Loading...
HomeMy WebLinkAbout11101 WHITE LN 11111111111 15 IE Appendix VI (Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at hftp://www.waterboards.ca.gov) Monitoring System Certification For Use By All Jurisdictions Within the State of California Authority Cited:Chapter 6.7,Health and Safety Code;Chapter 16,Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work.A copy of f this form must be provided to the tank system owner/operator.The owner/operator must submit a copy of this form to the local agency regulating US systems within 30 days of test date. A. General Information Facility: Pacific Bell Telephone Co.dba AT&T California GEO PAR#SA532 Address: 11101 WHITE LANE City:BAKERSFIELD Zi :93307. Facility Contact Person: Grant Armstrong Contact Phone No:661-327-6903 Make/Model of Monitoring System:Veeder Root TLS 350 Service Date:07/06/2010 B. Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment Inspected/servlced: Tank ID: SA532A001 Tank ID: ®In-Tank Gauging Probe Model:646391-602 ❑In-Tank Gauging Probe Model: ®Annular Space or Vault Sensor Model:794380-340 ❑Annular Space or Vault Sensor Model: ❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ❑Mechanical Line Leak Detector Model: ❑Mechanical Una Leak Detector Model: []Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ®Tank Overfill/High Level Sensor Model:790091-001 ❑Tank Overfill/High Level Sensor Model: ❑Other(Specify equipment type and model In Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2) Tank ID: Tank ID: ❑In-Tank Gauging Probe Model: ❑In-Tank Gauging Probe Model: ❑Annular Space or Vault Sensor Model: ❑Annular Space or Vault Sensor Model: ❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ❑Tank Overfill/High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model: ❑Other(Specify equipment type and model In Section E on Page 2) ❑Other(Specify equipment type and model In Section E on Page 2) Dispenser ID: Dispenser ID: ❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model: ❑Shear Valve(s) ❑Shear Valve(s) ❑Dispenser Containment Float(s)and Chains) ❑Dispenser Containment Float(s)and Chains) Dispenser ID: Dispenser ID: ❑Dispenser Containment Sensors) Model: ❑Dispenser Containment Sensor(s) Model: ❑Shear Valves) ❑Shear Velve(s) ❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s) Dispenser ID:. I Dispenser ID: ❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model: ❑Shear Valve(S) ❑Shear Valve(s) ❑Dispenser Containment Float(s)and Chains) ❑Dispenser Containment Fioat(s)and Chains) •If the facility contains more tanks or dispensers,copy this form.Include information for every tank and dispenser at the facility. C. Certification•I certify that the equipment identified in this document was Inspectediserviced in accordance with the manufacturers'guidelines.Attached to this Certification Is Information(e.g.manufacturers'checklists)necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment.For any equipment capable of generating such reports,I have also attached a copy of the report; (check all that apply): ®sy ,1p oWetp _0A jp6 history report Technician Name(Print):Robert George Si nature: Certification No:A24059 License No: 588098 TesUnq Company Name:TAIT ENVIRONMENTAL SERVICES Phone No: 714 560-8222 Testing Company Address:2131 South Dupont Drive Anaheim CA 92806 Date of Testin /Servicin :07/06/2010 Monitoring System Certification Page 1 of 4 12107 1 2/21/07 iIIIIIII 6IIIII M 16 1 Monitoring System Certification Address: 11101 WHITE LANE BAKERSFIELD 93301 Service Date: 07/06/2010 D. Results of Testing/Servicing Software Version Installed: 119.05 Complete the fol owing checklist: ®Yes ❑No* Is the audible alarm operational? ®Yes ❑No* Is the visual alarm operational? ®Yes ❑ No* Were all the sensors visually inspected,functionally tested, and cofirmed operational? ®Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? ®Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g. modem) operational? ❑N/A ❑Yes ❑No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak,fails to operate, or is electrically disconnected? If yes:which sensors initiate positive shut- ❑ Sump/Trench Sensors ❑ Dispenser Containment Sensors ®N/A down?: Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑Yes ❑No ®Yes ❑No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e. no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the ❑ N/A tank fill point(s)and operating properly?If so, at what percent of tank capacity does the alarm trigger?: 90% ❑Yes* ® No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E below. Was liquid found inside any secondary containment systems designed as dry systems? ❑Yes* ®No If yes, check the type(s)of liquid found and describe causes in Section E, below. ❑Product ❑Water ®Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable ®Yes ❑No* Is all monitoring equipment operational per manufacturer's specifications? *In Section E below,describe how and when these deficiencies were or will be corrected. E. Comments Monitoring System Certification Page 2 of 4 12/07 2 2121/07 Monitoring System Certification Address: 11101 WHITE LANE BAKERSFIELD 93307 Service Date: 07/06/2010 F. In-Tank Gauging/SIR Equipment ❑Check this box if tank gauging is used only for inventory control ❑Check this box if no tank gauging or SIR Equipment is installed This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring Complete the fol owing checklist •Yes ❑No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults? •Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup? •Yes ❑No* Was accuracy of system product level readings tested? ❑Yes ® No* Was accuracy of system water level readings tested? •Yes ❑ No* Were all probes reinstalled properly? •Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed? *In the Section H below, describe how and when these deficiencies were or will be corrected G. Line Leak Detectors (LLD): ®Check this box if LLDs are not installed Complete the fol owing checklist ❑Yes ❑No* For equipment start-up or annual equipment certification,was a leak simulated to verify LLD performance? ❑ N/A Simulated Leak Rate(check all that apply) ❑3.0 g.p.h ❑0.1 g.p.h ❑0.2 g.p.h ❑Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements? ❑Yes ❑ No* Was the testing apparatus properly calibrated? ❑Yes ❑No* For mechanical LLDs,does the LLD restrict product flow if it detects a leak? ❑ N/A ❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? ❑ N/A ❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ❑ N/A ❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? ❑ N/A ❑Yes ❑ No* For electronic LLDs, have all accessible wiring connections been visually inspected? ❑ N/A ❑Yes ❑No* Were all items on the equipment manufacturer's maintenance checklist completed? *In the Section H below, describe how and when these deficiencies were or will be corrected H. Comments The monitoring system is operational at this time therefore no ground faults are present. The tank probe does not have water detection capability. Location is a suction system. Monitoring System Certification Page 3 of 4 12/07 3 2/21/07 Monitoring System Certification Address: 11101 WHITE LANE BAKERSFIELD 93307 Service Date: 07/06/2010 UST monitoring Site Plan AAw Date map was drawn: 07/06/2010 Instructions If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic line leak detectors; and in-tank liquid level probes (if used for leak detection). In the space provided, note the date this Site Plan was inspected. Monitoring System Certification Page 4 of 4 12/07 4 2/21/07 SWRCB,January 2006 SPILL BUCKET TESTING REPORT FORM This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printout from tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1.FACILITY INFORMATION. Facility Name:Pacific Bell Telephone Co. dba AT&T California Date of Testing:07/06/2010 Facility Address: 11101 WHITE LANE BAKERSFIELD CA 93307 GEO PAR#SA532 Facility Contact:Grant Armstrong Facili Phone: Date Local Agency Was Notified of Testing: 06/14/2010 Name of Local Agency Inspector if present during testing): Ernie Medina 2.TESTING CONTRACTOR INFORMATION Company Name:TAIT ENVIRONMENTAL SERVICES Technician Conducting Test:Robert George Credentials: ®CSLB Contractor ®ICC Service Tech ❑SWRCB Tank . ❑Other(Specify) Tester License Number(s):A ASB HAZB C-10. 588098. 5252187-UT 3.SPILL BUCKET TESTING INFORMATION Test Method Used ®Hydrostatic ❑Vacuum ❑Other Test Equipment Used: Tape Measure I Equipment Resolution: 1/16" Identify Spill Bucket(By Tank Number, I SA532AO01 2 3 4 Stored Product,etc) ❑Direct Bury ❑Direct Bury ❑Direct Bury El Direct Bury Bucket Installation Type ❑Contained in Sump ❑Contained in Sump El Contained in Sump El Contained in Sump ®On top of AST ❑On top of AST El On top of AST El On top of AST Bucket Diameter inches 12" Bucket Depth inches 12" Wait Time between applying 15 MIN vacuum/water and start of test Test Start Time: 9:30 Initial Reading Ri): 8 1/2" Test End Time: 10:30 Final Reading(R f): 8 1/2" Test Duration: 1 Hour Change in Reading Rf-Ri : 0 Pass/Fail Threshold or Criteria: 0 Test Result Pass Comments:Water returned to TES. CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is t e,accurate and in full compliance with legal requirements Technician's Signature Date 07/06/2010 I50301 JUL 13, 2010 2:05 PM # 1:BKFDCAI9 SA532 ❑ ❑ I50302 JUL 13, 2010 2:05 PM # 2:11101 WHITE LANE ❑ I50303 JUL 13, 2010 2:05 PM # 3:BAKERSFIELD,CA 93307 I50304 JUL 13, 2010 2:05 PM # 4:661 665-2381 ❑ 151700 JUL 13, 2010 2:05 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50F00 JUL 13, 2010 2:05 PM MON DD YYYY HH:MM:SS xM ❑ I10200 JUL 13, 2010 2:05 PM BKFDCA19 SA532 11101 WHITE LANE BAKERSFIELD,CA 93307 661 665-2381 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 162756 162521 2 2 WIRE CL 68512 68301 3 UNUSED 9928755 9850962 4 UNUSED 9894997 9863619 5 UNUSED 9891795 9854823 6 UNUSED 9900522 9848066 7 UNUSED 9890895 9852421 8 UNUSED 9901966 9855467 9 RELAY BOARD 14972 14993 10 UNUSED 9908241 9868974 11 UNUSED 9892922 9860672 12 UNUSED 9885179 9855545 13 UNUSED 9891917 9846535 14 UNUSED 9887376 9861487 15 UNUSED 9895266 9859771 16 UNUSED 9873019 9859900 COMM 1 FAXMODEM BOARD 40353 40234 COMM 2 UNUSED 9893236 9861573 COMM 3 UNUSED 9893466 9854515 COMM 4 UNUSED 9892796 9852713 COMM 5 UNUSED 9884990 9861423 COMM 6 UNUSED 9897108 9845376 ❑ I60100 JUL 13, 2010 2:05 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 DIESEL TK#5A532A001 ON 2 OFF '3 OFF 4 OFF I60200 JUL 13, 2010 2:05 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 DIESEL TK#SA532A001 2 3 4 El I60300 JUL 13, 2010 2:05 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 DIESEL TK#SA532A001 1 2 2 3 3 4 4 I60400 JUL 13, 2010 2:05 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 DIESEL TK#SA532A001 2000 2 0 3 0 4 0 ❑ I60700 JUL 13, 2010 2:05 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 DIESEL TK#SA532A001 47.00 2 0.00 3 0.00 4 0.00 ❑ I60900 JUL 13, 2010 2:05 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 DIESEL TK#SA532A001 0.000450 2 0.000000 3 0.000000 4 0.000000 I61200 JUL 13, 2010 2:05 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL MANIFOLDED TANKS 1 DIESEL TK#SA532A001 NONE 2 NONE 3 NONE 4 NONE ❑ I62100 JUL 13, 2010 2:06 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK#SA532A001 500 2 0 3 0 4 0 ❑ I62200 JUL 13, 2010 2:06 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK#SA532A001 1900 2 0 3 0 4 0 I62300 JUL 13, 2010 2:06 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK#SA532A001 1800 2 0 3 0 4 0 I62400 JUL 13, 2010 2:06 PM I62800 JUL 13, 2010 2:06 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK#SA532A001 2000 2 0 3 0 4 0 ❑ I62900 JUL 13, 2010 2:06 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK#SA532A001 1000 2 0 3 0 4 0 El I74300 JUL 13, 2010 2:06 PM 2 WIRE CL TYPE SENSOR LOCATION TYPE 1 ANNULAR ULTRA 2 2 DISCRIM. INTERSTITIAL 3 DISCRIM. INTERSTITIAL 4 DISCRIM. INTERSTITIAL 5 DISCRIM. INTERSTITIAL 6 DISCRIM. INTERSTITIAL 7 DISCRIM. INTERSTITIAL 8 DISCRIM. INTERSTITIAL I90200 JUL 13, 2010 2:06 PM SOFTWARE REVISION LEVEL VERSION 119.05 SOFTWARE# 346119-100-F CREATED - 00.02.25.12.15 S-MODULE# 330160-002-A SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS CSLD Fl I11100 JUL 13, 2010 2:06 PM BKFDCA19 SA532 11101 WHITE LANE BAKERSFIELD,CA 93307 661 665-2381 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 7-06-10 10:21AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 7-06-10 10:19AM T 1 TANK DIESEL TK#SA532A001 OVERFILL ALARM CLEAR 7-06-10 10:17AM T 1 TANK DIESEL TK#SA532A001 OVERFILL ALARM ALARM 7-06-10 10:11AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 7-06-10 10:05AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 7-06-10 10:05AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 7-06-10 10:00AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 7-06-10 9:59AM T 1 TANK DIESEL TK#SA532A001 LOW PRODUCT ALARM CLEAR 7-06-10 9:57AM T 1 TANK DIESEL TK#SA532A001 LOW PRODUCT ALARM ALARM 7-06-10 9:37AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 7-06-10 9:37AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 7-06-10 9:36AM T 1 TANK DIESEL TK#SA532A001 LOW PRODUCT ALARM CLEAR 7-06-10 9:31AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 7-06-10 9:31AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 7-06-10 9:31AM C 1 ANNULAR ANNULAR FUEL ALARM CLEAR 7-06-10 9:29AM C 1 ANNULAR ANNULAR FUEL ALARM ALARM 7-06-10 9:22AM T 1 TANK DIESEL TK#SA532A001 LOW PRODUCT ALARM ALARM 7-06-10 9:20AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 7-06-10 9:20AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 7-06-10 9:19AM T 1 TANK DIESEL TK#SA532A001 MAX PRODUCT ALARM CLEAR 8-11-04 11:42PM T 1 TANK DIESEL TK#SA532A001 MAX PRODUCT ALARM ALARM 8-11-04 11:42PM T 1 TANK DIESEL TK#SA532A001 MAX PRODUCT ALARM CLEAR 8-11-04 9:40PM T 1 TANK DIESEL TK#SA532A001 MAX PRODUCT ALARM ALARM 8-11-04 9:40PM T 1 TANK DIESEL TK#SA532A001 LOW PRODUCT ALARM CLEAR 4-14-04 1:24PM T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 4-14-04 1:24PM T 1 TANK DIESEL TK#SA532A001 OVERFILL ALARM CLEAR 4-14-04 1:23PM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 4-14-04 1:23PM T 1 TANK DIESEL TK#SA532A001 LOW PRODUCT ALARM ALARM 4-14-04 1:23PM T 1 TANK DIESEL TK#SA532A001 OVERFILL ALARM ALARM 4-14-04 1:23PM T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 4-14-04 1:21PM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 4-14-04 1:19PM C 1 ANNULAR ANNULAR FUEL ALARM CLEAR 4-14-04 1:12PM C 1 ANNULAR ANNULAR FUEL ALARM ALARM 4-14-04 1:12PM C 1 ANNULAR ANNULAR FUEL ALARM CLEAR 4-14-04 1:08PM C 1 ANNULAR ANNULAR FUEL ALARM ALARM 4-14-04 1:07PM C 1 ANNULAR ANNULAR FUEL ALARM CLEAR 4-17-03 9:47AM C 1 ANNULAR ANNULAR FUEL ALARM ALARM 4-17-03 9:46AM T 1 TANK DIESEL TK#SA532A001 MAX PRODUCT ALARM CLEAR 4-17-03 9:40AM T 1 TANK DIESEL TK#SA532A001 MAX PRODUCT ALARM ALARM 4-17-03 9:34AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 4-17-03 9:33AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 4-17-03 9:32AM D 1 OTHER CALL CENTER AUTODIAL FAILURE CLEAR 4-22-02 9:35AM T 1 TANK DIESEL TK#SA532A001 LOW PRODUCT ALARM CLEAR 4-22-02 8:50AM D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 1-30-02 1:10AM T 1 TANK DIESEL TK#SA532A001 PROBE OUT CLEAR 1-29-02 2:58PM T 1 TANK DIESEL TK#SA532A001 PROBE OUT ALARM 1-29-02 2:57PM T 1 TANK DIESEL TK#SA532A001 LOW PRODUCT ALARM ALARM 1-29-02 2:57PM T 1 TANK DIESEL TK#SA532A001 MAX PRODUCT ALARM CLEAR 1-29-02 2:572M T 1 TANK DIESEL TK#SA532A001 MAX PRODUCT ALARM ALARM 1-29-02 2:57PM I11200 JUL 13, 2010 2:06 PM BKFDCA19 SA532 11101 WHITE LANE BAKERSFIELD,CA 93307 661 665-2381 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK DIESEL TK#SA532A001 DELIVERY NEEDED CLEAR 7-06-10 9:57AM T 1 TANK DIESEL TK#SA532A001 INVALID FUEL LEVEL CLEAR 7-06-10 9:57AM T 1 TANK DIESEL TK#SA532A001 HIGH PRODUCT ALARM CLEAR 7-06-10 9:37AM T 1 TANK DIESEL TK#SA532A001 DELIVERY NEEDED ALARM 7-06-10 9:37AM T 1 TANK DIESEL TK#SA532A001 INVALID FUEL LEVEL ALARM 7-06-10 9:37AM T 1 TANK DIESEL TK#SA532A001 HIGH PRODUCT ALARM ALARM 7-06-10 9:31AM T 1 TANK DIESEL TK#SA532A001 DELIVERY NEEDED CLEAR 7-06-10 9:31AM T 1 TANK DIESEL TK#SA532A001 INVALID FUEL LEVEL CLEAR 7-06-10 9:31AM T 1 TANK DIESEL TK#SA532A001 DELIVERY NEEDED ALARM 7-06-10 9:20AM T 1 TANK DIESEL TK#SA532A001 INVALID FUEL LEVEL ALARM 7-06-10 9:20AM SYSTEM PRINTER ERROR CLEAR 12-01-09 1:35PM SYSTEM PRINTER ERROR ALARM 12-01-09 1:35PM SYSTEM PRINTER ERROR CLEAR 12-01-09 1:12PM SYSTEM PRINTER ERROR ALARM 12-01-09 1:12PM SYSTEM PRINTER ERROR CLEAR 12-01-09 1:12PM SYSTEM PRINTER ERROR ALARM 12-01-09 1:12PM SYSTEM PRINTER ERROR CLEAR 12-01-09 1:12PM SYSTEM PAPER OUT CLEAR 12-01-09 1:12PM SYSTEM PRINTER ERROR ALARM 12-01-09 1:12PM SYSTEM PAPER OUT ALARM 12-01-09 1:12PM SYSTEM PRINTER ERROR CLEAR 2-11-09 9:11AM SYSTEM PAPER OUT CLEAR 2-11-09 9:11AM SYSTEM PAPER OUT ALARM 2-11-09 9:10AM SYSTEM PRINTER ERROR ALARM 2-11-09 9:10AM SYSTEM PRINTER ERROR CLEAR 2-11-09 9:08AM SYSTEM PRINTER ERROR ALARM 2-11-09 9:08AM SYSTEM PRINTER ERROR CLEAR 2-11-09 9:05AM SYSTEM PAPER OUT CLEAR 2-11-09 9:05AM SYSTEM PRINTER ERROR ALARM 2-11-09 7:OOAM SYSTEM PAPER OUT ALARM 2-11-09 7:OOAM SYSTEM PRINTER ERROR CLEAR 3-28-08 7:05AM SYSTEM PAPER OUT CLEAR 3-28-08 7:05AM SYSTEM PRINTER ERROR ALARM 3-28-08 7:03AM SYSTEM PAPER OUT ALARM 3-28-08 7:03AM SYSTEM PRINTER ERROR CLEAR 7-19-07 11:04AM SYSTEM PAPER OUT CLEAR 7-19-07 11:04AM SYSTEM PRINTER ERROR ALARM 7-19-07 11:03AM SYSTEM PAPER OUT ALARM 7-19-07 11:03AM SYSTEM PRINTER ERROR CLEAR 10-31-06 6:22AM SYSTEM PRINTER ERROR ALARM 10-31-06 6:22AM SYSTEM PRINTER ERROR CLEAR 2-07-05 11:43AM SYSTEM PRINTER ERROR ALARM 2-07-05 11:42AM SYSTEM PRINTER ERROR CLEAR 2-07-05 11:42AM SYSTEM PAPER OUT CLEAR 2-07-05 11:42AM SYSTEM PRINTER ERROR ALARM 2-07-05 11:42AM SYSTEM PAPER OUT ALARM 2-07-05 11:42AM T 1 TANK DIESEL TK#SA532A001 DELIVERY NEEDED CLEAR 11-22-04 8:19AM T 1 TANK DIESEL TK#SA532A001 DELIVERY NEEDED ALARM 11-19-04 10:15AM T 1 TANK DIESEL TK#SA532A001 HIGH PRODUCT ALARM CLEAR 8-11-04 11:42PM T 1 TANK DIESEL TK#SA532A001 HIGH PRODUCT ALARM ALARM 8-11-04 11:42PM Fl I20600 JUL 13, 2010 2:07 PM BKFDCAI9 SA532 11101 WHITE LANE BAKERSFIELD,CA 93307 661 665-2381 TANK ALARM HISTORY TANK 1 DIESEL TK#SA532A001 OVERFILL ALARM JUL 6, 2010 10:11 AM APR 14, 2004 1:23 PM JAN 28, 2002 2:58 PM LOW PRODUCT ALARM JUL 6, 2010 9:37 AM JUL 6, 2010 9:20 AM APR 14, 2004 1:23 PM HIGH PRODUCT ALARM JUL 6, 2010 9:31 AM AUG 11, 2004 11:42 PM AUG 11, 2004 9:40 PM INVALID FUEL LEVEL JUL 6, 2010 9:37 AM JUL 6, 2010 9:20 AM JAN 29, 2002 2:57 PM PROBE OUT JUL 6, 2010 10:19 AM JUL 6, 2010 10:05 AM JUL 6, 2010 9:59 AM DELIVERY NEEDED JUL 6, 2010 9:37 AM JUL 6, 2010 9:20 AM NOV 19, 2004 10:15 AM MAX PRODUCT ALARM AUG 11, 2004 11:42 PM AUG 11, 2004 9:40 PM APR 17, 2003 9:34 AM LOW TEMP WARNING APR 14, 2004 1:24 PM JAN 28, 2002 2:54 PM I34200 JUL 13, 2010 2:07 PM BKFDCAI9 SA532 11101 WHITE LANE BAKERSFIELD,CA 93307 661 665-2381 2 WIRE CL ALARM HISTORY REPORT SENSOR LOCATION 1 ANNULAR JUL 6, 2010 9:22 AM FUEL ALARM APR 14, 2004 1:12 PM FUEL ALARM APR 14, 2004 1:07 PM FUEL ALARM �2Ss TAI T piste¢ro T.. 2131 S. Dupont Drive, Anaheim, CA 92806 p:714/56018222 -.tait.com July 16, 2010 VIA FED EX: 7988 5744 4032 Bakersfield Fire Department 1501 Truxtun Ave. Bakersfield CA 93301 Re: Monitoring System Certification Spill Bucket Testing Pacific Bell Telephone Co. dba AT&T California 11101 WHITE LANE, BAKERSFIELD, CA 93307 GEOPAR: SA532 To Whom It May Concern: Enclosed are the results for the following tests completed on July 6, 2010: ■ Monitoring System Certification Report Form ■ Spill Bucket Testing Report Form Please do not hesitate to call me if you have any questions. Ve r urs, M tth w enison Program Manager CA Iic#588098 1 AZ Iic#095984 1 NV tica 0049666 I TX lica CR0000041