HomeMy WebLinkAbout2010 RESULTS { Y MONITORING SYSTEM CERTIFICATION VIII III 79 For Use By All Jurisdictions Within the State of California IE Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each monitoring_system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator. The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility Name: ARCO#01960 Bldg.No.: Site Address: 1701 BRUNDAGE LANE City: BAKERSFIELD Zip: 93304 Facility Contact Person: RICH GOSSETT Contact Phone No.: (714)670-3958 Make/Model of Monitoring System: VEEDER-ROOT TLS-350 Date of Testing/Servicing: 8/412010 B. Inventory of Equipment Tested/Certified Check the appropriate boxes to indicatespecific equipment inspected/serviced: Tank ID: 87(N) Tank ID: 87(C) ®In-Tank Gauging Probe. Model: MAG 1 ®In-Tank Gauging Probe. Model: MAG 1 ®Annular Space or Vault Sensor. Model: 409 Z Annular Space or Vault Sensor. Model: 409 ®Piping Sump/Trench Sensor(s). Model: 208 Z Piping Sump/Trench Sensor(s). Model: 208 ®Fill Sump Sensor(s). Model: 208 ®Fill Sump Sensor(s). Model: 208 ®Mechanical Line Leak Detector. Model: LD2000 ®Mechanical Line Leak Detector. Model: LD2000 ❑Electronic Line Leak Detector. Model: ❑Electronic Line Leak Detector. Model: ®Tank Overfill/High-Level Sensor. Model: ATG ®Tank Overfill/High-Level Sensor. Model: ATG ❑Other(specify equipment type and model in Section E on Page 2). ❑Other(specify equipment type and model in Section E on Page 2). Tank ID: (S)87 Tank ID: 91 ®In-Tank Gauging Probe. Model: MAG 1 Z In-Tank Gauging Probe. Model: MAG 1 ®Annular Space or Vault Sensor. Model: 409 Z Annular Space or Vault Sensor. Model: 409 ®Piping Sump/Trench Sensor(s). Model: 208 ®Piping Sump/Trench Sensor(s). Model: 208 ®Fill Sump Sensor(s). Model: 208 ®Fill Sump Sensor(s). Model: 208 ®Mechanical Line Leak Detector. Model: LD2000 ®Mechanical Line Leak Detector. Model: LD2000 ❑Electronic Line Leak Detector. Model: ❑Electronic Line Leak Detector. Model: ®Tank Overfill/High-Level Sensor. Model: ATG ®Tank Overfill/High-Level Sensor. Model: ATG ❑Other(specify equipment type and model in Section E on Page 2). ❑Other(specify equipment type and model in Section E on Page 2). Dispenser ID: 1 -2 Dispenser ID: 3-4 ®Dispenser Containment Sensor(s). Model: 208 ®Dispenser Containment Sensor(s). Model: 208 ®Shear Valve(s). ®Shear Valve(s). ❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s). Dispenser ID: 5-6 Dispenser ID: 7-8 ®Dispenser Containment Sensor(s). Model: 208 ®Dispenser Containment Sensor(s). Model: 208 ®Shear Valve(s). ®Shear Valve(s). ❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s). Dispenser ID: 9-10 Dispenser ID: 11 -12 ®Dispenser Containment Sensor(s). Model: 208 Z Dispenser Containment Sensor(s). Model: 208 ®Shear Valve(s). ®Shear Valve(s). ❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s). •If the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility. C. Certification-I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers' guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is correct and a Plot Plan showing the layout of monitoring a uipment. For any equipment capable of generating such reports,I have also attached a copy of the report;(check all that apply): System set-up ®Alarm history report Technician Name(print): ED GARC/A Signature: Certification No.: A23959 License.No.: 803705 Testing Company Name: TANK-TEK ENVIRONMENTAL CORPORATION Phone No.: (951) 699-8058 Testing Company Address: 31828 CERCLE CHAMBERTIN, TEMECULA, CA 92591 Date of Testing/Servicing: 81412010 Page 1 of 4 UN-036_ w".unidocs.org I IIIIIII VIII III IIII 80 Rev.01117/08 IE Monitoring System Certification D. Results of Testing/Servicing Software Version Installed: 328.03 Complete the following checklist: ®,Yes ❑ No* Is the audible alarm operational? ®' Yes ❑ No* Is the visual alarm operational? ® Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational? ❑ Yes ® No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their proper operation? ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) ® N/A operational? ® Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment ❑ N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes:which sensors initiate positive shut-down? (Check all that apply) ® Sump/Trench Sensors; ®Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ®Yes; ❑No. ® Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no ❑ N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? 90% ❑ Yes* ® No Was any monitoring equipment replaced? If yes,identify specific sensors,probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E,below. ❑ Yes* ® No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) ❑Product; ❑Water. If yes,describe causes in Section E,below. ® Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable ® Yes ❑ No* I Is all monitoring equipment operational per manufacturer's specifications? * In Section E below,describe how and when these deficiencies were or will be corrected. E. Comments: 87 SOUTH ANNULAR SENSOR WAS NOT A LOW POINT.PLACED SENSOR AT LOW POINT. SENSOR IS IN ALARM. Page 2 of 4 UN-036— www.unidomorg Rev.01/17/08 Monitoring System Certification F. In-Tank Gauging/SIR Equipment: ❑ Check this box if tank gauging is used only for inventory control. ❑ Check this box if no tank gauging or SIR equipment is installed. This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring. Complete the following checklist: ® Yes ❑ No* Has all input wiring been inspected for proper entry and termination,including testing for ground faults? ® Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup? ® Yes ❑ No* Was accuracy of system product level readings tested? ® Yes ❑ No* Was accuracy of system water level readings tested? ® Yes ❑ No* Were all probes reinstalled properly? ® Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed? *In Section H,below,describe how and when these deficiencies were or will be corrected. G. Line Leak Detectors (LLD): ❑ Check this box if LLDs are not installed. Complete the followin g checklist: ® Yes ❑ No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance? ❑ N/A (Check all.that apply) Simulated leak rate: ® 3 g.p.h.; [10.1 g.p.h; ❑ 0.2 g.p.h. ® Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements? ® Yes ❑ No* Was the testing apparatus properly calibrated? ® Yes ❑ No* For mechanical LLDs,does the LLD restrict product flow if it detects a leak? ❑ N/A ❑ Yes ❑ No* For electronic LLDs,does the turbine automatically shut off if the LLD detects a leak? ® N/A ❑ Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled ® N/A or disconnected? ❑ Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions ® N/A or fails a test? ❑ Yes ❑ No* For electronic LLDs,have all accessible wiring connections been visually inspected? ® N/A KYes ❑ No* Were all!items on the equipment manufacturer's maintenance checklist completed? * In Section H,below,describe how and when these deficiencies were or will be corrected. H. Comments: Page 3 of 4 UN-036— www.unidocs.org Rev.01/17/08 SWRCB,January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of LIST spill containment structures. The completed form and printouts from tests (if applicable)should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: ARCO#01960 1 Date of Testing: 814110 Facility Address: 1701 BRUNDAGE LANE,BAKERSFIELD, CA 93304 Facility Contact: RICH GOSSETT I Phone: (714) 670-3958 Date Local Agency Was Notified of Testing: 7/28/10 Name of Local Agency Inspector(f present during testing): NONE PRESENT 2. TESTING CONTRACTOR INFORMATION Company Name: TANK TEK ENVIRONMENTAL CORPORATION Technician Conducting Test: ED GARCIA Credentials': ® CSLB Contractor ❑ ICC Service Tech. ❑ SWRCB Tank Tester ❑ Other(Specify) License Number(s): 803705 3. SPILL BUCKET TESTING INFORMATION Test Method Used: ®Hydrostatic ❑Vacuum ❑ Other(Spec) Test Equipment Used: VISUAL Equipment Resolution: +1.0.002" Identify Spill Bucket(By Tank Number, Stored Product, etc.) 87(N) FILL 87(N)VAPOR 87(C)FILL 87(C)VAPOR Bucket Installation Type: ❑Direct Bury ❑Direct Bury ❑ Direct Bury ❑Direct Bury ®Contained in Sump ® Contained in Sump ®Contained in Sump ®Contained in Sump Bucket Diameter: 12.00" 12.00" 12.00" 12.00" Bucket Depth: 12.00" 12.00" 12.00" 12.00" Wait time between applying 5 MIN 5 MIN 5 MIN 5 MIN vacuum/water and start of test: Test Start Time(Ti): 9:00 AM 9:00 AM 9:00 AM 9:00 AM Initial Reading(RI): 9.00" 8.00" 8.00" 8.25" Test End Time(TF): 10:00 AM 10:00 AM 10:00 AM 10:00 AM Final Reading(RF): 9.00" 8.00" 8.00" 8.25" Test Duration(TF—TI): 1 HR 1 HR 1 HR. 1 HR Change in Reading(RF-Rj): 0 0 0 0 Pass/Fail Threshold or Criteria: +/-0.002" +/-0.062" +/-0.002" +1-0.002" Tesf Result ® Pass ❑Fail ® ;Pass... ..❑Fail ;Pass ❑Fail ® :Pass.;. ❑Fail, Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) I CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report Is true,accurate,and in full compliance with legal requirements. Technician's Signature: Date: 814110 State laws and regulations do not currently require testing to be performed by a qualified contractor.However,local requirements may be more stringent. SWRCB,January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable)should be provided to the facility owner/operator for submittal to the local regulatory agency: 4. FACILITY INFORMATION Facility Name: ARCO#01960 1 Date of Testing: 814110 Facility Address: 1701 BRUNDAGE LANE,BAKERSFIELD, CA 93304 Facility Contact: RICH GOSSETT Phone: (714)670-3958 Date Local Agency Was Notified of Testing: 7/28/10 Name of Local Agency Inspector(if present during testing): NONE PRESENT 5. TESTING CONTRACTOR INFORMATION Company Name: TANK TEK ENVIRONMENTAL CORPORATION Technician Conducting Test: ED GARCIA Credentials': ®CSLB Contractor ❑ ICC Service Tech. ❑ SWRCB Tank Tester ❑Other(Spec) License Number(s): 803705 6. SPILL BUCKET TESTING INFORMATION Test Method Used: ®Hydrostatic El Vacuum ❑Other(Specify) Test Equipment Used: VISUAL Equipment Resolution: +/-0.002" Identify Spill Bucket(By Tank Number, Stored Product, etc.) 87(S) FILL 87(S)VAPOR 91 FILL 91 VAPOR Bucket Installation Type: . ❑ Direct Bury ❑Direct Bury ❑ Direct Bury ❑Direct Bury ®Contained in Sump ® Contained in Sump ® Contained in Sump ®Contained in Sump Bucket Diameter: 12.00" 12.00" 12.00" 12.00" Bucket Depth: 12.00" 12.00" 12.00" 12.00" Wait time between applying 5 MIN 5 MIN 5 MIN 5 MIN vacuum/water and start of test: Test Start Time(TI): 9:00 AM 9:00 AM 9:00 AM 9:00 AM Initial Reading(R): 8.00" 8.50" 8.25" 8.00" Test End Time(TF): 10:00 AM 10:00 AM 10:00 AM 10:00 AM Final Reading(RF): 18.001, 8.50" 8.25" 8.00" Test Duration(TF—Tj): 1 HR 1 HR 1 HR 1 HR Change in Reading(RF-RI): 0 0 0 0 Pass/Fail Threshold or Criteria: +1-0.002" +1-0.002" +/-0.002" +/-0.002" Test Result ;® ;Pass ❑ Fail ®::Pass ❑Fail ® :Pass ❑Fail:.:. Pass ❑Fail Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report Is true,accurate,and in full compliance with legal requirements. Technician's Signature: Date: 814110 ' State laws and regulations do not currently require testing to be performed by a qualified contractor.However,local requirements may be more stringent. by Line Leak Detector Test Data Sheet Station# 01960 Date 8/4 20 10 Address 1701 BRUNDAGE LANE BAKERSFIELD, CA 93304 Test Information 1 2 3 4 5 Product 87 87 87 91 Manufacturer VMI VMI VMI VMI Model LD2000 LD2000 LD2000 LD2000 Full Operating Pressure (psi) Y8 PSI 32 PSI 30 PSI 32 PSI Line Bleed Back(ml) 80 ML 130 ML 235 ML 150 ML Trip Time (sec) 2 SEC 4 SEC 3 SEC 4 SEC Metering Pressure (psi) 10 PSI 10 PSI 10 PSI 10 PSI F/E Holding Pressure (psi) 28 PSI 32 PSI 30 PSI 32 PSI Test Leak Rate (ml/min)(gph) 3 GPH 3 GPH 3 GPH 3 GPH PASS or FAIL PASS PASS PASS PASS Comments: This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the equipment manufacturers procedures and limitations and the results as listed are to my knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. Inspected By: Contractor TANK-TEK ENVIRONMENTAL CORP. Technician ED GARCIA Lic# A23959 Signature �" K. Float and Chain Equipment: ® Check this box if floats and chains are not present at this site. ❑ Check this box if float and chain equipment is installed but only as secondary leak detection. This section must be completed if floats and chains are used to perform leak detection monitoring. Complete the following checklist: ❑Yes ❑ No* Were all float and chain equipment properly inspected and tested for correct functionality? ❑Yes ❑ No* Were all float and chain equipment certified to be working properly? * In the Section M,below,describe how and when these deficiencies were or will be corrected. L. Impact Valves: ❑ Check this box if impact valves are not installed. Complete the following checklist: ®Yes ❑ No* Were all impact valves properly inspected and tested for correct functionality? ®Yes ❑ No* Were all impact valves certified to be working properly? *In the Section M,below,describe how and when these deficiencies were or will be corrected. M. Comments: Page 5 of 5 Monitoring System Certification Facility#: 01960 p Contractor: TANK-TEK ENVIRONMENTAL CORP. Address: 1701 BRUNDAGE LANE Address: 31828 CERCLE CHAMBERTIN City, _State: BAKERSFIELD,CA City, State: TEMECULA,CA 92591 Test Date: 81412010 Phone: 951)699-8058 Type of test: ENVIRONMENTAL COMP Impact Valve Yes No Testing Technician: ED GARCIA Test rformed Burin line test? impact Secure Valve Impact Secure Valve Disp# Grade Make Mount? Lock? Pass/Fail Comment Disp# Grade Make Mount? Lock? Pass/Fail Comment 1 -2 87 OPW Yes Yes Pass 1 -2 91 OPW Yes Yes Pass 3-4 87 OPW Yes Yes Pass 3-4 91 OPW Yes Yes Pass 6-6 87 OPW Yes Y e s Pass 5-6 91 OPW Yes Yes Pass 7-8 87 OPW Yes Yes Pass 7-8 91 OPW Yes Yes Pass 9-10 87 OPW Yes Yes Pass 9-10 91 OPW Yes Yes Pass 11 -12 87 OPW Yes Yes Pass 11 -12 91 OPW Yes Yes Pass Monitoring System Certification UST Monitoring Site Plan 1701 BRUNDAGE LANE,BAKERSFIELD,CA 93304 Site Address: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . .12 L18 11 . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1.1. . . . . L10• L9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 . . . I . . . . . . . . . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . . . . . . L5] . . . . . . . . . . . . . . . . . . . . . . . . . .E. . . . . . . . . . F . . . . . . . . . . . . . . . . . . . . . . . . . . -EiiED. * ' ' . . . * . 4 . . . . . . 2 . . . . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . . . . . L14. . . . . L13' L12 . . . . . . . . . . ' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. 7 . . . . . . . . . . . . 5 . . . . . . . . . . . I . , . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . .E. . . . . . . . . . 8 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1. . . . . .L16 L15 . . . . . . . . . . . . . . . . . . ! . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87(N) \4 D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I . . . . . I . . . . . . . . . . . . . . . . . . . . . . L4. . . . . .L3 - L2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . .VAPOR. ANNUI-AR. . . . MONITOR . . . . . . PIFINQ . . . . . . . . . . . . . FILL O. . . . . TURBINE. O VENT .0 . . . . . . ATG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I . . . . . . . . 8 4 10 Date map was drawn: Instructions If you already have a diagram that shows all required information,you may include it rather than this page,with your Monitoring System Certification. On your site plan,show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installed:monitoring system control panels;sensors monitoring tank annular spaces,sumps,dispenser pans,spill containers,or other secondary containment areas;mechanical or electronic line. leak detectors;and in-tank liquid level probes(if used for leak detection). In the space provided,note the date this Site Plan was prepared. Monitoring System Certification 12/07 2/21/07 o�a�o 24672' Aldi;i� am, Fm l y 1701 Brundage Lane Bat"ersf i el d y CA 91304 S7Sitl~I 'JrTUb` AUG 4, 2010 7fo AM AUG' 4, wolo 7:51 .AM- - ti;'ZSTEM .STl b7jREPORT ALL F1P'CTI:OPJS`,tty+�Rf)rit. ,'F'..fir„ ,,;;_,' . ,' .I >J •., VOLi7N '=~k SOFTWARE REVISION LEVEL 90%' ULLULLAGE. , VERSION 328.05 SOFTWARE# 346328-100-D ske9r3 FG E= 4399 GALS sf��{.�; .:-�� *I�t°,`�','�;•`,"`�<tt�'s'r`>: �:•;: „.1• TC V c CREATED - 08.06.06.17.21 VOLUME�._ :�.a��l GFiLN HEIGHT 40.69 INCHES' ME ISH"�`$� WATER VOL 0 GALS S-MODULE# 330160-104-a �iIFT TIME 2 DISABLEI, WATER 0.00 INCHES SYSTEM FEATURES: ';RIFT TIi"IE 3 DISABLE: TEMP 81 .3 DEC F PERIODIC IN-TANK TESTS -RIFT TIME 4 DISABLE: ANNUAL .I N-TANK TESTS BIR ;::,41 FT BIR PRINTOUTS T 2:UNLEADED R ISD 11iSABLED VOLUME = 4287 CAL2 :)LILY BIR PRINTOUTS ULLAGE = 5397 GALS i,'SABLED 90%S ULLAGE,- 4428 �artLS !' CI:ETED�DELIVERY . TC VOLUME = 4226 GALS DISABLED HEIGHT - 40.48 INCHES T.".NK PER TST NEEDED WRI•- WATER VOL = 0 GALS DISABLED WATER = 0.00 1NCHES TANK ANN TST NEEDED HR!l TEMP = 80,3 DEG F DISABLED t LINE RE-ENABLE METHOD T 3:UM,EADED.R PASS LINE TEST VOLUME 4286 GALS ULLAGE = 5396 GALS LINE PER TST NEEDED WRN 90: ULLAGE 4429 GALS DISABLED TC VOLUME = 4220 GALS LINE ANN TST NEEDED WRN HEIGHT A 40.47 INCHES DISABLED WATER VOL u 03AL8 WATER = 0.00 I Ni'HES PRINT TC VOLUMES TEMP 82.0 DEC F ENABLED TEMP COMPENSATION T 4:UL PREMIUM VALUE (DEG F ) : 60.0 VOLUME 2087 GALS STICK HEIGHT OFFSET ULLAGE = 7597 GALS DISABLED 90% LJLLAGE- 6622 GALS ULLAGE: 90% TC VOLUME = 2049 GALS HEIGHT - 2,I.,;a INCHE.. H-PROTOCOL DATA FORHAT WATER VOL - •0 GALS HEIGHT WATER 0.00 INCHE:, PRECISION TEST DURATION TEMP 85.4 -DEG F HOURS: 72 DAYLIGHT SAVING TIME ENABLED MANIFOLDED TANKS START DATE MAR WEE}; 2 SUN TOTALS T 1 :UNLEADED START TIME 2:00 TIME.R AM T 2:UNLEADED R DATE T 3:UNLEADED 'R END 1 SUN VOLUME g. 12889 GALS i END TIME TC VOL IJI� .. 12697 GAL 2:00 AM RE-DIRECT LOCAL PRINTOUT COMMUNICATIONS SETUP PORT SETTINGS: COMM BOARD 1 (RS-23?) BAUD RATE 9600 PARITY NONE STOP BIT I STOP DATA LENGTH: B DATA RS-232 SECURITY EURO PROTOCOL PREFIX CODE : DISABLED S COMM BOARD : 2 (EIiIM ) _ RS-232 SECURITY -- CODE. : DISABLED AUTO DIAL TIME 3,,CJP.:::`: SYSTEM SECURITY COMM BOARD 3 (S-&;T ) CODE 000000 BAUD RATE 9600 PARITY NONE D B:VEEDER ROOT (FMS) MAINTENANCE HISTORY STOP BIT i STOP DIAL ON DATE DISABLED VATA,.I.ENGTH: 8 DATA .JUL 22. 2010 DIAL TIME 5:25 AM TANK CHART SECURITY �.:, I ,_: RECEIVER REPORTS i DISABLED .:' �ifAT1jr .HIGH CUSTOM ALARMS F(IIvGS: DISABLED �4tRCI I~IPl IT SERVICE NOTICE M I T DISABLED AUTO OVERFILL LIMIT D I SABIjED MASS/DENSITY AUTO L W PRODUCT DISABLED DISABLEW AUTO THEFT LIMIT DISABLED AUTO DELIVERY START DISABLED AUTO DELIVERY END DISABLED AUTO EXTERNAL INPUT 014 DISABLED AUTO EXTERNAL INPUT OFF DISABLED AUTO SENSOR FUEL ALARM DISABLED AUTO SENSOR WATER ALAR1? DISABLED AUTO SENSOR OUT ALARM DISABLED RECEIVER SETUP: D 8:VEEDER ROUT (FMS) C2 RCVR TYPE: COMPUTER PORT NO: 3 RETRY NO: 5 RETRY DELAY: 5 CONFIRMATION REPORT: RS-232 END OF DISABLED AUTO DIAL ALARM SETUP 1 SD SITE ALAFJ°i;. - - - - - -- ISD STAGE I WARN ISD GROSS PRES WARN IN-TANK SETUP D 8:VEEDER ROOT (FMSi ISD GROSS PRES FAIL — — — — — — — — — — ISD DEGRD PRES WARN IN•-TANK AL;A' MS ISD DEGRD PRES FAIL T 1 :UNLEADED R ALL:.HIC,H WATER ALARM PRODUCT CODE 1 ALL:SUDDEN LOSS ALARM ISD VAPOR LEAK WARN TWERMAL: GOEFF, : .0010700 ALL;PROBE OUT ISD VAPOR LEAK FAIL 52,00 �_.::' ALL:H 1� T. WA.N I..i ISD VF PRES WARN # <) ,,,r+�» 20 PTS ALL ISD VP PRES FAIL F: _ `�': '' 9684' ISD VP STATUS WARN v h. ALL C, �r.,r �, 5624.. ISD VP STATUS FAIL ;.`*.f; 93130 MISSING RELAY SETUP 9020 1 MISSING HOSE SETUP . , b.:;�?. sa , :. 8580 MISSING TANK SETUP _ ,' `. `'`; .. 8079 MISS VAPOR FLOW MTR 7529 MISS VAPOR PRES SEN '. 8:, 695 7 MISSING VP INPUT '55:2 I NCH VOL E942 r` NE•. �, #'i ISD SETUP WARN 50.6 INCH VOL 5'x07 :,gLL' Nk► .. i� ti: ISD SETUP FAIL 46.0 INCH VOL 5061 '' '= ISD SENSOR OUT WARN 41 .4 INCH VOL 4413 ,gLL:W ;u, ISD SENSOR OUT FAIL 36.8 INCH VOL 37t37 ALL:Hl Ld 1S-A I''ls PC—ISD FAILURE 32.2 INCH VOL 3157 ALL:LOW LIQUID ALARM 27.6 INCH VOL 2550 ALL:LIQUID WARNING ISD HOSE ALARMS 23.0 INCH VOL 1973 ALL:GROSS COLLECT WARN 10.4 INCH VOL 1437 COMM SIDE DIM ALM ALL:GROSS COLLECT FAIL 13.8 INCH VOL 966 ALL:DISABL.ED DIM ALARM ALL:DEGRD COLLECT WARN 9.2 INCH VOL : 648 ALL:COMMUNICATION ALARM ALL:DEGRD COLLECT FAIL 4.6 INCH VOL 217 ALL:TRANSACTION ALARM ALL:FLOW COLLECT WARN METER DATA NO ALL;FLOW COLLECT FAIL RECONCILIATION ALM ALL:AIRFLOW MTR SETUP ALL:PROD THRESHOLD ALM FLOAT SIZE: 2.0 IN. ALL:CLOSE SHIFT WARNING VAPOR FLW MTR ALMS ALL:CLOSE DAILY WARNING ALL:CHK VAPOR FLOW MTR WATER WARNING 0.8 PRESSURE LINE LEAK PMC ALARMS HIGH WATER LIMIT: 1 .0 ALL:GROSS LIr4E FAIL VP RUNTIME FAULT MAX OR LABEL VOL: 9684 ALL:ANNUAL LINE FAIL VP EMISSIONS WARN OVERFILL LIMIT 90:% VP EMISSIONS FAIL 8715 . ALL:PLLD OPEN ALARM VP PRESSURE WARN HIGH PRODUCT 95% ALL:UNKNOWN ALARM VP PRESSURE FAIL 9199 ALL:PLLD SHUTDOWN ALARM VP DUTY CYCLE WARN DELIVERY LIMIT 10 110 ALL:UNKNOWN ALARM VP DUTY CYCLE FAIL 968 ALL:UNKNOWN ALARM ALL:PERIODIC LINE FAIL PMC SETUP FAIL LOW PRODUCT 550 ALL:LOW PRESSURE ALARM LEAK ALARM LIMIT: 15 ALL:UNKNOWN ALARM SUDDEN LOSS LIMIT: 40 ALL:CONT HANDLE ALM TANK TILT 0.00 ALL:LN EQUIP FAULT ALM PROBE OFFSET 0.00 ::MARTSENSOR ALARMS ALL:SETUP DATA WARNING ,:"IPHON MANIFOLDED TANKS . ALL:COMMUNICATION ALARM -#! 02.03 ALL:SENSOR FAULT ALARM _ — — — - - - - i.INE MANIFOLDED TANKS ALL:FUEL WARNING T#: NONF ALL:FUEL ALARM ALL:WATER WARNING ALL:WATER ALARM ALL:HIGH LIQUID WARNING ALL:HIGH LIQUID ALARM ALL:LOW LIQUID WARNING ALL:LOW LIQUID ALARM ALL:TEMPERATURE WARNING ALL:RELAY ACTIVE ALL:INSTALL ALARM ALL:SENSOR FAULT WARN ALL:VACUUM WARNING ALL:NO VACUUM ALARM LEAK M I N ANNUAL ;;fib!': FLOA'C b 1'Llr: WATER WARNING 0.8 i HIGH WATER LIMIT: 1 .0 T 3:UNLEADED R PERIODIC TEST TYPE ':' PRODUCT CODE 1 STANDARD MAX OR LABEL VOL: %84 THERMAL COEFF : .000700 OVERFILL LIMIT 90%; TANK DIAMETER 92.00 ANNUAL TEST FAIL 8715 TANK PROFILE 20 PTS ALARM DISABLED HIGH PRODUCT 95% FULL VOL 9684 9199 67.4 INCH VOL 9624 PERIODIC TEST FAIL DELIVERY LIMIT 10% 82.8 INCH VOL 9380 ALARM DISABLED 968 78.2 INCH VOL 9020 73.6 INCH VOL 8580 GROSS TEST FAIL LOW PRODUCT 55U LEAK ALARM LIMIT: 15 69.0 INGH VOL 8079 . ALARM DISABLED SUDDEN LOSS LIMIT: 40 59.8 INCH VOL : 6957 ANN TEST AVERAGING: OFF TANK TILT 0.50 55..2 INCH VOL 6342 PER TEST AVERAGING: OFF PROBE OFFSET 0.00 50.6 INCH VOL 5707 46.0 INCH VOL 5061 TANK TEST NOTIFY: OFF SIPHON-MAN1FOLDED TANKS 36.8 INCH VOL 3787 TNX TST SIPHON BREAK:OFF TO: 01,03 32.2 INCH VOL 3157 LINE MANIFOLDED TANKS 27.6 INCH VOL. 2550 DELIVERY DELAY 1 MIN TO: NONE 23.0 INCH VOL 1973 PUMP THRESHOLD 10.00% 18.4 INCH VOL 1437 13.8 INCH VOL 966 LEAK MIN PERIODIC:: 25% 9.2 INCH VOL 548 2421 4.6 INCH VOL 217 LEAK MIN ANNUAL 50% °!ETER DATA NO 4842 FLOAT SIZE: 2.0 IN. PERIODIC TEST TYPE WATER WARNING 0.8 STANDARD HIGH I,,IATER LIMIT: 1 .0 T 2:UNLEADED.R. ANNUAL TEST FAIL MAX. OR.,LABJEL :VOL; 9684 PRODUG"l ,'. +» °.r•i: ALARM DISABLED OVERF TILL L 1 M I T 90% 5 8715 Tti'•h . THE PERIODIC TEST FAIL k ¢f U 4108 , ur-r3" 95.c ALARM DISABLED ,10%.. GROSS TEST FAIL 968 ALARM DISABLED ;� i;v`�` /^t•�,+' ���{ i F� ANN TEST AVERAGING: OFF LA $;;LF�1f "F+': 15 PER TEST AVERAGING; OFF ;i • . +f S ` `� 1 .1 0 TANK OBE T F hLT:'"'` FSET n.00 :c r tx3 .I :} q TANK TEST NOTIFY: OFF PR O G :y0 ;;rya.,, ::s �12 55'' " ' TNK TST SIPHON BREAK:OFF 50.6 fiICHw �i I!': kil 46.0 1 NCH 50E,1 DELIVERY DELAY 1 MIN 41 .4 INCH VOL 4413 PUMP THRESHOLD 10.00% 36.8 INCH VOL : .D787 32.2 INCH VOL 3157 27.6 INCH VOL 2550 23.0 INCH VOL. 1973 18.4 INCH VOL 1437 13.8 INCH VOL. 966 9.2 INCH VOL 548 4.6 INCH VOL 217 METER DATA : NO rLUlil :ii�E. �.� ; ;• S 1 PHON MAN I FOLDED TANK;3 WATER WARNING 0.LI T#: 01.02 HIGH WATER LIMIT: 1 .0 L I NE MAN I FOLDED TANKS TO: NONE "1AX GR�,IgA LEAK MIN PERIODIC:GD I C: 25� �, ^�•'°ice: `�� _ LEAK MIN ANNUAL 5 w k 4842 LINE LEAK LOCKOUT SETUP 4 - - - - - - - - - - - .. PERIODIC TEST T`.PEd ,,: LOCKOUT SCHEDULE DAILY �AtVk'fil; " DAILY P12OB1= CS"FIS >`? ":z'' ;`00 START TIME: DISABLED ' STOP TIME DISABLED ANNUAL TEST FAIL ALARM DISABLED SIPHON IIANIFOLDED TANKSh PERIODIC TEST FAIL T#' NONE ALARM DISABLED LINE MANIFOLDED Ti=NKS T#: NONE GROSS TEST FAIL ALARM DISABLED LEAK MIN PERIODIC: 25% ANN TEST AVERAGING: OFF 2421 PER TEST AVERAGING: OFF LEAK MIN ANNUAL 50% TANK TEST NOTIFY: OFF 4842 LIQUID SENSOR SETUP TNK TST SIPHON B�:EAK:UF1' - - - - µ - - - - - - . PERIODIC: TEST TYPE DELIVERY DELAY 1 N 11 STANDARD L• 1 :87 NORTH STP SUMP PUMP THRESHOLD 10.00% TRI-STATE (SINGLE FL.06'1 ANNUAL TEST FAIL CATEGORY : S'TP SUMP ALARM DISABLED PERIODIC .TEST FAIL L 2:91 ANNULAR ALARM DISABLED TRI-STATE (SINGLE FLOAT) CATEGORY : ANNULAR SPACE ✓: GROSS TEST FAIL ... ALARM DISABLED ANN TEST AVERAGING: OFF L 3:91 FILL SUMP PER TEST AVERAGING: OFF TRI-STATE (SINGLE FLOr;T CATEGORY : PIPING SUMP PRODUCT CODE T 4:U PREMIUM M 3 TANK TEST NOTIFY: OFF THERMAL COEFF : .000706 L. 4:91 UNL STP SUMP 'TANK DIAMETER 92.00 TNK TST SIPHON bREAK:t?FF TANK PROFILE 20 TRI--STATE i S I NGLE FLv{�t i • I FULL VOL 9681 DELIVERY DELAY 1 MIN CATEGORY STP SUMP 87.4 INCH VOL 9624 PUMP THRESHOLD 10.00% 82.8 INCH VOL 9380 "r: q 78.2 INCH VOL 9020 ;;j=?� �:rBT. I . s ;.11 : '<'-<. 73.6 INCH VOL 8580 .tY4r,. ""::ti ',FEOFi; 69.0 INCH VOL 8079 4.4 I VOL 7529 r . 6 NCH k 59.8 INCH VOL 69v: �s f.:•9'9.'' '`?F. ,'. : .�' 55.2 INCH VOL • 6342 I, " s` ' r 50.6 INCH VOL • 5707 "zF FLOAT - 46.0 0 I NCH VOL : 506: 41 .4 INCH VOL : 4410 36.8 INCH VOL : 378? 32.2 INCH VOL 3157 LEAK TEST METHOD 27.6 INCH VOL 2550 L 7:DISP.5-6 UDC 23,0 INCH VOL : 1973 r - TRI -STATE (SINGLE FLOAT 18.4 INCH VOL : 143'1 TEST ON DATE e: ALL TANK 13.8 INCH VOL 966 JUN 6, 2008 CATEGORY DISFEhVSER PAL 9.2 INCH VOL 548 START TIME : DISABLED 4.6 INCH VOL 217 TEST RATE :0.20 GAL/HR - -.- - — - — METER DATA NO DURATION 2 HOURS — — TST EARLY STOP:DISABLED LEAK TEST REPORT FORMAT NORMAL PLLD LINE DISABLE SETUP OUTPUT 1?ELAY SETUP L is:1J 1 L:.. — — —.ti —..ii.:- _..—....;.y'-4:, — — TR I-STA TE S 1 NGLE !LUH'1 CATEGORY DISPENSER PAN F:.t 9:67 SOUTH ANNULHk 4t TRI—STATE !SINGLE FLOAT) r =t , ;;1 RECONCILIATION SETUP CATEGORY ANNULAR SPACF. r. -• �+ EDIM 1 G 1,10:87 SOUTH FILL. SUMP t AUTOMATIC DAILY CLOSING TR1-STATE (SINGLE FLOAT) T 3: .' x TIME: 2:00 AM .-'ATEC.ORY P I P I,NG SUMP LIQUID PENS ALMS AUTO SHIFT itl CLOSING. ALL:FUEL ALARM TIME: DISABLED L11 :87 SOUTH STP SUP•IP ALL:SENSOR OUT AI ARPI TRI-STATE (SINGLE Fi.AAe) ALL:SHORT ALARM AUTO SHIFT 02 CLOSING CATEGORY : STP SUMP ISD SITE REARMS TIME: DISABLED ISD GROSS PRES FAIL. t!3 CLC�S I IOC. L12:87 CENTER ANNULAR ISD DEGRD PRES FAIL TIME:AUTO SHIFT FT 03D TRI-STATE (SINGLE FLOAT) ISD VAPOR LEAK FAIL CATEGORY : ANNULAR SPACE i.SD HOSE ALARMS AUTO SHIFT 04 CLOSING ALL:GROSS COLLECT FAIL TIME: DISABLED ALL:DEGRD COLLECT FAIL 13:87 CENTER FILL SUMP PERIODIC REtONCILIATIC'! TRI-STATE (SINGLE FLOAT) R 2:PREMIUM SHUTDOWN MODE' MONTF.:..' CATEGORY PIPING SUMP TYSTANDARD ALARM: DISABI. NORMALLY CLOSED TEMP COMPENSATION 1-14:87. CENTER STP,.SUF1P:, >;,; : "� STANDARD TRI-STATE (S.I N 1.E:;EE Pi ,r=,;j TANK 0: 4 METER CALIBRATION CATEGORY STP OFFSE],�;,' 0.000 IN-TANK ALARMS BUS.SLOt .IrLI,EI METER T�: ' T 4:H I G H WATER ALARM 1-15:87 NORTH ANNULAR': �.."'`'; , . Y,w..R-L-,..�,:,t::`a:,;':�: _. •. TRI-STATE (2 I d,4 LE FLOAT� ;`: .I, 1>��T.Y. LIQUID SENSOR ALMS CATEGORY ANNIiLAR, SPAC{^ , ALL:FUEL ALARM ALL:SENSOR OUT ALARM +�•�=; � ALL:SHORT ALARM L16.';37 NORTH FILL SUMP e<� �: ' a• TRI—STATE (SINGLE FLOAT) ISD SITE ALARMSa ISD GROSS PRES FAIL CATEGORY PIPING S UMF ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL L17:DISP.9-10 UDt.' TRI-STATE (SINGLE FLOAT) -ISD HOSE ALARMS CATE( )RY : DISPENSER PAN ALL:GROSS COLLECT FAIL SMARTSENSOR SETUP ALL:DEGRD COLLECT FAIL 1 3:OVERFILL ALARM s I :DISPI-2 FLM L18:D1SP.11-12 UDC TYPE: CATEGORY AIR FLOW METER TRI-STATE (SINGLE FLOAT) t:OSTANDARD * CATEGORY DISPENSER PAN s 2:DISP.3-4 FLM :INK tt: ' NONE CATEGORY AIR FLOW METER s 3:DISP,5-6 FLM CATEGORY AIR FLOW METER !N-TANK ALARMS ALL:OVERFILL ALARM s 4:DISP.7-8 FLM ALL:HIGH PRODUCT ALARM (70TEGORY AIR FLOW METER ALL:MAX PRODUCT ALARM <a 5:DISP.9-10 FLM CATEGORY AIR FLOW METER 6:DISP.11-12 FLM CATEGORY AIR FLOW ME'T'ER s 7:PRESRURE SENSOR CATEGORY VAPOR PRESSURE �PMC SETUP EVR TYPE: VACUUhIa '_ i pMC VERSION: 01 .01 VACUUM ASSIST TYP1?:,'''':'i': " HEALY VAC J i VAPOR PROCESSOR TYPE NOZZLE A./ RARANGE !. NONE I_ MAX: 1 . 15 11IN: 0.95 PROCESSOR CONTROL LEVEL: VAPOR PROCESSOR TYPE NONE NONE ANALYSIS TIMES TIME: 7:59 AM DELAY MINUTES: 1 ACCEPT HIGH ORVR: ---- IN-TANK ALARM ----- - -- I N -TANK ALHRI°I ENABLED T 1 :UILEADED R T 3:UNLEADED R PROBE OUT INVALID FUEL LEVEL ISD HOSE TABLE AUG 4, 2010 8:45 AM AUG 4, 2010 8:49 All ID FP FL HL AA RR - 01 01 01 02 01 UU 02 02 02 02 01 UU 03 03 03 02 02 UU 04 04 04 02 0" UU 05 05 05 02 0:3 UU 06 06 06 02 03 UU 07 07 07 02 04 UU 08 08 08 02 04 UU ---- IN-TANK ALARM ----- '-- IN-TANK ALARM ----- 09 . 09 09 02 05 UU T 2:UNLEADED R T 4:UL PREMIUM 10 10 10 02 05 UU PROBE OUI PROBE OUT 11 11 11 02 O6 UU AUG 4, 2010 8:46 All AUG 4, 2010 850 API 12 12 12 02 06 UU ISD A I RFL0W.r1ETQ,' MAP I D SER : 4 rrSS w IN-TANK ALARM - -- t� T 2:UNLEADED 'R INVALID FUEL LEVEL �'' AUG a. 2010 8:47 AM 4. 01 901 501 301 U U 1 02 902 502 302 U U 1 03 903 503 303 U U 2 04 904 504 304 U U 2 05 905 505 305 U U 3 --- IN--TANK ALARM -- - 06 906 506 306 U U 0 T 2:LINLEADFD R 07 907 507 307 U U 4 PROBE OUT 08 908 508 308 U U 4 AUG 4. 2010 8:48 All 09 909 509 309 U U 5 10 910 510 310 U U 5 11 911 511 311 U U 6 12 912 512 312 U U 6 LABEL TABLE I ' ---- 2: BLENDS 3: REGULAR 4: MID GRADE ?G 5: PREMIUM 6: GOLD 7: BRONZE 8: SILVER 9:' BLEND2 10: BLEND4 2467`22 ARC'O am,vFrn 19 T I :UNLEADED R 1701 Brunda•ae Lane INVENTORY INCREASE Baker zfiald CA 93304 INCREASE START ---- 1N-TANK HLARM ----- AUG 4, 2010 8:49 AM T 4:UL PREMIUM AUG 4, 2010 8:58 AM HIGH WATEP ALARM VOLUME 7943 GALS � . AUG 4, 2010 8:54 AM HEIGHT - 67.84 1 NCHES,'.:.: WATER - 3.50 INC H 132 y SYSTEM STATUS REPORT TEMP 84.3 DEG .1:';' ... - - - - - - - - - - - - . T 1 :HIG'H WATER ALARM INCREASE END t T 1 :PROBE OUT AUG 4, 2010 8:t3 AM T 1 :H1GH WATER WARNIW VOLUME - 7944 GALS HEIGHT - 67.84 INCHES ---- IN-TANK ALARM ----- T '?:INVALID DUEL LEVEL WATER = 2.50 INCHES T 4:UL PREMIUM T 2;PROBE OUT TEMP = 8S.5 DEG F i I GH WATER WARNING AUG 4, 2010 6:54 All T 3:HIGH WATER ALARM GROSS INCREASE= 1 TC NET INCREASE= -7 T 3:INVALID FUEL LEVEL T 3:PROBE OUT T ':UNLEADED R INVENTORY INCREASE T 3:HIGH WATER WARNING INCREASE :WART T 4:HIGH WATER ALARM AUG 4, 2010 6:49 AM ---- IN-TANK ALARM - --- T I :UNLEADED R T. 4:PROBE OUT T 2:INVALID FUEL. LEVEL HIGH WATER ALARM VOLUME = 0 GALS AUG 4, 2010 8:56 AM T 4:H I GH WATER WAR1J 1 Nr.: HEIGHT = 0.00 INCHES TEMP a 0.0 DEG F INVENTOR`i REPORT INCREASE END AUG 4, 2010 6:53 AM T 1 :UNLEADED R VOLUME = 7949 GALS: VOLUME 0 i3ALS ULLAGE = 17:35 GAL;' HEIGHT = 0.00 INCHES 90% ULLAGE= 766 GAL:., TFJ1IP = G, 0 DEG F ---- IN-TANK ALARM -- -- TO VOLUME = 7786 GALS T I :UNLEADED R HEIGHT = 67.89 INCHES HIGH WATER WARNING WATER VOL = 0 GALS �. . GP.O.S:-NO E': ':,'•r" :. AUG 4, 2010 8:56 All WATER e 0.00 INCHES TEMP 89.1 DEG F T 3:UNLEADED R VOLUME - 7914 GALS ULLAGE 1770 GALS 90% ULLAGE- 001 GALS TC VOLUME = 7764 GALS HEIGHT = 67.59 INCHES 1 N-TA IVIC ALARM ---- WATER VOL = 0 GALS ' }. WATER 0.00 1 NCHE:. HE I GH F:+ti '`= tt s.. 5 .biES T 3:UNLEADED R WRIER "'''' ''' i °[�^ l�J`` .• t HIGH MATER ALr RH TEMP = 86.9 DEG F TEMP O.0 DEG F AUG 4, 2010 8:56 All T 4:UL PREMIUM INCREASE END VOLUME - 8406 GALS AUG 4, 2010 8:53 Art ULLAGE - 1276 GALS 90% ULLAGEL 307 GALS VOLUME _ ?914 GALS TC VOLUMr. .,. . : 'ALL. . HEIGHT 67.59 INCHES HE ">� 5 a GA , �# WATER = 3.04 INCHES W�x£R TEMP = 82.9 DEG Fgfi ,� + � :s E' +{� •. T +. �' a J. fE` GROSS INCREASE= 7914 ~ TC NET I Ni_REAaE= 1786 MAN I FOLDED TANKS ' I WENTORY INCREASE T ] :UNLEADED R f 3: T 2:UNLEADED R VOLU1 '.+.:'.,.zt C .. T 3:UNLEADED R Tv VOLUME =`1555L7 f3-AL8 VOLUME m 7915 GALS 246722 ARCO art Pm 19 1701 Brundage Lane Baker5f l el d 246722 tiktir am- rN.i 1'y CA 93304 170,1.;.Hrurr 'a�q. },anQ B aft s£ g AUG 4, 2010 8"58 AM SYSTEM STATUS REPORT ` '' T 2:INVALID FUEL LEVEL kT+"' .. `�Kx-::._k� �•.;ti: �`�s �:.: _ ---- IN-TANK ALARM -- -- :::,,: •.. . i 't 2:PROBE OUT fi �'::P NV ;y f'UEL°LEVEL T ! :UNLEADED R HIGH PRODUCT ALARM T 2:PROBE OUT AUG 4. 2010 8:59 AM INVENTORY REPORT INVENTORY REPORT T ! :UNLEADED R VOLUME = 7949 GALS ULLAGE. = 1735 GALS T ! :UNLEADED R 90% ULLAGE= 766 GALS VOLUME - 7949 GALS TO VOLUME 7766 GALS ULLAGE 1735 GALS '.';:;'•;:r,'�- {.U :,,.,: ,-.,-.;. HEIGHT = 67.89 INCHES 90'5 ULLAGE= 766 GALS WATER VOL = 0 GALS TC VOLUME = 7786 GALS WATER = 0.00 INCHES HEIGHT - 67.89 INCHES TEMP = 89.1 DEG F WATER VOL - 0 GALS WATER = 0.00 I NCHES TEMP 89.1 DEG F .. • : IT 3:UNLEADED R ' f VOLUME 7914 GALS ULLAGE 1770 GALS T 3:UNLEADED R 90a ULLAGE= 801 GALS VOLUME = 7914 GALS TO VOLUME = 7764 GALS ULLAGE = 1770 GALS HEIGHT = 67.59 INCHES 90% ULLAGE= 801 GALS WATER VOL = 0 GALS TO VOLUME = 7764 GALS WATER = 0.00 INCHES HEIGHT = 67.59 INCHES TEMP = 86.9 DEG F WATER VOL - 0 GALS WATER = 0.00 INCHES TEMP = 87.0 DEG F T 4:UL PREMIUM VOLUME = 8408 GALS ULLAGE - 1276 GALS T 4:UL PREMIUM 90% ULLAGE- 307 GALS VOLUME - 8408 GALS TO VOLUME = 8246 GALS ULLAGE = 1276 GALS HEIGHT = 71 .98 INCHES 90%0' ULLAGE= 307 GALS WATER VOL = 0 GALS TO VOLUME _ 8246 GALS WATER = 0.00 INCHES HEIGHT - 71 .98 INCHE::• TEMP = 87.5 DEG F WATER VOL = 0 1:;ALS WATER - 0.00 I NCHEE3 TEMP - 87,6 DEG F MANIFOLDED TANKS ' INVENTORY TOTALS T 1 :UNLEADED R MANIFOLDED TANKS T 2:UNLEADED R INVENTORY TOTALS T 2:INVALID FUEL LEVEL T 1 :UNLEADED R T 3:UNLEADED R T 2:UNLEADED R VOLUME - 15863 GALS T 2:INVALID FUEL LEVEL TO VOLUME. = 15550 GALS T 3:UNLEADED R VOLUME - 15863 GALS r END A X * x )( TO VOLUME = 15550 GALS * * END T I 'UNLEADED R `INVENTORY INCREASE _.,._.._, .. INCREASE STAR G T ' 5`, h 7 AUG 4, UlU U.JO r,1°1J� � �fi.;t_'• VOLUME = 7949 GALS HEIGHT 6 7.89 INCHES �'' [1i_ :at' :;X1`1:17. WATER = 0.00 INCHES "..x TEMP = 89.2 DEC F SYSTEM :T ATU2 REPORT -� �Y�Ttt�►:-r�t.r�>�t Y- a--- T - - - TUN° D ) 'R ­ INC END _ � >✓R4 � A M AUG 4. 2010 9:01 AM T INVALID FUEL LEVEL E;,• w z �,' F: T ' :PROBE OUT VOLUME = 9617 GALS HEIGHT = 87.24 INCHES µ•.w'x k� " t', WATER - 0.00 INCHES TEMP 89.7 DEC F GROSS INCREASE= 1 668 ,,•>.. :";.,:; ;:: TC NET INCREASE= 1631 'rANr: T 3:UNLEADhL R T 2:UNLEADED R MAX PRODUCT OLAR11 INVENTORY INCREASE - IN-TANK. ALARM ----- AUG 4, 2011. 9:02 A'M INCREASE START 'I 2:UNLEADED R AUG 4, 2010 8:58 AM OVERFILL ALARM AUG 4. 2010 9:02 API T 2:INVALID FUEL LEVEL VOLUME 0 GALS HEIGHT = 0.00 INCHES TEMP 0.0 DEG F 246722 ARCO arr./pm i INCREASE END 1701 Brundage Lane AUG 4, 2010 9:01 AM Bakersfield IN--TANK (ad ARM _._.__ CA 93304 VOLUME °� 0 GALS HEIGHT =. 0.00 INCHES T :;:UNLEADED R OVERFILL ALARM AUG 4, 2010 9:03 TEMP 0.0 DEG F AUG 4, 2010 9:02 AM 1 GROSS INCREASE= 0 SYSTEM STATUS REPORT TC NET INCREASE= 0 - - - - - - - - - - - T 2:OVERFILL ALARM T 3:UNLEADED R T 2:HIGH PRODUCT ALARM INVENTORY INCREASE T 2:MAX PRODUCT ALARM INCREASE START ---- IN-TANK ALARM •_.__..... AUG 4. 2010 8:58 AM T 2:UNLEADED R T 3:OV£RFILL ALARM HIGH PRODUCT AL�iRM VOLUME = 7914 GALS 3UG 4. 1010 9:02 AM T 3:HIGH PRODUCT ALARM HEIGHT = 67.59 INCHES WATER = 0.00 INCHES T 3:MAX PRODUCT ALARM TEMP = 87.2 DEG F INCREASE END AUG 4, 2010 9:01 AM VOLUME o 7914 GALS HEIGHT - 67.59 INCHES ---- IN-TANK ALARM ----- WATER - 0.00 INCHES T 3:UNLEADED R TEMP B7,5 DEG F HIGIi PRODUCT ALARM IJG 4, 2010. ti:02 AM GROSS INCREASE= 0 TC NET INCREASE= -2 MANIF'OLDED TANKS INVENTORY INCREASE T 1 :UNLEADED R T 2:UNLEADED R T 3:UNLEADED R VOLUME - 1669 r�AT S: INVENTORY INCREASE — -- 1 N-TANK Hi-mKi i INCREASE START T 4:1JL PREMIUM AUG 4, 2010 9.01 AM OVERF I LL, ALr RM AUG 4. 2010 9:04 AM VOLUME = 7476 GALS HEIGHT = 63.96 INCHES WATER = 0.00 INCHES TEMP = 89.9 DEG F INCREASE END AUG 4, 2010 9:04 Ail ---- IN-TANK ALARM ----- T 2:UNLEADED R- VOLUME = 7476 GALS ---- IN--TANK ALARM - - - PROBE OUT HEIGHT = 63.96 INCHES T 4:UL PREMIUM AUG 4, 2010 9:11 All WATER = 0.00 INCHES HIGH PRODUCT ALARM TEMP = 90.2 DEG F AUG 4, 2010 9:05 AM GROSS INCREASE= 0 TO NET INCREASE= 2 T 2:UNLEADED R INVENTORY INCREASE ---- IN-TANK ALARM -- 'F 3:1JNLEADED R INCREASE START ---- IN-TANK ALARM ---- PROBE OUT AUG 4. 2010 9:01 AM T 4:UL.P$EMI M AUG 4. 2010 9:12 Ahi T 2:I NVAL.i D FUEL LEVEL -AU •. ;� a F�.;+' t'` ; VOLUME 0 GALS ;��,,•,.. � �•,� i,;:s.-,.... HEIGHT = 0.00 INCHES WATER 0.00 INCHES TEMP = 0.0 DEG F 1 NCREASE END AUG 4. ;.i ---- _. g xn. q.. ALARM 2010 :04 AM �,� ' ,�t � ,, . :3'.'���: I N-TANK C 3:UNLEADED R GALS VOLUME = 9684 ----. : ',�;r.A:•TM. r3S :`.::. Y' ., h9' `:L_ ::-.:• LOW TEMP WARNING HEIGHT = 94.71 INCHES y ..;.;.::..<,:.::' AUG 4, 2010 9:12 A(' WATER 0.00 INCHES T 1 :IJID ; °. - TEMP = 69.3 DEG F PROBE AUG 4., 2010 9:06 AI°1 GRQSS I NCRLA` E= 9684 TO NET INCREASE= 9495 IN--TANK ALARM °r •::,- ;... . ': T 4:UL PREMIUM T 4:UL PREMIUM PROBE OUT F INVENTORY INCREASE AUG 4, 2010 9:13 Al') 1I� kiT: �, 61]I GALS :NCREASE START BNGH +Uta 4. 2010 9:04 AM WATER TEMP _:' '89.6 DEG F 4OLUME t3409 GALS HEIGHT - 71 .98 INCHES - 0.00 INCHES IATER I NCREAS E END TEMP 89.2 DEG F AUG 4, 2010 9'94 HM VOLUME = 9684 GHLS INCREASE END HEIGHT = 92. 19 1 NCHES .: ?« . ;IJG 4. 2010 9:07 AM WATER 0.00 INCHES 89 TEMP = .6 DEG F JLUME - 9684 GALS F2I GHT - 91 .85 INCH HATER - 0.00 I NCH. GROSS INCREASE:- 1770 TEMP - 89.9 DEG F TO NET INCREASE= 1?27 7AR11 FOLIiEi1 TANKS GROSS INCREASE- 1275 INVENTORY INCREASE TC NET INCREASE- 1244 1 : UNLEADED R 2:UNLEADED R i 3:UNLEADED R OLUME = 11454 GALS t T IN-TANK ALAxil INVENTORY I NCR& 3E T 2:UNLEADED R PROBE OUT INCREASE START AUG 4, XiIO 9:16 AM -- -- sr-f.oR- AUG 4, 2010 9: 12 All L16:87 NORTH FII;a....��Uh1P PIPING SUMP VOLUME - 4244 C3ALS FUEL ALARM HEIGHT = 40. 16 INCHES AUG 4, .2010 s AN WATER = 0.00 INCHES TEMP = 03.9 DEC F INCREASE END AUG 4, 2010 9:15 AM ----- SENSOR ALARM ----- L 4:91 UNL .STP SLIMP VOLUME = 4244 GALS STP SUMP HEIGHT = 40. 16 INCHES FUEL ALARM WATER - 0.00 INCHES AUG 4. 2010 9:22 AM ----- SENSOR ALARM - TEMP = 83.3 DEC F L15:07 NORTH ANNULAR ANNULAR SPACE FUEL ALARM GROSS. 1NC.REASE= 0 AUG 4. 2010 9:27. AM TC NET .INCREASE= 2 T 2:UNLEADED R I NVENTOR?l I NC:REASE ----- SENSOR ALARM ---- INCREASE START L 3:91 FILL SUMP AUG 4, 2010 9:12 Art PIPING SUMP FUEL ALARM VOLUME = 4224 GALS AUG 4, 2010 9:23 AM ----- SEIJSOR ALARM -- HEIGHT = 40.02 INCHES "12:87 CENTER ANNULAR TEMP. - 90.9 DEG F riNNULAR SPACE i'UEL ALARM ;AUG 4. 2010 9:29 AM INCREASE END AUG 4, 2010 9:15 (41 VOLUME = 4225 GALS HEIGHT = 40.03 INCHES TEMP = 89.3 DEG F a ------ SENSOR ALARM — --- L 2:91 ANNULAR GROSS INCREASE- 1 ANNULAR SPACE FUEL ALARM TC NET INCREASE= 6 AUG 4. 2010 9:23 AM ---- SENSOR ALARM L13:87 CENTER FILL S' '.i1 PIPING SUMP T 3:UNLEADED R FUEL ALARM INVENTORY INCREASE AUG 4. 2010 9:31 A�'! INCREASE START AUG 4. 2010 9: 12 AM VOLUME — U GALS -HEIGHT = 0.00 INCHES ----'•- SENSOR ALARM ----- ,JATER = 0.00 INCHES L 2:91 ANNULAR TEMP = 0.0 DEG F ANNULAR SPACE FUEL ALARM INCREASE ASE EhJD AUG 4, 9:24 AM ----- SENSOR ALARM — INC 4. 2010 9:15 Art STP CENTER STP Slh i_ STP SUMP FUEL ALARM VOLUME r;..q. E. uALS AUG 4. 2010 9:31 Ah! HE SENSOR ALARM '- --- 1 :87 NORTH STP .SUMP ,7i ,std 4 ,�, �� ,t , �t � 1 � ,. .xv•�� tQ4,.�r.r,,, :sfti;., ' I�I� .5��.�rH. .a. 4,i .n. `fe• .}.��L- �r.� --Kh �.-'�.}r-_,. T 1 :UN T 2:UN�ERY�EI�,i�`r. 'Y,. y ^1„-a"• �:}h,;' T 3:UNLEADED 'R +1�)LQMIE 4357 GALS - -- SENSOR ALARM L 9:87 SOUTH ANNULAR. -- SENSOR ALARM -- ANNULAR SPACE 1-10:87 SOUTH FILL SUMP FUEL ALARM P I P I NC" SUMP AUG 4. 2� ':� q:39 AM --- - SENSOR ALARH ---- FUEL ALARM L 6:DISP.3-4 UDC AUG 4, 2010 9:33 AM DISPENSER PAN FUEL ALARM AUG 4, 2010 9:48 All 2402 2.- ki..att�r;w.in.,19 -- SENSOR ALARM L 9:87 SOUTH ANNULAR ANNULAR SPACE - FUEL ALARM ' } L.:..6::; ` AUG 4, 2010 7•35 All MR.�, ��R!� '�?• �'.yy},,i�' 17..,. r `15,RE F�:)RT 2':PRJ1 ,`t3liT 9:FUEL'ALARM 246722 ARCO 19 1701 Brundage Lane Bakersflald --- - SENSOR ALFiRM CA 9304 L 7:DISP.5-6 LID DISPENSER PAN AUG 4. 2010 9:37 AM FUEL ALARM AUG 4, 2010 9:49 f;r' SYSTEM STATUS REPORT --- SENSOR ALARM -- - - - - - - - - - - - - - L9:8? SOUTH ANNULAR T 2:PROBE CUT ANNULAR SPACE DATA L 9:FUEL ALARM AUGUP4. 2010 WARNING AM ---- SENSOR. ALARM L 8:D1SP.7-8 LIDO DISPENSER PAN FUEL ALARM AUG 4. 2010 9:50 AM ----- SENSOR ALARM - --- L17:DISP.9-10 UDC DISPENSER PAN FUEL ALARM AUG 4, 2010 9:46 PJ11 ----- SENSOR ALARM ----- L17:DISP.9-10 UDC DISPENSER PAN SENSOR OUT ALARM AUG 4, 2010 9:52 AM ----- SENSOR ALARI°I ----- L 9:87 SOUTH ANNULAR ANNULAR SPACE - SENSOR ALARM - - SETUP DATA WARNING L18:DISP.11-12 UDC AUG 4, 2010 9:39 AM DISPENSER PAN FUEL ALARM AUG 4, 2010 9:47 AM P I P I Nu SENSOR.OUT ALARM' AUG 4. 2010 '9:52 AM ----- SENSOR ALARM ----- L18:DISF'.11-12 UDC -' SE;NSuIi r1Lt1h''i DISPENSER PAN -- SENSOR OUT ALARM L14:87 CENTER STP SUMP AUG 4. 2010 9:52 AM M SENSOR OUT ALARM AUG 4, 2010 9:52 AM ----- SENSOR ALARM ----- L 4:91 UNL STP SUMP STP SUMP SENSOR OUT ALARM AUG 4. 2010 9:52 AH ---- SENSOR ALARM ----- L,13:87 .CENTER FILL SUMP PIPING SUMP ----- SENSOR ALARM --- -SENSOR OUT ALARM L 5:1)]SP.I-2 UDC AUG 4. 2010 9:52 AM DISPENSER. PAN SENSOR OUT ALARM AUG 4, 2010 9:52 AN ----- SENSOR ALARM - L 6:DISP.3-4 UDC: DISPENSER PAN SENSOR OUT ALARM AUG 4, 2010 9:52 All! ----- SENSOR ALARM ----- 1-11 :87 SOUTH STP SUMP ----- SENSOR ALARf°1 - -- STP SUMP SENSOR OUT ALARM L15:87 NORTH ANNULAR AUG 4, 2010 9:52 All ANNULAR SPACE SENSOR OUT ALARM AUG 4, 2010 9:52 AN SENSOR ALARM ---�- L 7:DISP.5-6 UDC: DISPENSER PAN SENSOR OUT ALARM AUG 4. 2010 9:52 AM ----- SENSOR ALARM -- - _ L12:87 CENTER ANNULAR ----- SENSOR ALARM - - ANNULAR SPACE 1.16:67 NORTH FILL SUMP �7,ENSOP. OUT ALARM PIPING SUMP "AUG 4. 2010 9:52 AI 11 SENSOR OUT ALARM AUG 4. 2010 9:52 All ----- SENSOR ALARM --. L 8:DISP.7-8 UDC DISPENSER PAN ' SENSOR OUT ALARM AUG 4, 2010 9:52 Af• t x � kt ------ SENSOR ALARM --- °- i i.• L 1 '87 NORTH :STP SIJIIP STP SUMP SENSOR OUT ALARM AUG ----- SENSOR ALARM L 2:91 ANNULAR ANNULAR SPACE SENSOR OUT ALARM d. 2010 9:52 2 ;- _ ;J 4' -----• SENSOR ALARM - --- L 9'87 SOUTH ANNULAR ANNULAR SPACE FUEL ALARM - SENSOR ALriRh'1 _--_ AUG 4, 2010 10:04 AM L 9:87 ''OUTH ANNULAR ---- 1N-TANK ALARM - --- ANNULAR SPACE T 2:UNLEADED R SETUP DATA WARNING PROBE OUT AUG 4. 2010 9:53 AM AUG. 4, 2010 10:41 All --- SENSOR AI.1;Ri°t -------- L 9:87 SOUTH ANNULAR ; : .. ANNULAR SPACE FUEL. ALARM ,':' -.; :;.'9`` '•r::'. I ' °--- AUG 4, 2010 10:05 AM ----- SENSOR ALARM --- }' L 9:87 SOUTH ANNULAR ANNULAR SPACE FUEL ALARM AUG 4, 2010 11 :01 AM ----- SENSOR AL,Ak1°I ----- , ' SENSOR ALARM '`''`'' ` `'' L 9:87 SOUTH ANNULAR L 9:87 SOUTH ANNULAR .,;,` ;,. =.'.t.; ANNULAR SPACE ANNULAR SPACE '```:,7•..; FUEL ALARM SETUP DATA WARNING AUG 4, 2010 10:00 AM AUG 4, 2710 11 :05 A1°1 SENSOR ALARM ----- L 9:8 7 SOUTH ANNULAR ANNULAR SPACE FUEL ALARM -- :8 TENSOR ANNUL - AUG 4. 2010 10:17 AM ALARM HISTORY REPORT L 9:87 S4UfH ANNULAR ANNULAR SPACE ---- SYSTEM ALARM FUEL ALARM PAPER OUT . AUG 4, 2010 10:01 AM �; AUG + ;.2, L, ' AM ---- IN-TANK ALARM T 2:UNLEADED R HIGH WATER WARNING AUG 4, 2010 10:17 AM -- -- SENSOR ALARM L 9:87 SOUTH ANNULAR ANNULAR SPACE FUEL ALARM ENT f AUG 4, 2010 11-1:03 A°i ----- SENSOR ALARM ----- L 9:87 SOUTH ANNULAR ANNULAR SPACE SETUP DATA WARNING AUG 4, 2010 10:20 AM ALARM HISTORY REPORT ---- 1N—TANK. ALARM ----- T 3:UNLEADED R ALARI l f�I S 1'vF;'' kEPORT ALARM T1?R — F1 I u H WATER ALARM --- AUG 4. 2010 8:56 A IN--TANK ALARM All OVERFILL ALARM T 1 :UNLEADED R AUG 4. 2010 9:02 AM `•,k., ; ;: JAN 28, 2010 3:48 AM HIGH WATER ALARM ,' JAN 28, 2010 3:35 AM AUG 4, 2010 0:5i; AM • .,� LOW PRODUCT ALARM r1. X `• si 1. JUN 19. 2.009 6:13 PM OVERFILL ALARM N�I: ,, `��M . AUG 4. 2010 6:59 Ah9 ' � ' `; ,1 HIGH PRODUCT ALARM AUG' '�"F: 17.., ��'�f-�;?�.'.;�. AUG 4, 2009 9:39 All AUG . JUN 21, 2009 1 :12 FM AUG 4, 2010 9:02 AM INVALID FUEL LEVEL JAN 28. 2010 3:36 AM HIGH PRODUCT ALARM AUG 4, 2010 8:47 AM AUG 4. 2009 9:49 AM AUG 4, 2010 8:59 AM AUG 4, 2009 11 :46 AM JUN 21, 20109 1 :14 FM INVALID FUEL LEVEL JUN 18, 2009 10:51 PM I PROBE 001' AUG 4, 2010 8:49 AM AUG 4, 2010 10:46 AM JUN 29, 2009 8:57 PI°I PROBE OUT AUG 4. 2010 9:16 AM JUN 19. 2009 6:07 PM AUG 4, 2010 9:06 AM AUG 4, 2010 9:13 AM AUG 4. 2010 8:45 AM PROBE OUT AUG 4, 2009 11 :45.AM HIGH WATER WARNING AUG 4, 2010 9:12 AM AUG 4. 2010 Iq:17 AM AUG 4, 2010 8:49 AM HIGH WATER WARNING AUG 4, 2009 11 :45 All AUG 4, 2010 8:56 AI°I DELIVERY NEEDED HIGH WATER WARNING AUG 4. 2010 9:56 AM MAY 29. 2010 ^:28 PM DELIVERY NEEDED MAY 29, 2010 7:45. PH MAX PRODUCT ALARM DELIVERY NEEDED AUG 4, 2010 9:02 AM MAY 29, 2010 7.45 PI°1 LOW TEMP WARNING JUL 1, 2009 8:31 AM AUG 4, 2009 11 :46 Atli JUN 29, 2009 7:49 PM MAX PRODUCT ALARM AUG 4. 2010 9:02 A11 LOW TEMP WARNING AUG 4. 20 t 0 9:12 Fall ?� END O .X X x END +I. } (;LARP4 H 1 a 1"tid,'• 1;P:1'+1k1' ALARM HISTORY REPORT ---- IN-TANK ALARM --__._ ALARM HISTORY REPORT ----- SENSOR ALARl1 ----- T 4:UL PREMIUM L 2:91 ANNULAR ----- SENSOR ALARM -- -- ANNULAR SPACE L 4:91 UNL STP SUMP HIGH WATER ALARM SENSOR OUT ALARM STP SUMP AUG 4, 2010 8:54 All AUG 4, 2010 9:52 AM SENSOR OUT ALARM AUG 4. 2010 9:52' All OVERFILL ALARM FUEL ALARM FUEL ALARM 4, 2010 9:04 AM AUG 4, 2010 9:24 All AUG 4, '20t:0::.a:22, Art HIGH PRODUCT ALARM FUEL ALARM AUG 4, 2010 9:05 AM AUG 4, 2010 9:23 AM AUG 4, 2009 9:50 AM PROBE OUT <' AUG 4, 2010 9: 13 AM "^ ` AUG 4. 2010 8:50 AM AUG 4, 2009 11 :43 AM HIGH WATER WARNING AUG 4, 2010 8:54 Ar'1 X END X A X * x MAX PRODUCT ALARM * * END * x AUG 4. 2010 9:05 Ahl LOW TEMP WARNING AUG 4, 2009 11 :44 All ALARM HISTORY REPORT ALARM HISTORY REPORT ----- SENSOR ALARM ----- L 3:91 FILL SUMP ---- ' SENSOR ALARM --- - PIPING SUMP L 5:DISP. 1-2 UDC: x END * SENSOR OUT ALARM DISPE14SER PAN AUG 4, 2010 9:52 AM SENSOR OUT ALARM AUG 4� 2010 9:52 All FUEL ALARM AUG 4, 2010 9:23 AM FUEL ALARM AUG 4, 2010 9:48 Al") FUEL ALARM JUN 25, 2010 10:52 PM SEfCOR OUT ALARM AUG 4, 2009 9:29 All ALARM HISTORY REPORT -- SENSOR ALARM ----- L 1 :81 NORTH STP SUMP STP SUMP SEN20P OI.1T ALARM AUG 4, 2010 9:52' Pill X END XXx � ri END x n FUEL ALARM AUG 4..-.201:W: . FY ALARM HISTORY REPORT ALARM HI 70RY REPORT ---- SENSOR ALARM ----- ALARM HISTORY REPORT L B:D ISP.7-8 UDC ---- - SENSOR ALARH --- DISPENSER PAN L10:87 SOUTH FILL SUMP ----- SENSOR ALARM -_- SENSOR OUT ALARM PIPING SUMP L 6:DISP,3-4 UDC AUG 4. 2010 9:5 . AM SENSOR OUT ALARM DISPENSER PAN FUEL ALARM AUG 4, 2017 9:52 AM SENSOR OUT ALARM AUG 4, 2010 9:50 AM FUEL ALARM AUG 4, 2010 5:52 AM AUG 4, 2010 9:33 AM FUEL ALARM SENSOR OUT ALARM All 4, 2009 9:29 AM FUEL ALARM AUG 4, 2010 9:48 Ai FEB 27, 2010 12:54 AM SENSOR OUT ALARM AUG 4, 2009 9:2'9 All * i € END X c X x A A * END x x ALARM HISTORY REPORT ALARM HISTORY REPORT ----- SENSOR. ALARM --- ALARM H 1 STORY REPORT L 9:87 SOUTH ANNULAR ----- SENSOR: ALAR111 - - ANNULAR SPACE L11 :87 SOUTH STP SUMP SETUP DATA WARNING STP SUMP SENSOR HLARM - --- AUG 4, 2010 11 :05 AM SENSOR OUT ALARM L-7:DIti'P,5-6 UDC DISPENSER PAN FUEL ALARM AUG 4, 2010 4:52 Hhl SENSOR OUT ALARM AUG 4. 2010 11 :01 AM FUEL ALARM AUG 4, 22010 9:52 AM AUG 4, 2010 9:32 AM FUEL ALARM SETUP DATA WARNING AUG 4, 2410 9:ay AM 4, 2010 10:20 AM SENSOR OUT ALARM AUG 4, 2009 9:29 AM SENSOR. OUT ALARM AUG 4, 2009 9:29 All END - iE' i,. r4 a END �E 14 iE 3e i4�1 •i+,.y ..', ., , ALARM HISTORY REPORT SENSOR ALARM -1P L16:0 NORTH FILL SUI k ALARM HISTORl REPORT PIPING SUMP ----- SENSOR ALARM SENSOR OUT ALARM AUG 4. 2010 9:52 AM L14:87 CENTER STP SUMP STP SUMP SENSOR OUT ALARM FUEL ALARM ULA AUG 4, 2010 9:26 AM S AUG 4. 2010 9:52 AN OP-'SGUTI AUG 41 ��bio '9:52 N-1 FUEL ALARM SENSOR OUT ALARM AUG 4, 2010 9:31 W AUG 4, 2009 9:29 All FUEL ALARM AUG 4, 2010 9-2'9 All SENSOR OUT ALARM AUG 4- 2009 9:29- All FUEL ALARM AUG 4, 2009 12:57 P11 END Et4D#'k 01 ALARM HISTORY REPOF."I' t1A ALARM HISTORY REPORT Ll :87' Ndlk' H 141�'IULAR ----- SENSOR ALARM ----- ANNULAR' SPACE L13-87 CENTER FILL SUMP SENSOR OUT ALARM . PIPING SUMP AUG 4, 2010 9'52 All SENSOR OUT Ab�Rll AUG 4, 2010 9:52 All FUEL ALARM AUG I�UG 4, 2010 9:27 AM FUEL ALARM AUG 4, 2010 9:31 AN FUEL ALARM FUEL ALARM AUG 4, 2009 12:56 PM APR 12, 2010 2:39 AM END END END ALARM HISTOR'`t REPORT -'---- SENSOR ALARM L1S:DISP.11-12 UDC DISPENSER PAN SENSOR OUT ALARM AUG 4, 2010` 9:52 AM FUEL ALARM ALARM H 1 STOPY kEPOk-T AUG 4, 2010 9:47 AM ------ :3EhJS:ik ALARM -----. SENSOR OUT ALARM L23: AUG 4, 2009 9:30 AM ALARM HISTORY REPORT OTHER SENSORS ----— SENSOR ALAR1 L21 : OTHER SENSORS i ie i ie END . if 3F ie ii 3E iE I I END r:•Y, i rI ALARM HISTORY REPORT" " ALARM HISTORY REPORT ----- SENSOR ALARM ----- SENSOR ALARM ----- L24: L19: ALARM HISTORY REPORT OTHER SENSORS OTHER SENSOR ----- SENSOR ALARM -- -- L22: OTHER SENSORS ri * END x is :X E ND * 34 rt * ri END . ALARM HISTORY REPORT ----- SE1'•JSOR ALARM — —_ L20: OTHER SEN20RS f� :1''�"���'d<��,Z^ter` :Yy r•.. .�•i.. � . eTA) TRANSMITTAL TO ENVIRONMENTAL AGENCY Report submitted on: September 6, 2010 City of Bakersfield Fire Department 2101 H Street Bakersfield CA 93301 TESTING SITE: ARCO#01960 1701 BRUNDAGE LANE, BAKERSFIELD Test(s) checked below were performed at the above site, Precision Line Test x Monitoring System Certification X Pressurized Piping Leak Detection Certification x U.S.T. Monitoring Site Plan X Spill Bucket Testing Report Form SB-989 Testing Enclosed test results are submitted on behalf of: BP WEST COAST PRODUCTS LLC If you have any questions or concerns, please feel free to contact our office Phone: (951) 699-8058 Cc: ARCO#01960 TANK.TEK ENVIRONMENTAL CORPORATION 807 Elmira Road,PMB 338,Vacaville,CA 88887 — Ph,(707)448.8181 - Fax (707)448-8192 - E-mail;tank-tekQcwnet,com 31828 Carole Chamberlin,Temecula, CA 02891 — Ph,(981)899-8088 - Fax(981)899-8089 - E-mail:bballrelch verizon,not