HomeMy WebLinkAbout2011 SB989 RESULTS SWRCB,January 2W2 1191111 35 Page of Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of thisform to report results for all components tested The completed form,written test procedures,and printouts from tests(rf applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Fastrip Store#346 Date of Testing: 3116111 Facility Address: 2698 Oswell St.Bakersfield Ca. Facility Contact: Jamieson Hill Phone: 661-396-7000 Date Local Agency Was Notified of Testing: 3/10/11 Name of Local Agency Inspector(rf present during testing): 2. TESTING CONTRACTOR INFORMATION Company Name: Sunset Mechanical Technician Condu Test: Scott Olinger Credentials: WCSLB Licensed Contractor ❑SWRCB Licensed Tank Tester License Type: C-36 C-10 License Number: 589517 z Manufacturer Training Manufacturer Com onen s Date Training Expires Incon TS-STS Inspection Equipment 1/18/13 Veeder Root —Monitoring System 1/15/12 ICC Cal UST Service Tech 1/18/13 3. SUAMARY OF TEST RESULTS Component Pass Fail Not Repairs Component Pass Fail Not Repairs Tested Made Tested Made UDC 1-2 ❑ ❑. ❑ FILL 3 0 10 ❑ ❑ ❑ UDC 3-4 ❑ ❑ ❑ FILL 4 ❑ ❑ ❑ UDC 5-6 ❑ ❑ ❑ SPILL 1 ❑ ❑ ❑ UDC 7-9 ❑ ❑ ❑ SPILL 2 ❑ ❑ ❑ TRAN 1 ❑ p Ef SPILL 3 ❑ ❑ ❑ TRAN 2 ❑ ❑ SPILL 4 ❑ ❑ ❑ STP 1 ❑ ❑ ❑ VSPILL 1 ❑ ❑ ❑ STP 2 V ❑ ❑ ❑ VSPILL 2 ❑ ❑ ❑ STP 3 ❑ ❑ ❑ VSPILL 3 ❑ ❑ ❑ STP 4 ❑ ❑ ❑ VSPILL 4 ❑ ❑ ❑ FILL 1 ❑ ❑ ❑ ANN SPACE 1 ❑ ❑ ❑ FILL 2 ❑ ❑ ❑ ANN SPACE 2 ❑ ❑ p If hydrostatic testing was performed,describe what was done with the water after completion of tests: CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To tyre best of my Knowledge,the fads stated in this document are accurate and in full compliance with legal requirements Technician's Signature: Date:-3/16/11 IIIIIIIIVIIIIIIIIII 36 IE SWRCB,January 2002 Page of Secondary Containment Testing Report Form This form is intended for use by contractors performing periodic testing of UST secondary containment systems. Use the appropriate pages of thisform to report results for all components tested The completed form,written test procedures, and printouts from tests(rf applicable),should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: Fastrip Store#346 Date of Testing: 3/16/11 Facility Address: 2698 Oswell St.Bakersfield Ca. Facility Contact: Jamieson Hill Phone: 661-396-7000 Date Local Agency Was Notified of Testing: 3/10/11 Name of Local Agency Inspector(ifpresent during testing): 2. TESTING CONTRACTOR INFORMATION Company Name: Sunset Mechanical Technician Condu ' Test: Scott Olinger Credentials: 9CSLB Licensed Contractor ❑SWRCB Licensed Tank Tester License Type: C-36 C-10 License Number. 589517 Manufacturer Training Manufacturer Component(s) Date Training Expires Incon TS-STS Inspection E ui ment 1/18/13 Veeder Root Monitorin System 1/15/I2 ICC Cal UST Service Tech 1/18/13 3. SUMMARY OF TEST RESULTS Component Pass Fait Not Repairs Component pass Fail Not Repairs Tested Made Tested Made ANN SPACE 3 ❑ ❑ ❑ ❑ ❑ ❑ ❑ ANN SPACE 4 ❑ ❑ ❑ ❑ ❑ ❑ ❑ PIPING RUN 1 ❑ ❑_ ❑ ❑ ❑ ❑ ❑ PIPING RUN 2 ❑ ❑ ❑ ❑ ❑ 0 ❑ PIPING RUN 3 ❑ ❑ ❑ ❑ ❑ 0 ❑ PIPING RUN 4 ❑ ❑ ❑ ❑ 0 0 0 ❑ ❑ ❑ ❑ ❑ ❑ ❑ 0 ❑ 0 ❑ 0 ❑ 0 ❑ ❑ ❑ ❑ ❑ ❑ 0 0 0 0 If hydrostatic testing was performed,describe what was done with the water after completion of tests: CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING To the best of my knowledge,the fa stated in this document are accurate and in full compliance with legal requirements Technician's Signature: Date: 3/16/11 SWRCB,January 2002 Page_of 4..TANK ANNULAR TESTING Test Method Developed By: Rf Tank Manufacturer 0 industry Standard 0 Professional Engineer ❑Other(Specify) Test Method Used: 0 Pressure EK Vacuum 0 Hydrostatic 0 Other(Specify) Test Equipment Used.4"GEL FILLED GAUGE W/CERTS Equipment Resolution:0-30 Tank#1 Tank#2 Tank#3 Tank#4 Is Tank Exempt From Testing?' 0 Yes dNo 0 Yes d No 0 Yes No 0 Yes No Tank Capacity: 12,000 12,000 12,000 12,000 Tank Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS Tank Manufacturer. MODERN MODERN MODERN MODERN Product Stored:- PREM DIESEL UNL UNL Wait time between applying pressuretvacuum/water and 10 MIN 10 MIN 10 MIN 10 MIN starting test. Test Start Time: 9:30 9:30 12:00 12:00 Initial Reading 7 HG 7 HG 7 HG 7 HG Test End Time: 10:30 10:30 1:00 1:00 Final Reading(RF): 7 HG 7 HG 7 HG 7 HG Test Duration: I 14R I]HR I HR I HR Change in Reading(RF-Rj)- 0 0 0 0 Pass/Fail Threshold or Criteria: 0 0 0 0 A Test Reiult. li". .0 Fail '19 P"S' 0 al /Ilisis ❑Fail Fait. F' I Was sensor removed for testing? i-�Yes ❑No 0 NA &Yes 0 No 0 NA Yes D No DNA ffYes ❑No DNA Was sensor —rly replaced and prope S/Yes ❑No 0 NA JYes 0 No 0 NA &s 0 No ❑NA Q�es 0 No DNA verified functional after testis ? Comments—(include information on repairs made prior to testing; and recommended follow-up for failed tests) Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment testing. (California Code of Regulations,Title 23,Section 2637(a)(6)1 SVMCB,January 2002 Page_of 5. SECONDARY PIPE TESTING Test Method Developed By: B6 Piping Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum 1KHydrostatic ❑Other(Specify) Test Equipment Used: INCON TS,—STS Equipment Resolution: 0.0000' Piping Run#1 Piping Run#2 Piping Run#3 Piping Run#4 Piping Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS Piping Manufacturer. AO SMITH AO SMITH AO SMITH AO SMITH Piping Diameter. 3" 3" 3" 3" Length of Piping Run: 50' 60' 70' 801 Product Stored: PREM DIESEL UNL UNI, Method and location of TEST BOOT AT ST? TEST BOOT AT STP TEST BOOT AT iping7run isolation: STP TEST BOOT AT STP p Waittime between applying pressure/vacuum/water and 10 MIN 10 MIN 10 NUN 10 MIN starting test: Test Start Time: 8:20 8:20 8:20 8:20 Initial Reading(RO: 4.8743 7.0334 3.7053 4.1568 Test End Time: 8:35 8:35 8:35 8:35 Final Reading(RF): 4.8735 7.0331 3.7047 4.1556 Test Duration: 15 N41N 15 MIN 15 MIN 15 MIN Change in Reading(RF-M: .0008 .0003 .0006 .0012 Pass/Fail Threshold or .002 .002 .002 .002 Criteria; TesY,Resuilr Pass Fail Pass OFaV Tass�- 0 FWI :4 Comments—(include information on repairs made prior to testing and recommended follow-up fiorfailed tests) SWRCB,January 2002 Page_of 6. PIPING SLTW TESTING Test Method Developed By: IV Sump Manufacturer ❑industry Standard ❑Professional Engineer ❑Other(Specify) 4 Test Method Used: ❑Pressure D Vacuum Hydrostatic ❑Other(Specify) Test Equipment Used:MCON TS—STS Equipment Resolution: OWO RINNE Sump #1 Sump#2 Sump#3 Sump#4 Sump Diameter: 48" 48" 48" 48" Sump Depth: 60" 58" 61" 65" Sump Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS Height from Tank Top to Top of 14" 16" 15" 15" Highest Piping Penetration: Height from Tank Top to Lowest 20" 15" 14" 14" Electrical Penetration: Condition of sump prior to testing: DRY DRY DRY DRY Portion of Sump Tested' 16" 18" 17" 17" Does turbine shut down when sump sensor detects liquid(both d E Yes ❑No D NA (Yes ❑No ❑NA R(Yes ❑No ❑NA N(Yes ❑No ❑NA p roduct and water?• Turbine shutdown response time Is system programmed for fail-safe shutdown? dyes 0 No ❑NA Yes ❑No ❑NA DNA WYes ONo DNA Was fail-safe verified to be _WY—es ❑No DNA C/Yes oNo nNA —7Yes ONo DNA Yes ❑No ❑NA operational?* Wait time between applying pressure/vacuum/water and starting 10 MIN 10 MIN 10 MIN 10 NHN test: Test Start Time: 10:42 10:42 11:53 MCA Initial Reading(Ri): 4.9525 3.4552 4.0729 4.6115 Test End Time: 10:57 10:57 12:08 12:08 Final Reading(RF): 4.9518 3.4590 4-0729 4.6101 Tea Duration: is MEN 15 MIN 15 NUN 15 AM Change in Reading(RF-Rj): .0007 .0002 .0001 .0014 Pass/Fail Threshold or Criteria: .002, .00; .002 .002, lot. 0 Fall af Patss O'Faif Pass ❑Fait Xeit Result: civiii Pass sensor removed for ON6 DNA 9'Yes ONo DNA dYes ONo DNA Kes DNo DNA Was sensor property replaced and verified functional after Le - ❑No ❑NA Wes ONo DNA WYes ONo DNA M/Yes ❑No DNA Comments—(include information on repairs made prior to testing,and recommended follow-upfor failed tests) REPLACED#2 FIBERLITE SEAL REPLACED STP#2—13X2 TERM BOOT If the entire depth of the sump is not tested,specify how much was tested. If the answer to M of the questions indicated with an asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page_of 6. PIPING SUMP TESTING Test Method Developed By: IjSump Manufacturer ❑Industry Standard ❑Professional Engineer 0 Other(Specify) oe Test Method Used: 0 Pressure 0 Vacuum WHydrostatic 0 Other(Specify) Test Equipment Used:INCON TS—STS Equipment Resolution: SUMP#TRAN I Sump#TRAN 2 Sump# Sump# Sump Diameter: 18"X 24" 18"X 24" Sump Depth- 28" 28" Sump Material: FIBERGLASS FIBERGLASS Height from Tank Top to Top of 12" 12" Highest Piping Penetration: Height from Tank Top to Lowest 12" 10" Electrical Penetration: Condition of sump prior to testing: DRY DRY Portion of Sump Tested' 14" 14" Does turbine shut down when sump sensor detects liquid(both dyes ❑No 0 NA 54es ONo DNA 0Yes ONo DNA OYes 0No DNA pro duct and water)9* Turbine shutdown response time IS System programmed for fail-safe shutdown? es D No DNA ONo DNA OYes ONo DNA ❑Yes 0 No ❑NA Was fail-safe verified to be Yes ❑No 0 NA okes ONo DNA OYes DNo DNA ❑Yes 0 No ❑NA OP ional?* Wait time between applying pressure/vacuum/water and starting 10 MIN 10 MIN test: Test Start Time: 1:19 1:19 Initial Reading(Rj: 3.7458 5.2839 Test End Time: 1:34 1:34 Final Reading(RF): 3.7457 5.2838 Test Duration: 15 P41N 15 MIN Change in Reading(RF-RO: .0001 .0001 Pass/Fail Threshold or Criteria: .002/ .002, :P Test.Result: :,O,Pikss� ❑Fan ❑ afl- pan Q'F" Pass 0 Fail- Was sensor removed for t ONo DNA [YYes DNo DNA ❑Yes 0 No 0 NA DYes DNo DNA Was sensor property replaced and Yes ONo, DNAJ M/Yes ONo ONA ❑Yes ONo [INA 0 Yes ❑No DNA verified functional after testing? I j Comments—(include informafion on repairs made prior to testing; and recommended follow-up for�afled tests) TRAN 1-1-2"ENTRY BOOT INSTALLED TRAN 2—1-2"ENTRY BOOT INSTALLED RETESTED. If the entire depth of the sump is not tested,specify how much was tested. If the answer to My of the questions indicated with an asterisk(*)is"NO"or"NA-,the entire sump must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page_of 7- UNDER21LSPENSF-R CONTAWME:NT(2!DTEST1NG Test Method Developed By: IYUDC Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Z Test Method Used: ❑Pressure ❑Vacuum WHydrostatic ❑Other(Specify) Test Equipment Used. INCON TS-STS Equipment Resolution: UDC#1-2 UDC#34 UDC#5-6 UDC#7-8 UDC Manufacturer. AM CON AM CON AM CON AM CON UDC Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS UDC Depth: 28" 28" 28" 2T' Height from UDC Bottom to Top 9" 101, 10" 10" of Highest Piping Penetration: Height from UDC Bottom to 12" 12" 12" 12" Lowest Electrical Penetration: Condition of UDC prior to DRY DRY DRY DRY testin Portion of UDC Tested' Does turbine shut down when UDC sensor detects liquid(both O/Yes ❑No ❑NA iYes ❑No DNA 9/Yes ONo DNA M/Yes ❑No ❑NA product and mmw Turbine shutdown response time Is system programmed for fail- yes ❑No ❑NA d1Yes ONo DNA 2Yes ONo DNA E(Yes ONo [INA safe shutdown?* 4 1 Was fail-safe verified to be operational?* 2TYes ❑No DNA es ONo ❑NA R/Yes ON6 DNA es DNa DNA Wait time between applying 10 MIN 10 MIN 10 MIN 10 MIN pressure/vacuum/water and starting test Test Start Time: 9:10 9:10 9:10 9:10 Initial Reading(R4): 4.4725 3.8075 1.6211 2.7430 Test End Time: 9:25 9:25 9:25 9:25 Final Readin 4.4724 3.8076 1.6211 2.7417 Test Duration: 15 N41N 15 MIN 15 MIN 15 NJIN Change in Read!M(RF-gl): .001 .0002 .0000 .0013 Pass/Fail Threshold or Criteria: .002 .002 .002 .002 TVA�' UIV PM Of a I OOass ]Fafl Pass DFgdt, 1pikil Was sensor removed for testing? EgXEs ❑No ❑NA Les ❑No DNA es ONo DNA ❑No DNA Was sensor property replaced and dYes nNo DNA G/Yes ❑No DNA G/Yes ONo DNA Ayes ONo DNA verified functional after teslin cy COMMentS—(0clude information on repairs made prior to testing, and recommended follow-up for failed tests) If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) SWRCB,January 2002 Page_of 8. FILL RISER CONTAINMENT SUMP TESTING Facility is Not f4p ipped With Fill Riser Containment Sumps ❑ Fill Riser Containment Sumps are Present but were Not Tested 0 Test Method Developed By N(Sump Manufacturer ❑Industry Standard 0 Professional Engineer 0 Other(Specify) 4 Test Method Used: 0 Pressure ❑Vacuum &(Hydrostatic ❑Other(specify) Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000 FBI Sump#I FBI Sum p#2 FBI Sump#3 Fill Sump#4 Sump Diameter: 42" 42" 42- 42" Simp Depth: 60" 58" 61" 65" Height from Tank Top to Top of 0 0 0 0 Highest Piping Penetration: Height from Tank Top to Lowest 0 0 0 0 Electrical Penetration: Condition of sump prior to DRY DRY DRY DRY testing: Portion of Sump Tested 1211 12" 12" 12" Sump Material: FIBERGLASS FIGERGLASS FIBERGLASS FIBERGLASS Wait time between applying 10 MIN 10 N41N 10 MIN 10 MIN pressure/vacuum/water and startin g test Test Start Time: 10:26 10:26 12:08 12:08 Initial Reading W: 1.1361 5.3494 4.1533 5.6768 Test End Time: 10:41 10:41 12:24 12:24 Final Reading QW: 1.1355 53484 4.1536 5.6755 Test Duration: 15 MIN 15 MIN 15 MIN 15 NUN Change in Reading(&44): .0006 .0000 .0003 .0013 Pass/Fail Threshold or Criteria: .002 4 .002 .002 .002 pass TekResuitl. 1D Elail Is there a sensor in the sump? 0 Yes No 0 Yes No 0 Yes No 0 Yes No Does the sensor alarm when either product or water is 0 Yes ONO U(NA ❑Yes 0 No /NA El Ym 0 No 9/NA ❑Yes ONO &INA detected? 4 A Was sensor removed for testing? D Yes 0 No El NA 0 Yes 0 No ❑Yes 0 No 9 NA 0 Yes 0 No VRA- Was sensor properly replaced and 0 Yes 0 No QbA 0 Yes ❑No 44A ❑Yes ❑No NA 0 Yes 0 No NA] verified fimcdonal after!!!tin ? Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) SWRCB,January 2002 Page_of 9. SPHUOVERFILL CONTABOMW BOXES Facility is Not Equipped With Spill/Overfifl Containment Boxes 0 Spill/Overfill Containment Boxes are sent,but were Not Tested 0 Test Method Developed By: Bf Spill Bucket Manufacturer D Industry Standard 0 Professional Engineer 0 Other(Specify) 4 Test Method Used: 0 Pressure 0 Vacuum 1YHydrostatic 0 Other(Specify) Test Equipment Used:INCON TS-STS Equipment Resolution:0.0000 -7-7775"'7 7, Spill Box#I Spill Box#V1 Spill Box#2 Spill Box#V2 Bucket Diameter. 12" 12" 12" 1211 Bucket Depth: IT$ 12" 1213 12" Wait time between applying pressure/vacuum/water and 10 MIN 10 MIN 10 MIN 10 MIN starting test Test Start Time: 10:25 10:25 11:20 11:20 Initial Reading(RI): 33772 3.4913 3.0823 3.8527 Test End Time: 10:40 10:40 11:35 11:35 Final Reading(RF): 3.3768 3.4913 3.0821 3-8528 Test Duration: 15 N41N 15 MIN 15 MIN 15 MIN Change in Reading(RF-": .0004 .0000 .0002 .0001 Pass/Fail Threshold or .002 .002 .002 .002 Criteria: 47 Pass 0`#A Ivpass Te's&Residt: .--,,�,*-Pass fts�, 0 Fail Comments—(include it formation on repass made prior to testing,and recommended follow-up for failed tests) SWRCB,January 2002 Page of 9. SPILUOVERFELL CONTAINMENT BOXES Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ SpH I/Overfill Containment Boxes are Ment,but were Not Tested ❑ Test Method Developed By: 6 Spill Bucket Manufacturer ❑Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ❑Pressure ❑Vacuum VHydrostatic ❑Other(Specify) Test Equipment Used.INCON TS—STS Equipment Resolution: Spill Box#4 Spill Box#V4 Spill Box#3 Spill Box#V3 Bucket Diameter. 12 12" IT' 12" Bucket Depth. IT, 12" 12" 12" Wait time between applying pressure/vacuum/water and 10 MIN IOMIN 10 MIN 10 MIN starting test: Test Start Time: 11:52 11:52 12:52 1:19 Initial Reading(Rr): 2.7049 3.4974 4.0422 3.6022 Test End Time: 12:07 12:07 1:07 1:34 Final Reading(RF): 2.7049 3.4975 4.0409 3.6022 Test Duration: 15 MIN 15 MW 15 MIN 15 MIN Change in Reading(P.I-Ro: .0000 .0001 .0013 .0000 Pass/Fail Threshold or .002 .002 .002 .002 Criteria: Test ResuIfc 6:Pass 0-Fail Pass.'-"O Fail. _gPass ❑1ail.. _]Pas _0 Comments—(include information on repairs made prior to testing and recommended follow-up for failed tests) �FASTRIP 346 FASTRIP 34b 2698 OSWELL ST FASTRIP 346 2698 OSWELL ST BAKERSFIELD 93306 2698 OSWELL ST BAKERSFIELD 93306 SUNSET CONST BAKERSFIELD 93306 SUNSET CONST 1-800-984-6266 SUNSET CONST 1-800-984-6266 1-800-984-6266 03/16/2011 1:50 PM 03/16/2011 1:07 PM 0311612011 1:34 PM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT TRAN1 SPILL4 TRAN1 TEST STARTED 1:35 PM TEST STARTED 12:52 PM TEST STARTED 03/16/2011 TEST STARTED 1:19 PM TEST STARTED 03/16/2011 BEGIN LEVEL 3,7458 IN TEST STARTED 03/16/2011 BEGIN LEVEL 4,0422 IN END TIME 1:50 PM BEGIN LEVEL 3,7458 IN END TIME 1:07 PM END DATE 03116 12011 END TIME 1:34 PM END DATE 03/16/2011 END LEVEL 3.7458 IN END DATE 03/16/2011 END LEVEL 4,0409 IN LEAK THRESHOLD 0,002 IN END LEVEL 3,7457 IN LEAK THRESHOLD 0,002 IN TEST RESULT. PASSED LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED TRAN2 TRAN2 TEST STARTED 1:35 PM FASTRIP 346 TEST STARTED 03/16/2011 TEST STARTED 1:19 FM 2698 OSWELL ST BEGIN LEVEL 5,2839 IN TEST STARTED 03/16/2011 BAKERSFIELD 93306 END TIME 1:50 PM BEGIN LEVEL 5,2839 IN SUNSET CONST END DATE 03/16/2011 END TIME 1:34 PM 1-800-984-6266 END LEVEL 5,2838 IN END DATE 03/16/2011 LEAK THRESHOLD 0,002 IN END LEVEL 5,2838 IN 03/1612011 12:49 PM TEST RESULT PASSED LEAK THRESHOLD 0,002 IN TEST RESULT PASSED SUMP LEAK TEST REPORT VSPILL4 SPILL4 VSPILL4 TEST STARTED 1:35 PM TEST STARTED 12:34 PM TEST STARTED 03/16/2011 TEST STARTED 1:19 PN TEST STARTED 03/16/2011 BEGIN LEVEL 3,6021 IN TEST STARTED 03/16/2011 BEGIN LEVEL 4.0422 IN END TIME 1:50 PM - BEGIN LEVEL 3,6022 IN END TIME 12:49 PM END DATE 03/16/2011 END TIME 1:34 PM END DATE 03/16/2011 END LEVEL 3,6018 IN END DATE 03/16/2011 END LEVEL 4,0421 IN LEAK THRESHOLD 0,002 IN END LEVEL 3,6022 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED LEAK THRESHOLD 0.002 IN TEST RESULT PASSED TEST RESULT PASSED - 2698 OSNELLvST 2698 OSWELLVST FASTRIP 346 BAKERSFIELD 93306 BAKERSFIEhD 93306 2698 OSHELL ST SUNSET CONST SUNSET CONST BAKERSFIELD 93306 1-800-984-6266 1-800-984-6266 SUNSET CONST 1-800-984-6265 03/16/2011 11:14 AM 03/16/2011 12:08 PM 03/16/2011 12:24 PM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT STPI STP3 STP3 TEST STARTED 10:59 AM TEST STARTED 11:53 AM TEST STARTED 03/16/2011 TEST STARTED 03/16/2011 TEST STARTED 12:08 PM BEGIN LEVEL 4,9513 IN BEGIN LEVEL 4,0729 IN TEST STARTED 03/16/2011 END TIME 11:14 AM END TIME 12:08 PM BEGIN LEVEL 4.0727 IN END DATE 03116/2011 END.DATE 03/16/2011 END TIME 12:24 PM END LEVEL 4.9522 IN END LEVEL 4.0728 IN END DATE 03/16/2011 LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN END LEVEL 4.0726 IN TEST RESULT PASSED TEST RESULT PASSED LEAK THRESHOLD 0.002 IN TEST RESULT PASSED STP2 STP4 STP4 TEST STARTED 10:59 AM TEST STARTED 11:53 AM TEST STARTED 03/16/2011 TEST STARTED 03/16/2011 TEST STARTED 12:08 PM BEGIN LEVEL 3,4544 IN BEGIN LEVEL 4,6115 IN TEST STARTED 03/16/2011 END TIME 11:14 AM END TIME 12:08 PM BEGIN LEVEL 4,6079 IN END DATE 03/16/2011 END DATE 03/16/2011 END TIME 12:24 PM END LEVEL 3.4512 IN END LEVEL 4,6101 IN END DATE 03/16/2011 LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN END LEVEL 4.6090 IN TEST RESULT FAILED TEST RESULT PASSED LEAK THRESHOLD 0,002 IN TEST RESULT PASSED FILL1 FILLS FILL3 TEST STARTED 10:59 AM TEST STARTED 11:53 AM TEST STARTED 03/16/211 TEST STARTED 03/16/2011 TEST STARTED 12:08 PM BEGIN LEVEL 1.1385 IN BEGIN LEVEL 4.1523 IN TEST STARTED 03/16/2011 END TIME 11:14 AM END TIME 12:08 PM BEGIN LEVEL 4.1533 IN END DATE 03/16/2011 - END DATE 03/16/2011 END TIME 12:24 PM END LEVE! 1. 1387 IN END LEVEL 4.1529 IN END DATE 03/16/2011 LEAK THRESHOLD ';,032 IN LEAK THRESHOLD 0,002 IN END LEVEL 4, 1536 IN TEST RESULT PASSED TEST RESULT PASSED LEAK THRESHOLD 0.002 IN TEST RESULT PASSED FILL2 FILL4 FILL4 TEST STARTED 10:5b AM TEST STARTED 11:53 AM TEST STARTED 03/16/2011 TEST STARTED 03116/2011 TEST STARTED 12:08 PM BEGIN LEVEL 5,3535 IN BEGIN LEVEL 5.6768 IN TEST STARTED 03/16/2011 END TIME 11:14 AM END TIME 12:08 PM BEGIN LEVEL 5.6768 IN END DATE 03/16/2011 =ND DATE 03/16/2011 END TIME 12:24 PM END LEVEL 5,3560 IN :ND LEVEL 5,6775 IN END DATE 03/16/2011 LEAK THRESHOLD 0.002 IN EAK THRESHOLD 0,002 IN END LEVEL 5.6755 IN TEST RESULT INCREASED -ST RESULT PASSED LEAK THRESHOLD 0.002 IN TEST RESULT PASSED -------� �AS?RlP 3�6 2698 OSHE�L �T �� �� O��� �� �AvE*Sr�u-o ���n` -' ----- @�J��FIEl�` 93306 SUNSET CONST ' SUNSET COKST Sy�sET COUST � 1-880-984-6266 1-880-9O4-6266 �l:18 �� 03/16/281� 18:41 An 03/16/201� 12:07 PM TE�T R[PO�r SUMP LBH< TEST SUMP U���T R[�]RT � SUMP LEAK TEST REPORT SPIiL2 SPV ! '.' SPILL3 T�ST STHRTE& 11:03 AM TE3T ST�RTED 1�:25 �M TEST STARTED 11:52 HM TEST STARTED 03/16/2011 TES 03/16/2811 TEST STARTED W3/16/201� 8EGIN LEVEL 3.0828 IN 8[8IN LEVEL 3^3772 TN BEGIN LEVEL 2 7049 IN . [N0 TIME 11:18 HM [N0 TlME 10:40 AM END TIME �2:07 pM END DATE 0�^16/2��1 E�D C�TE ' 0I/16'�01l END DHT� ^16/2011 END LEVEL 3.0824 IN END LEvEL 3^3768 IN END LEVEL n�'704g IN LEAK THRESHOLD 0.002 IN L��� IHREI��OLD 0^002 I� LEAK THRESHOL0 �^m~002 IN S T TEST RESULT PASSED TEST RESULT PASSED 7E RESULT Pf4SS[D VSPII 1-2 VSpILL� VgpILL3 TEST STARTED 11:03 AN TEST STARTED 10:25 AN TEST STARTED 11:52 AM TEST S��� �/16/�1z �� ST�� 03/16/�11 BEGIN LEVEL 3.9532 �N BEGIN LEVEL 3.4913 IN �ESr STARTED 03/16~�Wzz ^ END TIHE 10:40 HM BEGIN LEVEL 3.4974 IN END TIME 11 i8 HM END DK7[ 03/16/20511 [ND TIME 12:07 PM END CAT� 03/16/2011 E}0 LEVEL 3 o913 IN END DATE 03/16/20�1 �N0 LEo[L 3.8�29 [|� �� � ' END LB�� J 4975 IN LEAK THRESHOLD 0.002 IN LEAK THRE�H0LD 0.002 IN. , ^ TEST s�SULT PASSED LEAK THRESHOLD 0.002 IN - TEST RESULT PASSED RESULT PASSED �_-*STR_lp 346 FAGTRIp 346 =HSTRIp 346 2698 OSWElL ST 2698 0SH8-L ST 2698 USWEI� S� 3HK[RSFIELD 93�06 8AKERSFlELD 93306 B�KERSFIE�D ��' SUNSET CONST SUNSET CONS/ SUNSET � ,^3o" 1-800-984-6266 z-800+�84-6266 �_O8x�' CONS; 0J/16/20�� �1'35 H� 03/16/201� le-57 Hw 03/\6/2@!1. 12:23 pri SUMP LEHK -rEST REPORT SUMP LEAK TEST REPORT uuMp Lssz TEST REPORT SPILL-2 SPiLL1 6 plLL3 7 EST STARTED 11-:20 HM TEST STARTED 8:42 AM T��T STARTED 12:08 PM TEST ST�RTE� 03/i6/2011 TEST ST�lTED 03/16/2011 TEST STARTED 83/16/2011 3EGI@ LIDEL 3 0823 �� BEGIN LBVEL 3.3769 IN ` END TIME 10:57 H� 8[GIA LFVEL 2.7048 IN CND TI�E 11:35 AM [ND DATE 03/1G^��11 END TIME 12^23 p� . END DATE 03/16/2011 END LEVEL 3 3767 IN � DATE 03/16/2011 END LEVEL 3.0821 IN ^ [M0 LEVEL 2.7056 IN THR[SHOLD 8 0�1 IN LEHK LD �^0U2 I� L��k THRE3HULD ' 002 I'M ^ TEST RESULT PHSS[0 n. TEST RESULT PASSED TEST RESULT PASSED uSPIL12 VSPILL1 VSPILL3 TEST STARTED 11:20 4�M TEST STAR—iED 10:42 All- ' T[ST STARTED 03/16^N-^ TEST STARTED 12:08 pM 7E3T STARTED 03/16/2811 BEGIN �[oE� 3.49-14 J TEST STARTED 03/16/2011 BEGIN LEVEL 3.8527 �N ^ / 8�SlN LEl�L 3 4g74 IN END TIME 11:35 HM 3�D TIME 10:57 , [ND D�TE 03/16/20�� END V�T[ ' 03/�6/2� END TIME 12:23pM D LE 3.92 IN o CE 3.413 N 0T /16/ 011 _ ^ LEAK THRESHOLD 0 0�� END LElU]_ 3.4974 IN LEAK THRESHOLD 0.002 �H ^ LEAK THRESHOLD 0.002 IN �� RE�� p�� �� �BULT PHf TE� RBVLT ^PASSED Inul4\11 04U 2698 OSWELL ST rnairttr J4U rmblKtr J40 BAKERSFIELO 93306 2698 OSYELL ST 2698 OSYELL ST SUNSET CONST BAKERSFIELD 93305 BAKERSFIELD 93306 1-800-984-6266 SUNSET CONST SUNSET CONST 1-800-984-6266 1-800-984-6266 03/16/2011 8:36 AM 03/16/2011 10:41 AM 03J16/2011 14:57 AM SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT SUMP LEAK TEST REPORT UDC1-2 STP1 STP1 TEST STARTED 8:20 AM TEST STARTED 10:26 AM TEST STARTED 03/16/2011 TEST STARTED 03/16!2011 TEST STARTED 10;42 AM BEGIN LEVEL 4,8743 IN BEGIN LEVEL 49529 IN TEST STARTED 03/16/2011 , END TIME 8:35 AM BEGIN LEVEL 4,9525 IN END DATE 03/16/2011 END TIME 10:41 'AM END TIME 10:57 AM END LEVEL 4,8735 I.N END DATE 03/16/2011 END DATE 03/16/2011 LEAK THRESHOLD 0.002 IN END LEVEL 4.9529 IN END LEVEL 4.9518 IN TEST RESULT PASSED LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED TEST RESULT PASSED UDC3-4 STP2 STP2 TEST STARTED 8:20 AM TEST STARTED 10:26 AM TEST STARTED 03/16/2011 TEST STARTED 03/16/2011 TEST STARTED 10:42 AM BEGIN LEVEL 7,0334 IN BEGIN LEVEL 3,4554 IN TEST STARTED 03/16/2011 END TIME 8:35 BEGIN LEVEL 3,4552 IN END DATE 03/16/2011 END TIME 10:41 AM END TIME 1 10:57 AM END LEVEL 7,0331 IN END DATE _ 03/16/2011 END DATE 03/16/2011 LEAK THRESHOLD 0,002 IN END LEVEL 3,4552 IN END LEVEL 3,4550 IN TEST RESULT PASSED 'LEAK THRESHOLD 0,002 IN LEAK THRESHOLD 0.002 IN TEST RESULT PASSED TEST RESULT PASSED uDCS-s FILL1 FILLi TEST.STARTED 8:20 AM TEST STARTED 10:26 AM TEST STARTED 03/16/2011 TEST STARTED 03!16/2011 TEST STARTED 10:42 AM BEGIN LEVEL 3.7053 IN TEST STARTED 03/16/2011 END TIME 8:35 AM BEGIN LEVEL 1.1361 IN BEGIN LEVEL 1.1360 IN END DATE 03/16/2011 END TIME 10:41 AM END TIME 10:57 AN END LEVEL 3,7047 IN END DATE 03/16/2011 END DATE 03/16/2011 LEAK THRESHOLD 0.002 IN END LEVEL 1.1355 IN - END LEVEL -1. 1387 IN TEST RESULT PASSED LEAK THRESHOLD 0,002 IN LEAK THRESNOL;I :;;d.002 IF; TEST RESULT PASSED TEST RESULT "�CREa�ED UDC7-8 FILL2 FILL2 TEST STARTED 8:20 AM TEST STARTED 10:26 AM TEST STARTED 03/16/2u1 TEST STARTED 03/16/2011 r EST STARTED BEGIN LEVEL 4. 1568 IN EST STARTED 03/16/2011 END TIME 8:35 AM BEGIN LEVEL 5,3484 IN :GIN LEVEL 5.3484 iN END DATE 03/16/2011 END TIME 10:41 AM 0 TIME 10:57 AM END LEVEL 4, 1556 IN END DATE 03!16/2011 1 DATE 03/16/2011 LEAK THRESHOLD 0,002 IN END LEVEL 5,3484 IN LEVEL 5,3487 IN TEST RESULT PASSED LEAK THRESHOLD 0.002 IN ' THRESHOLD 0,002 IN _ TEST RESULT PASSED RESULT PASSED FASTRIP 346 2698 OSVELL-ST- BAKERSFIELD 93306 SUNSET CONST 1-800-984-6266 03/16/2011 9:25 AM SUMP LEAK TEST REPORT UDC1-2 TEST STARTED 9:10 AM TEST STARTED 03/16/2011 BEGIN LEVEL 4.4725 IN END TIME 9:25 AN END DATE 03/16/2011 END LEVEL 4.4724 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED UDC3-4 TEST STARTED 9:10 AN TEST STARTED 03/16/2011 BEGIN LEVEL 3.8074 IN END TIME 9:25 AM END DATE 03/16/2011 END LEVEL 3,8076 IN LEAK THRESHOLD 0.002 IN TEST RESULT PASSED UDC5-6 TEST STARTED 9:10 AM TEST STARTED 03/16/2011 BEGIN LEVEL 1.6211 IN END TIME 9:25 AM END DATE 03/16/2011 END LEVEL 1.6211 IN LEAK THRESHOLD 0,002-IN TEST RESULT PASSED UDC7-8 TEST STARTED 9:10 AM TEST STARTED 03/16/2011 BEGIN LEVEL 2.7430 IN END TIME 9:25 AM END DATE 03/16/2011 END LEVEL 2.7417 IN LEAK THRESHOLD 0,002 IN TEST RESULT PASSED