Design, Installation, Inspection, & Repair of Fire Sprinkler Systems
Bakersfield San Francisco Livermore
October 20, 2008
5 YEAR SERVICE
LIST OF DEFICIENCIES
# 1426
Bakersfield Mazda
3201 Cattle Drive
Bakersfield, CA 93313
lst Floor:
1. Fire Department Connection: Not identified by sign: Add.
2. Parts Counter Small Closet in Sales Office: Escutcheons missing: Replace.
2na Floor
1. West End Office: Heads over spaced: Add Sprinkler Heads.
2. Parts Storage: not free from obstruction: Remove
R L H Fire Protection
3430 Unicorn Rd. Bakersfield, CA 93308 Voice:661.322.9344 Fax:661.322.6816 Lic.# 777717
~ `
. ~.: `,
Design, Installation, Inspectian, & Repair of Fire Sprinkler Systems
_____
Bakersfield San Francisco Livermore
FIVE YEAR SYSTEM CHECK REPORT FORM
WET PIPE SPRINKLER 5YSTEMS (Title 19, Sec. 904.5)
Facility: Bakersfield Mazda Date: 10/20/08
Address: 3201 Cattle Dr. MC#: 1426
Bakersfield, CA 93313
Reviewer: B. Barillas Notes: 3101 & 3201 have 1 FDC
FIRE DEPARTMENT CONNECTION YES N/A NO
1. Are fire de artment connections free of obstructions? X
2. Are fire de artment connections in ood condition? X
3. Are cou lin s free and rotate freel ? X
4. Do cla ers move freel and close com letel ? X
5. Are askets in lace and in ood condition? X
6. Are ca s in lace? X
7. Are inlets identified with a si n? X
CONTROL VALVES
1. Are control valves free of leaks? X
2. Are control valves secured in o en osition? X
3. Are control valves free of visible or ext. obstruction? X
GAUGES
1. Are au es in ood condition? X
2. Are au e valves turned on? X
3. S stem ressure? Record 70 P.S.I. X
4. Su 1 ressure? Record P.S.I X
RISER
1. Is riser free of leaks? X
2. Is riser bracin ro erl secured and free of dama e? X
3. Is riser free of visible or exterior damage? X
4. Water motor and on test satisfacto ? Electric 77 Sec. X
PIPING
1. Is accessible i in free of dama e? X
2. Is i in free of visible or exterior obstructions? X
SPRINKLER HEADS
1. Are sprinkler heads free of leaks and corrosion? X
Is all stora e at least 18" below deflectors? X
3. Are s rinklers installed in ro er osition? X
4. Are extra heads and ro er orifice wrench available? X
5• Are extra heads of the ro er size and tem erature? X
WATER FLOW TEST
Water Pressure (City) PSI Tank PSI Fire Pump PSI
Test Pi e Located Size Yi e Yressure iietore r 1ow rress rress. aiter
Riser 4" 2" Drain 70 55 70
R L I-# F i r~ P~+sa t~~ t i aa ua
34~0 UnicoPn Rd. Bakersfield, CA 93308 Vaice:681.322.9344 Faac:8B1.322.8816 Lic.# TT7717
~, ~c `.
~ ,.
Design, Installation, Inspection, & Repair of Fire Sprinkler Systems
Bakersfield San Francisco Livermore
FIVE YEAR SERVICE REPORT
AUTOMATIC FIRE SPRINKLER SYSTEMS (TITLE 10, SECTION 904.6)
Business Name: Bakersfield Mazda Date: 10/10/08
Address: 3201 Cattle Drive
City: Bakerstield. CA 93313
Reviewer: B. Barlillas Job # 1426
SYSTEM TYPE: Wet
The followinE procedures have been performed in accordance with Title 19:
SAT N/A NOT
SAT
1. Back flush of fire de artment connection. X
2. Post indicator valves, underground gate valves and OS&Y X
valves o erated and examined for dama e.
3. Flow test using inspectors test valve. System's audible device X
activates to within 90 seconds of valve opening (on dry pipe or
delu e s stem, use alarm test line .
4. Main drain test conducted see ins ection re ort . X
5. Test gauge installed at test gauge opening to determine gauge X
accurac .
6. If system supplied by gravity tank, suction tank and reservoirs X
ins ected to insure ro er o eration.
7. If system supplied by pressure tank, air pressure gauge and X
water supply gauge inspected and automatic filling system
o erated durin s stem flow.
8. Supervisory devices on control valves tested to insure proper X
functionin and alarm transmittal to a ro riate location.
9. Fire um s, if an , flow tested. X
10. Pump supervisory devices tested to insure proper functioning X
and alarm transmittal to appropriate location.
11. Delu e, re-action or d i e valve ins ected. X
12. Air com ressor tested. X
13. Quick opening devices tested. X
14. Deluge, pre-action or dry pipe valves trip tested by actuating X
su lemental fire detection s stem.
15. D i e valves located to rotect from freezin . X
COMMENTS:
DATE SERVICE LABEL ATTACHED
1~E~H ~ir~ P~rcit~~~~~aar~
34~0 Unico~n Rd. Bakersfield, CA933Q8 Voioe:~1.322.8Ci44 Faix:B81.322.8816 Lia# 777717