HomeMy WebLinkAboutFMC 2010 MONITORING SYSTEM CERTIFICATION
For Use By All Jurisdictions Within the State of California
Authority Cited: Chapter 6 7,Health and Safety Code;Chapter 16,Division 3, Title 23, California Code of Regulations
This form must be used to document testing.and servicing of monitoring equipment. A separate certification or resort must be prepared for each
,monitoring,system control panel by the technician who performs the work. A copy of this form must be provided to the tank system owner/operator.
The owner/operator must submit a copy of this form.to the local agency regulating UST systems within 30.days of test date.
A. General Information IIIIIIIIIIIIIIIIIIII 25
Facility Name: BASHAAR'S CHEVRON lE Bldg.No.:
Site Address: 2301 PANAMA LANE City: BAKERFIELD Zip: 93307
Facility Contact Person: Contact Phone No.: ( )
Make/Model of Monitoring System:.TLS450 Date of Testing/Servicing: 911512010
B. Inventory of Equipment Tested/Certified
Check the a ro riate boxes to indicate specific quipment ins ed/serviced:
Tank ID: UNL87 Tank ID: PLUS88
®m-Tank Gauging Probe. Model: MAGI Z In-Tank Gauging Probe. Model: MAGI
❑Annular Space or Vault Sensor. Model: ❑Annular Space or Vault Sensor. Model:
®Piping Sump/Trench Sensor(s). Model: 208 ®Piping Sump/Trench Sensor(s). Model: 208
❑Fill Sump Sensor(s). - Model: ❑Fill Sump Sensor(s). Model:
®Mechanical Line Leak Detector. Model: RED.JACKET ®Mechanical Line Leak Detector. Model: RED JACKET
❑Electronic Line Leak Detector. Model: . ❑Electronic Line Leak Detector. Model:
❑Tank Overfill/High-Level Sensor. Model: ❑Tank Overfill/High-level Sensor. Model:
❑Other(specify equipment type and model in Section E on Page 2). ❑Other(specify equipment type and model in Section E on Page 2).
Tank ID: PREM91 Tank ID: TRANSITION SUMP
®In-Tank Gauging Probe. Model:.MAGI ®In-Tank Gauging Probe. Model: MAGI
❑Annular Space or Vauh Sensor. Model: ❑Annular Space or Vault Sensor. Model:
®Piping Sump/Trench Sensor(s). Model: 208 ®Piping Sump/Trench.Sensor(s). Model: RONAN SENSOR
❑Fill Sump Sensor(s). Model: ❑Fill Sump Sensor(s). Model:
®Mechanical Line Leak Detector. Model: RED JACKET ❑Mechanical Line.Leak Detector. Model:
❑Electronic Line Leak Detector. Model: ❑Electronic Line Leak Detector. Model:
❑Tank Overfill/High-Level Sensor. Model ❑Tank Overfill/High-Level Sensor. Model:
❑Other(specify equipment type and model in Section on.Page 2). ❑Other(specifyequipment type and model in Section E on'Page 2).
Dispenser ID: 112 Dispenser ID: 314
®Dispenser Containment Sensor(s). Model: DIS-01 ®Dispenser Containment Sensor(s). Model: 406
®Shear Vdve(s). ®Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s);and Chain(s).
Dispenser ID: 516 Dispenser ID: 718
®Dispenser Containment Sensor(s). Model: DIS-01 ®Dispenser Containment Sensor(s), Model: DIS-01
®Shear Valve(s). ®Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
Dispenser ID: Dispenser ID:
❑Dispenser Containment Sensor(s). Model: ❑Dispenser Containment Sensor(s). Model:
❑Shear Valve(s): ❑Shear Valve(s).
❑Dispenser Containment Float(s)and Chain(s). ❑Dispenser Containment Float(s)and Chain(s).
'If the facility contains more tanks or dispensers,copy this form. Include information for every tank and dispenser at the facility.
C. Certification-I certify that the equipment identified in this document was inspected/serviced in accordance with the manufacturers'
guidelines. Attached to this Certification is.information (e.g. manufacturers' checklists) necessary verify that this information is
correct and a Plot Plan showing the layout of monitoring equipment. For any equi meat capable erating such reports,I have also
attached a copy of the report;(check all.that.apply): ®System-set-up Alarm report
Technician Name(print):. RICH PHILLIPS Signature:
Certification No.: A29084/1036169-UT License.N C611 D40 809850
Testing Company Name: RICH ENVIRONMENTAL Phone No.:(661) 392-8687
Testing Company Address: 5643 BROOKS CT. BAKERSFIELD,CA 93308 Date.of Testing/Servicing: 9/15/2010
Page 1 of 5
UN-036—1/4 www.unidomorg I IIIIIII IIIII III IIII 26 Rev.01117/08.
IE
Monitoring System Certification �� y
A Results of Testing/Servicing
Software Version Installed: 8.05
Complete the following checklist:
• Yes ❑ No* Is the audible alann.operational?
• Yes ❑ No* Is the visual alarm operational?
• Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational)
® Yes ❑ No* Were all sensors installed at lowest point of secondary containment.and positioned so that other equipment will
not interfere with their proper operation?
❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem)
® N/A operational?
® Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment
❑ N/A monitoring system detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate
positive shut-down?. (Check all that apply) ®'Sump/Trench.Sensors; ❑Dispenser Containment Sensors.
Did you confirm positive shut-down due to leaks.and sensor:fkdure/disconnection? ®Yes; ❑No.
❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no
® N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank
fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? %
❑ Yes* ® No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced
and list the manufacturer name and model for all replacement parts in Section.E,below:
❑ Yes* ® No Was liquid found.inside any secondary containment systems designed as dry systems? (Check all that apply)
❑Product; ❑Water. If yes,describe causes in Section E,.below.
® Yes ❑ No Was monitoring system set=up reviewed to ensure proper settings?Attach set up reports,if applicable
® Yes ❑ No* Is all monitoring equipment operational.per manufacturer's specifications?
*In,Section E below,describe how and when these deficiencies were or will be corrected.
E. Comments:
Page 2 of 5
UN-036—2/4 wwwxitidomorg Rev.01/17/08
Monitoring System Certification
F. In-Tank Gauging/SIR Equipment: ❑ Check this box if tank gauging is used only for inventory control.
❑ Check this box if no tank gauging or.SIR equipment is installed,
This section must be completed if in-tank gauging equipment.is used to perform leak detection monitoring.
Complete the following checklist:
• Yes ❑ No* Has all input wiring been inspected for proper entry and termination,:including testing for ground faults?
• Yes ❑ No* Were all tank gauging probes visually inspected for damage and residue buildup?
• Yes ❑ No* Was accuracy of system product level readings tested?
• Yes ❑ No* Was accuracy of system water level.readings tested?
• Yes ❑ No* Were all probes reinstalled properly?
• Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
*In Section H,below,describe how and when these deficiencies were or will be corrected.
G. Line Leak Detectors(LLD): ❑ Check this box if LLDs are not installed..
Com lete the folio win checklist:
® Yes ❑ No* For equipment start-up or annual.equipment certification, was a leak simulated to verify LLD performance?
❑ N/A (Check all that apply) Simulated leak rate: ®3.g,p.h.; ❑0.l g.p.h; ❑0.2 g.p.h.
• Yes ❑ No* Were all LLDs confirmed operational and accurate within regulatory requirements?
• Yes ❑ No* Was the testing apparatus.properiycalibrated?
® Yes ❑ No* For mechanical LLDs,does the LLD restrict product flow if it.detects a leak?
❑ N/A
• Yes ❑ No* For electronic.LLDs,does the turbine automatically shut off if the LLD detects a leak?
® N/A
• Yes ❑ No* For electronic.LLDs, does the.turbine automatically shut off if any portion of the monitoring system is disabled
® N/A or disconnected?
• Yes ❑ No* For electronic LLDs,does the turbine automatically shut off if any portion of.the monitoring system malfunctions
® N/A or fails a test?
• Yes ❑ No* For electronic LLDs,have all accessible wiring connections been visually inspected?
® N/A
® Yes ❑ No* Were all items on the equipment manufacturer's maintenance checklist completed?
*In Section H,below,describe how and when these deficiencies were or will'be corrected.
H. Comments:
Page 3 of 5
UN-036—3/4 www.unidoc5.org Rev.01/17/08
::$1`-1
Monitoring System Certificafion
UST Monitoring Site Plan
232-0 72
- : -
- - - - - . - - - . - - . - -
- - . . . . . . . . . . . . . . - - - - - - . _ .. -a . - - - - . - • - - - -
. . .. . . . w . . . . . . . . . . . . .. - • w. . ! r ,. _ �1}- _ _ • _ w
• - - - • - - - - - - - - - - - - - - -
r w . . . . . . . • . . . . . . • [[• - ! - r • _ _ _ r _ _ _ _ _ _ . _ • _
_ . • . • _ _ w _ • . . • • • _ _ _ _ r ., s • - - - - . - r - - - - - - - - r
- - - - - - - - . . - - - - - - - - _ . r
r . . • . . . . . •. . . . . . . . . . . ... _ _. . . r r r - - - - - - - - - - - - -
! . . . .. . . . . . . . . . . . • . . . . . _ • • .. _ .. _ • . • . . - - - - -
_ . . • r
.. . . . . . . . . ! . r • • Y. ... _ . • . . _. r - • . . . . .
• - -- - - - - - - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
I
(� . . . . . . . . . . r - - - - - - - - - - - - - - - - - • . . _ . . - . . _ - • r . -
..� �. ..
• . • • r • r r . . _ ! - . r ! . . . . ! - - - - - - - - - . L. - - - -
_ . / . _ _ • . . _ w_ • - - . - _ - - - - - - - - - - - - - r - - - - - _. . r . . . . . . .. . . . . . . . . r . -. . . . . .
. . . . . -. r ._ . • - . -. _ r . . _ _ _ -Y . . • . _ _ - - -- - - - - - - - - - - - - _ w . . . . _ .. r _w r r _ _ - - . _ _
- i _ - - ' - - - - - - - - - - - - - • - - - . . . .- - - - - - - - - - - - _ • . . • • _ _ - r .. . . . -- - - - - - - - - - - - - - .
w - • . - • . . . • _ . -
Date map was drawn:. . .
Ing,-uctions
Wyou already have a diagram that shows all required information,you may include it,rather than this page,with your
Monitoring System C.eatificatiom On your site plan,show the general IayoW of tanks and pipimg.Clearly ideatiify
locations of the following equipment, if installed:monitoring system control panels;sensflra monitoring tank annular
spaces,sumps,dispenser pans,spill containers,or other secondary containment areas;mechanical or electronic line leak
detectors,and in-tank liquid level probes(1f used for Ieak detection).In the space provided,note the date this Site Plan
was prepared.
Page of__, vstoo
Monitbring System Certification.Form:Addendum for Vacuum/Pressure Interstitial Sensors
Y. Results of Vacuum/Pressure Monitoring Equipment Testing
This page should be used to document testing and,servicing of vacuum and pressure interstitial sensors. A copy of
this form must be included with the Monitoring System Certification Form,. which must be provided to the tank
system ownerloperator. The owner/operator must submit a copy of the Monitoring System Certification Form to the
local agency regulating UST systems within 3d days of test date.
Manufacturer: Model: System Type:.❑Pressure;❑Vacuum
Sensor ID
Component(s)Monitored by this Sensor:
Sensor Functionality Test Result: ❑Pass; ❑ Fail Interstitial Communication Test.Result: ❑Pass; ❑ Fail
Component(s)Monitored by this Sensor:
Sensor Functionality Test Result: ❑Pass; 11 Fail Interstitial Communication Test Result:❑Pass; ❑ Fail
Component(s)Monitored bythis Sensor:.
Sensor Functionality Test.Result: []Pass; ❑ Fail Interstitial Communication Test.Result:❑Pass; ❑ Fail
Component(s)Monitored by this Sensor:
Sensor Functionality Test Result: ❑Pass; ❑ Fail Interstitial Communication Test Result:0 Pass; ❑ Fail
Component(s)Monitored by this Sensor:
Sensor Functionality Test Result:❑Pass; ❑ Fail. Interstitial Communication Test.Result:❑Pass; ❑ Fail
Component(s)Monitored by this Sensor:
Sensor Functionality Test Result:[-]'Pass; ❑. Fail Interstitial Communication Test Result:❑Pass; ❑ Fail
Component(s)Monitored.by this Sensor:
Sensor Functionality Test.Result:❑.Pass; ❑ Fail Interstitial Communication Test Result:❑Pass; ❑ Fail
Component(s)Monitored by this Sensor:
Sensor Functionality Test Result:❑Pass; ❑ Fail Interstitial Communication Test.Result:❑Pass; ❑ Fail
Component(s)Monitored by tbis Sensor:
Sensor Functionality Test Result:❑Pass; ❑ Fail Interstitial Communication Test Result:❑Pass; ❑ Fail
Component(s)Monitored by this Sensor:
Sensor Functionality Test Result:❑Pass; ❑ Fail Interstitial Communication Test Result:❑Pass; ❑ Fail
How was interstitial communication verified?
❑ Leak Introduced at Far End of Interstitial:Space;' ❑ Gauge; ❑ Visual Inspection; ❑ Other(Describe in Sec.J, below)
Was vacuum/pressure restored to operating levels.;in all interstitial spaces? ED Yes El No(Ifno, describe in Sec.J, below)
J. Comments: NIA
Page 4 of 5
' If the sensor successfully detects:a.simulated vacuum/pressure leak introduced in the interstitial space at the furthest point from the
sensor,vacuum/pressure has been demonstrated to be communicating throughout the interstice.
UN-036A-1/1 www.unidomorg Rev.01@6/06
993
RICH ENVIRONMENTAL
5643 BROOKS CT. BAKERSFIELD, CA. 93308
OFFICE(661)392-8687 FAX(661)392=0621
PRODUCT LINE LEAK DETECTOR TEST
WORK SHEET
W/0#:
FACILITY NAME:. BASHAA.R'S CHEVRON
FACILITY ADDRESS: 2301 PANAMA LANE,BAKERSFIELD
PRODUCT LINE TYPE: PRESSURE
PRODUCT LEAK DETECTOR TYPE TEST TRIP PASS
BELOW P.S.I. OR
SERIAL.NUMBER .3 G.P.H. FAIL
UNL87 LID TYPE.i MECHANICAL YES .10 PASS
SERIAL#RED JACKET
PLUS 89 LID TYPE:MECHANICAL YES PASS
SERIAL# RED JACKET 9
PREM91 LID TYPE:MECHANICAL YES 10 PASS
SERIAL#RED JACKET
L/D TYPE: YES PASS
SERIAL# NO FAEL
I CERTIFY THE ABOVE:TESTS WERE CONDUCTED ON THIS DATE ACCORDING TO RED
JACKET PUMPS FIELD TEST APPARATUS TESTING PROCEDURE AND LIMITATIONS.
THE MECHANICAL LEAK DETECTOR TEST PASS/FAIL IS DETERMINED BY USING A.
LOW FLOW THRESHOLD TRIP RATE OF 3 GALLONS-PERMOUR OR LESS AT 10 P.S.I.I
ACKNOWLEDGE THAT ALL DATA COLLECTED IS TRUE AND CORRECT TO:THE.BEST
OF MY KNOWLEDGE.
TECHNICIAN RICA PHI
SIGNATURE: DATE: 9115/10
SWRCB,January 2006
Spill Bucket Testing Report Form
This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and
printouts from tests(if applicable),should be provided to the facility.owner/operator for submittal to the local regulatory agency.
1. FACILITY INFORMATION.
Facility Name: BASHAAR'S CHEVRON Date of Testing: 9/15/10
Facility Address: 2301 PANAMA LANE.BAKERSFIELD
Facility Contact: Phone:
Date Local Agency Was Notified of Testing 811-1/10
Name of Local Agency Inspector(if present during testing):
2. TESTING CONTRACTOR INFORMATION
Company Name: RICH ENVIRONMENTAL
Technician Conducting Test: RICH PHILLIPS
Credentials': ❑CSLB Contractor X ICC Service Tech. 0 SWRCB Tank Tester ❑.Other(Spec)
License Number(s): 1035169-UT
3. SPILL BUCKET TESTING.INFORMATION
Test Method Used: X Hydrostatic ❑Vacuum 0 Other
Test Equipment Used:VISUAL Equipment Resolution:0
Identify Spill Bucket(By"Tank j Z 3 4
UAVM PLUS89 DREW
Number,Stored Product, etc.)
Bucket Installation Type: X Direct Bury X Direct Bury X Direct Bury 11 Direct Bury
❑Contained in Sump d Contained in Sump ❑Contained in Sump ❑Contained in Sum
Bucket Diameter: '12" 12" 12"
Bucket Depth: 16" 16" 16"
Wait time between applying 30 MIN 30 MIN 30 MIN
vacuum/water and start of test:
Test Start Time(TI): 9:AM 9:AM 9:AM
Initial Reading 12 13" 12"
Test End Time(TF): 1Q:AM 10:AM 1O:AM
Final Reading(RF): 12" 9 12"
Test Duration(Tr—Tj): 1-HOUR 1'-HOUR 1-HOUR
Change in Reading(RF-RD. 0 4" 0
Pass/Fait Threshold or +/_0.00 +/=0.00 +/-0.00
Criteria:
sac.
s q
i,� .C' !ii I i .L !1' �! t I , ,.t,• r 'ii' ie'�'�
Comments—(include information.on repairs made prior to testing, and recomrn_ended follow-up for failed tests)
89 BUCKET CRACKED
CERTIFICATION OF TEC RESPONSIBLE FOR CONDUCTING THIS TESTING
1 hereby certify that all the lnformado ' ed in this report,is:true,"accurate,and in full compliance with legal requirements.
Technician's Signature: Date 9/15/10
1
State-laws and regulations.do not currently require testing to be performed by a qualified contractor.However,local.requirements
may be more stringent.
SYSTEM SETUP
IN-TANK SETUP- _ _ _ _ _ COMMUNICATIONS SETUP SEP 15, 2010 8:40 AM- _
T 1 :SUPER 1 PORT SETTINGS'. SYSTEM UNITS
PRODUCT COD E 000700 U.S.
THERMAL COEFF '3 .00 COMM BOARD 5 (RS-�485}
AMETER S5'STENI LANGUAGE
TANK DI BAUD PATE 2400 ENGLISH
TANK PROFILFVOL 99sU PARITY : .EVEN SYSTEM DATE;•TIME FORMAT
STOP BIT ESTOP MON DD YYYY HH:MM:SS xM
DATA LENGTH: 7 DATA
FLOAT SIZE: 4.0 IN. RS-232 SECURITY PASHAARS CHEVRON
CODE : DISABLED
WATER WARNING : 2.0
WATER L.lM IT: 3.0 COMM BOARD : 6 (k:'-2:32) 661-632-4551,
HIGH BAUD RATE 1201
rgAX. OR LABEL VOL' 5980 PARITY :.. O LT, SHIFT TI-111E 1 : 11 :00. PM
OVERFILL L1h1IT 95% STOP BIT 1 i:,E' SHIFT. TIME 2 : 7:00 AM
5481 DATA LENGFH: 7 DHiCA SHIFT TIME 3 : DISABLED
99%, RS-232 SECURITY SHIFT TIME 4 : DISABLED
HIGH PRODUCT 9880 CODE, : DISABLED
4% TANK PER TST NEEDED WRN
DELIVERY LIMIT 399 DISABLED
AUTO TRANSMIT SETTINGS: TANK. ANN TST. NEEDED WRN
LOW PRODUCT 399 DISABLED
LEAK ALARM L I ICI T: 50 AUTO LEAK ALARM LIMIT
hi I T
SUDDEN LOSS LIMIT: 3,:50 DISABLED LINE RE-ENABLE METHOD
TANK TILT AUTO HIGH WATER LIMIT PASS LINE TEST
TANK OFFSET 0.00 DISABLED
AUTO OVERFILL LIMIT LINE PER TST NEEDED WRN
DISABLED DISABLED
SIPHON MANIFOLDED TANKS AUTO LOW. PRODUCT LINE .ANN TST NEEDED WRN
T : NONE DISABLED DISABLED
LINF MANIFOLDED TANKS AUTO THEFT LIMIT
LIt: NONE DISABLED PRINT TC VOLUMES
AUTO DELIVER': START ENABLED
° DISABLED
LEAK MIN PERIODIC: 1/ AUTO DELIVERY END TEMP COMPENSATION
99 DISABLED VALUE (DEC. F ) : 60.0
AUTO EXTERNAL INPUT ON STICK HEIGHT OFFSET
LEAK MIN ANNUAL 99 DISABLED
BLEXTERNAL INPUT OFF DISABLED
90%.
DISABLED.
.AUTO SENSOR FUEL ALARM H-PROTOCOL DATA FORMAT
PERIODIC TEST 1 STANDARD AUTOBSENSOR WATER ALARM DAYIGHT SAVING TIME
DISABLEDr DISABLED
ANNUAL TEST FAIL AUTO SENSOR OUT'ALARM REDIRECT LOCAL PRINTOUT
ALARM DISABLED DISABLED DISABLED
PERIODIC TEST FAIL EURO PROTOCOL PREFIX
ALARM DISABLED
GgOSB TEST AI AR 1 UISABLED f.
SYSTEM SECURITY
ANN TEST AVERAGING: OFF CODE 000000
PER TEST AVERAGING. OFF RS-232 END OF MESSAGE
)ISABLEI? MAINTENANCE HISTORY
TANK TEST NOTIFY: OFF DISABLED
TNK TST SIPHON BREAK:OFF TANK CHART SECURITY
DELIVERY DELAY 15 MIN DISABLED
pUMP THRESHOLD 10.008:
CUSTOM ALARMS
DISABLED
SERVICE NOTICE
DISABLED
ISO 3166 COUNTRY
CODE:
LEAK TEST METHOD MASS/DENSITY
TEST WEEKLY ALL TANK DISABLED
MONnT T IMP 2:00
ALARM HISTORY REPORT ��
---- IN-TANK ALARM --- PMC.•SfiTUP
T 2:PLUS PW-' VERSION:, 01 .02
HIGH WATER ALARM VAPOR PROCESSOR TYPE
MAY 8, 2009 3:30 PM VEEDER-ROOT POLISHER
MAY 5, 2009 12:57 PM
ANALYSIS TIMES LIQUID SENSOR SETUP
TJ
OVERFILL ALARM TIME: 11 :TI ES - - - - - - - - - - -
NOV 30, 2009 1 :1.8 PM DELAY MINUTES:
MAY 9, 2009 7:32 AM 1 L 1 :SUPER .
TRI-STATE (SINGLE FLOAT)
LOW PRODUCT ALARM CATEGORY : STP SUMP
MAY 9. 2009 7:35 AM
MAY 9, 2009 7:26 AM
MAY 5. 2009 12:59 PM L 2:PLUS
TRI=STATE. (SINGLE FLOAT)
SUDDEN LOSS ALARM CATEGORY : STP SUMP
NOV 30, 2009 3:04 All
HIGH PRODUCT ALARM ALARM H18TORY REPORT L .3:UNLEADED
NOV 30, 2009 ::1 q AM PM - IN-TANK ALARM - --_ CATEGORYE:(STP SUMP
INVALID FLOAT)MAY 9. 2009 ?:32 ' "-
INVALID FUEL LEVEL T I :SUPER
MAY 5. 2009 12:59 PM SETUP DATA WARNING NORMALLY MAY 5. 2009 12:03 PM CLOSED
JAN 29, 2009 1 :59 PM CATEGORY PIPING SUMP
PROBE OUT SUDDEN LOSS 'ALARM
MAY 9, 2009 7:35 AM JUL 19, 2
MAY 9. 2009 7:27 AM 010 3:18 AM
MAY 8, 2009 2:52 PJH INVALID FUEL LEVEL
HIGH WATER WARNING SEP 13, 2010 12;10 PM
MAY S. 2009 3:30 PM SEP ' 6: 201.0 2:13 PM
MAY 5, 2009 12:58 PM AUG 26. 2010 7:28 PM
DELIVER`! NEEDED DELIVERY NEEDED
MAY 9. 2009 7:35 AM JAN 29. 2009 1 :59 PM
MAY 9, 2009 7:26 AM OUTPUT RELAY SETUP
MAY 5, 2009 12:.59 PM - - - - - - - - -
R 1 :SHUTDOWN
TYPE:
STANDARD
NORMALLY CLOSED
LIQUID SENSOR ALMS
* * * * ALL:FUEL ALARM
3� * ENDS:
SMARTSENSOR SETUP
ALARM HISTORY REPORT s 1 :PRESSURE SENSOR
CATEGORY VAPOR PRESSURE
---- IN-TANK ALARM -----
T 3:UNLEADED CATEGORY VAPORHVALVE
INVALID FUEL LEVEL s. 8:.ATM
AUG 16. 2009 7:37 PM CATEGORY ATM P SENSOR
AUG 12, 2009 3:28 PM
AUG 2, 2009 2:14 PM
PROBE OUT
MAY 5. 2009 1 :41 PM
MAY 5. 2009 1 :36 PM
MAY 5. 2009 12:52 PIH
HIGH WATER. WARNING
MAY 5. 2005 1 :27 PM
----- SENSOR ALARM ----
L 1 :SUPER
STP SUMP
FUEL ALARM
SEP 15. 2010 9:04 AM
-- SENSOR ALARM =-- -
L 2:PLUS BASHAF;RS CHEVRON
STP SUMP
SENSOR OUT ALARMr 661-$32-4551
SEP 15.- 2010 9:36 AM
SEP 15, 2010 9:15 At-1
----- SENSOR ALARM -----
L 3:UNLEADED
SYSTEM STATUS REPORT STP SUMP
- - _ _ FUEL ALARM
L 2:FUEL ALARM SEP 15. 2010 9:05 AM
----- SENSOR ALARM -----
L 3:UNLEADED
STP SUMP
SENSOR OUT ALARM
SEP 15, 2010 9:36 AM
----- SENSOR ALARM -----
L 2:PLUS
=- SENSOR. ALARM ----- STP SUMP
L 4:PIPING SUMP FUEL ALARM
PIPING SUMP 'SEP 15. 2010 9:05 AM
FUEL ALARM
l3ASHAARS CHEVRON SEP 15, 2010. 9:24 AM
661-832-4551
SEP 15, 2010 9:36 AM
----- SENSOR ALARM -----
SYSTEM STATUS REPORT L 2:PLUS
- - -- SENSOR ALARM -- - STP SUMP
ALL FUNCTIONS NORMAL L 4_'.PIPING SUMP FUEL ALARM
PIPING SUMP SEP 15. 2010 9:.06 AM
FUEL ALARM
SEP I5. 201.01 5.:36 AM
SOFTWARE REVISION LEVEL
VERSION 329.01 -- -- SENSOR ALARM -----
SOFTWARE# 346329=100-9 L 2:PLUS
CREATED - 09.01 ..29.15.44 ----- SENSOR ALARM ----_ STP SUMP
L 1 :SUPER
FUEL ALARM
NO SOFTWARE MODULE STP SUMP SEP 15, 201-0 9:08 AM
.SYSTEM FEATURES: SENSOR OUT ALARM
PERIODIC IN-TANK TESTS' SEP 15, 2010 9:36 AM
ANNUAL IN-TANK TESTS
OUTPUT RELAY SETUP
- - - - - - - - -- - -
R I :SHUTDOWN
TYPE:
STANDARD
NORMALLY CLOSED
LIQUID SENSOR ALMS
ALL:FUEL ALARM
MONITOR CERT. FAELURE REPORT
SITE NAME : BASHAAR'S CHEVRON DATE : 9/15/10
ADDRESS 2301 PANAMA LANE TECHNICIAN: RICH PHILLIPS
CITY : BAKERSFIELD.. SIGNATURE:
THE FOLLOWING COMPONENTS WERE.REPLACED/REPAIRED TO COMPLETE
TESTING.
REPAIRS; 89 BUCKET HAS A CRACK-NEEDS TO BE REPLACED
lv-iZJ� c-A 4-L- 1*,-,q EP' A&6 6 S 4&Aw"'gv)
LABOR: NONE
PARTS INSTALLED • NONE
NAME : TITLE :
SIGNATURE
THE ABOVE NAMED PERSON TAKES FULL RESPONSIBILITY OF NOTIFYING
THE APPROPRIATE PARTY TO HAVE CORRECTIVE ACTION TAKEN TO REPAIR
THE ABOVE LISTED PROBLEMS AND NOTIFYING RICH ENVZRONNL NTAI:FOR
ANY NEEDED RETESTING.THIS ALSO RELEASES RICH ENVIRONMENT_ AL OF
ANY FINES'ORTENALTIES OCCURING FROM NON-COMPLIANCE.
A COPY OF THIS DOCUMENT HAS BEEN LEFT ON-SITE FOR YOUR.
CONVIENENCE.