HomeMy WebLinkAboutSPRINKLER CHECKS
x
0
0
0
~,
.,~ _ .
~. ..
DATE: January, 2006
We herewith enclose a copy of an automatic fire sprinkler system check report for the
following facility:
9001VIohawk
~akers~ield, CA
to the party checked below:
Owner;
Fire Dept:
Thank You
RLH Fire Protection
File: 7338
cc:
David and Alice Silveira
1609 Sutton Court
Tulare, CA 93274
Bakersfield City Fire Department
Fire Prevention Division
900 Truxtun Avenue, Suite 210
Bakersfield, CA 93301
~n1 ..:::, --~ i " [1 ['r' ~_~ ~;;:. [t' ~ ~ ~~ C~~ ~ I:I <~) [ill
310 30th Street Bakersfield, CA 93301 Voice 661.322.9344 Fax 661.322.6816 License# 777717
_ _
;,~..
,~~ ,
r. ._ yea; ., .. .~-': ". ~ z. ,T .t~'~i~.~tfi'36s ,.. ":L;~ ~s~tE" ~']'~ d""P"i:; :::~_:fi;~~4;.~t~S" ;.:,~~yr ~c'.3"!S,`.~~'
C' .'~:~~ L. ~.-~{~ 1 , ~:~. ~ I~~~ ::,1 'f l~l~ ~~1~ .ICi. iii _1C~ ~ <<.'iL' ~. ,~'~
SYS'TEIVI CI~ECK REP®RT' F®R1VI
WET PIPE SPRINKLER SYS'TElVIS ('Title 19, Sec. 904.5
Facility: Date: 01/23/06
Address: 9001VIohawk 1VIC#: 733
Bakersfield, CA
Reviewer: R. Gentry Notes: Last Five Year Service: 04/11/2003
FIRE DEPARTMENT CONNECTION YES N/A NO
1. Are fire de artment connections free of obstructions? X
2. Are fire department connections in good condition? X
3. Are cou lin s free and rotate freely? ~ X
4. Do cla ers move freely and close com letely? X
5. Are gaskets in lace and in good condition? X
6. Are ca s in place? X
7. Are inlets identified with a sign? X
CONTROL VALVES
1. Are control valves free of leaks? X
2. Are control valves secured in o en osition? X
3. Are control valves free of visible or ext. obstruction? X
GAUGES
1. Are auges in good condition? X
2. Are auge valves turned on? X
3. System ressure? Record 85 P. S. I.
4. Su ly ressure? Record P. S. I.
RISER
1. Is riser free of leaks? X
2. Is riser bracing ro erl secured and free of damage? X
3. Is riser free of visible or exterior damage? X
4. Water motor and (gong) test satisfacto ? X
PIPING
1. Is accessible i in free of dams e? X
2. Is i ing free of visible or exterior obstructions? X
SPRINKLER HEADS
1. Ares rinkler heads free of leaks and corrosion? X
2. Is all stora a at least 18" below deflectors? X
3. Ares rinklers installed in ro er osition? X
4. Are extra heads and ro er orifice wrench available? X
5. Are extra heads of the ro er size and tem erature? X
WATER FLOW TEST
Water Pressure City PSI Tank PSI Fire Pump PSI
Test Pi a Located Size Pie Pressure Before Flow Press Press. After
Riser 2" 85 60 75
I~ ~ f1-~ f~l [~ - ~i r~~ c~ f~ = ~r~ o f'~ c~~~ c~~ f~ ii c~~ ~ri~
310 30th Street Bakersfield, CA 93301 Voice 661.322.9344 Fax 661.322.6816 License# 777717