HomeMy WebLinkAbout215 21ST ST (3) Monitoring System Certification IIIIIIIIIIIIIIIIIIII 51 For Use By All Jurisdictions Within the State of California IE Authority Cited:Chapter 6.7, Health and Safety Code;Chapter 16, Division 3, Title 23, California Code of Regulations This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each monitoring system control panel by the technician who performs the work.A copy of is omi a provided o e n System owner .opera or.The owner/operator must su mi a copy of this form to the local agency regulating UST systems within 30 days of test date. A. General Information Facility: Pepsi Bottling Company Bld No: Address: 215 East 21st St. City: Bakersfield Zi p: 93305 Facility Contact Person: George Contact Phone No: (661)635-1109 Make/Model of Monitoring System: Veeder-Root/Simplicity Service Date: 08/04/2008 B. Inventory of Equipment Tested/Certified Check the appropriate boxes to Indicate specific equipment Inspected/serviced: Tank ID: Diesel Fuel Tank ID: ®In-Tank Gauging Probe Model:846390-109 ❑In-Tank Gauging Probe Model: ®Annular Space or Vault Sensor Model:794390-302 ❑Annular Space or Vault Sensor Model: ®Piping Sump/Trench Sensor(s) Model:794380-352 ❑Piping�Sump/Trench Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ®Mechanical Line Leak Detector Model:FX-1VD ❑Mechanical Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ❑Tank Overfill/High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model: ❑Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2) Tank ID: Tank ID: ❑In-Tank Gauging Probe Model: ❑In-Tank Gauging Probe Model: ❑Annular Space or Vault Sensor Model: ❑Annular Space or Vault Sensor Model: ❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model: ❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model: ❑Tank Overfill/High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model: ❑Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2) Dispenser ID: 1 &2 Dispenser ID: ❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model: ®Shear Valve(s) ❑Shear Valve(s) ®Dispenser Containment Float(s)and Chain(s) I ❑Dispenser Containment Float(s)and Chain(s) Dispenser ID: Dispenser ID. ❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model: ❑Shear Valve(s) ❑Shear Valve(s) ❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s) Dispenser ID: Dispenser ID: ❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model: ❑Shear Valve(s) ❑Shear Valve(s) ❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s) If the facility contains more tanks or dispensers,copy this form.Include information for every tank and dispenser at the facility. C. Certification-I certify that the equipment Identified In this document was Inspected/serviced in accordance with the manufacturers'guidelines.Attached to this Certification Is Information(e.g. manufacturers'checklists)necessary to verify that this Information Is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports,I have also attached a copy of the report; (check all that apply): ®System set-up ®Alar ry-report Technician Name (Print):Adolfo Aguilar Signature: Certification No: A20066 License No: 588098 Testing Company Name: TAIT ENVIRONMENTAL Phone No: (714)560-8222 SERVICES Page 1 of 4 IIIIIIIIIIIIIIIIIIII 52 IE Monitoring System Certification Address: 215 East 21st St. Bakersfield 93305 Service Date: 08/04/2008 D. Results of Test!ng/Servicing Software Version Installed: 119.05 Complete the fol owing checklist: ®Yes F-1 No* Is the audible alarm operational? ®Yes ❑No* Is the visual alarm operational? ®Yes ❑No* Were all the sensors visually inspected, functionally tested, and cofirmed operational? ®Yes ❑No* Were all sensors installed at lowest point of secondary containment and positioned so that other e ui ment will not interfere with their proper operation? ®Yes ❑No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g. modem) operational? ❑N/A ®Yes ❑No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes:which sensors initiate positive shut- ®Sump/Trench Sensors ❑Dispenser Containment Sensors ❑N/A down?: Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ®Yes ❑No ❑Yes ❑No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the ®N/A tank fill point(s)and operating properly?If so, at what percent of tank capacity does the alarm trigger?: ❑Yes* ®No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the manufacturer name and model for all replacement parts in Section E below. Was liquid found inside any secondary containment systems designed as dry systems? ❑Yes* ®No If yes,check the type(s)of liquid found and describe causes in Section E, below. ❑product ❑Water ®Yes ❑No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable ®Yes ❑No* Is all monitoring equipment operational per manufacturers specifications? *In Section E below,describe how and when these deficiencies were or will be corrected. E. Comments OPW Flapper Valve Present For Overfill Provention. Page 2 of 4 Monitoring System Certification Address: 215 East 21 st St. Bakersfield 93305 Service Date: 08/04/2008 F. In-Tank Gauging/SIR Equipment ®Check this box if tank gauging is used only for inventory control ❑Check this box if no tank gauging or SIR Equipment is installed This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring Complete the fol owing checklist ®Yes ❑No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults? ®Yes F-1 No* Were all tank gauging probes visually inspected for damage and residue buildup? ®Yes ❑No* Was accuracy of system product level readings tested? ®Yes F-1 No* Was accuracy of system water level readings tested? ®Yes ❑No* Were all probes reinstalled properly? ®Yes ❑No* Were all items on the equipment manufacturers maintenance checklist completed? * In the Section H below, describe how and when these deficiencies were or will be corrected G. Line Leak Detectors (LLD): ❑Check this box if LLDs are not installed Complete the fol owing checklist ®Yes ❑No* For equipment start-up or annual equipment certification,was a leak simulated to verify LLD performance? ❑N/A Simulated Leak Rate(check all that apply) ®3.0 g.p.h ❑0.1 g.p.h ❑0.2 g.p.h ®Yes F-1 No" Were all LLDs confirmed operational and accurate within regulatory requirements? ®Yes ❑No* Was the testing apparatus properly calibrated? ®Yes ❑No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak? ❑N/A ❑Yes ❑No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak? ®N/A ❑Yes El No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ®N/A ❑Yes ❑No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a test? ®N/A ❑Yes ❑No* For electronic LLDs, have all accessible wiring connections been visually inspected? ®N/A ®Yes ❑No* Were all items on the equipment manufacturers maintenance checklist completed? * In the Section H below, describe how and when these deficiencies were or will be corrected H. Comments Veeder-Root Is Reading "All Functions Normal", Therefore No Ground Faults Present @ This Time. Page 3 of 4 Monitoring System Certification Address: 215 East 21 st St. Bakersfield 93305 Service Date: 08/04/2008 UST monitoring Site Plan Pepsi Batdicg Group 215 E.21st Street Bakersfield,Ca. Lot Aroa----------.—_.) 1/2 epehuer North I I—Product Run Amin/ I Glrect Buried Spill Bucketpl �urbinelATG Sump E.S.O.Switch = = = = J Security Check Inn. Veeder-Root Tank Nonitor System Gall shack) Gate Door Entry -------_---__.._______—_----------------------------Fast 21st Strret-------------------------------------_.-------- Date map was drawn: 08/04/2008 Instructions If you already have a diagram that shows all required information, you may include it, rather than this page, with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping. Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment areas; mechanical or electronic line leak detectors; and in-tank liquid level probes (if used for leak detection). In the space provided, note the date this Site Plan was inspected. Page 4 of 4 SWRCB,January 2006 SPILL BUCKET TESTING REPORT FORM This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printout from tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1.FACILITY INFORMATION Facility Name: Pepsi Bottling Company Date of Testing: 08/04/2008 Facility Address: 215 East 21st St. Bakersfield CA 93305 Facility Contact: George lFacility Phone: 714-522-9669 Date Local Agency Was Notified of Testing: 07/16/2008 Name of Local Agency Inspector if present during testing): Eddie Medina Bakersfield Fire . 2.TESTING CONTRACTOR INFORMATION Company Name: TAIT ENVIRONMENTAL SERVICES Technician Conducting Test: Adolfo Aguilar Credentials: ®CSLB Contractor ®ICC Service Tech ❑SWRCB Tank ❑Other(Specify) ICC Technician Tester 5238610-UT License Number (s): A ASB HAZB C-10 588098 3.SPILL BUCKET TESTING INFORMATION Test Method Used ®Hydrostatic ❑Vacuum ❑Other Test Equipment Used: Incon TS-STS I Equipment Resolution: .0006 Identify Spill Bucket(By Tank Number, 1 Diesel Bucket 2 3 4 Stored Product,etc) Bucket Installation Type ®Direct Bury El Direct Bury ❑Direct Bury F-71 Direct Bury ❑Contained in Sump []Contained in Sump ❑Contained in Sump ❑Contained in Sump Bucket Diameter inches 12" Bucket Depth inches 13" Wait Time between applying 15 Minutes vacuum/water and start of test Test Start Time: 10:13 am/ 10:33 am Initial Reading 2.2931"/2.2909" Test End Time: 10:28 am/ 10:48 am Final Reading(R f): 2.2927"/2.2890" Test Duration: 15 min./ 15 min. Change in Reading Rf-Ri : -.0004"/-.0019" Pass/Fail Threshold or Criteria: .002" Test Result Pass Comments: Left Haz-Waste Test Water @ Site In A 55 Gallon Drum Properly Labeled And Marked. CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING i hereby certify that all the information t 'ne in this report is true,accurate and in full compliance with legal requirements Technician's Signature Date 08/04/2008 — Tait Environmental Services UST Construction • Design • Maintenance • Compliance LEAK DETECTOR TESTING Facility Name: Pepsi Bottling Company Technician: Adolfo Aguilar Location Tested: 215 East 21$ Street Bakersfield Tech ID#: 5238610-UT Contact: 714-560-8222 Test Date: 8/4/2008 Test Leak Rate Metering Opening F/E Hold Pass/ Product M1/Min PSI Slow Flow PSI Bleed Back Time PSI. Fail Ser# Diesel 189 29 psi 11 psi 80 ml 2 Sec. 30 psi Pass UNK Leak Detector Type (Check One): ❑ XLD P/N 116036 ❑ FX IV ❑ PLD P/N 116030 ® FX IDV ❑ BFLD P/N 116012 ❑ VAPORLESS LD 2000 ❑ XLP P/N 116035 ❑ VAPORLESS LD 2200 ❑ BLFLD (XL Model) P/N 116039 ❑ VAPORLESS LD 3000 ❑ DLD P/N 116017 ❑ TOKHEIM ❑ FE PETRO ❑ OTHER Technician Signature: CA Lic#588098 • AZ Lic#095984 • NV Lic#0049666 1863 North Neville Street • Orange, California 92865 • 714.560.8222 • 714.685.0006 Fax 11280 Trade Center Drive- Rancho Cordova, California 95742 • 916.858.1090 • 916.858.1011 Fax www.talt.com � e SWRCB,January 2002 Page 1 of 5 Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containments systems. Use the appropriate pages of this form to report results for all components tested. The completed form, written test procedures, and printout from tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1.FACILITY INFORMATION Facility: Pepsi Bottling Company Service Date: 08/04/2008 Facility Address: 215 East 21st St. Bakersfield CA 93305 Facility Contact: George Facility Phone: 714-522-9669 Date Local Agency Was Notified of Testing: 07/16/2008 Test Type: 36 Month Name of Local Agency Inspector if present during testing): Eddie Medina(Bakersfield Fire). 2. TESTING CONTRACTOR INFORMATION Company Name: Tait Environmental Systems Technician Providing Test: AGUILAR ADOLFO Credentials ®CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester ®ICC UST Service Technician License Type:A B ASB C-10 HAZ ILicense Number: 588098 Manufacturer Training Manufacturer Component(s) Date Training Expires ICC Technician 5238610-UT 02/24/2009 Incon TS-STS 2957353761 01/13/2010 3. SUMMARY OF TEST RESULTS Component Pass Fail Not Repairs Component Pass Fail Not Repairs Tested Made Tested Made Turbine Sump ® ❑ ❑ M ❑ ❑ ❑ UDC Sump ® ❑ ❑ 7 ❑ ❑ ❑ Supply Secondary Line X ❑ ❑ ❑ ❑ ❑ Annular ❑ ❑ ® El I ❑ ❑ I❑ ❑ ❑ ❑ El I ❑ ❑ ❑ ❑ ❑ ❑ El El ED ❑ ❑ ❑ El 10 Lj ❑ ❑ ❑ ❑ ❑ ❑ El ❑ ❑ ❑ p ❑ ❑ ❑ ❑ ❑ ❑ 10 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ -Mlt I Q III I El F-1 If hydrostatic testing was performed,describe what was done with the water after completion of tests: Left Haz-Waste Test Water @ Site Properly Labeled And Secured,Total(4)55 Gallon Drums. CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge,the facts stated in this document are accurate and in full compliance with legal requirements Technician's Signature Date 08/04/2008 S WRCB,January 2002 Page 2 of 5 4.TANK ANNULAR TESTING Test Method Developed by ❑ Tank Manufacturer ❑ Industry Standard ❑ Professional Engineer ® Other(Specify) Test Method Used ❑ Pressure ❑ Vacuum ❑ Hydrostatic ® Other(Specify) Test Equipment Used: Equipment Resolution: Tank#Diesel Tank# Tank# Tank# Is Tank Exempt From Testing?(1) ® Yes ❑ No ❑ Yes ❑No ❑ Yes ❑ No ❑ Yes ❑ No Tank Capacity: Tank Material: Tank Manufacturer: Product Stored: Wait Time between applying pressure/vacuum/water and starting test: Test Start Time: Initial Reading(Ri): Test End Time. Final Reading(Rf): Test Duration: Change in Reading(Rf-Ri): Pass/Fail Threshold or Criteria: Test Result ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail Was Sensor Removed for Testing? ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA Was Sensor properly replaced and ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA verified after testing? Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests The tank's annular space is brine filled.Does not have to be tested. (1)Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment,such as sysrtems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) SWRCB,January 2002 Page 3 of 5 5. SECONDARY PIPE TESTING Test Method Developed by ❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer ❑ Other(Specify) Test Method Used ® Pressure ❑ Vacuum ❑ Hydrostatic ❑ Other(Specify) Test Equipment Used:4"Dial Gauge Equipment Resolution: .1 Piping Run#Supply Piping Run# Piping Run# Piping Run# Sec. Piping Material: Fiberglass Piping Manufacturer: A.O. Smith Piping Diameter: 3" Length of Piping Run: Approx. 15' Product Stored: Diesel Method and location of piping-run test boot @ Turbine isolation: sum Wait Time between applying 15 Minutes pressure/vacuum/water and starting test: Test Start Time: 9:50 AM Initial Reading(Ri): 5 PSI Test End Time: 10:50 AM Final Reading(Rf): 5 PSI Test Duration: One Hour Change in Reading(Rf-Ri): 0 Pass/Fail Threshold or Criteria: 0 Test Result ® Pass 13 !!il_jj ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests SWRCB,January 2002 Page 4 of 5 6.PIPING SUMP TESTING Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer ❑ Other(Specify) Test Method Used ❑ Pressure ❑ Vacuum ® Hydrostatic ❑ Other(Specify) Test Equipment Used: Incon TS-STS Equipment Resolution: .0006 Sump#Piping Sump# Sump# Sump# Sump Diameter 48" Sump Depth 48" Sump Material Fiberglass Height from Tank Top to Top of 24" Highest Pil)ing Penetration Height from Tank Top to Lowest 20" Electrical Penetration Condition of sump prior to testing Clean Portion of Sump Tested(1) 2"above piping penetration Does turbine shut down when sump sensor detects liquid(both ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA product and water)?* Turbine shutdown response time N/A Is sytem programmed for fail-safe ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA shutdown?* Was fail-safe verified to be ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA operational?* Wait time between applying pressure/vacuum/water and starting 15 Minutes test Test Start Time 10:13 am 10:33 am Initial Reading Ri) 6.3561" 6.3571" Test End Time 10:28 am 10:48 am Final Reading 6.3565" 6.3565" Test Duration 15 15 Change in Reading Rf-Ri +.0004" -.0006" Pass/Fail Threshold or Criteria .002" Test Result ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail Was sensor removed for testing? ® Yes ❑ No ❑ NA E01 es ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA Was sensor properly replaced and ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA verified functional after testin ? Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests (1)If the entire depth of the sump is not tested,specify how much was tested.If the answer to any of the questions indicated with an asterisk(*)is"NO"or"NA",the entire sump must be tested.(See SWRCB LG-160) SWRCB,January 2002 Page 5 of 5 7. UNDER-DISPENSER CONTAINMENT TESTING Test Method Developed by ❑ UDC Manufacturer ® Industry Standard ❑ Professional Engineer ❑ Other(Specify) Test Method Used ❑ Pressure ❑ Vacuum ® Hydrostatic ❑ Other(Specify) Test Equipment Used: Incon TS-STS Equipment Resolution: .0006" UDC#1 &2 UDC# UDC# UDC# UDC Manufacturer Bravo UDC Material Steel UDC Depth 10" Height from UDC Bottom to Top 6" of Hi hest Piping Penetration Height from UDC Bottom to 0" Lowest Electrical Penetration Condition of UDC prior to testing Clean Portion of UDC Tested 1 2"above piping Does turbine shut down when UDC sensor detects liquid(both product ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA and water)? Turbine shutdown response time N/A Is sytem programmed for fail-safe ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA shutdown? Was fail-safe verified to be ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA operational? Wait time between applying pressure/vacuum/water and starting 15 Minutes test Test Start Time 10:13 AM 10:33 AM Initial Reading Ri) 2.5760" 2.5757" Test End Time 10:28 am 10:48 am Final Reading 2.5759" 2.5756" Test Duration 15 15 Change in Reading Rf-Ri -.0001" -.0001" Pass/Fail Threshold or Criteria .002" Test Result ® Pass ❑ Fall ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail Was sensor removed for testing? ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA Was sensor properly replaced and verified functional after testing? ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests Bravo Float On UDC,No Sensor. (1)If the entire depth of the UDC is not tested,specify how much was tested.If the answer to any of the questions indicated with an asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) PEPSI - 215-E.-21ST._ - - - BAKERSFIELD CA PEPSI y S E_ LD 21ST. 98/94i2998 IE 19:13 AM BAKERSF CA `:SUMP LEVEL REPORT 08✓04�2008. 9:35 AM SUMP LEVEL REPORT SUMP:TURBINE 6.356 IN _;SUPIP.`DSP 1 2.576 IN SUMP.::BUCKET 2.293 IN SUMP TURBINE 0.000 IN :.SUMP:.DSP 1 1.726 IN SUMP :BUCKET 2.300 IN SOFTWARE REVISION LEVEL VERS I QN_1 19..-05- SOFTWARE# 346119-100-F CREATED - 00.02.25.12.15 S-MODULE# 330160-105-A SYSTEM-FEATURES: � PEPSI PERIODIC IN-TANK TESTS 215 E.21ST. ANNUAL IN-TANK TESTS `'BAKERSFIELD CSLD CA HIR PEPSI FUEL MANAGER 215 E.21ST. 0812008 10:29 AM BAKERSFIELD CA SLIMP LEAK TEST REPORT 08/04/2008 9:53 AM TURBINE NO SUMP LEVEL REPORT TE7 STARTED. 10:13 AM FT�ST STARTED 08/0412808 ""'BEGIN LEVEL: 6.3561 IN SUMP TURBINE 6.357 INENp TIME' 19:28 AM SKIMP DSP 1 2.576 IN END DATE. 08/04/2008 108889 PEPSI SITE 9 SUMP.BUCKET 2.299 IN ;:EhiD._LEVEL. x.3565 IN 215 EAST 21ST STREET LEAK`THRESHOLD 0.002 IN HAKERSFIELD.CA 93305 TEST"RESULT PASSED 81152324905001 AUG 4, 2008 8:23 AM DSP 1 TEST::STARTED 19:13 AM TEST STARTED 08/0412008 SYSTEM STATUS REPORT BEGIN".LEVEL 2.5760 IN ALL FUNCTIONS NORMAL PEPSI END TIME 10:28 AM 215 E.21ST. END DATE 98/0412008 BAKERSFIELD ENI?LEVEL 2.5759 IN CA LEAK :THRESHOLD 8.002 IN TEST-.RESULT PASSED 08/0412008 _ 10:00 AM SUMP LEVEL REPORT BUCKET TEST STARTED 10:13 AM SUMP TURBINE 6.357 IN TEST STARTED 08/04/2908 BEGIN LEVEL 2.2931 IN SUMP DSP 1: 2.576 IN END TIME 19:28 AM � 1 BUCKET 2:298 IN END DATE 08/04/2008 3 END:LEVEL 2.2927 IN t�� ° LEAK THRESHOLD-.,0.002.:IN , RESULT :PASSED TEST DATE: 114/08 CLIENT:PEPSI BAKERSFEILD PAGE OF__L --- SENSOR ALARM------ L 1 :ANNULAR SPACE ANNULAR SPACE LOW LIQUID ALARM 108889 PEPSI SITE 9 AUG 4, 2008 9:02 AM 215 EAST--2IST-STREET BAKERSFIELD.CA 93305 -. 81152324905001 -----7 "fk AUG 4, 2008 9:32 AM PEPSI: ---- li BRKERSFIELD CA SYSTEM STATUS REPORT - - - - - - - - - - - - 08�04%Z088 10:48 AIM ----- SENSOR ALARM ----- ALL FUNCTIONS NORMAL SUMP LEAK TEST REPORT L 2:TURBINE SUMP STP SUMP TURBINE FUEL ALARM AUG 4, 2008 9:02 AM TEST STARTED 10:33 AM -JEST STARTED 08/04/2008 BEGIN?LEVEL 6.3571 IN >END.`T.lME 10:48 AM _ E,ND DATE 08/04/2008 ----- SENSOR ALARM ----- ``END LEVEL . 6.3565 I4 L 1 :ANNULAR SPACE LEAK.:THRESHOLD 0.002 IN ANNULAR SPACE TESTt RESULT PASSED LOW LIQUID ALARM ----- SENSOR ALARM AUG 4. 2008 9:33 AM DSP 1 L 2:TURBINE SUMP STP SUMP TEST STARTED 10:33 AM FUEL ALARM ,I ST'STARTED 0 ,02008 AUG 4. 2008 9:02 AM BEGIN.::LEVEL 2.5757 IN ':END TIME 10:48 AM DATE 08/04/2008 END.`LEVEL : 2.5756 IN ,LEAK...THRESHOLD 0.002 IN ---- IN-TANK ALARM ----- TEST`.RESULT PASSED T 1 :DIESEL FUEL DELIVERY NEEDED AUG 4, 2008 9:37 AM BUCKET ----- SENSOR ALARM ----- STARTED 10:33 AM L 1 :ANNULAR SPACE ANNULAR SPACE TEST:;STARTED. .08/8412008 SENSOR OUT ALARM :'BEGIN:;'LEVEL. . 2:2989 IN AUG 4, 2008 9:04 AM :?END TIME: 10:48 AM END DATE 08/04/2008 -i5,ND LEVEL 2.2890: I.N f LEAK-THRESHOLD 0.002 IN ESTpRESULT' PASSED ---- IN-TANK ALARM ----- � 3 T 1 :DIESEL FUEL. PROBE OUT .,...,.. ..._..._ AUG 4. 2008 9:37 AM ----- SENSOR ALARM ----- _ L 2:TURBINE SUMP STP SUMP SENSOR OUT ALARM AUG 4, 2008 9:04 AM TEST DATE: 8/4/08 CLIENT: PEPSI BAKERSFEILD PAGE ;? OF_ 1 T 1 :DIESEL FUEL - --. IN-TANK ALARM ------ INVENTORY INCREASE - T I :DIESEL FUEL INCREASE START LOW TEMP WARNING AUG 4, 200 AUG 4. 2008 11 :11 AM 8 11 :47 AM VOLUME = 6688 GALS HEIGHT - 54.45 INCHES WATER = 1 .31 INCHES T_1 :D_I-ESEL -FUEL- TEMP = 108.1 DEG F INVENTORY INCREASE INCREASE START INCREASE END AUG 4, 2008 11 :01 AM AUG 4, 2008 11 :18 AM T I :DIESEL FUEL VOLUME = 8279 GALS VOLUME = 6807 GALS INVENTORY INCREASE HEIGHT = 63.94 INCHES HEIGHT = 55.15 INCHES INCREASE START WATER = 1 .20 INCHES WATER - 0.78 INCHES AUG 4. 2008 11 :31 AM TEMP = 10.6.5 DEG F TEMP = 108. 1 DEG F VOLUME = 6807 GALS 9 HEIGHT = 55.16 INCHES GROSS INCREASE= 11 INCREASE END AUG 4, 2008 11 :09 AM TC NET INCREASE= 116 WATER = 0.78 INCHES TEMP = 108.6 DEG F VOLUME = 8356 GALS HEIGHT = 64.41 INCHES INCREASE END WATER = 1 .22 INCHES AUG 4, 2008 11 :51 AM TEMP = 107.0 DEG F VOLUME = 9567 GALS HEIGHT - 71 .77 INCHES GROSS INCREASE= 77 WATER = 1 .69 INCHES TC NET INCREASE- 74 TEMP = 110.3 DEG F T I :DIESEL FUEL GROSS INCREASE= 2760 ADJUSTED DELIVERY REPORT TC NET INCREASE= 2692 AUG 4, 2008 11 :11 AM DELIVERY VOLUME = 117 TC DLVY VOLUME = 119 T I :DIESEL FUEL ADJUSTED DELIVERY REPORT AUG 4. 2008 11 :01 AM T 1 :DIESEL FUEL ADJUSTED DELIVERY REPORT DELIVERY VOLUME = -1585 TC DLVY VOLUME = -1556 AUG 4. 2008 11 :31 AM DELIVERY VOLUME = -2439 ---- IN-TANK ALARM ----- TC DLVY VOLUME = -2357 T 1 :DIESEL FUEL PROBE OUT AUG 4, 2008 11 :39 AM TEST DATE: 8/4/08 CLIENT:PEPSI BAKERSFEILD PAGE ' OF FLOAT SIZE: 4.0 IN.. 8496 RS-232 SECURITY- WATER WARNING - : 1 .5 CODE flD0000 HIGH WATER LIMIT: 2.0 MAX OR LABEL VOL: 15102 OVERFILL LIMIT 88'i 13289 RS-232 END OF MESSAGE HIGH PRODUCT 92% DISABLED 13893 DELIVERY LIMIT 20% AUTO DIAL ALARM SETUP 3020 LOW PRODUCT 1000 D 8:SIMPLICITY CENTER LEAK ALARM LIMIT: 24 108889 PEPSI SITE 9 SUDDEN LOSS LIMIT: 50 215 EAST _21ST.STREET- IN-TANK ALARMS TANK TILT 1 .51 BAKERSFIELD.CA 93305 ALL:LEAK ALARM 81152324905001 ALL:SUDDEN LOSS ALARM MANIFOLDED TANKS AUG 4. 2008 8:21 AM ALL:PROBE OUT TO: NONE ALL:GROSS TEST FAIL FUEL MANAGEMENT SETUP ALL:PERIODIC TEST FAIL - - - - _ _ - _ - - _ - ALL:NO CSLD IDLE TIME LEAK MIN PERIODIC: 0% ALL:CSLD INCR RATE WARN 0 DELIVERY WARN DAYS: 0.4 ALL:ACCU_CHART CAL WARN AUTO PRINT: DISABLED ALL:LOW TEMP WARNING LEAK MIN ANNUAL ox ALL:GROSS FAIL LINE TNK 0 LIQUID SENSOR ALMS T 1 :DIESEL FUEL ALL:FUEL ALARM PERIODIC TEST TYPE AVG SALES-SUN: 12 GAL ALL:SENSOR OUT ALARM STANDARD AVG SALES-MON: 458 GAL ALL:SHORT ALARM ----AVG_SALES-TUE: 532 GAL ALL:WATER ALARM ANNUAL TEST FAIL AVG SALES-WED: 704 GAL ALL:WATER OUT ALARM ALARM DISABLED AVG SALES-THR: 483 GAL ALL:HIGH LIQUID ALARM AVG SALES-FRI : 503 GAL ALL:LOW LIQUID ALARM PERIODIC TEST FAIL AVG SALES-SAT: 191 GAL ALL:LIQUID WARNING ALARM DISABLED RECEIVER ALARMS GROSS TEST FAIL SERVICE REPORT WARN ALARM DISABLED LIQUID SENSOR SETUP ALARM CLEAR WARNING - - - - _ - - - - - - - Al l� i EST AVERAGING: OFF POWER SIDE DIM ALM PER TEST AVERAGING: OFF L I :ANNULAR SPACE ALL:DISABLED DIM ALARM DUAL FLOAT HYDROSTATIC ALL:COMMUNICATION ALARM TANK TEST NOTIFY: OFF CATEGORY : ANNULAR SPACE TNK TST SIPHON BREAK:OFF DELIVERY DELAY 5 MIN L 2:TURBINE SUMP DUAL FLT. HIGH VAPOR CATEGORY STP SUMP IN-TANK SETUP T 1 :DIESEL FUEL PRODUCT CODE 1 THERMAL COEFF : .000450. LEAK TEST METHOD TANK DIAMETER 119.50 - - - - - - - - - - - - TANK PROFILE 4 PTS TEST CSLD ALL TANK FULL VOL 15102 Pd = 99• 89.6 -INCH VOL 12290 CLIMATE FACTOR:MODERATE 59.8 INCH VOL 7580 29.9 INCH VOL 2838 METER DATA YES LEAK TEST REPORT FORMAT END FACTOR: HEMISPHER NORMAL CAL UPDATE: IMMEDIATE TEST DATE: 8/4/08 CLIENT: PEPSI BAKERSFEILD PAGE S OF_L_ SYSTEM SETUP AUG:. 4, 2008 8:20 AM 108889 PEPSI SITE 9 215 EAST- .21.ST STREET SYSTEM SECURITY BAKERSFIELD.CA 93305 CODE 000000-- 81152324905001 SYSTEM UNITS U.S. AUG 4, 2008 12:01 PM SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM SYSTEM STATUS REPORT - - - - - - -___108889 PEPSI SITE 9 T 1 :PROBE OUT 215 EAST 21ST STREET $AKERSFIELD.CA 93305 T I :DELIVERY NEEDED 81152324905001 T 1 :LOW TEMP WARNING SHIFT TIME 1 6:00 AM COMMUNICATIONS SETUP - - - SHIFT TIME 2 DISABLED L 1 :LOW LIQUID ALARM SHIFT TIME 3 DISABLED D B:ALARM CLEAR WARNING SHIFT TIME 4 DISABLED PORT SETTINGS: SHIFT BIR PRINTOUTS COMM BOARD : 2 (FXMOD) DISABLED BAUD RATE : 2400 INVENTORY REPORT DAILY BIR PRINTOUTS PARITY : ODD DISABLED STOP BIT : 1 STOP TICKETED DELIVERY DATA LENGTH: 7 DATA T 1 :DIESEL FUEL DISABLED DIAL TYPE : TONE VOLUME = 4367 GALS TANK PER TST NEEDED WRN ANSWER ON : i RING ULLAGE. = 10735 GALS DISABLED 90e ULLAGE- 9224 GALS TANK ANN TST NEEDED WRN TC VOLUME = 4310 GALS DISABLED RECEIVER SETUP: HEIGHT = 40.19 INCHES WATER VOL = 0 GALS LINE RE-ENABLE METHOD WATER = 0.00 INCHES PASS LINE TEST D B:SIMPLICITY CENTER TEMP = 88.8 DEG F LINE PER TST NEEDED WRN CVR T 743-8379 CVR DISABLED R TYPE: COMPUTER * * * * PORT N0. 2 END * LINE ANN TST NEEDED WRN DISABLED RETRY DE 5 RETRY DELAY: 5 PRINT TC VOLUMES CONFIRMATION REPORT: OFF ENABLED TEMP COMPENSATION VALUE (DEG F ) : 60.0 STICK HEIGHT OFFSET DISABLED H-PROTOCOL DATA FORMAT 108889 PEPSI SITE 9 HEIGHT 215 EAST 21ST STREET DAYLIGHT SAVING TIME BAKERSFIELD.CA 93305 ENABLED AUTO DIAL TIME SETUP: 81152324905001 START DATE _MAR WEEK 3 SUN AUG 4, 2008 12:01 PM START TIME D 8:SIMPLICITY CENTER 2:05 AM DIAL MONTHLY END DATE WEEK 2 FRI NOV WEEK 1 SUN DIAL TIME : 1 :49 AM SYSTEM STATUS REPORT END TIME RECEIVER REPORTS: - - - - - - - - - - - - 2:00 AM D 8:ALARM CLEAR,WARNING RE-DIRECT LOCAL PRINTOUT DISABLED EURO PROTOCOL PREFIX S TEST DATE: 8/4108 CLIENT: PEPSI BAKERSFEILD PAGE OF -I OUTPUT RELAY SETUP - - - ALAN HIS-TORY- REPORT- - - ALARM HISTORY REPORT R 2:POSITIVE SHUTDOWN ---- IN-TANK ALARM ----- -- SENSOR ALARM ----- TYPE: T 1 :DIESEL FUEL L 1 :ANNULAR SPACE STANDARD ANNULAR SPACE NORMALLY CLOSED HIGH WATER ALARM SENSOR OUT ALARM JUL 22, 2004 11 :24 AM AUG B. 2007 10:36 AM IN-TANK ALARMS OVERFILL ALARM LOW LIQUID ALARM ALL:LEAK ALARM JUL 22. 2004 11 :15 AM AUG 8, 2007 10:34 AM ALL:SUDDEN LOSS ALARM MAR 17. 2004 8:43 AM LIQUID SENSOR ALMS JUL 16, 2003 9:48 AM LOW LIQUID ALARM L I :FUEL ALARM AUG 8', 2007 10:29 AM L 2:FUEL ALARM LOW PRODUCT ALARM 1 :SENSOR OUT ALARM MAY 25. 2005 2:50 PM - L - L :SENSOR OUT ALARM MAY 25. 2005 2:36 PM L 1 :SHORT ALARM MAY 19. 2005 10:58 PM ALARM HISTORY REPORT L 2:SHORT ALARM HIGH PRODUCT ALARM ----- SENSOR ALARM ----- L 1 :HIGH LIQUID ALARM AUG 2. 2005 9:34 AM L 2:TURBINE SUMP L 1 :LOW LIQUID ALARM JUL, 22, 2004 11 :15 AM STP SUMP JUL 16, 2003 9:47 AM SENSOR OUT ALARM INVALID FUEL LEVEL AUG 8. 2007 10:36 AM MAY 25, 2005 2:49 PM FUEL ALARM MAY 25. 2005 2:36 PM AUG 8. 2007 10:28 AM MAY 19. 2005 10:58 PM FUEL ALARM PROBE OUT AUG 7, 2006 12:14 PM JAN 17. 2008 4:56 PM JAN 17, 2008 4:50 PM - - RECONCILIATION SETUP JAN 17, 2008 4:38 PM - - - - - - - - - - - - 108889 PEPSI SITE 9 HIGH WATER WARNING 215 EAST 21ST STREET MDIM 1 : TTGG JUL 22. 2004 11 :24 AM BAKERSFIELD.CA 93305 81152324905001 AUTOMATIC DAILY CLOSING DELIVERY NEEDED AUG 4. 2008 8:21 AM TIME: 2:00 AM JUL 1. 2008 7:20 AM AUTO SHIFT #1 CLOSING JUN 13. 2008 7:03 AM TIME: DISABLED APR'.25, 2008 3:50 AM SYSTEM STATUS REPORT AUTO SHIFT tt2 CLOSING ACCU CHART CAL WARN TIME: DISABLED ALL FUNCTIONS NORMAL JUL 30, 2001 11 :30 AM AUTO SHIFT #3 CLOSING INVENTORY REPORT TIME: DISABLED RECON WARNING JAN 27. 2003 9:30 AM AUTO SHIFT #4 CLOSING JAN 20. 2003 2:30 PM T 1 :DIESEL FUEL TIME: 6:00 AM JAN 13. 2003 2:30 PM VOLUME = 4372 GALS ULLAGE = 10730 GALS RECON ALARM 90% ULLAGE= 9219 GALS PERIODIC RECONCILIATION JAN 27. 2003 1 :30 PM TC VOLUME = 4316 GALS MODE: MONTHLY JAN 20. 2003 3:30 PM HEIGHT = 40.22 INCHES ALARM: DISABLED JAN 13, 2003 2:30 PM WATER VOL = 0 GALS WATER = 0.00 INCHES TEMP COMPENSATION LOW TEMP WARNING Tom' = 88.3 DEG.F STANDARD MAY 19, 2005 1 :33 PM JUL 22. 2004 11 :26 AM BUS SLOT FUEL METER TANK JUL 9. 2004 11 :30 AM 2 10 0 0 1 2 10 1 . 0 1 TEST DATE: 8/4/08 CLIENT:PEPSI BAKERSFEILD PAGE OF 108889 PEPSI SITE 9 215 EAST_ 21ST_STREET HAKERSFIELD XA 93305 81152324905001 AUG 4. 2008 8:22 AM SYSTEM STATUS REPORT ALL FUNCTIONS NORMAL TEST DATE: 8/4/08 CLIENT:PEPSI BAKERSFEILD PAGE OF 9 � Tait Environmental Services UST Construction Design Maintenance Compliance FedEx Tracking #:8664 6551 0980 August 22, 2008 Bakersfield Fire Department Prevention Services Attn: Steve Underwood 1501 Truxtun Avenue, Bakersfield, CA 93301 Re: Testing Results \ Pepsi Bottling Group 215 East 21st Street Bakersfield, CA ,--Inspector Ernie Medina Please fnd^enclosed the following test results dated August 4, 2008 for the above referenced facility: ■ Monitoring System Certification ■ Spill Bucket Testing Report Form ■ Leak Detector Testing ■ SB989 Testing If you have any questions regarding any of the enclosures please feel free to call me at (714) 567-6413 or email me at bharmon @tait.com. Sincerely, Brian Harmon Compliance Manager CA Lie #588098 • AZ Lie #095984 • NV Lic #0049666 2131 South Dupont Drive, Anaheim, California 92865 • 714.560.8222 • 714.978.2615 Fax 11280 Trade Center Drive • Rancho Cordova, California 95742 • 916.858.1090 • 916.858.1011 Fax www.tait.com