~} - Y -.
C:a~>ir~s-a, ra~t~~i~t=s<~, 8r ~{-~~ ~tic~rs ~r~~ ta~.~~x`€€~ ~~f ="°~r~ ~~.~a i~~;~`e•~:a~ ~~;-~~~:r~~
_.. _:~C<.~~ .
SYS'TEl®'i C1~IECK REP®RT F®R1iR
`VET POPE SPRflN;KEER SYS'TElVIS (Title fl9, Sec. 904.5
Facility: Fountain Plaza Date: 01/31/06
Address: 600 Coffee Road MC#: 7256
Bakersfield, CA
Reviewer: R. Gentry Notes: 5 Year Service 10/25/2004
FIRE DEPARTMENT CONNECTION YES N/A NO
1: Are fire de artment connections free of obstructions? X
2. Are fire de artment connections in good condition? X
3. Are couplings free and rotate freely? X
4. Do cla ers move freel and close com letel ? X
5. Are gaskets in place and in good condition? X
6. Are ca sin place? X
7. Are inlets identified with a si n? ~ X
CONTROL VALVES
1. Are control valves free of leaks? X
2. Are control valves secured in open position? X
3. Are control valves free of visible or ext.. obstruction? X
GAUGES
1. Are gauges in ood condition? X
2.. Are gauge valves turned on? X
3. S stem ressure? Record 88 P. S. I. X
4. Su pl pressure? Record P. S. I.
RISER
1. Is riser free of leaks? X
2. Is riser bracin ro erl secured and free of dama e? X
3. Is riser free of visible or exterior dama e? X
4. Water motor and on test satisfactory? Electric Bell X
PIPING
1. Is accessible i in free of dama e? X
2. Is pi in free of visible or exterior obstructions? X
SPRINKLER HEADS
1. Ares rinkler heads free of leaks and corrosion? X
2. Is all stora eat least 18" below deflectors? X
3. Are sprinklers installed in proper osition? X
4. Are extra heads and pro er orifice wrench available? X
5. Are extra heads of the proper size and temperature? X
WATER FLOW TEST
Water Pressure City PSI Tank PSI Fire Pump PSI
Test Pi a Located Size Pie Pressure Before Flow Press Press. After
Riser 2" 88 55 75