HomeMy WebLinkAbout2011 FMC RESULTS (Copies of Monitoring System Certification form and UST Monitoring'Plot Plan available at hftp://www.waterboards.ca.gov)
Monitoring System Certification
For Use By All Jurisdictions Within the State of California
Authority Cited:Chapter 6.7, Health and Safety Code;Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work.A copy of this form must be provided to the tank system owner/operator.The
owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information IIIIIIIIIIIIIIIIIII) 05
Facility: AT&T Corporation GEO PAR#CAK010 IE
Address: 1520 20th St. City: Bakersfield Zi p: 93301
Facility Contact Person: Grant Armstrong Contact Phone No: 661-327-6903
Make/Model of Monitoring System: Veeder Root TLS-350 Service Date: 02/10/2011
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to indicate specific equipment Inspected/serviced:
Tank ID: CAK0100001 Tank ID: CAK01OA002
®In-Tank Gauging Probe Model:847390-105 ®In-Tank Gauging Probe Model:847390-301
®Annular Space or Vault Sensor Model:794390-420 ®Annular Space or Vault Sensor Model:794380-208
®Piping Sump/Trench Sensor(s) Model:794380-208 ❑Piping Sump/Trench Sensor(s) Model:
®Fill Sump Sensor(s) Model:794380-208 ❑Fill Sump Sensor(s) Model:
❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
®Tank Overfill/High Level Sensor Model:790091-001 ❑Tank Overfill/High Level Sensor Model:
®Other(Specify equipment type and model in Section E on Page 2) ®Other(Specify equipment type and model in Section E on Page 2)
TanklD: TanklD:
❑In-Tank Gauging Probe Model: ❑In-Tank Gauging Probe Model:
❑Annular Space or Vault Sensor Model: ❑Annular Space or Vault Sensor Model:
❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model:
❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model:
❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
❑Tank Overfill/High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model:
❑Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑lvgpenser Containment Float(s)and Chain(s)
*If the facility contains more tanks or dispensers,copy this form.Include infonmatkm for every tank and dispenser at the facility.
C. Certification-!certify that the equipment identified in this document was Inspected/serviced in accordance with the
manufacturers'guidelines.Attached to this Certification is information(e.g. manufacturers'checklists)necessary to verify
that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of
generating such reports, I have also attached a copy of the report; (check all that apply):
®S tern set-up ®Alarm history report
Technician Name (Print): Paul McLane Si nature: `
Certification No: A27638 I License No: 588098
Testing Company Name: TAIT ENVIRONMENTAL SERVICES I Phone No: 714 560-8222
Testing Company Address: 2131 South Dupont Drive Anaheim GA R2806____ 1 Date of Testing/Servicing: 02/10/2011
Monitoring System Certification Page 1 of 4 IIIIIIIIIIIIIIII IIII 12/07
06
IE
Monitoring System Certification
Address: 1520 20th St. Bakersfield 93301 Service Date: 02/10/2011
D. Results of Testing/Servicing
Software Version Installed: 120.00
Complete the fol owing checklist:
•Yes ❑ No* Is the audible alarm operational?
•Yes ❑ No* Is the visual alarm operational?
•Yes ❑ No* Were all the sensors visually inspected,functionally tested, and cofirmed operational?
•Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
®Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem)
operational?
❑ N/A
❑Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
containment monitoring system detects a leak, fails to operate, or is electrically disconnected?
If yes:which sensors
initiate positive shut- ❑ Sump/Trench Sensors ❑ Dispenser Containment Sensors
® N/A down?:
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑ Yes ❑ No
❑Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the
® N/A tank fill point(s)and operating properly?If so, at what percent of tank capacity does the alarm trigger?:
❑Yes* ® No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E below.
Was liquid found inside any secondary containment systems designed as dry systems?
El ® No If yes,check the type(s)of liquid found and describe causes in Section E, below. ❑Product ❑Water
®Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable
®Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications?
*In Section E below,describe how and when these deficiencies were or will be corrected.
E. Comments
Other sensors from page#1:
L3 CAK010A002 Rupture Basin sensor 794380-208-Certified.
L6 Piping Box sensor 794380-208-Certified.
L7 Remote Pump Cabinet sensor 794380-208-Certified.
An Overfill Prevention Valve is installed in the drop tube.
Monitoring System Certification Page 2 of 4 12/07
Monitoring System Certification
Address: 1520 20th St. Bakersfield 93301 Service Date: 02/10/2011
F. In-Tank Gauging/SIR Equipment ®Check this box if tank gauging is used only for inventory control
❑Check this box if no tank gauging or SIR Equipment is installed
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring
Complete the fol owing checklist
❑Yes ❑ No* Has all input wiring been inspected for proper entry and termination, including testing for ground
faults?
❑Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup?
❑Yes ❑ No* Was accuracy of system product level readings tested?
❑Yes ❑ No* Was accuracy of system water level readings tested?
❑Yes ❑ No* Were all probes reinstalled properly?
❑Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H below, describe how and when these deficiencies were or will be corrected
G. Line Leak Detectors (LLD): ®Check this box if LLDs are not installed
Complete the fol owing checklist
❑Yes ❑ No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD
performance?
❑ N/A Simulated Leak Rate(check all that apply) ❑3.0 g.p.h ❑0.1 g.p.h ❑0.2 g.p.h
❑Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements?
❑Yes ❑ No* Was the testing apparatus properly calibrated?
❑Yes ❑ No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is
disabled or disconnected?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system
malfunctions or fails a test?
❑ N/A
❑Yes ❑ No* For electronic LLDs, have all accessible wiring connections been visually inspected?
❑ N/A
0 Yes ❑ No* jWere all items on the equipment manufacturer's maintenance checklist completed?
*In the Section H below,describe how and when these deficiencies were or will be corrected
H., Comments
Suction system.
Monitoring System Certification Page 3 of 4 12/07
Monitoring System Certification
. �
Addrmoo: 152O2Oth St. Bakersfield 933U1 Service Date: U2/1O/2O11
UST monitoring Site Plan
Monitoring Plan Site Map
aW
Orawing NOT to Scale
Business Name-, Pa6fic Bell Telephone Co. dba AT&T Cal. (CAK010)
Sensors Stetsorifi
8K UST Diesel
od Sensor
AT&T building
250 gal.Day lank 4"F110M
E r Pjj
rNino Room
IN
2&Street— A
Date map was drawn: 02/10/2011
Instructions
If you already have diagram that&aoms all required infmmnmti»n -include it, rather than this
with your'Monitodng System Certificabon. On your site plan, show the general layout of tanks and piping.
Clearly identify locations of the follovAng equipment, if installed: monitoring system control panels; sensors
monitoring tank annular spaces, sumps, dispenser pans, spill containers,,or other secondary containment
~....' ....~.~..~~. or electronic —line leak detectors; and in-tank q__ level ,.---- `' used for __. --'----`.
|n the space provided, note the date this Site Plan was inspected.
Monitoring System Certification Page 4 of 4 12/07
SWRCB,January 2006
SPILL BUCKET TESTING REPORT FORM
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printout from
tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name: AT&T Corporation Date of Testing: 02/10/2011
Facility Address: 1520 20th St. Bakersfield CA 93301 GEO PAR#CAK010
Facility Contact: Grant Armstrong Facility Phone: 661-327-6903
Date Local Agency Was Notified of Testing: 01/27/2011
Name of Local Agency Inspector if present during testing):None
2.TESTING CONTRACTOR INFORMATION
Company Name: TAIT ENVIRONMENTAL SERVICES
Technician Conducting Test:Paul McLane
Credentials: ®CSLB Contractor ®ICC Service Tech ❑SWRCB Tank El Other(Specify)
Tester
License Number (s):A ASB HAZB C-10. 588098. 5238651-UT
3.SPILL BUCKET TESTING INFORMATION
Test Method Used ®Hydrostatic ❑Vacuum ❑Other
Test Equipment Used: MarkerNisual Tape Measure Equipment Resolution: 1/16"
Identify Spill Bucket(By Tank Number, 1 CAK0100001 2 3 4
Stored Product,etc)
❑Direct Bury ❑Direct Bury ❑Direct Bury ❑Direct Bury
Bucket Installation Type ®Contained in Sump El Contained in Sump ❑Contained in Sump El Contained in Sump
❑On top of AST ❑On top of AST ❑On top of AST ❑On top of AST
Bucket Diameter inches 12"
Bucket Depth inches 14"
Wait Time between applying 30 min
vacuum/water and start of test
Test Start Time: 9:30 am
Initial Reading Ri): 14"
Test End Time: 10:30 am
Final Reading 14"
Test Duration: 1 Hour
Change in Reading Rf-Ri : 0
Pass/Fail Threshold or Criteria: 0
Test Result Pass
Comments:Removed test water from site.Took back to TES shop.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true,accurate and in full compliance with legal requirements
Date 02/10/2011
Technician's Signature � f✓
I50301
FEB 14, 2011 2:44 PM
# 1:BKFDCA01 CAK010
ri
I50302
FEB 14, 2011 2:44 PM
# 2:1520 20TH ST
I50303
FEB 14, 2011 2:44 PM
# 3:BAKERSFIELD,CA 93301
El
I50304
FEB 14, 2011 2:44 PM
# 4:661-869-1846
I51700
FEB 14, 2011 2:44 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50F00
FEB 14, 2011 2:44 PM
MON DD YYYY HH:MM:SS xM
Fl
El
I10200
FEB 14, 2011 2:44 PM
BKFDCA01 CAK010
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 162295 162195
2 INTERSTITIAL BD 201439 201012
3 UNUSED 15000000 15000000
4 UNUSED 15000000 15000000
5 UNUSED 15000000 15000000
6 UNUSED 15000000 . 15000000
7 UNUSED 151100000 15000000
8 UNUSED 15000000 15000000
9 RELAY BOARD 14933 14970
10 COMBO I/O BOARD 9929 9953
11 UNUSED 15000000 15000000
12 UNUSED 15000000 15000000
13 UNUSED 15000000 15000000
14 UNUSED 15000000 15000000
15 UNUSED 15000000 15000000
16 UNUSED 15000000 15000000
COMM 1 FAXMODEM BOARD 40571 40518
COMM 2 UNUSED 15000000 15000000
COMM 3 UNUSED 15000000 15000000
COMM 4 UNUSED 15000000 15000000
COMM 5 UNUSED 15000000 15000000
COMM 6 UNUSED 15000000 15000000
El
I60100
FEB 14, 2011 2:45 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK#CAKO10U001 ON
2 DIESEL TK#CAKO1OA002 ON
3 OFF
4 OFF
160200
FEB 14, 2011 2:45 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK#CAKO1OU001
2 DIESEL TK#CAKO1OA002
3
4
160300
FEB 14, 2011 2:45 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK#CAKO10U001 1
2 DIESEL TK#CAKO1OA002 1
3 3
4 4
160400
FEB 14, 2011 2:45 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#CAKO1OU001 8002
2 DIESEL TK#CAKO10A002 250
3 0
4 0
❑
❑
I60700
FEB 14, 2011 2:45 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK#CAKO1OU001 82.00
2 DIESEL TK#CAKO1OA002 30.00
3 0.00
4 0.00
I60900
FEB 14, 2011 2:45 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK#CAK010U001 0.000450
2 DIESEL TK#CAK010A002 0.000450
3 0.000000
4 0.000000
I61200
FEB 14, 2011 2:45 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL MANIFOLDED TANKS
1 DIESEL TK#CAKO1OU001 NONE
2 DIESEL TK#CAKO1OA002 NONE
3 NONE
4 NONE
I62100
FEB 14, 2011 2:45 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1. DIESEL TK#CAKO10U001 4000
2 DIESEL TK#CAKO10A002 105
3 0
4 0
I62200
FEB 14, 2011 2:45 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#CAKO10U001 7601
2 DIESEL TK#CAKO10A002 237
3 0
4 0
I62300
FEB 14, 2011 2:45 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#CAKO1OU001 7201
2 DIESEL TK#CAKO10A002 225
3 0
4 0
I62400
FEB 14, 2011 2:45 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK#CAKO1OU001 2.0
2 DIESEL TK#CAKO10A002 2.0
I62800
FEB 14, 2011 2:45 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#CAKO1OU001 8002
2 DIESEL TK#CAKO1OA002 250
3 0
4 0
I62900
FEB 14, 2011 2:45 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#CAKO1OU001 4000
2 DIESEL TK#CAKO10A002 125
3 0
4 0
I70300
FEB 14, 2011 2:45 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 FILL SUMP TRI-STATE (SINGLE FLOAT)
2 PIPIN SUMP TRI-STATE (SINGLE FLOAT)
3 DAYTANK RUPTURE BASN TRI-STATE (SINGLE FLOAT)
4 DAY TANK ANNULAR TRI-STATE (SINGLE FLOAT)
5 ANNULAR TRI-STATE (SINGLE FLOAT)
6 PIPING BOX TRI-STATE (SINGLE FLOAT)
7 REMOTE PUMP CABINET TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
I90200
FEB 14, 2011 2:45 PM
r SOFTWARE REVISION LEVEL
VERSION 120.00
SOFTWARE# 346120-100-A
CREATED --00.07.28.15.33
S-MODULE# 330160-002-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
I11100
FEB 14, 2011 2:45 PM
BKFDCA01 CAK010
1520 20TH ST
BAKERSFIELD,CA 93301
661-669-1846
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 7 OTHER REMOTE PUMP CABINET FUEL ALARM CLEAR 2-10-11 1:04PM
L 7 OTHER REMOTE PUMP CABINET FUEL ALARM ALARM 2-10-11 1:OOPM
L 6 PIPE PIPING BOX FUEL ALARM CLEAR 2-10-11 10:57AM
L 6 PIPE PIPING BOX FUEL ALARM ALARM 2-10-11 10:52AM
T 2 TANK DIESEL TK#CAK010A002 HIGH WATER ALARM CLEAR 2-10-11 10:28AM
T 2 TANK DIESEL TK#CAK01OA002 PROBE OUT CLEAR 2-10-11 10:27AM
T 2 TANK DIESEL TK#CAK01OA002 PROBE OUT ALARM 2-10-11 10:27AM
T 2 TANK DIESEL TK#CAK01OA002 HIGH WATER ALARM ALARM 2-10-11 10:26AM
T 2 TANK DIESEL TK#CAK01OA002 OVERFILL ALARM CLEAR 2-10-11 10:23AM
T 2 TANK DIESEL TK#CAK010A002 OVERFILL ALARM ALARM 2-10-11 10:21AM
T 2 TANK DIESEL TK#CAK010A002 LOW PRODUCT ALARM CLEAR 2-10-11 10:20AM
T 2 TANK DIESEL TK#CAK01OA002 PROBE OUT CLEAR 2-10-11 10:19AM
T 2 TANK DIESEL TK#CAK010A002 PROBE OUT ALARM 2-10-11 10:18AM
T 2 TANK DIESEL TK#CAK010A002 LOW PRODUCT ALARM ALARM 2-10-11 10:18AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM CLEAR 2-10-11 10:16AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM ALARM 2-10-11 10:11AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM CLEAR 2-10-11 10:10AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM ALARM 2-10-11 10:04AM
T 1 TANK DIESEL TK#CAK010U001 HIGH WATER ALARM CLEAR 2-10-11 9:58AM
T 1 TANK DIESEL TK#CAK01OU001 PROBE OUT CLEAR 2-10-11 9:58AM
T 1 TANK DIESEL TK#CAK01OU001 PROBE OUT ALARM 2-10-11 9:56AM
T 1 TANK DIESEL TK#CAK010U001 HIGH WATER ALARM ALARM 2-10-11 9:52AM
T 1 TANK DIESEL TK#CAK01OU001 OVERFILL ALARM CLEAR 2-10-11 9:49AM
T 1 TANK DIESEL TK#CAK010U001 OVERFILL ALARM ALARM 2-10-11 9:47AM
T 1 TANK DIESEL TK#CAK010U001 LOW PRODUCT ALARM CLEAR 2-10-11 9:45AM
T 1 TANK DIESEL TK#CAK010U001 PROBE OUT CLEAR 2-10-11 9:45AM
T 1 TANK DIESEL TK#CAK01OU001 PROBE OUT ALARM 2-10-11 9:43AM
T 1 TANK DIESEL TK#CAK010U001 LOW PRODUCT ALARM ALARM 2-10-11 9:43AM
L 2 PIPE PIPIN SUMP FUEL ALARM CLEAR 2-10-11 9:40AM
L 2 PIPE PIPIN SUMP FUEL ALARM ALARM 2-10-11 9:35AM
L 1 STP SUMP FILL SUMP FUEL ALARM CLEAR 2-10-11 9:34AM
L 1 STP SUMP FILL SUMP FUEL ALARM ALARM 2-10-11 9:3OAM
L 5 ANNULAR ANNULAR FUEL ALARM CLEAR 2-10-11 9:29AM
L 5 ANNULAR ANNULAR FUEL ALARM ALARM 2-10-11 9:25AM
T 1 TANK DIESEL TK#CAK01OU001 LEAK ALARM CLEAR 10-15-10 11:15AM
T 1 TANK DIESEL TK#CAK01OU001 LEAK ALARM ALARM 10-14-10 2:44PM
T 1 TANK DIESEL TK#CAK01OU001 LEAK ALARM CLEAR 10-13-10 11:12AM
T 1 TANK DIESEL TK#CAK010U001 LEAK ALARM ALARM 10-13-10 11:06AM
D 1 OTHER CALL CENTER AUTODIAL FAILURE CLEAR 10-13-10 4:57AM
T 1 TANK DIESEL TK#CAK010U001 LEAK ALARM CLEAR 10-13-10 4:57AM
D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 10-12-10 11:18PM
D 1 OTHER CALL CENTER. AUTODIAL FAILURE CLEAR 10-12-10 11:18PM
T 1 TANK DIESEL TK#CAK010U001 LEAK ALARM ALARM 10-12-10 10:52PM
D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 10-12-10 9:14PM
T 2 TANK DIESEL TK#CAK010A002 SUDDEN LOSS ALARM CLEAR 10-12-10 9:54PM
T 2 TANK DIESEL TK#CAK010A002 SUDDEN LOS'S ALARM ALARM 10-12-10 8:39PM
D 1 OTHER CALL CENTER AUTODIAL FAILURE CLEAR 4-05-10 12:08PM
T 1 TANK DIESEL TK#CAK010U001 SUDDEN LOSS ALARM CLEAR 4-05-10 12:03PH
D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 4-04-10 4:04PM
T 1 TANK DIESEL TK#CAK01OU001 PROBE OUT CLEAR 4-04-10 3:46PM
I11200
FEB 14, 2011 2:46 PM
BKFDCA01 CAK010
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK DIESEL TK#CAK010A002 HIGH WATER WARNING CLEAR 2-10-11 10:28AM
T 2 TANK DIESEL TK#CAK010A002 HIGH WATER WARNING ALARM 2-10-11 10:26AM
T 2 TANK DIESEL TK#CAK01OA002 HIGH PRODUCT ALARM CLEAR 2-10-11 10:21AM
T 2 TANK DIESEL TK#CAK01OA002 HIGH PRODUCT ALARM ALARM 2-10-11 10:21AM
T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED CLEAR 2-10-11 10:20AM
T 2 TANK DIESEL TK#CAK010A002 INVALID FUEL LEVEL CLEAR 2-10-11 10:20AM
T 2 TANK DIESEL TK#CAK01OA002 INVALID FUEL LEVEL ALARM 2-10-11 10:18AM
T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED ALARM 2-10-11 10:18AM
T 1 TANK DIESEL TK#CAK01OU001 HIGH WATER WARNING CLEAR 2-10-11 9:58AM
T 1 TANK DIESEL TK#CAK01OU001 HIGH WATER WARNING ALARM 2-10-11 9:52AM
T 1 TANK DIESEL TK#CAK010U001 DELIVERY NEEDED CLEAR 2-10-11 9:45AM
T 1 TANK DIESEL TK#CAK010U001 DELIVERY NEEDED ALARM 2-10-11 9:43AM
T 1 TANK DIESEL TK#CAK01OU001 LOW TEMP WARNING CLEAR 4-04-10 3:58PM
T 1 TANK DIESEL TK#CAK010U001 LOW TEMP WARNING ALARM 4-04-10 3:48PM
SYSTEM PRINTER ERROR CLEAR 2-19-10 1:10PM
SYSTEM PRINTER ERROR ALARM 2-19-10 1:10PM
T 1 TANK DIESEL TK#CAK010U001 HIGH WATER WARNING CLEAR 2-19-10 10:21AM
T 1 TANK DIESEL TK#CAK01OU001 HIGH WATER WARNING ALARM 2-19-10 10:16AM
T 1 TANK DIESEL TK#CAK010U001 DELIVERY NEEDED CLEAR 2-19-10 10:06AM
T 1 TANK DIESEL TK#CAK01OU001 DELIVERY NEEDED ALARM 2-19-10 10:05AM
T 2 TANK DIESEL TK#CAK01OA002 INVALID FUEL LEVEL CLEAR 2-19-10 10:01AM
T 2 TANK DIESEL TK#CAK01OA002 INVALID FUEL LEVEL ALARM 2-19-10 10:01AM
T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM CLEAR 2-19-10 10:00AM
T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM ALARM 2-19-10 9:58AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 2-19-10 9:58AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 2-19-10 9:57AM
T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM CLEAR 2-19-10 9:57AM
T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM ALARM 2-19-10 9:57AM
T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED CLEAR 2-19-10 9:57AM
T 2 TANK DIESEL TK#CAK01OA002 INVALID FUEL LEVEL CLEAR 2-19-10 9:57AM
T 2 TANK DIESEL TK#CAK010A002 INVALID FUEL LEVEL ALARM 2-19-10 9:57AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 2-19-10 9:55AM
SYSTEM PRINTER ERROR CLEAR 5-01-09 2:59PM
SYSTEM PAPER OUT CLEAR 5-01-09 2:59PM
SYSTEM PRINTER ERROR ALARM 5-01-09 2:58PM
SYSTEM PAPER OUT ALARM 4-29-09 12:48PM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 4-28-09 11:37AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-28-09 11:14AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 4-06-09 11:58AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-06-09 11:56AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 4-06-09 11:14AM
T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED ALARM 4-06-09 11:06AM
T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED CLEAR 4-06-09 11:01AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-06-09 10:47AM
T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED CLEAR 4-01-09 9:34AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-01-09 9:07AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 4-01-09 9:06AM
T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-01-09 9:06AM
T 2 TANK DIESEL TK#CAK01OA002 HIGH PRODUCT ALARM CLEAR 4-01-09 8:21AM
T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM ALARM 4-01-09 8:20AM
120600
FEB 14, 2011 2:47 PM
BKFDCA01 CAK010
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
TANK ALARM HISTORY
TANK 1 DIESEL TK#CAK01OU001
LEAK ALARM OCT 14, 2010 2:44 PM
OCT 13, .2010 11:06 AM
OCT 12, 2010 10:52 PM
HIGH WATER ALARM FEB 10, 2011 9:52 AM
FEB 19, 2010 10:16 AM
JAN 16, 2009 11:37 AM
OVERFILL ALARM FEB 10, 2011 9:47 AM
FEB 19, 2010 10:11 AM
MAR 6, 2009 10:25 AM
LOW PRODUCT ALARM FEB 10, 2011 9:43 AM
FEB 19, 2010 10:05 AM
MAR 6, 2009 10:23 AM
SUDDEN LOSS ALARM APR 4, 2010 3:43 PM
FEB 19, 2010 10:08 AM
FEB 19, 2010 10:05 AM
PROBE OUT FEB 10, 2011 9:56 AM
FEB 10, 2011 9:43 AM
APR 4, 2010 3:46 PM
HIGH WATER WARNING FEB 10, 2011 9:52 AM
FEB 19, 2010 10:16 AM
JAN 16, 2009 11:37 AM
DELIVERY NEEDED FEB 10, 2011 9:43 AM
FEB 19, 2010 10:05 AM
MAR 6, 2009 10:23 AM
CSLD INCR RATE WARN DEC 10, 2008 9:38 AM
SEP 18, 2008 10:06 AM
SEP 18, 2008 6:58 AM
LOW TEMP WARNING APR 4, 2010 3:48 PM
TANK 2 DIESEL TK#CAK010A002
HIGH WATER ALARM FEB 10, 2011 10:26 AM
OVERFILL ALARM FEB 10, 2011 10:21 AM
APR 11, 2008 1:50 PM
LOW PRODUCT ALARM FEB 10, 2011 10:18 AM
FEB 19, 2010 9:55 AM
APR 6, 2009 11:07 AM
SUDDEN LOSS ALARM OCT 12, 2010 8:39 PM
FEB 19, 2010 9:55 AM
APR 28, 2009 11:13 AM
HIGH PRODUCT ALARM FEB 10, 2011 10:21 AM
FEB 19, 2010 9:58 AM
FEB 19, 2010 9:57 AM
INVALID FUEL LEVEL FEB 10, 2011 10:18 AM
FEB 19, 2010 10:01 AM
FEB 19, 2010 9:57 AM
PROBE OUT FEB 10, 2011 10:27 AM
FEB 10, 2011 10:18 AM
FEB 19, 2010 10:00 AM
HIGH WATER WARNING FEB 10, 2011 10:26 AM
DELIVERY NEEDED FEB 10, 2011 10:18 AM
FEB 19, 2010 9:57 AM
FEB 19, 2010 9:55 AM
MAX PRODUCT ALARM FEB 19, 2010 9:58 AM
FEB 19, 2010 9:57 AM
MAR 6, 2009 12:39 PM
I30200
FEB 14, 2011 2:47 PM
BKFDCA01 CAK010
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 FILL SUMP
FEB 10, 2011 9:30 AM FUEL ALARM
FEB 19, 2010 9:18 AM FUEL ALARM
APR 1, 2009 9:20 AM FUEL ALARM
2 PIPIN SUMP
FEB 10, 2011 9:35 AM FUEL ALARM
FEB 19, 2010 9:22 AM FUEL ALARM
MAR 6, 2009 10:02 AM FUEL ALARM
3 DAYTANK RUPTURE BASN
FEB 10, 2011 10:04 AM FUEL ALARM
FEB 19, 2010 9:44 AM FUEL ALARM
APR 28, 2009 1:49 PM FUEL ALARM
4 DAY TANK ANNULAR
FEB 10, 2011 10:11 AM FUEL ALARM
FEB 19, 2010 9:50 AM FUEL ALARM
MAR 6, 2009 11:49 AM FUEL ALARM
5 ANNULAR
FEB 10, 2011 9:25 AM FUEL ALARM
FEB 19, 2010 9:14 AM FUEL ALARM
FEB 19, 2010 9:11 AM FUEL ALARM
6 PIPING BOX
FEB 10, 2011 10:52 AM FUEL ALARM
FEB 19, 2010 9:27 AM FUEL ALARM
MAY 4, 2009 2:05 PM FUEL ALARM
7 REMOTE PUMP CABINET
FEB 10, 2011 1:00 PM FUEL ALARM
MFR 2, 2010 10:42 AM FUEL ALARM
OCT 13, 2009 10:08 AM SENSOR OUT ALARM
TA 1 T
asrr 1.THa exr,tGCe+oe 2131 5. Oupon*Ori,e,A.nohei,n, CA 92806
p:?14 560'£322.2 v: •;:.ta;I c
February 16, 2011
VIA FED EX. 7967 7236 6635
Bakersfield Fire Department
2101 H Street
Bakersfield CA 93301
Re: Monitoring System Certification
Spill Bucket Testing
AT&T Corporation
1520 20th STREET, BAKERSFIELD, CA
GEOPAR: CAK010
To Whom it May Concern:
Enclosed are the results for the following tests completed on February 10, 2011:
■ Monitoring System Certification Report Form
■ Spill Bucket Testing Report Form
Please do not hesitate to call me if you have any questions.
I Yours,
Ma h L. Denison
Pro ram Manager
CA lick 588098 AZ I1c#095984 i NV I.cN 0049566 1 TX lino CR0000041