HomeMy WebLinkAboutFMC 2010 MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California IE
Authority Cited: Chapter 6 7, Health and Safety Code; Chapter 16, Division 3, Title 23, California Code of Regulations
This form must be used to document testing and servicing of monitoring equipment. A separate certification or report must be prepared for each
monitoring system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form to the local agency regulating UST systems within 30 days of test date.
A. General Information
Facility Name: Arco Am-Pm Bldg.No.:
Site Address: 2301 "F" Street City: Bakersfield Zip: 93301
Facility Contact Person: Kamal Contact Phone No.: (661) 303-7961
Make/Model of Monitoring System: Veeder Root TLS-350 Date of Testing/Servicing: 12/1/2010
B. Inventory of Equipment Tested/Certified
Check the ap2ropriate boxes to indicate specific a ui ment inspected/serviced:
Tank ID: 87 Unleaded Slave Tank ID: 91 Unleaded Premium
®In--Tank Gauging Probe. Model: 847390-109 ®In-Tank Gauging Probe. Model: 847390-109
®Annular Space or Vault Sensor. Model: 794390-409 ®Annular Space or Vault Sensor. Model: 794390-409
®Piping Sump/Trench Sensor(s). Model: 794380-208 ®Piping Sump/Trench Sensor(s). Model: 794380-208
❑Fill Sump Sensor(s). Model: ❑Fill Sump Sensor(s). Model:
®Mechanical Line Leak Detector. Model: RJFX1 V ®Mechanical Line Leak Detector. Model: RJFX1 V
❑Electronic Line Leak Detector. Model: ❑Electronic Line Leak Detector. Model:
®Tank Overfill/High-Level Sensor. Model: OPW Flapper ®Tank Overfill/High-Level Sensor. Model: OPW Flapper
❑Other(specify equipment type and model in Section E on Page 2). ❑Other(specify equipment type and model in Section E on Page 2).
Tank ID: 87 Unleaded Master Tank ID:
®In-Tank Gauging Probe. Model: 847390-109 ❑In-Tank Gauging Probe. Model:
®Annular Space or Vault Sensor. Model: 794390-409 ❑Annular Space or Vault Sensor. Model:
®Piping Sump/Trench Sensor(s). . Model: 794380-208 ❑Piping Sump/Tre nch Sensor(s). Model:
❑Fill Sump Sensor(s). Model: ❑Fill Sump Sensor(s). Model:
®Mechanical Line Leak Detector. Model: RJFX1 V ' ❑Mechanical Line Leak Detector. Model:
❑Electronic Line Leak Detector. Model: ❑Electronic Line Leak Detector. Model:
®
Tank Overfill/High-Level Sensor. Model: OPW Flapper ❑Tank Overfill/High-Level Sensor. Model:
❑Other(specify equipment type and model in Section E on Page 2). ❑Other(specify equipment type and model in Section E on Page 2).
Dispenser ID: 1/2 Dispenser ID: 7/8
®Dispenser Containment Sensor(s). Model: 794380-208 ®Dispenser Containment Sensor(s). Model: 794380-208
®Shear Valve(s). ®Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
Dispbnser ID: 3/4 Dispenser ID: 9/10& 11/12
®Dispenser Containment Sensor(s). Model: 794380-208 ®Dispenser Containment Sensor(s). Model: 794380-208
ED Shear Valve(s). ®Shcar Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Floats)and Ch"ain(s).
Dispbiiser ID: 5/6 Dispenser ID: 13/14& 15/16
®Dispenser Containment Sensor(s). Model: 794380-208 ®Dispenser Containment Sensor(s). Model: 794380-208
®Shear Valve(s). ®Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
*If the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility.
C. Certification -I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is information (e.g. manufacturers' checklists) necessary to verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equipment capable of generating such reports,I have also
attached a copy of the report;(check all that apply)_: ®System set-up ®Alarm history report.
Technician Name (print): Jerry Rangel Signature:
Certification No.: ICC: 5309489=UT,VR: B35460 License.No.: 532878 A-haz
Testing Company Name: Redwine Testing Services, Inc. Phone No.: (661) 834-6993
Site Address: P.O. Box 1567, Bakersfield,CA.93302 Date of Testing/Servicing: 1211/2010
Page 1 of 3
"-036—1/4 www.unidoes.org I IIII I III I I IIII 12 Rev.01/26/06
IE
Monitoring System Certification
D. Results of Testing/Servicing
Software Version Installed: 15.01
Complete the following checklist:
® Yes ❑ No* Is the audible alarm operational?
• Yes ❑ No* Is the visual alarm operational?
• Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational?
® Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will
not interfere with their proper operation?
❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
® N/A operational?
® Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
❑ N/A monitoring system detects a leak,fails to operate, or is electrically disconnected? If yes: which sensors initiate
positive shut-down? (Check all that apply) ®Sump/Trench Sensors; ®Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ®Yes; ❑No.
❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
® N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? %
❑ Yes* ® No Was any monitoring equipment replaced? If yes,identify specific sensors, probes,or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section E,below.
❑ Yes* ® No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply)
❑ Product; ❑ Water. If yes, describe causes in Section E,below.
r::O::Ye ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable
❑ No* Is all monitoring equipment operational per manufacturer's specifications?
*In Section E below,describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 3
UN-036—2/4 www.unidocs.org Rev.01/26/06
Monitoring System Certification
F. In-Tank Gauging/SIR Equipment: ® Check this box if tank gauging is used only for inventory control.
❑ Check this box if no tank gauging or SIR equipment is installed.
This section must be completed if in-tank gauging equipment is used to perform leak detection monitoring.
Complete the following checklist:
® Yes ❑ No* Has all input wiring been inspected for proper entry and termination,including testing for ground faults?
• Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup?
• Yes ❑ No* Was accuracy of system product level readings tested?
® Yes ❑ No* Was accuracy of system water level readings tested?
® Yes ❑ No* Were all probes reinstalled properly?
® Yes ❑ No* I Were all items on the equipment manufacturer's maintenance checklist completed?
*In the Section H,below,describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors(LLD): ❑ Check this box if LLDs are not installed.
Complete the following checklist:
® Yes ❑ No* For equipment start-up or annual equipment certification, was a leak simulated to verify LLD performance?
❑ N/A (Check all that apply) Simulated leak rate: ® 3 g.p.h.; ❑0.1 g.p.h; ❑0.2 g.p.h.
❑ Yes ® No* Were all LLDs confirmed operational and accurate within regulatory requirements?
® Yes ❑ No* Was the testing apparatus properly calibrated?
❑ Yes ® No* For mechanical LLDs,does the LLD restrict product flow if it detects a leak?
❑ N/A
❑ Yes ❑ No* For electronic LLDs,does the turbine automatically shut off if the LLD detects a leak?
® N/A
❑ Yes ❑ No* For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled
® N/A or disconnected?
❑ Yes ❑ No* For electronic LLDs,does the turbine automatically shut off if any portion of the monitoring system malfunctions
® N/A or fails a test?
❑ Yes ❑ No* For electronic LLDs,have all accessible wiring connections been visually inspected?
® N/A
® Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
*In the Section H,below,describe how and when these deficiencies were or will be corrected.
H. Comments: 91 premium LLD failed testing. unable to connect to the 87 LLD's.
Page 3 of 3
UN-036—1/4 www.unidoes.org Rev.01/26/06
ALARM H I STORY REPORT
ALARM HISTORY REPORT ---- IN-TANK ALARM -----
IN-TANY ALARM T 2:87 MAIN TANK
T 1 :91 SETUP DATA WARNING
AUG 3, 2010 3: 13 Pfl
ALARH HI STt-%RY R'Ef.:'ORT S.E T U P E*)TH b)HRIIJING LIG 0, 2010 3:09 Pfl
"'i"'STEI'l AUC; 3, 2010 1 :21 P11 AUG 3, 2010 3:0'2 PM
S H AUG 3, 20 10 1 : 10 PM
PAPER OUT r"'I U G 3�- 2010 cA:224 AM HIGH WATER ALARM
NOV "1 , 2010 3:06 Pt"I AUG 3. 2010 2:226 Pm
PR I LATER ERROR LO(-J PRODUCT ALARM
NOV 21 , '2010 3:06 P11 NOV 24. 2010 2:56 PM LO(..J PRODUCT ALARM
BATTERY IS OFF NOV 22, --,Olo x3:43 All NOV 17, 2010 49 P11
JAN 1 1996 AM OCT 2.- 201 IJ 9:24 All OCT 22, 2010 3:20 PH
SEP 28,3, 2010 3:00 Pfl
I NVAL I D F UEL L0 EL
AUG 3, 2010 3:31 Ptl I NVAL I D FUEL LEVEL
AUG 3, 2010 2:50 Pm NOV 17. '_'010 "1:4 6 PH
OCT 9-2, 2010 3: 19 PI-I
PROBE OUT SEP '2h, 2010 2,:5e PH
AUG 3.. 2010 3:28 P11
PROBE OUT
AUG 3. 2010 1 .14 P111
A LIG 3, 2010 9:24 All AUG 3, 2010 51 P11
AUG 3, '2'010 3:'27 Pl"I
END AUG 3. 2010 3:08 PH
DELIVER`! NEEDED
NOV '24.. 2010 12:G6 Pt I
DEL I VER NEEDED
NOV 21 , 2)0 10 7: 16 Ptl Y
NOV 19. 21 010 2:23 P111 NOV 24.- `1010 8:33 PH
NOV 17, 'G1 U 2: 16 Pt"I
NOV 13, 2010 10:59 AM
X END X X X
END x X �
,-,LARM HISfORY REDRT
----- NSA ALARM -----
L 1 :91.27 ANNULAR ALAR11 H12•`i; REPORT
ANNULAR SPACE
SETUP DATA WARNING ----- SENSOR ALARP'l -----
A 3, 21010 5:24 AM L 4:87 MAIN ANNULAR
ANNULAR SP�E
SETUP DATA WARNING
AUG 3, 2010 9:224 �
ALARM H1 Y REPORT
I N-TANY HLARH -----
E[AD
T 3-1:-1:37 TA[-6� 2
SETUP D'" WiR 1'4 1 tlG E IAD
AUG 3, 2010 2:35 P11
Au Cl' 3, 2010 22:06, PIl
AUG 3, 2010 11 :49 r;ll"l
HIGH [,,JATER PlLi-ARI'l
AUG a, 2010 2 P11
LOW PRODUCT
110V /o. 2010 2:34 PH ALAP11 HISTO REPORT
NO'v' 24, 2010 5:33 PM
NOV 21 , 2010 3.04 P11 ----- �NSOR L`Rll -----
IN AL I D FUEL LEVEL L 2:91 TURBINE HLr`lRl"l HISTC"R", REPORT
A UG 3, 2010 2:35 Pf"I STP SUMP
SETUP DATA W;RNING ----- --3ENS,:)P -'LARH -----
PROBE OUT AUG 3, 2010 9:24 AM L 5:87 TURBINE
STP SUMP
A U C, 3' 2010 ,�_ :56 Pl"I SETUP DATA WARNING
AUG 3 -1010 :3: 15 PH AUG 3, 2010 9:2-4 AM
ALA �_j 2_1 0 t 0 3:09 Pill
DE LIVE R'i' NEEDED
NOV 30. 2010 1 :51 Pl"l
NOV 27, 2010 9:38 PM
NOV 24, 2010 4:44 P11
Err X
E 1AE)
LARM HICYT li REPORT
----- SENSOR �ARM -----
E 3:87 TURBINE ALARM HISITORV REPORT
STP SUMP
SETUP DATA WARNING ----- -"'ENSOR ALARM -----
Au 3, 2010 9:24 At"I L 6:
OTHER SENSORS
END * �. * * -. EN *
ALARM H!STORY REPORT ALARM REPORT
----- SENS �ARM ----- ----- S E WS 0 R r"i L A R M -----
L10:3-4 UDC L13:9-10 UDC
(�LiL�R['l H ISTCR", REPORT DISPENSER PA14 DISPENSER PAN
SETUP DATA WARNING SETUP DATA WARNING
SEN'r!,,C":,R HLARH ----- AUG 3. 2010 9:24 HM HUG 3, 2010 9:24 HP1
OTHER SENSORS
X X El--iD 71. X ENE Eros
ALARM HI2-',TOR'Z REPORT ALARM HISTOR'i" REPORT ALARII H! OP? REPORT
----- SENSOR ALARM ----- ----- SENSOR HLHRM -----
E14: ! !-!2 UDC
;-,EN2-',OR HLr'IRM L I I :Fj-b- UDC
L 8: DISPENSER PAN DISPENSEi
OTHER SENSORS SETUP DATA WARNING SETUP DATA �J`RI'411`4(3
rl
AUG 3, 2010 9:24 All AUG 3, 2010 9:224 All
El-Z -k
END * E fID * --z
ALA RII HI; ? REPORT
----- SENS� HLARIII HISTOR',/ REPORT ALARII HISTORY REPORT
L 9: 1-2 UDC:
DISPENSER PAN ----- SENSOR ''LAPM ----- SENS',R HLHT-I'l
SETUP DATA dr'IRNING -8 UD(- L15: 1'-14 UDC
L12:7
- 'ER PAN
AUG 3, 2010 9:24 Hill DISPENSER PAN DISPENS
SETUP IAT Wi:�RNI TUP DATA WARNItJO
AUG 3, 2010 9:24 All AUG S. 112010 9:24 All
END
END
ALAPH HISTORY PEPORT
----- SEt,1SCR 4LARI'l -----
L16: 15-16 UDC
DISPENSER PAN
SETUP DATA 1,J"'RNING
AUG 3, 2010 9:224 AM
EVE) +
ALHRH HIST-DR`I' REPORT
SENSOR HLAR11
L 1 :91-87 ANNULAR
ANNULAR SPACE
SETUP DATA WARNING
AUG 3, 2010. 9:24 A41
END
S/S`I'Efl SETUP
-
ARC", - - - - -7:42- - - - -
:- PtlPm DEC, In 2010 AM
2301 F STREET
BAKER S:7FIELD. C A9:3301
80146445705001
S'Y'STEll UNITS
DEC
1 - 2010 7:42" AP-1 U.S.
SYSTEll UiI,4GUAGE
ENGLISH
SYSTEM Dt�-;TE.,TP,IE FORMAT
23"i'�_lEm STATUS REPORT MON DD YYll.'Y HH:I,,Irl:SS x[,l
— — — — -- — — — — — — —
ALL FUNC_'TIO IS N_iRMAL ARCO AMP11 SETUP
2301 F STREET — — — — — — — —
I f`A,'Et4'fOP'Y` REPORT BAKERSFIELD, CA93301
8014644570500I
PORT
T 1 :191 SHIFT TIME I DISABLED
VOL UflE = 12247 GALS SHIFT TIME 21 DISABLED COMI'l BOARD 22
ULLAGE = 9 122 GALS SHIFT TIME :3 DISABLED BAUD RATE 9600
90% ULLAc,E= 8085 C4ALS SHIFT TIME 4 D ISABLED PAP I TY NONE
TC %)C*,LL4-,iE = 1243 GALS STOP BIT I STOP
HEIGHT = 21 -80 INCHES TANK PERIODIC, WARN[[.ICS DATA LENGTH: 8 DATA
WATER 'vViL = 0 G A LS DISABLED
WATER = 0.CIO 11,41_:HES TANK ANNUAL IJARNINGS
TEMP = 63.7 DEG F DISABLED REC".EIVER SETUP:
LINE PERIODIC t,JHR[lINGS
DISABLED NONE
T 1:87 tlAli,i TANK LINE ANNUAL L-Jh'RNiNGS
VOLUME = 55122 GALS DISABLED
ULLAGE = 14191 GALS
90% ULI_AC3E= 1'22'20 GALS PRINT TC VOLUMES
TC V,,lUtlE = 5512 GALS ENABLED
HEIGHT = 38.04 INCHES
WATER VOL = 0 GALS TEMP COMPENSAT TON
WATER = 0.00 INCHES VALUE (DEG F ) : 60.0
TEP•P = E,9.9 DEG F STICK HEIGHT OFFSET
DISABLED
T 3:87 THHY H—PFI,'�TOCOL DATA FORMAT AUTC1 DIAL TlIlE SETUP:
VOLUME = 2016 GALS HEIGHT
ULLAGE = 8353 GALS DA%''LIGHT SAVING TIME NONE
90% ULLAGE= 7316 GALS ENABLED
TC VOLUME = 2016 GALS START DATE
HEIGHT = 30.09 INCHES MAR WEEK 3 SUN
WATER VOL = 0 GALS START TIME
WATER = 0.00 INCHES 2:05 AM
TEMP = 59.4 DEG F ENE) DATE
NOV WEEK I SLIN
END TIME
MA111FOLDED TANKS 2:00 AM
I NVENTORY TOTALS
T 2'8' tlAIN TANI" RE—DIRECT LOCAL PRINTOUT
T 3'87 TANI 2 DISABLED ES-232 SECURITY
VOLUME = 752CI GALS CODE : 000000
Ti: VOLUME = 7528 _'.HLS SYSTEM SECURITY
CODE : OOOOOCI
x lk < PID -*z 'I,
ENO OF t9ESSI;1GE
DISABLED
AUTO DIAL ALARM SETUP
- - - - - - - - - - - - T 87 TANK 2
PRODUCT CODE
1 N-TAP-Jl' SETUP THEPHHL COEFF : .000700
- - - - - -- -- - - - - - T 2:87 MAIN TANK TANK DIAMETER 117.00
PRODUCT CODE 2 TANK PROFILE 4 PTS
T 1 :91 THERMAL f"OEFF : .0013700 FULL VOL 10369
PRODUCT CODE I TANK DIAMETER 117.00 87.8 INCH VOL 8460
THERMAL f-7c+EFF : .000700 TANK PROFILE 4 P T S 50.5 1 NCIIH VCL 5199
TANK DIAMETER 117.00 FULL VOL 19703 29.3 1 Nl'.,H VOL 1933
TANK PROFILE 4 PTS 87.8 INCH VOL 15948
FULL 0--)L 10369 58.5 INCH VOL 9879
8''7.8 INCH VOL 8472 29.3 INCH VOL 3801 FLOAT SIZE: 4.0 IN. 6496
58.5 INCH VOL 5199
2 2,0 WATER WARN I N(-�9.3 INCH VOL 1933
FLOAT SIZE: 4.0 IN. 8436 HIGH iJATER LIMIT'.
FLOAT SIZE: 4.0 111. 8496 IJHTER Wr"IRN I NG 2.0 ll OR LABEL VOL: 10369
HIGH WATER LIMIT: 3.0 OVERFILL LIMIT 130%
WATER WARN 1116 1.0
9332
'
HIGH WATER LIMIT: 3.0 lllk�" OR LABEL VOL: 1970!3' HIC,H PRODUCT 95%
OVERFILL LIMIT 90;4 9850
MA, OR LABEL VOL; 10369 17739 DEL I VERI. L I("I I T 10%
J ERFILL LIMIT HIGH PRODUCT 95%
90%� 1036
93:32 18718
HIGH PRODUCT 95`%: DELIVERY LIMIT 10% LOW PRODUCT Soo
9850 1970 LEAK ALARM LIMIT: 99
DELIVERY LIMIT 101.1 SUDDEN LOSS LIMIT: 99
1036 LOW PRODUJ- 800 TANK TILT 2.35
LEAK ALARM LIMIT: 99
LOW PRODUCT Boo SUDDEN LOSS LIMIT: 99 flANIFOLDED ThtlKS
LEAK Al-(�PH LIMIT: 99 TANK TILT 1 .75 T#: 02
SUDDEN LOSS LIMIT: 99
TANK TILT 0.00 t1ANIFOLDED TA1'4K---,
T#: 03 LEAK MIN PERIODIC: 5?-.
MANIFOLDED TANKS i7l
2592
TO' NONE
LEAK M11-4 PERIODIC: 25% LEAK MIN ANNUAL 2 5�S
• 4925 59q
LEAK H I N PERIODIC: "25%
'-'59'2 LEAK MIN ANNUAL 25
49''25 PERIODIC TEST T'f"PE
LEAK Mll'-1 ANNUAL STANDARD
'259'2
PERIODIC TEST TYPE ANNUAL TEST FAIL
STANDARD ALARM DISABLED
PERIODIC, TEST T"1'?E
STANDARD
S ANNUAL TEST FAIL PERIODIC TEST FAIL
ALARM DIP,14BLED ALARM DISABLED
ANNUAL TEST FAIL
ALARM DISABLED PERIODIC TEST FAIL GROSS TEST FAIL
ALARM DISABLED ALARM DISABLED
PERIODIC TEST FAIL
* P
hLrlR(l DISABLED GROSS TEST FAIL ANN TEST AVERAGING: OFF
ALARM D I Sr"'iBLED PER TEST A�.,'ERAG I 11G: OFF
GROSIB TF-ST FAIL
ALARM DISABLED ANN TEST HVERAGING: OFF TANK TEST NOTIFY: OFF
PER TEST AVERAGING: OFF
r;*INIU TEST AVERAGINk-4: OFF TNK TST SIPHON BREAh:0-FF
PER TEST AVERAGING: OFF THNN TEST 14OTIF" OFF
TNK TST SIPHON BREAK:OFF DEL I'v'ERl' DELA'i" : 5 M I t"i
TANK TE,�31* N'.TI FY: OFF
Tf,11" TST SIPHON BREAK:OFF DEL I VERY DELA"x' : 5 M I I'l
DELIVERY DELA'-z' : 5 11 IN
LIQUID SENSOR SETUP
- - - - - - - - - - - - OUTPUT REL---%)-' SE'rup•
-- - -- - - - - - - - - -
L 1 1-,'tA,7 ANNULAR
TR I -STATE (S I NGLE FLOAT) R 1 :91 SHUTDOWN
CATEGORY .: ANNULAR SPACE T"..'PE:
STANDARD
NORMALLY CLOSED
L TURBIllE
TPi-STATE (SINGLE FLOAT' I ALHE.-f-IS
CATEGOR"' : STP SU11P T I :HIGH WATER ALARM
T 1 :LOW PRODUCT ALARM
L 3.87 TURBINE LIQUID SENSOR ALMS
TRI-;'-',TMTE (SINGLE FLOAT) ALL:FUEL ALARM
CATEGORY : STP SUMP ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
L 4:87 MAIN ANNULAR R 2:87 MAIN SHUTDOi,,JN
TRI-STATE ,SINGLE FLOAT) TYPE:
CATEGORY : ANNULAR SPA,:--'E STANDARD
LEAK TEST METHOD NORMLiLLY C-71-CISED
- - - - - - - -- - - - -
TEST ON DATE : ALL TANK
SAN I � 1996 L 5:87 TURBINE N-TANK
TRI-STATE (SINGLE FLOAT) T 2:HIGH WATER ALARl,l ST'RT TIME DISABLED
TEST RATE 0.220 G'AL. 'HR CATEGOR`/ : STF, SUMP T 2:LOtJ PRODUCT ALARM
DURATION 21 HOUR:
LIQUID SENSOR HLI%lrC
L 9: t2 UDC ALL:FUEL ALARM
TR I-;ST�.)TE (SlfJGLE FLOAT) ALL:SENSUR OUT ALARM
LEAK TEST REPC)PT FORMAT G TEC,'O'PY : DISPENSER PAN ALL:SHORT ALARM
NORMAL R :3:8�7 TANK 2 SHUTDOWN
TYPE:
LI0:3-4 UDC STANDARD
TRI-STATE (SINGLE FLOAT) NORMALLY CLOSED
CATEGORY : DISPENSER Pr-'IN
I 14-TANK ALARMS
T 3:Hlk-"H WATER ALARM
L 1 :5-6 UDC T 3:LOW PRODUCT ALARM
TRI-STATE (SINGLE FLOAT)
CATEGORY : DISPENSER PAI4 LIOUID SENSOR ALMS
ALL:FUEL ALARM
ALL:oENSOR OUT ALARM
ALL:SHORT ALARM
L I'--':7-8 UDC
TRI-STATE (SIN(iLE FLOAT)
CATEGORY : DISPENSER PAN
L13:9-10 UDC
TRI-STATE (.SINGLE FLOAT)
CATEGORY DISPENSER PAN
1-14: 11-12 UDC
TRI-STATE (SINGLE FLOAT)
CATEGORY DISPENSER PAN SOFTWARE REVISION LEVEL
VER��I�jt.4 1.5.1il"
SOFTWAREa 346ciII71-100-B
CREATED - 97. 10._'3.08.5b
L15:13-14 UDC
TRI-STATE (SINGLE FLOAT) NO SOFTWARE MODULE
CATEGOPI/ DISPENSER PAN SYSTEM FEATURES:
PERIODic,. IN-TAN)" TESTS'
ANNUAL IN-TANK TESTS
1-16: 15-16 LIDO
TRI-STATE FLOAT)
CATEGOP'i DISPENSER PAN
SWRCB,January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests(if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION
Facility Name: Arco Am-Pm I Date of Testing: 12/01/10
Facility Address: 2301 "F°'Street,Bakersfield,CA. 93301
Facility Contact: Kamal I Phone: 661.303.7961
Date Local Agency Was Notified of Testing: 11/24/10
Name of Local Agency Inspector(if present during testing): Ernie Medina
2. TESTING CONTRACTOR INFORMATION
Company Name: Redwine Testing Services Inc.
Technician Conducting Test: Jerry Rangel
Credentials': CSLB Contractor X ICC Service Tech. SWRCB Tank Tester Other(Specify)
License Number(s): ICC:5309489-UT
3. SPILL BUCKET TESTING INFORMATION
Test Method Used: X Hydrostatic Vacuum Other
Test Equipment Used: Measuring tape Equipment Resolution: '/a inch
Identify Spill Bucket(By Tank 87 slave fill 87 master fill A 87 master fill B 91 rill
Number, Stored Product, etc.)
Bucket Installation Type: Direct Bury Direct Bury Direct Bury Direct Bury
X Contained in Sump X Contained in Sump X Contained in Sump X Contained in Sum
Bucket Diameter: 12" 12" 12" 12"
Bucket Depth. 14" 14" 14" 14"
Wait time between applying
vacuum/water and start of test: 30 minutes 30 minutes 30 minutes 30 minutes
Test Start Time(TO: 1:00 pm 1:00 pm 1:00 pm 1:00 pm
Initial Reading(RI): 9" 9" 9" 9"
Test End Time(TF): 2:00 pm 2:00 pm 2:00 pm 2:00 pm
Final Reading(RF): 9" 9" 9" 9"
Test Duration(TF—Tj): 1 hour 1 hour 1 hour 1 hour
Change in Reading(RF-RO: one None None None
Pass/Fail Threshold or No drop No drop No drop . No drop
Criteria:
TestR ult SIN W&N XP F l�NOV*s `Fail XtP F X Pa s Fa►14
Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests)
CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING
I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements.
Technician's Signature: Date:-12/01/10
' State laws and regulations do not currently require testing to be performed by a qualified contractor. However,local requirements
may be more stringent.