HomeMy WebLinkAbout2011 FMC RESULTS (Copies of Monitoring System Certification form and UST Monitoring Plot Plan available at http://www.waterboards.ca.gov)
Monitoring System Certification
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6.7, Health and Safety Code;Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work.A copy of this form must be provided to the tank system owner/operator.The
owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility: Pacific Bell Telephone Co. dba AT&T Califomia GEO PAR#SA004
Address: 1918"M" STREET City: BAKERSFIELD Zi : 93301
Facility Contact Person: Grant Armstrong Contact Phone No: 661-327-6903
Make/Model of Monitoring System: Veeder Root TLS-350 Service Date: 01/13/2011
B. Inventory of Equipment Tested/Certified IIIIIIIIIIIIIIIIIIII
Check the appropriate boxes to indicate specific equipment Inspected/serviced: 25
IE
Tank ID: SA0040001 Tank ID:
®In-Tank Gauging Probe Model:847390-109 ❑In-Tank Gauging Probe Model:
®Annular Space or Vault Sensor Model:794390-420 ❑Annular Space or Vault Sensor Model:
®Piping Sump/Trench Sensor(s) Model:794380-208 ❑Piping Sump/Trench Sensor(s) Model:
®Fill Sump Sensor(s) Model:794380-208 ❑Fill Sump Sensor(s) Model:
❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
®Tank Overfill/High Level Sensor Model:790091-001 ❑Tank Overfill/High Level Sensor Model:
®Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2)
Tank ID: Tank ID:
❑In-Tank Gauging Probe Model: ❑In-Tank Gauging Probe Model:
❑Annular Space or Vault Sensor Model: ❑Annular Space or Vault Sensor Model:
❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model:
❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model:
❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
❑Tank Overfill/High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model:
❑Other(Specify equipment type and model in Section E on Page 2) 1 ❑Other(Specify equipment type and model in Section E on Page 2)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
If the facility contains more tanks or dispensers,copy this form.Include information for every tank and dispenser at the facility.
C. Certification-I certify that the equipment identified in this document was inspected/serviced in accordance with the
manufacturers'guidelines.Attached to this Certification is information(e.g. manufacturers'checklists)necessary to verify
that this Information is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of
generating such reports,I have also attached a copy of the report; (check all that apply):
®sy ®Alarm history report
Technician Name (Print): Patrick Banbury Si nature:
Certification No: A20465 IlLicense No: 88
Testing Company Name: TAIT ENVIRONMENTAL SERVICES I Phone No: 714 560-8222
Testing Company Address: 2131 South Dupont Drive Anaheim CA 92806 JDate of Testing/Servicing: 01/13/2011
Monitoring System Certification Page 1 of 4 IIIIIIII�IIIIIIIIII 26 12/07
IE
Monitoring System Certification
Address: 1918"M" STREET BAKERSFIELD 93301 Service Date: 01/13/2011
D. Results of Testing/Servicing
Software Version Installed: 123.01
Complete the fol owinq checklist:
•Yes ❑ No* Is the audible alarm operational?
•Yes ❑ No* Is the visual alarm operational?
•Yes ❑ No* Were all the sensors visually inspected,functionally tested, and cofirmed operational?
•Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other
equipment will not interfere with their proper operation?
®Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g. modem)
operational?
❑ N/A
❑Yes ® No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
containment monitoring system detects a leak, fails to operate, or is electrically disconnected?
If yes:which sensors
initiate positive shut- ❑ Sump/Trench Sensors ❑ Dispenser Containment Sensors
❑ N/A down?:
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑ Yes ❑No
❑Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the
® N/A tank fill point(s)and operating properly?If so, at what percent of tank capacity does the alarm trigger?:
❑Yes* ® No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E below.
Was liquid found inside any secondary containment systems designed as dry systems?
El Yes* ® No If yes,check the type(s)of liquid found and describe causes in Section E, below. ❑ Product ❑Water
®Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable
®Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications?
*In Section E below,describe how and when these deficiencies were or will be corrected.
E. Comments
Other sensor from page 1:
L4 Transition Sump sensor 794380-208-Certified
Section D: Back up generator system no possitive shut down or failsafe.
An Overfill Prevention Valve is installed in the drop tube.
Monitoring System Certification Page 2 of 4 12/07
Monitoring System Certification
Address: 1918"M" STREET BAKERSFIELD 93301 Service Date: 01/13/2011
F. In-Tank Gauging/SIR Equipment ®Check this box if tank gauging is used only for inventory control
❑Check this box if no tank gauging or SIR Equipment is installed
This,section must be completed if in-tank gauging equipment is used to perform leak detection monitoring
Complete the fol owing checklist
❑Yes ❑ No* Has all input wiring been inspected for proper entry and termination, including testing for ground
faults?
❑Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup?
❑Yes ❑ No* Was accuracy of system product level readings tested?
❑Yes ❑ No* Was accuracy of system water level readings tested?
❑Yes ❑ No* Were all probes reinstalled properly?
❑Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H below, describe how and when these deficiencies were or will be corrected
G. Line Leak Detectors (LLD): ®Check this box if LLDs are not installed
Complete the fol owing checklist
❑Yes ❑ No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD
performance?
❑ N/A Simulated Leak Rate(check all that apply) ❑ 3.0 g.p.h ❑0.1 g.p.h ❑0.2 g.p.h
❑Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements?
❑Yes ❑ No* Was the testing apparatus properly calibrated?
❑Yes ❑ No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is
disabled or disconnected?
❑ N/A
❑Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system
malfunctions or fails a test?
❑ N/A
❑Yes ❑ No* For electronic LLDs, have all accessible wiring connections been visually inspected?
❑ N/A
❑Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
* In the Section H below, describe how and when these deficiencies were or will be corrected
H. Comments
Line Leak Detector not installed in the backup generator system.
Monitoring System Certification Page 3 of 4 12/07
Monitoring System Certification
Address: 1918"M" STREET BAKERSFIELD 93301 Service Date: 01/13/2011
UST monitoring Site Plan
DAY TANK
ROOFTOP GENERATO EXTERNAL
R
ALARM
TRANSITION SUMP
794380-208
ALLEY WAY
VENT-''O ANNULAR
794390-420
LU
FILL SUMP V)
AT&T SA004 PARKING LOT 794380-208 rn
1918 M STREET TLM PROBE M
BAKERSFIELD, CA 847390-109
STP SUMP
794380-208
SA0040001
Date map was drawn: 01/13/2011
Instructions
If you already have a diagram that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping.
Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors
monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment
areas; mechanical or electronic line leak detectors; and in-tank liquid level probes (if used for leak detection).
In the space provided, note the date this Site Plan was inspected.
Monitoring System Certification Page 4 of 4 12/07
SWRCB,January 2006
SPILL BUCKET TESTING REPORT FORM
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printout from
tests(if applicable),should be provided to thefaacility owner/operator for submittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name:Pacific Bell Telephone Co.dba AT&T California Date of Testing:01/13/2011
Facility Address: 1918"M"STREET BAKERSFIELD CA 93301 GEO PAR#SA004
Facility Contact:Grant Armstrong Facility Phone:
Date Local Agency Was Notified of Testing:01/06/2011
Name of Local Agency Inspector if present during testing): Ernie Medina
2.TESTING CONTRACTOR INFORMATION
Company Name:TAIT ENVIRONMENTAL SERVICES
Technician Conduct' Test:Patrick Banbury
Credentials: ®CSLB Contractor ®ICC Service Tech ❑SWRCB Tank ❑Other(Specify)
Tester
License Number(s):A ASB HAZB C-10. 588098:5254955-UT
3,SPILL BUCKET TESTING INFORMATION
Test Method Used ®Hydrostatic ❑Vacuum ❑Other
Test Equipment Used:Tape Measure 1EQuipment Resolution: 1/16"
Identity Spill Bucket(By Tank Number, 1 SA0040001 2 3 4
Stored Product,etc)
❑Direct Bury ❑Direct Bury E)Direct Bury El Direct Bury
Bucket Installation Type ®Contained in Sump ❑Contained in Sump El Contained in Sump ❑Contained in Sump
❑On top of AST ❑On top of AST ❑On top of AST ❑On top of AST
Bucket Diameter inches I V
Bucket D th inches 16"
Wait Time between applying 5 min
vacuum/water and start of test
Test Start Time: 9:15am
Initial Readin R(Ri): 13.50"
Test End Time: 10:15am
Final Reading 13.50"
Test Duration: 1 Hour
Chan a in Reading Rf-Ri : 0.00"
Pass/Fail Threshold or Criteria: 0.00"
Test Result Pass
Comments:Liquid removed and taken back to TES.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information c.ined In this report is true,accurate and in full compliance with legal requirements
Technician's Signature r' Date 01/13/2011
J,
DATA CHART FOR USE WITH PETRO TITE LINE TESTER
Job Number. ATTPL11 Date of Test: 01/13/2011
LOCATION: 1918 M Street Bakersfield CA 93301
Street No. City State Telephone No.
OWNER: Pacific Bell Telephone Co. dba AT&T California
Name Address Representative Position Telephone No.
OPERATOR: Pacific Bell Telephone Co. dba AT&T California
Name Dealer,Mgr.Or Other Address(If different than location)Telephone No.
REASON FOR TEST: Annual Compliance
TEST REQUESTED BY:
Name Position Order No. Billing Address
SPECIAL INSTRUCTIONS: CUPA Inspector on site for test
---- -- -------------------------------------------------------------.-.-._.------------------------------------------
I declare under penalty of perjury that I am a licensed tank tester in the State of
California and that the information contained in this report is true and correct to the
best of my knowledge.
i
r
TECHNICIAN: Patrick Banbury 90-1413
Name Signaturr license Number
IS A TANK TEST TO,BE MADE WITH THIS LINE TEST? ❑Yes ® No
MAKE AND TYPE OF PUMP OR DISPENSERS Turbine
WEATHER Mild TEMPERATURE IN TANKS °F °c
COVER OVER LINES Concrete/Black Top APPROX. BURIAL DEPTH 24"
PRESSURE VOLUME
EACH LINE TIME PSI READING TEST RESULTS
AS TESTED MILITARY BEFORE AFTER BEFORE AFTER NET CHANGE CONCLUSIONS
Diesel 0940 PRETEST 75
SA0040001 1010 75 60 .0000 G.P.H.
1040 60 60 Line Tight®YES ❑ NO
1055 60 60 .0555 .0555 .0000 Bleed Back®OK
1110 60 60 .05 1 .0555 .0000 ❑ NOT OK
1111 BLEED BACK 60 0 .0555 1 .0990 .0435
BLEED BACK
START TEST G.P.H.
Line Tight❑YES ❑ NO
Bleed Back❑OK
❑ NOT OK
BLEED BACK
BLEED BACK
START TEST G.P.H.
Line Tight❑YES ❑ NO
Bleed Back❑OK
❑ NOT OK
BLEED BACK
COMMENTS: Westem Fiberglass 1.5"flex line.
I50301
JAN 17, 2011 2:57 PM
# 1:BKFDCAI2 SA004
150302
JAN 17, 2011 2:57 PM
# 2:1918 M ST.
El
150303
JAN 17, 2011 2:57 PM
# 3:BAKERSFIELD,CA 93301
I50304
JAN 17, 2011 2:57 PM
# 4:661-631-2540
I51700
.JAN 17, 2011 2:57 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
❑
I50F00
JAN 17, 2011 2:57 PM
MON DD YYYY HH:MM:SS xM
I10200
JAN 17, 2011 2:57 PM
BKFDCA12 SA004
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. . 164399 163979
2 INTERSTITIAL BD 201871 201714
3 UNUSED 15000000 15000000
4 UNUSED 15000000 15000000
5 UNUSED 15000000 15000000
6 UNUSED 15000000 15000000
7 UNUSED 15000000 15000000
8 UNUSED 15000000 15000000
9 COMBO I/O BOARD 9982 9962
10 UNUSED 15000000 15000000
11 UNUSED 15000000 15000000
12 UNUSED 15000000 15000000
13 UNUSED 15000000 15000000
14 UNUSED 15000000 15000000
15 UNUSED 15000000 15000000
16 UNUSED 15000000 15000000
COMM 1 FAXMODEM BOARD 40367 40318
COMM 2 UNUSED 15000000 15000000
COMM 3 UNUSED 15000000 15000000
COMM 4 UNUSED 15000000 15000000
COMM 5 UNUSED 15000000 15000000
COMM 6 UNUSED 15000000 15000000
160100
JAN 17, 2011 2:58 PM
TANe CONFItURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK#SA004U001 ON
2 OFF
3 OFF
4 OFF
❑
160200
JAN 17, 2011 2:58 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK#SA004U001
2
3
4
El
I60300
JAN 17, 2011 2:58 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK#SA004U001 1
2 2
3 3
4 4
160400
JAN 17, 2011 2:58 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 20149
2 0
3 0
4 0
❑
I60700
JAN 17, 2011 2:58 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA004U001 114.00
2 0.00
3 0.00
4 0.00
El
I60900
JAN 17, 2011 2:58 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK#SA004U001 0.000450
2 0.000000
3 0.000000
4 0.000000
I61200
JAN 17, 2011 2:58 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 DIESEL TK#SA004U001 NONE NONE
2 NONE NONE
3 NONE NONE
4 NONE NONE
❑
El
I62100
JAN 17, 2011 2:58 PM
TANK LOW PRODUCT LIMIT
TANK' PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 12000
2 0
3 0
4 0
162200
JAN 17, 2011 2:58 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 19141
2 0
3 0
4 0
162300
JAN 17, 2011 2:58 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 18134
2 0
3 0
4 0
❑
162400
JAN 17, 2011 2:58 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA004U001 2.0
I62800
JAN 17, 2011 2:58 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 20149
2 0
3 0
4 0
162900
JAN 17, 2011 2:58 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA004U001 12000
2 0
3 0
4 0
❑
170300
JAN 17, 2011 2:58 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 ANNULAR SPACE TRI-STATE (SINGLE FLOAT)
2 FILL SUMP TRI-STATE (SINGLE FLOAT)
3 PIPING SUMP TRI-STATE (SINGLE FLOAT)
4 TRANSITION SUMP TRI-STATE (SINGLE FLOAT)
5 TRI-STATE (SINGLE FLOAT)
6 TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
❑
8 TRI-STATE (SINGLE FLOAT)
I90200
JAN 17, 2011 2:58 PM
SOFTWARE REVISION LEVEL
VERSION 123.01
SOFTWARE# 346123-100-B
CREATED - 02.06.21.13.00
S-MODULE# `330160-002-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS .
ANNUAL IN-TANK TESTS
CSLD
Fl
I11100
JAN 17, 2011 2:58 PM
BKFDCAI2 SA004
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM CLEAR 1-17-11 11:40AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM ALARM 1-17-11 11:35AM
T 1 TANK DIESEL TK#SA0040001 SUDDEN LOSS ALARM CLEAR 1-13-11 11:56AM
T 1 TANK DIESEL TK#SA004U001 SUDDEN LOSS ALARM ALARM 1-13-11 11:55AM
T 1 TANK DIESEL TK#SA004UO01 SUDDEN LOSS ALARM CLEAR 1-13-11 11:55AM
T 1 TANK DIESEL TK#SA004U001 SUDDEN LOSS ALARM ALARM 1-13-11 10:18AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER ALARM CLEAR 1-13-11 10:18AM
T 1 TANK DIESEL TK#SA004U001 LOW PRODUCT ALARM CLEAR 1-13-11 10:18AM
T 1 TANK DIESEL TK#SA004UO01 PROBE OUT CLEAR 1-13-11 10:17AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT ALARM 1-13-11 10:16AM
T 1 TANK DIESEL TK#SA004O001 HIGH WATER ALARM ALARM 1-13-11 10:08AM
T 1 TANK DIESEL TK#SA004O001 OVERFILL ALARM CLEAR 1-13-11 10:05AM
T 1 TANK DIESEL TK#SA004O001 LOW PRODUCT ALARM ALARM 1-13-11 10:OOAM
T 1 TANK DIESEL TK#SA004U001 OVERFILL ALARM ALARM 1-13-11 9:59AM
T 1 TANK DIESEL TK#SA004U001 LOW PRODUCT ALARM CLEAR 1-13-11 9:58AM
T 1 TANK DIESEL TK#SA004UO01 SUDDEN 'LOSS ALARM CLEAR 1-13-11 9:58AM
T 1 TANK DIESEL TK#SA004U001 LOW PRODUCT ALARM ALARM 1-13-11 9:58AM
T 1 TANK DIESEL TK#SA004UO01 PROBE OUT CLEAR 1-13-11 9:57AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT ALARM 1-13-11 9:55AM
T 1 TANK DIESEL TK#SA004UO01 SUDDEN LOSS ALARM ALARM 1-13-11 9:55AM
L 4 OTHER TRANSITION SUMP FUEL ALARM CLEAR 1-13-11 9:52AM
L 4 OTHER TRANSITION SUMP FUEL ALARM ALARM 1-13-11 9:50AM
L 4 OTHER TRANSITION SUMP FUEL ALARM CLEAR 1-13-11 9:50AM
L 4 OTHER TRANSITION SUMP FUEL ALARM ALARM 1-13-11 9:50AM
L 1 ANNULAR ANNULAR SPACE FUEL ALARM CLEAR 1-13-11 9:42AM
L 1 ANNULAR ANNULAR SPACE FUEL ALARM ALARM 1-13-11 9:35AM
L 2 OTHER FILL SUMP FUEL ALARM CLEAR 1-13-11 9:35AM
L 2 OTHER FILL SUMP FUEL ALARM ALARM 1-13-11 9:28AM
L 3 STP SUMP PIPING SUMP FUEL ALARM CLEAR 1-13-11 9:26AM
L 3 STP SUMP PIPING SUMP FUEL ALARM ALARM 1-13-11 9:21AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM CLEAR 10-18-10 12:11AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM ALARM 10-18-10 12:06AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM CLEAR 7-20-10 11:28AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM ALARM 7-20-10 11:23AM
L 2 OTHER FILL SUMP FUEL ALARM CLEAR 4-23-10 9:04AM
L 2 OTHER FILL SUMP FUEL ALARM ALARM 4-22-10 2:15AM
T 1 TANK DIESEL TK#SA004U001 LEAK ALARM CLEAR 4-04-10 3:53PM
T 1 TANK DIESEL TK#SA004U001 SUDDEN LOSS ALARM CLEAR 4-04-10 3:53PM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT CLEAR 4-04-10 3:52PM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT ALARM 4-04-10 3:51PM
T 1 TANK DIESEL TK#SA004U001 LEAK ALARM ALARM 4-04-10 3:50PM
T 1 TANK DIESEL TK#SA004UO01 PROBE OUT CLEAR 4-04-10 3:48PM
T 1 TANK DIESEL•TK#SA004U001 PROBE OUT ALARM 4-04-10 3:47PM
T 1 TANK DIESEL TK#SA004U001 SUDDEN LOSS ALARM ALARM 4-04-10 3:46PM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM CLEAR 4-02-10 8:03AM
I 1 INPUT GENERATOR RUN EXTERN INPUT ALARM ALARM 4-02-10 7:58AM
T 1 TANK DIESEL TK#SA004O001 HIGH WATER ALARM CLEAR 1-28-10 11:31AM
T 1 TANK DIESEL TK#SA004U001 PROBE OUT CLEAR 1-28-10 11:31AM
T 1 TANK DIESEL TK#SA004UO01 PROBE OUT ALARM 1-28-10 11:29AM
T 1 TANK DIESEL TK#SA0040001 HIGH WATER ALARM ALARM 1-28-10 11:21AM
I11200
JAN 17, 2011 2:59 PM
BKFDCAI2 SA004
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK#SA004U001 LOW TEMP WARNING CLEAR 1-13-11 10:18AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING CLEAR 1-13-11 10:18AM
T 1 TANK DIESEL TK#SA004UO01 LOW TEMP WARNING ALARM 1-13-11 10:18AM
T 1 TANK DIESEL TK#SA004UO01 DELIVERY NEEDED CLEAR 1-13-11 10:18AM
T 1 TANK DIESEL TK#SA004U001 HIGH WATER WARNING ALARM 1-13-11 10:08AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED A00'U0❑$11Lkl3-11 10:00AM
T 1 TANK DIESEL TK#SA0040001 DELIVERY NEEDED CLEAR 1-13-11 9:58AM
T 1 TANK DIESEL TK#SA004UO01 INVALID FUEL LEVEL CLEAR 1-13-11 9:58AM
T 1 TANK DIESEL TK#SA004U001 DELIVERY NEEDED ALARM 1-13-11 9:58AM
T 1 TANK DIESEL TK#SA004U001 INVALID FUEL LEVEL ALARM 1-13-11 9:57AM
T 1 TANK DIESEL TK#SA004UO01 LOW TEMP WARNING CLEAR 4-04-10 4:12PM
T 1 TANK DIESEL TK#SA004UO01 LOW TEMP WARNING ALARM 4-04-10 3:50PM
T 1 TANK DIESEL TK#SA004UO01 HIGH WATER WARNING CLEAR 1-28-10 11:31AM
T 1 TANK DIESEL TK#SA004UO01 LOW TEMP WARNING CLEAR 1-28-10 11:31AM
T 1 TANK DIESEL TK#SA004UO01 LOW TEMP WARNING ALARM 1-28-10 11:31AM
T 1 TANK DIESEL TK#SA004UO01 HIGH WATER WARNING ALARM 1-28-10 11:21AM
L 2 OTHER FILL SUMP LIQUID WARNING CLEAR 1-28-10 10:24AM
L 2 OTHER FILL SUMP LIQUID WARNING ALARM 1-28-10 10:19AM
SYSTEM PRINTER ERROR CLEAR 1-04-10 9:53AM
SYSTEM PAPER OUT CLEAR 1-04-10 9:53AM
SYSTEM PAPER OUT ALARM 1-04-10 9:53AM
SYSTEM PRINTER ERROR ALARM 1-04-10 9:53AM
SYSTEM PRINTER ERROR CLEAR 1-04-10 9:52AM
SYSTEM PAPER OUT CLEAR 1-04-10 9:52AM
SYSTEM PRINTER ERROR ALARM 12-30-09 3:52PM
SYSTEM PAPER OUT ALARM 12-30-09 3:52PM
SYSTEM PRINTER ERROR CLEAR 2-18-09 10:51AM
SYSTEM PRINTER ERROR ALARM 2-18-09 10:51AM
T 1 TANK DIESEL TK#SA004UO01 HIGH PRODUCT ALARM CLEAR 2-18-09 10:30AM
T 1 TANK DIESEL TK#SA004UO01 HIGH PRODUCT ALARM ALARM 2-18-09 10:30AM
L 2 OTHER FILL SUMP LIQUID WARNING CLEAR 2-16-09 10:17AM
L 2 OTHER FILL SUMP LIQUID WARNING ALARM 2-18-09 10:13AM
SYSTEM PRINTER ERROR CLEAR 12-30-08 11:21AM
SYSTEM PRINTER ERROR ALARM 12-30-08 11:21AM
SYSTEM PRINTER ERROR CLEAR 12-30-08 11:21AM
SYSTEM PRINTER ERROR ALARM 12-30-08 11:21AM
SYSTEM PRINTER ERROR CLEAR 12-30-08 11:21AM
SYSTEM PAPER OUT CLEAR 12-30-08 11:21AM
SYSTEM PRINTER ERROR ALARM 12-28-08 9:09PM
SYSTEM PAPER OUT ALARM 12-28-08 9:09PM
SYSTEM PRINTER ERROR CLEAR 12-17-08 10:34AM
SYSTEM PRINTER ERROR ALARM 12-17-08 10:34AM
SYSTEM PRINTER ERROR CLEAR 10-23-08 3:08PM
SYSTEM PRINTER ERROR ALARM 10-23-08 3:08PM
SYSTEM PRINTER ERROR CLEAR 10-23-08 3:07PM
SYSTEM PAPER OUT CLEAR 10-23-08 3:07PM
SYSTEM PRINTER ERROR ALARM 10-23-08 8:OOAM
SYSTEM PAPER OUT ALARM 10-23-08 8:00AM
SYSTEM PRINTER ERROR CLEAR 8-11-08 9:45AM
SYSTEM PAPER OUT CLEAR 8-11-08 9:45AM
120600
JAN 17, 2011 2:59 PM
BKFDCA12 SA004
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
TANK ALARM HISTORY
TANK 1 DIESEL TK#SA004UO01
SETUP DATA WARNING APR 21, 2004 8:51 AM
APR 21, 2004 8:34 AM
APR 21, 2004 8:28 AM
LEAK ALARM APR 4, 2010 3:50 PM
APR 14, 2004 9:35 AM
HIGH WATER ALARM JAN 13, 2011 10:08 AM
JAN 28, 2010 11:21 AM
OVERFILL ALARM JAN 13, 2011 9:59 AM
JAN 28, 2010 11:06 AM
MAY 7, 2008 1:54 PM
LOW PRODUCT ALARM JAN 13, 2011 10:00 AM
JAN 13, 2011 9:58 AM
MAY 6, 2008 2:45 PM
SUDDEN LOSS ALARM JAN 13, 2011 11:55 AM
JAN 13, 2011 10:18 AM
JAN 13, 2011 9:55 AM
HIGH PRODUCT ALARM FEB 18, 2009 10:30 AM
FEB 27, 2008 10:29 AM
MAR 15, 2007 9:05 AM
INVALID FUEL LEVEL JAN 13, 2011 9:57 AM
MAY 6, 2008 2:43 PM
PROBE OUT JAN 13, 2011 10:16 AM
JAN 13, 2011 9:55 AM
APR 4, 2010 3:51 PM
HIGH WATER WARNING JAN 13, 2011 10:08 AM
JAN 28, 2010 11:21 AM
DELIVERY NEEDED JAN 13, 2011 10:00 AM
JAN 13, 2011 9:58 AM
MAY 6, 2008 2:45 PM
MAX PRODUCT ALARM MAR 29, 2006 9:32 AM
LOW TEMP WARNING JAN 13, 2011 10:18 AM
APR 4, 2010 3:50 PM
JAN 28, 2010 11:31 AM
I30200
JAN 17, 2011 3:00 PM
BKFDCA12 SA004
1918 M ST.
BAKERSFIELD,CA 93301
661-631-2540
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 ANNULAR SPACE
JAN 13, 2011 9:35 AM FUEL ALARM
JAN 28, 2010 10:37 AM FUEL ALARM
FEB 18, 2009 10:21 AM FUEL ALARM
2 FILL SUMP
JAN 13, 2011 9:28 AM FUEL ALARM
APR 22, 2010 2:15 AM FUEL ALARM
JAN 28, 2010 10:43 AM FUEL ALARM
3 PIPING SUMP
JAN 13, 2011 9:21 AM FUEL ALARM
JAN 28, 2010 10:50 AM FUEL ALARM
FEB 18, 2009 10:05 AM FUEL ALARM
4 TRANSITION SUMP
JAN 13, 2011 9:50 AM FUEL ALARM
JAN 13, 2011 9:50 AM FUEL ALARM
JAN 28, 2010 10:55 AM FUEL ALARM
TAiT
Rt5IN4�Q TH!CHAW"Of 2131 S. Dtupotij Drive, Annhcirn,CA 928 06
p:714i560;8222 w,toi t:com
January 20, 2011
VIA FED EX: 7966 8023 9715
Bakersfield Fire Department
2101 H Street
Bakersfield CA 93301
Re: Monitoring System Certification
Spill Bucket Testing
Product Line Testing
Pacific Bell Telephone Co. dba AT&T California
1918 "M" STREET, BAKERSFIELD, CA
GEOPAR: SA004
To Whom It May Concern:
Enclosed are the results for the following tests completed on January 13, 2011:
■ Monitoring System Certification Report Form
■ Spill Bucket Testing Report Form
■ Product Line Testing Report Form
Please do not hesitate to call me if you have any questions.
Truly Yours,
I
h . Denison
Program Manager
CA iica 588098 A2 llc#095984 i NV lica 0049666 i TX lira CR0000041