HomeMy WebLinkAbout215 21ST ST (3) Monitoring System Certification IIIIIIIIIIIIIIIIIIII 51
For Use By All Jurisdictions Within the State of California IE
Authority Cited:Chapter 6.7, Health and Safety Code;Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment.A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work.A copy of is omi a provided o e n System owner .opera or.The
owner/operator must su mi a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility: Pepsi Bottling Company Bld No:
Address: 215 East 21st St. City: Bakersfield Zi p: 93305
Facility Contact Person: George Contact Phone No: (661)635-1109
Make/Model of Monitoring System: Veeder-Root/Simplicity Service Date: 08/04/2008
B. Inventory of Equipment Tested/Certified
Check the appropriate boxes to Indicate specific equipment Inspected/serviced:
Tank ID: Diesel Fuel Tank ID:
®In-Tank Gauging Probe Model:846390-109 ❑In-Tank Gauging Probe Model:
®Annular Space or Vault Sensor Model:794390-302 ❑Annular Space or Vault Sensor Model:
®Piping Sump/Trench Sensor(s) Model:794380-352 ❑Piping�Sump/Trench Sensor(s) Model:
❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model:
®Mechanical Line Leak Detector Model:FX-1VD ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
❑Tank Overfill/High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model:
❑Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2)
Tank ID: Tank ID:
❑In-Tank Gauging Probe Model: ❑In-Tank Gauging Probe Model:
❑Annular Space or Vault Sensor Model: ❑Annular Space or Vault Sensor Model:
❑Piping Sump/Trench Sensor(s) Model: ❑Piping Sump/Trench Sensor(s) Model:
❑Fill Sump Sensor(s) Model: ❑Fill Sump Sensor(s) Model:
❑Mechanical Line Leak Detector Model: ❑Mechanical Line Leak Detector Model:
❑Electronic Line Leak Detector Model: ❑Electronic Line Leak Detector Model:
❑Tank Overfill/High Level Sensor Model: ❑Tank Overfill/High Level Sensor Model:
❑Other(Specify equipment type and model in Section E on Page 2) ❑Other(Specify equipment type and model in Section E on Page 2)
Dispenser ID: 1 &2 Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
®Shear Valve(s) ❑Shear Valve(s)
®Dispenser Containment Float(s)and Chain(s) I ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID.
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s) Model: ❑Dispenser Containment Sensor(s) Model:
❑Shear Valve(s) ❑Shear Valve(s)
❑Dispenser Containment Float(s)and Chain(s) ❑Dispenser Containment Float(s)and Chain(s)
If the facility contains more tanks or dispensers,copy this form.Include information for every tank and dispenser at the facility.
C. Certification-I certify that the equipment Identified In this document was Inspected/serviced in accordance with the
manufacturers'guidelines.Attached to this Certification Is Information(e.g. manufacturers'checklists)necessary to verify
that this Information Is correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of
generating such reports,I have also attached a copy of the report; (check all that apply):
®System set-up ®Alar ry-report
Technician Name (Print):Adolfo Aguilar Signature:
Certification No: A20066 License No: 588098
Testing Company Name: TAIT ENVIRONMENTAL Phone No: (714)560-8222
SERVICES
Page 1 of 4 IIIIIIIIIIIIIIIIIIII 52
IE
Monitoring System Certification
Address: 215 East 21st St. Bakersfield 93305 Service Date: 08/04/2008
D. Results of Test!ng/Servicing
Software Version Installed: 119.05
Complete the fol owing checklist:
®Yes F-1 No* Is the audible alarm operational?
®Yes ❑No* Is the visual alarm operational?
®Yes ❑No* Were all the sensors visually inspected, functionally tested, and cofirmed operational?
®Yes ❑No* Were all sensors installed at lowest point of secondary containment and positioned so that other
e ui ment will not interfere with their proper operation?
®Yes ❑No* If alarms are relayed to a remote monitoring station, is all communications equipment(e.g. modem)
operational?
❑N/A
®Yes ❑No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary
containment monitoring system detects a leak, fails to operate, or is electrically disconnected?
If yes:which sensors
initiate positive shut- ®Sump/Trench Sensors ❑Dispenser Containment Sensors
❑N/A down?:
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ®Yes ❑No
❑Yes ❑No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no
mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the
®N/A tank fill point(s)and operating properly?If so, at what percent of tank capacity does the alarm trigger?:
❑Yes* ®No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment
replaced and list the manufacturer name and model for all replacement parts in Section E below.
Was liquid found inside any secondary containment systems designed as dry systems?
❑Yes* ®No If yes,check the type(s)of liquid found and describe causes in Section E, below. ❑product ❑Water
®Yes ❑No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable
®Yes ❑No* Is all monitoring equipment operational per manufacturers specifications?
*In Section E below,describe how and when these deficiencies were or will be corrected.
E. Comments
OPW Flapper Valve Present For Overfill Provention.
Page 2 of 4
Monitoring System Certification
Address: 215 East 21 st St. Bakersfield 93305 Service Date: 08/04/2008
F. In-Tank Gauging/SIR Equipment ®Check this box if tank gauging is used only for inventory control
❑Check this box if no tank gauging or SIR Equipment is installed
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring
Complete the fol owing checklist
®Yes ❑No* Has all input wiring been inspected for proper entry and termination, including testing for ground faults?
®Yes F-1 No* Were all tank gauging probes visually inspected for damage and residue buildup?
®Yes ❑No* Was accuracy of system product level readings tested?
®Yes F-1 No* Was accuracy of system water level readings tested?
®Yes ❑No* Were all probes reinstalled properly?
®Yes ❑No* Were all items on the equipment manufacturers maintenance checklist completed?
* In the Section H below, describe how and when these deficiencies were or will be corrected
G. Line Leak Detectors (LLD): ❑Check this box if LLDs are not installed
Complete the fol owing checklist
®Yes ❑No* For equipment start-up or annual equipment certification,was a leak simulated to verify LLD
performance?
❑N/A Simulated Leak Rate(check all that apply) ®3.0 g.p.h ❑0.1 g.p.h ❑0.2 g.p.h
®Yes F-1 No" Were all LLDs confirmed operational and accurate within regulatory requirements?
®Yes ❑No* Was the testing apparatus properly calibrated?
®Yes ❑No* For mechanical LLDs, does the LLD restrict product flow if it detects a leak?
❑N/A
❑Yes ❑No* For electronic LLDs, does the turbine automatically shut off if the LLD detects a leak?
®N/A
❑Yes El No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is
disabled or disconnected?
®N/A
❑Yes ❑No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system
malfunctions or fails a test?
®N/A
❑Yes ❑No* For electronic LLDs, have all accessible wiring connections been visually inspected?
®N/A
®Yes ❑No* Were all items on the equipment manufacturers maintenance checklist completed?
* In the Section H below, describe how and when these deficiencies were or will be corrected
H. Comments
Veeder-Root Is Reading "All Functions Normal", Therefore No Ground Faults Present @ This Time.
Page 3 of 4
Monitoring System Certification
Address: 215 East 21 st St. Bakersfield 93305 Service Date: 08/04/2008
UST monitoring Site Plan
Pepsi Batdicg Group
215 E.21st Street
Bakersfield,Ca.
Lot Aroa----------.—_.)
1/2 epehuer
North
I
I—Product Run
Amin/ I
Glrect Buried Spill Bucketpl �urbinelATG Sump E.S.O.Switch
= = = = J
Security Check Inn.
Veeder-Root Tank Nonitor System Gall shack)
Gate Door Entry
-------_---__.._______—_----------------------------Fast 21st Strret-------------------------------------_.--------
Date map was drawn: 08/04/2008
Instructions
If you already have a diagram that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification. On your site plan, show the general layout of tanks and piping.
Clearly identify locations of the following equipment, if installed: monitoring system control panels; sensors
monitoring tank annular spaces, sumps, dispenser pans, spill containers, or other secondary containment
areas; mechanical or electronic line leak detectors; and in-tank liquid level probes (if used for leak detection).
In the space provided, note the date this Site Plan was inspected.
Page 4 of 4
SWRCB,January 2006
SPILL BUCKET TESTING REPORT FORM
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printout from
tests(if applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility Name: Pepsi Bottling Company Date of Testing: 08/04/2008
Facility Address: 215 East 21st St. Bakersfield CA 93305
Facility Contact: George lFacility Phone: 714-522-9669
Date Local Agency Was Notified of Testing: 07/16/2008
Name of Local Agency Inspector if present during testing): Eddie Medina Bakersfield Fire .
2.TESTING CONTRACTOR INFORMATION
Company Name: TAIT ENVIRONMENTAL SERVICES
Technician Conducting Test: Adolfo Aguilar
Credentials: ®CSLB Contractor ®ICC Service Tech ❑SWRCB Tank ❑Other(Specify) ICC Technician
Tester 5238610-UT
License Number (s): A ASB HAZB C-10 588098
3.SPILL BUCKET TESTING INFORMATION
Test Method Used ®Hydrostatic ❑Vacuum ❑Other
Test Equipment Used: Incon TS-STS I Equipment Resolution: .0006
Identify Spill Bucket(By Tank Number, 1 Diesel Bucket 2 3 4
Stored Product,etc)
Bucket Installation Type ®Direct Bury El Direct Bury ❑Direct Bury F-71 Direct Bury
❑Contained in Sump []Contained in Sump ❑Contained in Sump ❑Contained in Sump
Bucket Diameter inches 12"
Bucket Depth inches 13"
Wait Time between applying 15 Minutes
vacuum/water and start of test
Test Start Time: 10:13 am/ 10:33 am
Initial Reading 2.2931"/2.2909"
Test End Time: 10:28 am/ 10:48 am
Final Reading(R f): 2.2927"/2.2890"
Test Duration: 15 min./ 15 min.
Change in Reading Rf-Ri : -.0004"/-.0019"
Pass/Fail Threshold or Criteria: .002"
Test Result Pass
Comments: Left Haz-Waste Test Water @ Site In A 55 Gallon Drum Properly Labeled And Marked.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
i hereby certify that all the information t 'ne in this report is true,accurate and in full compliance with legal requirements
Technician's Signature Date 08/04/2008
— Tait Environmental Services
UST Construction • Design • Maintenance • Compliance
LEAK DETECTOR TESTING
Facility Name: Pepsi Bottling Company Technician: Adolfo Aguilar
Location Tested: 215 East 21$ Street
Bakersfield Tech ID#: 5238610-UT
Contact: 714-560-8222
Test Date: 8/4/2008
Test
Leak Rate Metering Opening F/E Hold Pass/
Product M1/Min PSI Slow Flow PSI Bleed Back Time PSI. Fail Ser#
Diesel 189 29 psi 11 psi 80 ml 2 Sec. 30 psi Pass UNK
Leak Detector Type (Check One):
❑ XLD P/N 116036 ❑ FX IV
❑ PLD P/N 116030 ® FX IDV
❑ BFLD P/N 116012 ❑ VAPORLESS LD 2000
❑ XLP P/N 116035 ❑ VAPORLESS LD 2200
❑ BLFLD (XL Model) P/N 116039 ❑ VAPORLESS LD 3000
❑ DLD P/N 116017 ❑ TOKHEIM
❑ FE PETRO ❑ OTHER
Technician Signature:
CA Lic#588098 • AZ Lic#095984 • NV Lic#0049666
1863 North Neville Street • Orange, California 92865 • 714.560.8222 • 714.685.0006 Fax
11280 Trade Center Drive- Rancho Cordova, California 95742 • 916.858.1090 • 916.858.1011 Fax
www.talt.com
� e
SWRCB,January 2002 Page 1 of 5
Secondary Containment Testing Report Form
This form is intended for use by contractors performing periodic testing of UST secondary containments systems. Use the appropriate
pages of this form to report results for all components tested. The completed form, written test procedures, and printout from tests(if
applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency.
1.FACILITY INFORMATION
Facility: Pepsi Bottling Company Service Date: 08/04/2008
Facility Address: 215 East 21st St. Bakersfield CA 93305
Facility Contact: George Facility Phone: 714-522-9669
Date Local Agency Was Notified of Testing: 07/16/2008 Test Type: 36 Month
Name of Local Agency Inspector if present during testing): Eddie Medina(Bakersfield Fire).
2. TESTING CONTRACTOR INFORMATION
Company Name: Tait Environmental Systems
Technician Providing Test: AGUILAR ADOLFO
Credentials ®CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester
®ICC UST Service Technician
License Type:A B ASB C-10 HAZ ILicense Number: 588098
Manufacturer Training
Manufacturer Component(s) Date Training Expires
ICC Technician 5238610-UT 02/24/2009
Incon TS-STS 2957353761 01/13/2010
3. SUMMARY OF TEST RESULTS
Component Pass Fail Not Repairs Component Pass Fail Not Repairs
Tested Made Tested Made
Turbine Sump ® ❑ ❑ M ❑ ❑ ❑
UDC Sump ® ❑ ❑ 7 ❑ ❑ ❑
Supply Secondary Line X ❑ ❑ ❑ ❑ ❑
Annular ❑ ❑ ® El I ❑ ❑ I❑
❑ ❑ ❑ El I ❑ ❑ ❑
❑ ❑ ❑ El El ED
❑ ❑ ❑ El 10
Lj
❑ ❑ ❑ ❑ ❑ ❑ El
❑ ❑ ❑ p ❑ ❑ ❑
❑ ❑ ❑ 10 ❑ ❑ ❑
❑ ❑ ❑ ❑ ❑ ❑
-Mlt I Q III I El F-1
If hydrostatic testing was performed,describe what was done with the water after completion of tests:
Left Haz-Waste Test Water @ Site Properly Labeled And Secured,Total(4)55 Gallon Drums.
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
To the best of my knowledge,the facts stated in this document are accurate and in full compliance with legal requirements
Technician's Signature Date 08/04/2008
S WRCB,January 2002 Page 2 of 5
4.TANK ANNULAR TESTING
Test Method Developed by ❑ Tank Manufacturer ❑ Industry Standard ❑ Professional Engineer
® Other(Specify)
Test Method Used ❑ Pressure ❑ Vacuum ❑ Hydrostatic
® Other(Specify)
Test Equipment Used: Equipment Resolution:
Tank#Diesel Tank# Tank# Tank#
Is Tank Exempt From Testing?(1) ® Yes ❑ No ❑ Yes ❑No ❑ Yes ❑ No ❑ Yes ❑ No
Tank Capacity:
Tank Material:
Tank Manufacturer:
Product Stored:
Wait Time between applying
pressure/vacuum/water and starting
test:
Test Start Time:
Initial Reading(Ri):
Test End Time.
Final Reading(Rf):
Test Duration:
Change in Reading(Rf-Ri):
Pass/Fail Threshold or Criteria:
Test Result ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail
Was Sensor Removed for Testing? ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
Was Sensor properly replaced and ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
verified after testing?
Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests
The tank's annular space is brine filled.Does not have to be tested.
(1)Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment,such as
sysrtems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment testing. {California Code of
Regulations,Title 23,Section 2637(a)(6))
SWRCB,January 2002 Page 3 of 5
5. SECONDARY PIPE TESTING
Test Method Developed by ❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer
❑ Other(Specify)
Test Method Used ® Pressure ❑ Vacuum ❑ Hydrostatic
❑ Other(Specify)
Test Equipment Used:4"Dial Gauge Equipment Resolution: .1
Piping Run#Supply Piping Run# Piping Run# Piping Run#
Sec.
Piping Material: Fiberglass
Piping Manufacturer: A.O. Smith
Piping Diameter: 3"
Length of Piping Run: Approx. 15'
Product Stored: Diesel
Method and location of piping-run test boot @ Turbine
isolation: sum
Wait Time between applying 15 Minutes
pressure/vacuum/water and starting
test:
Test Start Time: 9:50 AM
Initial Reading(Ri): 5 PSI
Test End Time: 10:50 AM
Final Reading(Rf): 5 PSI
Test Duration: One Hour
Change in Reading(Rf-Ri): 0
Pass/Fail Threshold or Criteria: 0
Test Result ® Pass 13 !!il_jj ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail
Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests
SWRCB,January 2002 Page 4 of 5
6.PIPING SUMP TESTING
Test Method Developed by ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer
❑ Other(Specify)
Test Method Used ❑ Pressure ❑ Vacuum ® Hydrostatic
❑ Other(Specify)
Test Equipment Used: Incon TS-STS Equipment Resolution: .0006
Sump#Piping Sump# Sump# Sump#
Sump Diameter 48"
Sump Depth 48"
Sump Material Fiberglass
Height from Tank Top to Top of 24"
Highest Pil)ing Penetration
Height from Tank Top to Lowest 20"
Electrical Penetration
Condition of sump prior to testing Clean
Portion of Sump Tested(1) 2"above piping penetration
Does turbine shut down when
sump sensor detects liquid(both ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
product and water)?*
Turbine shutdown response time N/A
Is sytem programmed for fail-safe ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
shutdown?*
Was fail-safe verified to be ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
operational?*
Wait time between applying
pressure/vacuum/water and starting 15 Minutes
test
Test Start Time 10:13 am 10:33 am
Initial Reading Ri) 6.3561" 6.3571"
Test End Time 10:28 am 10:48 am
Final Reading 6.3565" 6.3565"
Test Duration 15 15
Change in Reading Rf-Ri +.0004" -.0006"
Pass/Fail Threshold or Criteria .002"
Test Result ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail
Was sensor removed for testing? ® Yes ❑ No ❑ NA E01 es ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
Was sensor properly replaced and ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
verified functional after testin ?
Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests
(1)If the entire depth of the sump is not tested,specify how much was tested.If the answer to any of the questions indicated with an
asterisk(*)is"NO"or"NA",the entire sump must be tested.(See SWRCB LG-160)
SWRCB,January 2002 Page 5 of 5
7. UNDER-DISPENSER CONTAINMENT TESTING
Test Method Developed by ❑ UDC Manufacturer ® Industry Standard ❑ Professional Engineer
❑ Other(Specify)
Test Method Used ❑ Pressure ❑ Vacuum ® Hydrostatic
❑ Other(Specify)
Test Equipment Used: Incon TS-STS Equipment Resolution: .0006"
UDC#1 &2 UDC# UDC# UDC#
UDC Manufacturer Bravo
UDC Material Steel
UDC Depth 10"
Height from UDC Bottom to Top 6"
of Hi hest Piping Penetration
Height from UDC Bottom to 0"
Lowest Electrical Penetration
Condition of UDC prior to testing Clean
Portion of UDC Tested 1 2"above piping
Does turbine shut down when UDC
sensor detects liquid(both product ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
and water)?
Turbine shutdown response time N/A
Is sytem programmed for fail-safe ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
shutdown?
Was fail-safe verified to be ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
operational?
Wait time between applying
pressure/vacuum/water and starting 15 Minutes
test
Test Start Time 10:13 AM 10:33 AM
Initial Reading Ri) 2.5760" 2.5757"
Test End Time 10:28 am 10:48 am
Final Reading 2.5759" 2.5756"
Test Duration 15 15
Change in Reading Rf-Ri -.0001" -.0001"
Pass/Fail Threshold or Criteria .002"
Test Result ® Pass ❑ Fall ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail
Was sensor removed for testing? ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
Was sensor properly replaced and
verified functional after testing? ❑ yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA
Comments include any information on repairs made prior to testing,and recommended follow-up for failed tests
Bravo Float On UDC,No Sensor.
(1)If the entire depth of the UDC is not tested,specify how much was tested.If the answer to any of the questions indicated with an
asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160)
PEPSI
- 215-E.-21ST._ - - -
BAKERSFIELD
CA
PEPSI
y S E_ LD 21ST. 98/94i2998
IE 19:13 AM
BAKERSF
CA `:SUMP LEVEL REPORT
08✓04�2008. 9:35 AM
SUMP LEVEL REPORT SUMP:TURBINE 6.356 IN
_;SUPIP.`DSP 1 2.576 IN
SUMP.::BUCKET 2.293 IN
SUMP TURBINE 0.000 IN
:.SUMP:.DSP 1 1.726 IN
SUMP :BUCKET 2.300 IN
SOFTWARE REVISION LEVEL
VERS I QN_1 19..-05-
SOFTWARE# 346119-100-F
CREATED - 00.02.25.12.15
S-MODULE# 330160-105-A
SYSTEM-FEATURES: � PEPSI
PERIODIC IN-TANK TESTS 215 E.21ST.
ANNUAL IN-TANK TESTS `'BAKERSFIELD
CSLD CA
HIR PEPSI
FUEL MANAGER 215 E.21ST. 0812008 10:29 AM
BAKERSFIELD
CA SLIMP LEAK TEST REPORT
08/04/2008 9:53 AM TURBINE
NO
SUMP LEVEL REPORT TE7 STARTED. 10:13 AM
FT�ST STARTED 08/0412808
""'BEGIN LEVEL: 6.3561 IN
SUMP TURBINE 6.357 INENp TIME' 19:28 AM
SKIMP DSP 1 2.576 IN END DATE. 08/04/2008
108889 PEPSI SITE 9 SUMP.BUCKET 2.299 IN ;:EhiD._LEVEL. x.3565 IN
215 EAST 21ST STREET LEAK`THRESHOLD 0.002 IN
HAKERSFIELD.CA 93305 TEST"RESULT PASSED
81152324905001
AUG 4, 2008 8:23 AM DSP 1
TEST::STARTED 19:13 AM
TEST STARTED 08/0412008
SYSTEM STATUS REPORT BEGIN".LEVEL 2.5760 IN
ALL FUNCTIONS NORMAL PEPSI END TIME 10:28 AM
215 E.21ST. END DATE 98/0412008
BAKERSFIELD ENI?LEVEL 2.5759 IN
CA LEAK :THRESHOLD 8.002 IN
TEST-.RESULT PASSED
08/0412008 _ 10:00 AM
SUMP LEVEL REPORT BUCKET
TEST STARTED 10:13 AM
SUMP TURBINE 6.357 IN TEST STARTED 08/04/2908
BEGIN LEVEL 2.2931 IN
SUMP DSP 1: 2.576 IN END TIME 19:28 AM
� 1 BUCKET 2:298 IN END DATE 08/04/2008
3 END:LEVEL 2.2927 IN
t�� ° LEAK THRESHOLD-.,0.002.:IN
, RESULT :PASSED
TEST DATE: 114/08 CLIENT:PEPSI BAKERSFEILD PAGE OF__L
--- SENSOR ALARM------
L 1 :ANNULAR SPACE
ANNULAR SPACE
LOW LIQUID ALARM 108889 PEPSI SITE 9
AUG 4, 2008 9:02 AM 215 EAST--2IST-STREET
BAKERSFIELD.CA 93305
-.
81152324905001
-----7
"fk AUG 4, 2008 9:32 AM
PEPSI:
----
li
BRKERSFIELD
CA SYSTEM STATUS REPORT
- - - - - - - - - - - -
08�04%Z088 10:48 AIM ----- SENSOR ALARM ----- ALL FUNCTIONS NORMAL
SUMP LEAK TEST REPORT L 2:TURBINE SUMP
STP SUMP
TURBINE FUEL ALARM
AUG 4, 2008 9:02 AM
TEST STARTED 10:33 AM
-JEST STARTED 08/04/2008
BEGIN?LEVEL 6.3571 IN
>END.`T.lME 10:48 AM
_ E,ND DATE 08/04/2008 ----- SENSOR ALARM -----
``END LEVEL . 6.3565 I4 L 1 :ANNULAR SPACE
LEAK.:THRESHOLD 0.002 IN ANNULAR SPACE
TESTt RESULT PASSED LOW LIQUID ALARM
----- SENSOR ALARM AUG 4. 2008 9:33 AM
DSP 1 L 2:TURBINE SUMP
STP SUMP
TEST STARTED 10:33 AM FUEL ALARM
,I ST'STARTED 0 ,02008
AUG 4. 2008 9:02 AM
BEGIN.::LEVEL 2.5757 IN
':END TIME 10:48 AM
DATE 08/04/2008
END.`LEVEL : 2.5756 IN
,LEAK...THRESHOLD 0.002 IN ---- IN-TANK ALARM -----
TEST`.RESULT PASSED T 1 :DIESEL FUEL
DELIVERY NEEDED
AUG 4, 2008 9:37 AM
BUCKET
----- SENSOR ALARM -----
STARTED 10:33 AM L 1 :ANNULAR SPACE
ANNULAR SPACE
TEST:;STARTED. .08/8412008 SENSOR OUT ALARM
:'BEGIN:;'LEVEL. . 2:2989 IN AUG 4, 2008 9:04 AM
:?END
TIME: 10:48 AM
END DATE 08/04/2008
-i5,ND LEVEL 2.2890: I.N
f LEAK-THRESHOLD 0.002 IN
ESTpRESULT' PASSED ---- IN-TANK ALARM -----
� 3
T 1 :DIESEL FUEL.
PROBE OUT
.,...,.. ..._..._ AUG 4. 2008 9:37 AM
----- SENSOR ALARM ----- _
L 2:TURBINE SUMP
STP SUMP
SENSOR OUT ALARM
AUG 4, 2008 9:04 AM
TEST DATE: 8/4/08 CLIENT: PEPSI BAKERSFEILD PAGE ;? OF_ 1
T 1 :DIESEL FUEL - --. IN-TANK ALARM ------
INVENTORY INCREASE - T I :DIESEL FUEL
INCREASE START LOW TEMP WARNING
AUG 4, 200
AUG 4. 2008 11 :11 AM 8 11 :47 AM
VOLUME = 6688 GALS
HEIGHT - 54.45 INCHES
WATER = 1 .31 INCHES
T_1 :D_I-ESEL -FUEL- TEMP = 108.1 DEG F
INVENTORY INCREASE
INCREASE START INCREASE END
AUG 4, 2008 11 :01 AM AUG 4, 2008 11 :18 AM T I :DIESEL FUEL
VOLUME = 8279 GALS VOLUME = 6807 GALS
INVENTORY INCREASE
HEIGHT = 63.94 INCHES HEIGHT = 55.15 INCHES INCREASE START
WATER = 1 .20 INCHES WATER - 0.78 INCHES AUG 4. 2008 11 :31 AM
TEMP = 10.6.5 DEG F TEMP = 108. 1 DEG F
VOLUME = 6807 GALS
9 HEIGHT = 55.16 INCHES
GROSS INCREASE= 11
INCREASE END
AUG 4, 2008 11 :09 AM TC NET INCREASE= 116 WATER = 0.78 INCHES TEMP = 108.6 DEG F
VOLUME = 8356 GALS
HEIGHT = 64.41 INCHES INCREASE END
WATER = 1 .22 INCHES AUG 4, 2008 11 :51 AM
TEMP = 107.0 DEG F
VOLUME = 9567 GALS
HEIGHT - 71 .77 INCHES
GROSS INCREASE= 77 WATER = 1 .69 INCHES
TC NET INCREASE- 74 TEMP = 110.3 DEG F
T I :DIESEL FUEL GROSS INCREASE= 2760
ADJUSTED DELIVERY REPORT TC NET INCREASE= 2692
AUG 4, 2008 11 :11 AM
DELIVERY VOLUME = 117
TC DLVY VOLUME = 119
T I :DIESEL FUEL
ADJUSTED DELIVERY REPORT
AUG 4. 2008 11 :01 AM
T 1 :DIESEL FUEL
ADJUSTED DELIVERY REPORT
DELIVERY VOLUME = -1585
TC DLVY VOLUME = -1556 AUG 4. 2008 11 :31 AM
DELIVERY VOLUME = -2439
---- IN-TANK ALARM ----- TC DLVY VOLUME = -2357
T 1 :DIESEL FUEL
PROBE OUT
AUG 4, 2008 11 :39 AM
TEST DATE: 8/4/08 CLIENT:PEPSI BAKERSFEILD PAGE ' OF
FLOAT SIZE: 4.0 IN.. 8496
RS-232 SECURITY-
WATER WARNING - : 1 .5
CODE flD0000 HIGH WATER LIMIT: 2.0
MAX OR LABEL VOL: 15102
OVERFILL LIMIT 88'i
13289
RS-232 END OF MESSAGE HIGH PRODUCT 92%
DISABLED 13893
DELIVERY LIMIT 20%
AUTO DIAL ALARM SETUP 3020
LOW PRODUCT 1000
D 8:SIMPLICITY CENTER LEAK ALARM LIMIT: 24 108889 PEPSI SITE 9
SUDDEN LOSS LIMIT: 50 215 EAST _21ST.STREET-
IN-TANK ALARMS TANK TILT 1 .51 BAKERSFIELD.CA 93305
ALL:LEAK ALARM 81152324905001
ALL:SUDDEN LOSS ALARM MANIFOLDED TANKS AUG 4. 2008 8:21 AM
ALL:PROBE OUT TO: NONE
ALL:GROSS TEST FAIL FUEL MANAGEMENT SETUP
ALL:PERIODIC TEST FAIL - -
- - _ _ - _ - - _ -
ALL:NO CSLD IDLE TIME LEAK MIN PERIODIC: 0%
ALL:CSLD INCR RATE WARN 0 DELIVERY WARN DAYS: 0.4
ALL:ACCU_CHART CAL WARN AUTO PRINT: DISABLED
ALL:LOW TEMP WARNING LEAK MIN ANNUAL ox
ALL:GROSS FAIL LINE TNK 0
LIQUID SENSOR ALMS T 1 :DIESEL FUEL
ALL:FUEL ALARM PERIODIC TEST TYPE AVG SALES-SUN: 12 GAL
ALL:SENSOR OUT ALARM STANDARD AVG SALES-MON: 458 GAL
ALL:SHORT ALARM ----AVG_SALES-TUE: 532 GAL
ALL:WATER ALARM ANNUAL TEST FAIL AVG SALES-WED: 704 GAL
ALL:WATER OUT ALARM ALARM DISABLED AVG SALES-THR: 483 GAL
ALL:HIGH LIQUID ALARM AVG SALES-FRI : 503 GAL
ALL:LOW LIQUID ALARM PERIODIC TEST FAIL AVG SALES-SAT: 191 GAL
ALL:LIQUID WARNING ALARM DISABLED
RECEIVER ALARMS GROSS TEST FAIL
SERVICE REPORT WARN ALARM DISABLED LIQUID SENSOR SETUP
ALARM CLEAR WARNING - - - - _ - - - - - - -
Al l� i EST AVERAGING: OFF
POWER SIDE DIM ALM PER TEST AVERAGING: OFF L I :ANNULAR SPACE
ALL:DISABLED DIM ALARM DUAL FLOAT HYDROSTATIC
ALL:COMMUNICATION ALARM TANK TEST NOTIFY: OFF CATEGORY : ANNULAR SPACE
TNK TST SIPHON BREAK:OFF
DELIVERY DELAY 5 MIN L 2:TURBINE SUMP
DUAL FLT. HIGH VAPOR
CATEGORY STP SUMP
IN-TANK SETUP
T 1 :DIESEL FUEL
PRODUCT CODE 1
THERMAL COEFF : .000450. LEAK TEST METHOD
TANK DIAMETER 119.50 - - - - - - - - - - - -
TANK PROFILE 4 PTS TEST CSLD ALL TANK
FULL VOL 15102 Pd = 99•
89.6 -INCH VOL 12290 CLIMATE FACTOR:MODERATE
59.8 INCH VOL 7580
29.9 INCH VOL 2838
METER DATA YES LEAK TEST REPORT FORMAT
END FACTOR: HEMISPHER NORMAL
CAL UPDATE: IMMEDIATE
TEST DATE: 8/4/08 CLIENT: PEPSI BAKERSFEILD PAGE S OF_L_
SYSTEM SETUP
AUG:. 4, 2008 8:20 AM
108889 PEPSI SITE 9
215 EAST- .21.ST STREET SYSTEM SECURITY
BAKERSFIELD.CA 93305 CODE 000000--
81152324905001 SYSTEM UNITS
U.S.
AUG 4, 2008 12:01 PM SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
SYSTEM STATUS REPORT
- - - - - - -___108889 PEPSI SITE 9
T 1 :PROBE OUT 215 EAST 21ST STREET
$AKERSFIELD.CA 93305
T I :DELIVERY NEEDED 81152324905001
T 1 :LOW TEMP WARNING SHIFT TIME 1 6:00 AM COMMUNICATIONS SETUP - -
- SHIFT TIME 2 DISABLED
L 1 :LOW LIQUID ALARM SHIFT TIME 3 DISABLED
D B:ALARM CLEAR WARNING SHIFT TIME 4 DISABLED PORT SETTINGS:
SHIFT BIR PRINTOUTS COMM BOARD : 2 (FXMOD)
DISABLED BAUD RATE : 2400
INVENTORY REPORT DAILY BIR PRINTOUTS PARITY : ODD
DISABLED STOP BIT : 1 STOP
TICKETED DELIVERY DATA LENGTH: 7 DATA
T 1 :DIESEL FUEL DISABLED DIAL TYPE : TONE
VOLUME = 4367 GALS TANK PER TST NEEDED WRN ANSWER ON : i RING
ULLAGE. = 10735 GALS DISABLED
90e ULLAGE- 9224 GALS TANK ANN TST NEEDED WRN
TC VOLUME = 4310 GALS DISABLED RECEIVER SETUP:
HEIGHT = 40.19 INCHES
WATER VOL = 0 GALS LINE RE-ENABLE METHOD
WATER = 0.00 INCHES PASS LINE TEST D B:SIMPLICITY CENTER
TEMP = 88.8 DEG F
LINE PER TST NEEDED WRN CVR T 743-8379
CVR
DISABLED R TYPE: COMPUTER
* * * * PORT N0. 2
END * LINE ANN TST NEEDED WRN
DISABLED RETRY
DE 5
RETRY DELAY: 5
PRINT TC VOLUMES CONFIRMATION REPORT: OFF
ENABLED
TEMP COMPENSATION
VALUE (DEG F ) : 60.0
STICK HEIGHT OFFSET
DISABLED
H-PROTOCOL DATA FORMAT
108889 PEPSI SITE 9 HEIGHT
215 EAST 21ST STREET DAYLIGHT SAVING TIME
BAKERSFIELD.CA 93305 ENABLED AUTO DIAL TIME SETUP:
81152324905001 START DATE
_MAR WEEK 3 SUN
AUG 4, 2008 12:01 PM START TIME D 8:SIMPLICITY CENTER
2:05 AM DIAL MONTHLY
END DATE WEEK 2 FRI
NOV WEEK 1 SUN DIAL TIME : 1 :49 AM
SYSTEM STATUS REPORT END TIME RECEIVER REPORTS:
- - - - - - - - - - - - 2:00 AM
D 8:ALARM CLEAR,WARNING RE-DIRECT LOCAL PRINTOUT
DISABLED
EURO PROTOCOL PREFIX
S
TEST DATE: 8/4108 CLIENT: PEPSI BAKERSFEILD PAGE OF -I
OUTPUT RELAY SETUP - - - ALAN HIS-TORY- REPORT- - - ALARM HISTORY REPORT
R 2:POSITIVE SHUTDOWN ---- IN-TANK ALARM -----
-- SENSOR ALARM -----
TYPE: T 1 :DIESEL FUEL L 1 :ANNULAR SPACE
STANDARD ANNULAR SPACE
NORMALLY CLOSED HIGH WATER ALARM SENSOR OUT ALARM
JUL 22, 2004 11 :24 AM AUG B. 2007 10:36 AM
IN-TANK ALARMS OVERFILL ALARM LOW LIQUID ALARM
ALL:LEAK ALARM JUL 22. 2004 11 :15 AM AUG 8, 2007 10:34 AM
ALL:SUDDEN LOSS ALARM
MAR 17. 2004 8:43 AM
LIQUID SENSOR ALMS JUL 16, 2003 9:48 AM LOW LIQUID ALARM
L I :FUEL ALARM AUG 8', 2007 10:29 AM
L 2:FUEL ALARM LOW PRODUCT ALARM
1 :SENSOR OUT ALARM MAY 25. 2005 2:50 PM -
L -
L :SENSOR OUT ALARM MAY 25. 2005 2:36 PM
L 1 :SHORT ALARM MAY 19. 2005 10:58 PM ALARM HISTORY REPORT
L 2:SHORT ALARM HIGH PRODUCT ALARM ----- SENSOR ALARM -----
L 1 :HIGH LIQUID ALARM AUG 2. 2005 9:34 AM L 2:TURBINE SUMP
L 1 :LOW LIQUID ALARM JUL, 22, 2004 11 :15 AM STP SUMP
JUL 16, 2003 9:47 AM SENSOR OUT ALARM
INVALID FUEL LEVEL AUG 8. 2007 10:36 AM
MAY 25, 2005 2:49 PM FUEL ALARM
MAY 25. 2005 2:36 PM AUG 8. 2007 10:28 AM
MAY 19. 2005 10:58 PM
FUEL ALARM
PROBE OUT AUG 7, 2006 12:14 PM
JAN 17. 2008 4:56 PM
JAN 17, 2008 4:50 PM - -
RECONCILIATION SETUP JAN 17, 2008 4:38 PM
- - - - - - - - - - - - 108889 PEPSI SITE 9
HIGH WATER WARNING 215 EAST 21ST STREET
MDIM 1 : TTGG JUL 22. 2004 11 :24 AM BAKERSFIELD.CA 93305
81152324905001
AUTOMATIC DAILY CLOSING DELIVERY NEEDED
AUG 4. 2008 8:21 AM
TIME: 2:00 AM
JUL 1. 2008 7:20 AM
AUTO SHIFT #1 CLOSING JUN 13. 2008 7:03 AM
TIME: DISABLED APR'.25, 2008 3:50 AM
SYSTEM STATUS REPORT
AUTO SHIFT tt2 CLOSING ACCU CHART CAL WARN
TIME: DISABLED ALL FUNCTIONS NORMAL
JUL 30, 2001 11 :30 AM
AUTO SHIFT #3 CLOSING INVENTORY REPORT
TIME: DISABLED RECON WARNING
JAN 27. 2003 9:30 AM
AUTO SHIFT #4 CLOSING JAN 20. 2003 2:30 PM T 1 :DIESEL FUEL
TIME: 6:00 AM JAN 13. 2003 2:30 PM VOLUME = 4372 GALS
ULLAGE = 10730 GALS
RECON ALARM 90% ULLAGE= 9219 GALS
PERIODIC RECONCILIATION JAN 27. 2003 1 :30 PM TC VOLUME = 4316 GALS
MODE: MONTHLY JAN 20. 2003 3:30 PM HEIGHT = 40.22 INCHES
ALARM: DISABLED JAN 13, 2003 2:30 PM WATER VOL = 0 GALS
WATER = 0.00 INCHES
TEMP COMPENSATION LOW TEMP WARNING Tom' = 88.3 DEG.F
STANDARD MAY 19, 2005 1 :33 PM
JUL 22. 2004 11 :26 AM
BUS SLOT FUEL METER TANK JUL 9. 2004 11 :30 AM
2 10 0 0 1
2 10 1 . 0 1
TEST DATE: 8/4/08 CLIENT:PEPSI BAKERSFEILD PAGE OF
108889 PEPSI SITE 9
215 EAST_ 21ST_STREET
HAKERSFIELD XA 93305
81152324905001
AUG 4. 2008 8:22 AM
SYSTEM STATUS REPORT
ALL FUNCTIONS NORMAL
TEST DATE: 8/4/08 CLIENT:PEPSI BAKERSFEILD PAGE OF
9
� Tait Environmental Services
UST Construction Design Maintenance Compliance
FedEx Tracking #:8664 6551 0980
August 22, 2008
Bakersfield Fire Department
Prevention Services
Attn: Steve Underwood
1501 Truxtun Avenue,
Bakersfield, CA 93301
Re: Testing Results
\ Pepsi Bottling Group
215 East 21st Street
Bakersfield, CA
,--Inspector Ernie Medina
Please fnd^enclosed the following test results dated August 4, 2008 for the above referenced
facility:
■ Monitoring System Certification
■ Spill Bucket Testing Report Form
■ Leak Detector Testing
■ SB989 Testing
If you have any questions regarding any of the enclosures please feel free to call me at (714)
567-6413 or email me at bharmon @tait.com.
Sincerely,
Brian Harmon
Compliance Manager
CA Lie #588098 • AZ Lie #095984 • NV Lic #0049666
2131 South Dupont Drive, Anaheim, California 92865 • 714.560.8222 • 714.978.2615 Fax
11280 Trade Center Drive • Rancho Cordova, California 95742 • 916.858.1090 • 916.858.1011
Fax
www.tait.com