HomeMy WebLinkAboutSPRINKLER REPORTUC ONE, LLC
9100 MING AVENUE -
./
~.::. .
.;;f,;`; Design, Installation, Inspection and Repair of Fire Sprinkler Systems
C ~? I ~ ~ i ~ .~.__ ~_
~_ _, ~~ ~ ~G~~P~go~~d dad~~~orr~ p~~of~o~ ~r~o~~
,\
v
DATE: January, 2006
We herewith enclose a copy of an automatic fire sprinkler system check report for
the following facility:
UC ONE, LLC
9100 Ming Avenue
Bakersfield, CA
to the party checked below:
Owner: ~JC ONE, LLC
C/o Premier Management
P.O. Box 9116
Bakersfield, CA 93389
Fire Dept:
Thank You
RLH Fire Protection
File: 7298
cc:
Bakersfield City Fire Department
Fire Prevention Division
900 Truxtun Avenue, Suite 210
Bakersfield, CA 93301
310 30th Street Bakersfield, CA 93301 Voice 661.322.9344 Fax 661.322.6816 License# 777717
.+ '\
~~~ ~; r=,~;~` \ Design, Installation, Inspection and Repair of Fire Sprinkler Systems
z:. ..._..... ,
./ ~ ~~ o d~
\i..,_ _ n C§~1,~\Ll~l ~U~~~OG ~OC~'i~G'Gu7i OG'G '~c~GN()f~~C~ ~ C'CO~IC;
Y SYSTEM CHECK REPORT FORM
WET PIPE SPRINKLER SYSTEMS (Title 19, Sec. 904.5)
Facility: UC ONE, LLC Date: 02/03/06
Address: 9100 Ming Ave. MC#: 7298
Bakersfield, CA
Reviewer: R. Gentry Notes: 5 Year Service 07/12/2005
FIRE DEPARTMENT CONNECTION YES N/A NO
1. Are fire de artment connections free of obstructions? X
2. Are fire de artment connections in ood condition? X
3. Are cou lin s free and rotate freel ? X
4. Do cla ers move freel and close com letel ? X
5. Are askets in lace and in ood condition? X
6. Are ca sin lace? X
7. Are inlets identified with a si ? X
CONTROL VALVES
1. Are control valves free of leaks? X
2. Are control valves secured in o en osition? X
3. Are control valves free of visible or ext. obstruction? X
GAUGES
1. Are au es in ood condition? X
2. Are au e valves turned on? X
3. S stem ressure? Record 90 P. S. I. X
4. Su 1 ressure? Record P. S. I.
RISER
1. Is riser free of leaks? X
2: Is riser bracin ro erl secured and free of dama e? X
3. Is riser free of visible or exterior dama e? X
4. Water motor and on test satisfacto ? Electric X
PIPING
I. Is accessible i in free of dama e? X
2. Is i in free of visible or exterior obstructions? X
SPRINKLER HEADS
1. Ares rinlcler heads free of leaks and corrosion? X
2. Is all stora eat least 18" below deflectors? X
3. Ares rinklers installed in ro er osition? X
4. Are extra heads and ro er orifice wrench available? X
5. Are extra heads of the ro er size and tem erature? X
WATER FLOW TEST
Water Pressure City PSI Tank PSI Fire Pump PSI
Test Pi a Located Size Pie Pressure Before Flow Press Press. After
Riser 2" 90 65 85
l°3 lL. f.~l ~Jn«cy ~[~O~c~c~i~[[OtN
310 30th Street Bakersfield, CA 93301 Voice 661.322.9344 Fax 661.322.6816 License# 777717