HomeMy WebLinkAbout2011 FMC RESULTS (Copies of Monitoring System Certification form and UST Monitoring'Plot Plan available at hftp://www.waterboards.ca.gov) Monitoring System Certification For Use By All Jurisdictions Within the State of California Authority Cited:Chapter 6.7, Health and Safety Code;Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work.A copy of this form must be provided to the tank system owner/operator.The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information IIIIIIIIIIIIIIIIIII) 05 Facility: AT&T Corporation GEO PAR#CAK010 IE Address: 1520 20th St. City: Bakersfield Zi p: 93301 Facility Contact Person: Grant Armstrong Contact Phone No: 661-327-6903 Make/Model of Monitoring System: Veeder Root TLS-350 Service Date: 02/10/2011 B. Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment Inspected/serviced: Tank ID: CAK0100001 Tank ID: CAK01OA002 ®In-Tank Gauging Probe Model:847390-105 ®In-Tank Gauging Probe Model:847390-301 ®Annular Space or Vault Sensor Model:794390-420 ®Annular Space or Vault Sensor Model:794380-208 ®Piping Sump/Trench Sensor(s) Model:794380-208 ❑Piping Sump/Trench Sensor(s) Model: ®Fill Sump Sensor(s) Model:794380-208 ❑Fill Sump Sensor(s) Model: ❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ®Tank Overfill/High Level Sensor Model:790091-001 ❑Tank Overfill/High Level Sensor Model: ®Other(Specify equipment type and model in Section E on Page 2) ®Other(Specify equipment type and model in Section E on Page 2) TanklD: TanklD: ❑In-Tank Gauging Probe Model: ❑In-Tank Gauging Probe Model: ❑Annular Space or Vault Sensor Model: ❑Annular Space or Vault Sensor Model: ❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ❑Tank Overfill/High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model: ❑Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2) Dispenser ID: Dispenser ID: ❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model: ❑Shear Valve(s) ❑Shear Valve(s) ❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s) Dispenser ID: Dispenser ID: ❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model: ❑Shear Valve(s) ❑Shear Valve(s) ❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s) Dispenser ID: Dispenser ID: ❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model: ❑Shear Valve(s) ❑Shear Valve(s) ❑Dispenser Containment Float(s)and Chain(s) ❑lvgpenser Containment Float(s)and Chain(s) *If the facility contains more tanks or dispensers,copy this form.Include infonmatkm for every tank and dispenser at the facility. C. Certification-!certify that the equipment identified in this document was Inspected/serviced in accordance with the manufacturers'guidelines.Attached to this Certification is information(e.g. manufacturers'checklists)necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports, I have also attached a copy of the report; (check all that apply): ®S tern set-up ®Alarm history report Technician Name (Print): Paul McLane Si nature: ` Certification No: A27638 I License No: 588098 Testing Company Name: TAIT ENVIRONMENTAL SERVICES I Phone No: 714 560-8222 Testing Company Address: 2131 South Dupont Drive Anaheim GA R2806____ 1 Date of Testing/Servicing: 02/10/2011 Monitoring System Certification Page 1 of 4 IIIIIIIIIIIIIIII IIII 12/07 06 IE Monitoring System Certification Address: 1520 20th St. Bakersfield 93301 Service Date: 02/10/2011 D. Results of Testing/Servicing Software Version Installed: 120.00 Complete the fol owing checklist: •Yes ❑ No* Is the audible alarm operational? •Yes ❑ No* Is the visual alarm operational? •Yes ❑ No* Were all the sensors visually inspected,functionally tested, and cofirmed operational? •Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? ®Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) operational? ❑ N/A ❑Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes:which sensors initiate positive shut- ❑ Sump/Trench Sensors ❑ Dispenser Containment Sensors ® N/A down?: Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑ Yes ❑ No ❑Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the ® N/A tank fill point(s)and operating properly?If so, at what percent of tank capacity does the alarm trigger?: ❑Yes* ® No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E below. Was liquid found inside any secondary containment systems designed as dry systems? El ® No If yes,check the type(s)of liquid found and describe causes in Section E, below. ❑Product ❑Water ®Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable ®Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications? *In Section E below,describe how and when these deficiencies were or will be corrected. E. Comments Other sensors from page#1: L3 CAK010A002 Rupture Basin sensor 794380-208-Certified. L6 Piping Box sensor 794380-208-Certified. L7 Remote Pump Cabinet sensor 794380-208-Certified. An Overfill Prevention Valve is installed in the drop tube. Monitoring System Certification Page 2 of 4 12/07 Monitoring System Certification Address: 1520 20th St. Bakersfield 93301 Service Date: 02/10/2011 F. In-Tank Gauging/SIR Equipment ®Check this box if tank gauging is used only for inventory control ❑Check this box if no tank gauging or SIR Equipment is installed This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring Complete the fol owing checklist ❑Yes ❑ No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults? ❑Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup? ❑Yes ❑ No* Was accuracy of system product level readings tested? ❑Yes ❑ No* Was accuracy of system water level readings tested? ❑Yes ❑ No* Were all probes reinstalled properly? ❑Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed? * In the Section H below, describe how and when these deficiencies were or will be corrected G. Line Leak Detectors (LLD): ®Check this box if LLDs are not installed Complete the fol owing checklist ❑Yes ❑ No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? ❑ N/A Simulated Leak Rate(check all that apply) ❑3.0 g.p.h ❑0.1 g.p.h ❑0.2 g.p.h ❑Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements? ❑Yes ❑ No* Was the testing apparatus properly calibrated? ❑Yes ❑ No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak? ❑ N/A ❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? ❑ N/A ❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ❑ N/A ❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? ❑ N/A ❑Yes ❑ No* For electronic LLDs, have all accessible wiring connections been visually inspected? ❑ N/A 0 Yes ❑ No* jWere all items on the equipment manufacturer's maintenance checklist completed? *In the Section H below,describe how and when these deficiencies were or will be corrected H., Comments Suction system. Monitoring System Certification Page 3 of 4 12/07 Monitoring System Certification . � Addrmoo: 152O2Oth St. Bakersfield 933U1 Service Date: U2/1O/2O11 UST monitoring Site Plan Monitoring Plan Site Map aW Orawing NOT to Scale Business Name-, Pa6fic Bell Telephone Co. dba AT&T Cal. (CAK010) Sensors Stetsorifi 8K UST Diesel od Sensor AT&T building 250 gal.Day lank 4"F110M E r Pjj rNino Room IN 2&Street— A Date map was drawn: 02/10/2011 Instructions If you already have diagram that&aoms all required infmmnmti»n -include it, rather than this with your'Monitodng System Certificabon. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the follovAng equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers,,or other secondary containment ~....' ....~.~..~~. or electronic —line leak detectors; and in-tank q__ level ,.---- `' used for __. --'----`. |n the space provided, note the date this Site Plan was inspected. Monitoring System Certification Page 4 of 4 12/07 SWRCB,January 2006 SPILL BUCKET TESTING REPORT FORM This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printout from tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1.FACILITY INFORMATION Facility Name: AT&T Corporation Date of Testing: 02/10/2011 Facility Address: 1520 20th St. Bakersfield CA 93301 GEO PAR#CAK010 Facility Contact: Grant Armstrong Facility Phone: 661-327-6903 Date Local Agency Was Notified of Testing: 01/27/2011 Name of Local Agency Inspector if present during testing):None 2.TESTING CONTRACTOR INFORMATION Company Name: TAIT ENVIRONMENTAL SERVICES Technician Conducting Test:Paul McLane Credentials: ®CSLB Contractor ®ICC Service Tech ❑SWRCB Tank El Other(Specify) Tester License Number (s):A ASB HAZB C-10. 588098. 5238651-UT 3.SPILL BUCKET TESTING INFORMATION Test Method Used ®Hydrostatic ❑Vacuum ❑Other Test Equipment Used: MarkerNisual Tape Measure Equipment Resolution: 1/16" Identify Spill Bucket(By Tank Number, 1 CAK0100001 2 3 4 Stored Product,etc) ❑Direct Bury ❑Direct Bury ❑Direct Bury ❑Direct Bury Bucket Installation Type ®Contained in Sump El Contained in Sump ❑Contained in Sump El Contained in Sump ❑On top of AST ❑On top of AST ❑On top of AST ❑On top of AST Bucket Diameter inches 12" Bucket Depth inches 14" Wait Time between applying 30 min vacuum/water and start of test Test Start Time: 9:30 am Initial Reading Ri): 14" Test End Time: 10:30 am Final Reading 14" Test Duration: 1 Hour Change in Reading Rf-Ri : 0 Pass/Fail Threshold or Criteria: 0 Test Result Pass Comments:Removed test water from site.Took back to TES shop. CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true,accurate and in full compliance with legal requirements Date 02/10/2011 Technician's Signature � f✓ I50301 FEB 14, 2011 2:44 PM # 1:BKFDCA01 CAK010 ri I50302 FEB 14, 2011 2:44 PM # 2:1520 20TH ST I50303 FEB 14, 2011 2:44 PM # 3:BAKERSFIELD,CA 93301 El I50304 FEB 14, 2011 2:44 PM # 4:661-869-1846 I51700 FEB 14, 2011 2:44 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50F00 FEB 14, 2011 2:44 PM MON DD YYYY HH:MM:SS xM Fl El I10200 FEB 14, 2011 2:44 PM BKFDCA01 CAK010 1520 20TH ST BAKERSFIELD,CA 93301 661-869-1846 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 162295 162195 2 INTERSTITIAL BD 201439 201012 3 UNUSED 15000000 15000000 4 UNUSED 15000000 15000000 5 UNUSED 15000000 15000000 6 UNUSED 15000000 . 15000000 7 UNUSED 151100000 15000000 8 UNUSED 15000000 15000000 9 RELAY BOARD 14933 14970 10 COMBO I/O BOARD 9929 9953 11 UNUSED 15000000 15000000 12 UNUSED 15000000 15000000 13 UNUSED 15000000 15000000 14 UNUSED 15000000 15000000 15 UNUSED 15000000 15000000 16 UNUSED 15000000 15000000 COMM 1 FAXMODEM BOARD 40571 40518 COMM 2 UNUSED 15000000 15000000 COMM 3 UNUSED 15000000 15000000 COMM 4 UNUSED 15000000 15000000 COMM 5 UNUSED 15000000 15000000 COMM 6 UNUSED 15000000 15000000 El I60100 FEB 14, 2011 2:45 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 DIESEL TK#CAKO10U001 ON 2 DIESEL TK#CAKO1OA002 ON 3 OFF 4 OFF 160200 FEB 14, 2011 2:45 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 DIESEL TK#CAKO1OU001 2 DIESEL TK#CAKO1OA002 3 4 160300 FEB 14, 2011 2:45 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 DIESEL TK#CAKO10U001 1 2 DIESEL TK#CAKO1OA002 1 3 3 4 4 160400 FEB 14, 2011 2:45 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 DIESEL TK#CAKO1OU001 8002 2 DIESEL TK#CAKO10A002 250 3 0 4 0 ❑ ❑ I60700 FEB 14, 2011 2:45 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 DIESEL TK#CAKO1OU001 82.00 2 DIESEL TK#CAKO1OA002 30.00 3 0.00 4 0.00 I60900 FEB 14, 2011 2:45 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 DIESEL TK#CAK010U001 0.000450 2 DIESEL TK#CAK010A002 0.000450 3 0.000000 4 0.000000 I61200 FEB 14, 2011 2:45 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL MANIFOLDED TANKS 1 DIESEL TK#CAKO1OU001 NONE 2 DIESEL TK#CAKO1OA002 NONE 3 NONE 4 NONE I62100 FEB 14, 2011 2:45 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1. DIESEL TK#CAKO10U001 4000 2 DIESEL TK#CAKO10A002 105 3 0 4 0 I62200 FEB 14, 2011 2:45 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK#CAKO10U001 7601 2 DIESEL TK#CAKO10A002 237 3 0 4 0 I62300 FEB 14, 2011 2:45 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK#CAKO1OU001 7201 2 DIESEL TK#CAKO10A002 225 3 0 4 0 I62400 FEB 14, 2011 2:45 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 DIESEL TK#CAKO1OU001 2.0 2 DIESEL TK#CAKO10A002 2.0 I62800 FEB 14, 2011 2:45 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK#CAKO1OU001 8002 2 DIESEL TK#CAKO1OA002 250 3 0 4 0 I62900 FEB 14, 2011 2:45 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 DIESEL TK#CAKO1OU001 4000 2 DIESEL TK#CAKO10A002 125 3 0 4 0 I70300 FEB 14, 2011 2:45 PM LIQUID TYPE SENSOR LOCATION TYPE 1 FILL SUMP TRI-STATE (SINGLE FLOAT) 2 PIPIN SUMP TRI-STATE (SINGLE FLOAT) 3 DAYTANK RUPTURE BASN TRI-STATE (SINGLE FLOAT) 4 DAY TANK ANNULAR TRI-STATE (SINGLE FLOAT) 5 ANNULAR TRI-STATE (SINGLE FLOAT) 6 PIPING BOX TRI-STATE (SINGLE FLOAT) 7 REMOTE PUMP CABINET TRI-STATE (SINGLE FLOAT) 8 TRI-STATE (SINGLE FLOAT) I90200 FEB 14, 2011 2:45 PM r SOFTWARE REVISION LEVEL VERSION 120.00 SOFTWARE# 346120-100-A CREATED --00.07.28.15.33 S-MODULE# 330160-002-A SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS CSLD I11100 FEB 14, 2011 2:45 PM BKFDCA01 CAK010 1520 20TH ST BAKERSFIELD,CA 93301 661-669-1846 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 7 OTHER REMOTE PUMP CABINET FUEL ALARM CLEAR 2-10-11 1:04PM L 7 OTHER REMOTE PUMP CABINET FUEL ALARM ALARM 2-10-11 1:OOPM L 6 PIPE PIPING BOX FUEL ALARM CLEAR 2-10-11 10:57AM L 6 PIPE PIPING BOX FUEL ALARM ALARM 2-10-11 10:52AM T 2 TANK DIESEL TK#CAK010A002 HIGH WATER ALARM CLEAR 2-10-11 10:28AM T 2 TANK DIESEL TK#CAK01OA002 PROBE OUT CLEAR 2-10-11 10:27AM T 2 TANK DIESEL TK#CAK01OA002 PROBE OUT ALARM 2-10-11 10:27AM T 2 TANK DIESEL TK#CAK01OA002 HIGH WATER ALARM ALARM 2-10-11 10:26AM T 2 TANK DIESEL TK#CAK01OA002 OVERFILL ALARM CLEAR 2-10-11 10:23AM T 2 TANK DIESEL TK#CAK010A002 OVERFILL ALARM ALARM 2-10-11 10:21AM T 2 TANK DIESEL TK#CAK010A002 LOW PRODUCT ALARM CLEAR 2-10-11 10:20AM T 2 TANK DIESEL TK#CAK01OA002 PROBE OUT CLEAR 2-10-11 10:19AM T 2 TANK DIESEL TK#CAK010A002 PROBE OUT ALARM 2-10-11 10:18AM T 2 TANK DIESEL TK#CAK010A002 LOW PRODUCT ALARM ALARM 2-10-11 10:18AM L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM CLEAR 2-10-11 10:16AM L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM ALARM 2-10-11 10:11AM L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM CLEAR 2-10-11 10:10AM L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM ALARM 2-10-11 10:04AM T 1 TANK DIESEL TK#CAK010U001 HIGH WATER ALARM CLEAR 2-10-11 9:58AM T 1 TANK DIESEL TK#CAK01OU001 PROBE OUT CLEAR 2-10-11 9:58AM T 1 TANK DIESEL TK#CAK01OU001 PROBE OUT ALARM 2-10-11 9:56AM T 1 TANK DIESEL TK#CAK010U001 HIGH WATER ALARM ALARM 2-10-11 9:52AM T 1 TANK DIESEL TK#CAK01OU001 OVERFILL ALARM CLEAR 2-10-11 9:49AM T 1 TANK DIESEL TK#CAK010U001 OVERFILL ALARM ALARM 2-10-11 9:47AM T 1 TANK DIESEL TK#CAK010U001 LOW PRODUCT ALARM CLEAR 2-10-11 9:45AM T 1 TANK DIESEL TK#CAK010U001 PROBE OUT CLEAR 2-10-11 9:45AM T 1 TANK DIESEL TK#CAK01OU001 PROBE OUT ALARM 2-10-11 9:43AM T 1 TANK DIESEL TK#CAK010U001 LOW PRODUCT ALARM ALARM 2-10-11 9:43AM L 2 PIPE PIPIN SUMP FUEL ALARM CLEAR 2-10-11 9:40AM L 2 PIPE PIPIN SUMP FUEL ALARM ALARM 2-10-11 9:35AM L 1 STP SUMP FILL SUMP FUEL ALARM CLEAR 2-10-11 9:34AM L 1 STP SUMP FILL SUMP FUEL ALARM ALARM 2-10-11 9:3OAM L 5 ANNULAR ANNULAR FUEL ALARM CLEAR 2-10-11 9:29AM L 5 ANNULAR ANNULAR FUEL ALARM ALARM 2-10-11 9:25AM T 1 TANK DIESEL TK#CAK01OU001 LEAK ALARM CLEAR 10-15-10 11:15AM T 1 TANK DIESEL TK#CAK01OU001 LEAK ALARM ALARM 10-14-10 2:44PM T 1 TANK DIESEL TK#CAK01OU001 LEAK ALARM CLEAR 10-13-10 11:12AM T 1 TANK DIESEL TK#CAK010U001 LEAK ALARM ALARM 10-13-10 11:06AM D 1 OTHER CALL CENTER AUTODIAL FAILURE CLEAR 10-13-10 4:57AM T 1 TANK DIESEL TK#CAK010U001 LEAK ALARM CLEAR 10-13-10 4:57AM D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 10-12-10 11:18PM D 1 OTHER CALL CENTER. AUTODIAL FAILURE CLEAR 10-12-10 11:18PM T 1 TANK DIESEL TK#CAK010U001 LEAK ALARM ALARM 10-12-10 10:52PM D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 10-12-10 9:14PM T 2 TANK DIESEL TK#CAK010A002 SUDDEN LOSS ALARM CLEAR 10-12-10 9:54PM T 2 TANK DIESEL TK#CAK010A002 SUDDEN LOS'S ALARM ALARM 10-12-10 8:39PM D 1 OTHER CALL CENTER AUTODIAL FAILURE CLEAR 4-05-10 12:08PM T 1 TANK DIESEL TK#CAK010U001 SUDDEN LOSS ALARM CLEAR 4-05-10 12:03PH D 1 OTHER CALL CENTER AUTODIAL FAILURE ALARM 4-04-10 4:04PM T 1 TANK DIESEL TK#CAK01OU001 PROBE OUT CLEAR 4-04-10 3:46PM I11200 FEB 14, 2011 2:46 PM BKFDCA01 CAK010 1520 20TH ST BAKERSFIELD,CA 93301 661-869-1846 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 2 TANK DIESEL TK#CAK010A002 HIGH WATER WARNING CLEAR 2-10-11 10:28AM T 2 TANK DIESEL TK#CAK010A002 HIGH WATER WARNING ALARM 2-10-11 10:26AM T 2 TANK DIESEL TK#CAK01OA002 HIGH PRODUCT ALARM CLEAR 2-10-11 10:21AM T 2 TANK DIESEL TK#CAK01OA002 HIGH PRODUCT ALARM ALARM 2-10-11 10:21AM T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED CLEAR 2-10-11 10:20AM T 2 TANK DIESEL TK#CAK010A002 INVALID FUEL LEVEL CLEAR 2-10-11 10:20AM T 2 TANK DIESEL TK#CAK01OA002 INVALID FUEL LEVEL ALARM 2-10-11 10:18AM T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED ALARM 2-10-11 10:18AM T 1 TANK DIESEL TK#CAK01OU001 HIGH WATER WARNING CLEAR 2-10-11 9:58AM T 1 TANK DIESEL TK#CAK01OU001 HIGH WATER WARNING ALARM 2-10-11 9:52AM T 1 TANK DIESEL TK#CAK010U001 DELIVERY NEEDED CLEAR 2-10-11 9:45AM T 1 TANK DIESEL TK#CAK010U001 DELIVERY NEEDED ALARM 2-10-11 9:43AM T 1 TANK DIESEL TK#CAK01OU001 LOW TEMP WARNING CLEAR 4-04-10 3:58PM T 1 TANK DIESEL TK#CAK010U001 LOW TEMP WARNING ALARM 4-04-10 3:48PM SYSTEM PRINTER ERROR CLEAR 2-19-10 1:10PM SYSTEM PRINTER ERROR ALARM 2-19-10 1:10PM T 1 TANK DIESEL TK#CAK010U001 HIGH WATER WARNING CLEAR 2-19-10 10:21AM T 1 TANK DIESEL TK#CAK01OU001 HIGH WATER WARNING ALARM 2-19-10 10:16AM T 1 TANK DIESEL TK#CAK010U001 DELIVERY NEEDED CLEAR 2-19-10 10:06AM T 1 TANK DIESEL TK#CAK01OU001 DELIVERY NEEDED ALARM 2-19-10 10:05AM T 2 TANK DIESEL TK#CAK01OA002 INVALID FUEL LEVEL CLEAR 2-19-10 10:01AM T 2 TANK DIESEL TK#CAK01OA002 INVALID FUEL LEVEL ALARM 2-19-10 10:01AM T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM CLEAR 2-19-10 10:00AM T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM ALARM 2-19-10 9:58AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 2-19-10 9:58AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 2-19-10 9:57AM T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM CLEAR 2-19-10 9:57AM T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM ALARM 2-19-10 9:57AM T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED CLEAR 2-19-10 9:57AM T 2 TANK DIESEL TK#CAK01OA002 INVALID FUEL LEVEL CLEAR 2-19-10 9:57AM T 2 TANK DIESEL TK#CAK010A002 INVALID FUEL LEVEL ALARM 2-19-10 9:57AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 2-19-10 9:55AM SYSTEM PRINTER ERROR CLEAR 5-01-09 2:59PM SYSTEM PAPER OUT CLEAR 5-01-09 2:59PM SYSTEM PRINTER ERROR ALARM 5-01-09 2:58PM SYSTEM PAPER OUT ALARM 4-29-09 12:48PM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 4-28-09 11:37AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-28-09 11:14AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 4-06-09 11:58AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-06-09 11:56AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 4-06-09 11:14AM T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED ALARM 4-06-09 11:06AM T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED CLEAR 4-06-09 11:01AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-06-09 10:47AM T 2 TANK DIESEL TK#CAK010A002 DELIVERY NEEDED CLEAR 4-01-09 9:34AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-01-09 9:07AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED CLEAR 4-01-09 9:06AM T 2 TANK DIESEL TK#CAK01OA002 DELIVERY NEEDED ALARM 4-01-09 9:06AM T 2 TANK DIESEL TK#CAK01OA002 HIGH PRODUCT ALARM CLEAR 4-01-09 8:21AM T 2 TANK DIESEL TK#CAK010A002 HIGH PRODUCT ALARM ALARM 4-01-09 8:20AM 120600 FEB 14, 2011 2:47 PM BKFDCA01 CAK010 1520 20TH ST BAKERSFIELD,CA 93301 661-869-1846 TANK ALARM HISTORY TANK 1 DIESEL TK#CAK01OU001 LEAK ALARM OCT 14, 2010 2:44 PM OCT 13, .2010 11:06 AM OCT 12, 2010 10:52 PM HIGH WATER ALARM FEB 10, 2011 9:52 AM FEB 19, 2010 10:16 AM JAN 16, 2009 11:37 AM OVERFILL ALARM FEB 10, 2011 9:47 AM FEB 19, 2010 10:11 AM MAR 6, 2009 10:25 AM LOW PRODUCT ALARM FEB 10, 2011 9:43 AM FEB 19, 2010 10:05 AM MAR 6, 2009 10:23 AM SUDDEN LOSS ALARM APR 4, 2010 3:43 PM FEB 19, 2010 10:08 AM FEB 19, 2010 10:05 AM PROBE OUT FEB 10, 2011 9:56 AM FEB 10, 2011 9:43 AM APR 4, 2010 3:46 PM HIGH WATER WARNING FEB 10, 2011 9:52 AM FEB 19, 2010 10:16 AM JAN 16, 2009 11:37 AM DELIVERY NEEDED FEB 10, 2011 9:43 AM FEB 19, 2010 10:05 AM MAR 6, 2009 10:23 AM CSLD INCR RATE WARN DEC 10, 2008 9:38 AM SEP 18, 2008 10:06 AM SEP 18, 2008 6:58 AM LOW TEMP WARNING APR 4, 2010 3:48 PM TANK 2 DIESEL TK#CAK010A002 HIGH WATER ALARM FEB 10, 2011 10:26 AM OVERFILL ALARM FEB 10, 2011 10:21 AM APR 11, 2008 1:50 PM LOW PRODUCT ALARM FEB 10, 2011 10:18 AM FEB 19, 2010 9:55 AM APR 6, 2009 11:07 AM SUDDEN LOSS ALARM OCT 12, 2010 8:39 PM FEB 19, 2010 9:55 AM APR 28, 2009 11:13 AM HIGH PRODUCT ALARM FEB 10, 2011 10:21 AM FEB 19, 2010 9:58 AM FEB 19, 2010 9:57 AM INVALID FUEL LEVEL FEB 10, 2011 10:18 AM FEB 19, 2010 10:01 AM FEB 19, 2010 9:57 AM PROBE OUT FEB 10, 2011 10:27 AM FEB 10, 2011 10:18 AM FEB 19, 2010 10:00 AM HIGH WATER WARNING FEB 10, 2011 10:26 AM DELIVERY NEEDED FEB 10, 2011 10:18 AM FEB 19, 2010 9:57 AM FEB 19, 2010 9:55 AM MAX PRODUCT ALARM FEB 19, 2010 9:58 AM FEB 19, 2010 9:57 AM MAR 6, 2009 12:39 PM I30200 FEB 14, 2011 2:47 PM BKFDCA01 CAK010 1520 20TH ST BAKERSFIELD,CA 93301 661-869-1846 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 FILL SUMP FEB 10, 2011 9:30 AM FUEL ALARM FEB 19, 2010 9:18 AM FUEL ALARM APR 1, 2009 9:20 AM FUEL ALARM 2 PIPIN SUMP FEB 10, 2011 9:35 AM FUEL ALARM FEB 19, 2010 9:22 AM FUEL ALARM MAR 6, 2009 10:02 AM FUEL ALARM 3 DAYTANK RUPTURE BASN FEB 10, 2011 10:04 AM FUEL ALARM FEB 19, 2010 9:44 AM FUEL ALARM APR 28, 2009 1:49 PM FUEL ALARM 4 DAY TANK ANNULAR FEB 10, 2011 10:11 AM FUEL ALARM FEB 19, 2010 9:50 AM FUEL ALARM MAR 6, 2009 11:49 AM FUEL ALARM 5 ANNULAR FEB 10, 2011 9:25 AM FUEL ALARM FEB 19, 2010 9:14 AM FUEL ALARM FEB 19, 2010 9:11 AM FUEL ALARM 6 PIPING BOX FEB 10, 2011 10:52 AM FUEL ALARM FEB 19, 2010 9:27 AM FUEL ALARM MAY 4, 2009 2:05 PM FUEL ALARM 7 REMOTE PUMP CABINET FEB 10, 2011 1:00 PM FUEL ALARM MFR 2, 2010 10:42 AM FUEL ALARM OCT 13, 2009 10:08 AM SENSOR OUT ALARM TA 1 T asrr 1.THa exr,tGCe+oe 2131 5. Oupon*Ori,e,A.nohei,n, CA 92806 p:?14 560'£322.2 v: •;:.ta;I c February 16, 2011 VIA FED EX. 7967 7236 6635 Bakersfield Fire Department 2101 H Street Bakersfield CA 93301 Re: Monitoring System Certification Spill Bucket Testing AT&T Corporation 1520 20th STREET, BAKERSFIELD, CA GEOPAR: CAK010 To Whom it May Concern: Enclosed are the results for the following tests completed on February 10, 2011: ■ Monitoring System Certification Report Form ■ Spill Bucket Testing Report Form Please do not hesitate to call me if you have any questions. I Yours, Ma h L. Denison Pro ram Manager CA lick 588098 AZ I1c#095984 i NV I.cN 0049566 1 TX lino CR0000041